ITP No. :___________________
Inspection Gr. :___________________
Report No. :___________________
FILED INSPECTION REPORT Date :___________________
Quality Control Form
Inspection Type : Work No. :
Unit No. :
INSPECTION
FIRE ALARM SYSTEM Item No. :
Location :
Inspection Notice No. : Date / Names / Signature
Drawing No(s). : Company Contractor Subcontractor
J/B No. / Cabinet No. : / / / / / /
Manufacture :
:
:
1. Installation inspection :
No. Item to Check Result Remarks
Check conformity of Equipment (detector, call point, sounder, alarm
1
panel, etc …) and device installation to specification and drawing.
Visual check of system equipment and devices for any mechanical
2
damages.
3 Check zone number of circuit with reference to drawing.
4 Check installation of conduit correct with drawing.
5 Check cables and glands, weather proofing etc.
6 Check termination of equipment as per cabinet schedule.
7 Check connection of earthing system.
8 Check functional test of each detectors.
9 Check functional test of each call point.
10 Check functional test of each sounders.
Remarks :
Legend N.A: Not Applicable
www.Inspection-for-Industry.com
ITP No. :___________________
Inspection Gr. :___________________
FILED INSPECTION REPORT Report No. :___________________
Date :___________________
Inspection Type : Work No. :
Unit No. :
INSPECTION
FIRE ALARM SYSTEM Item No. :
Location :
Inspection Notice No. : Date / Names / Signature
Drawing No(s). : Company Contractor Subcontractor
Manufacture : / / / / / /
Type :
Serial No. :
Test Equipment :
1. Installation inspection :
No. Item to Check Result Remarks
1 Check nameplate installed and correct.
2 Check of type LCS is correct.
3 Check range of Ammeter is correct.
4 Check installation location correct as per drawing.
5 Check mounting height or stanchion height.
6 Check touch-up painting of supports or stanchion.
7 Check any mechanical damages during or after installation.
8 Check operation of lock facility.
9 Check conduit installed correctly.
10 Check cable connection and glanding tight.
11 Check wiring correct and cable tag, installed.
12 Check grounding connection correct.
13 Check function : 1) Test voltage
Volts
2) Eath impedance test current
Ohms
3) Each pole to earth (Record Min. Value)
A
4) Earth return path impedance measured
Remarks : Ohms
Legend N.A: Not Applicable