Quality Inspection Room Report

The document lists 48 items across various trades requiring rectification in a building. Items include non-functional doorbell chimes, exposed wires, missing panels and covers, uninstalled fixtures and equipment, insulation and sealing issues, calibration needs and unfinished mechanical, electrical and plumbing works. The items range from major safety and functionality snags to minor cosmetic snags that can be addressed after handover. Photos and sign-offs from various parties will be required to close out the items.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views32 pages

Quality Inspection Room Report

The document lists 48 items across various trades requiring rectification in a building. Items include non-functional doorbell chimes, exposed wires, missing panels and covers, uninstalled fixtures and equipment, insulation and sealing issues, calibration needs and unfinished mechanical, electrical and plumbing works. The items range from major safety and functionality snags to minor cosmetic snags that can be addressed after handover. Photos and sign-offs from various parties will be required to close out the items.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Item Trade Category Specific/Area/ Description

No. Room/Gridline

Green, red indicator doorbell


chimes not working

1 E A
Main
entrance

2 E A All areas Emergency light battery pack


not yet installed

Convinience outlet no power


supply / expose wires for proper
harnessing / faceplate missing

3 E A
Walk in
closet
RCU panel for cleaning / no
4 E A
Walk in diagram / no panel directory /
closet door handle missing

5 E A Bedroom Minibar not yet installed

Convinience outlet no power


6 E B Bedroom supply / Faceplate cover missing /
with gap

Convinience outlet no power


7 E B Bedroom supply / expose wires
Covelight need to identify LED
8 E B Bedroom driver location and install tagging

Covelight need to identify LED


9 E A Bathroom driver location and install tagging

Telephone device not yet


10 E A Bathroom installed

11 E B Bathroom Expose wires


12 E A Bathroom Curtain covelight not
working

13 E A Bathroom Convinience outlet no


power supply

14 C A Bathroom Rectify finish cove with gap

15 M B Bed room Dirty air filter and fcu


noisy
16 M B Bed room Chilled pipe accessories not
installed properly
Photo Reference Closed-out signed off Remarks
Date
HCC FM
Item Trade Category Specific/Area/ Description
No. Room/Gridline

Chilled valve no
17 M B Bed room insulation cover

18 M B Bed room Chilled valve no


insulation cover

19 M B Bed room Actuator not insatall


Drain pan dirty and drain pan
20 M B Bed room backflow

Chilled pipe incomplate


insulation/note.drain pan hard to
access for maintenance need
manhole

21 M B Bed room

Pop-up rod to adust too high


conflict to vanity mirror

22 P A Bathroom

23 P A Toilet area Water closet no power and


water supply
24 P A bathroom Cleaned and remove
unwanted materials

25 A Shower area Calibration oh shower


mixer (TMV)

Refixed of pipe support for hot


26 E A Powder water manifold header

27 E
rectify and provide flexible
conduit on exposed wire
cleaned and remove construction
28 P A Toilet area debris on above ceiling perimeter

29 P A bathroom Washbasin no water supply

30 E B Bathroom Re-seal of hole and final paint

31 P A Bathroom pedestal box cover hard to


open/closed
32 C B
Walk in Rectify finish of access
closet manhole ceiling

33 C B
Walk in Rectify finish of paint on RCU
closet door

34 C B
Walk in Seal the gap around
closet smoke detector

35 C B Bedroom Final touch up of paint on door


frame
36 C B
Walk in Sliding door handle loose
closet

37 C B Bathroom Rectify finish under wash basin

38 C B Bathroom Rectify finish of wire gap of


telephone

Rectify finish of hinges gap at the


39 C B Bathroom back of vanity mirror
Rectify finish of hinges gap at the
40 C B Bathroom back of vanity mirror

Rectify finish of wire gap at the


41 C B Bathroom back of vanity mirror

Rectify finish of wire gap on


42 C B Bathroom curtain ceiling

Rectify finish of paint on


43 C B Bathroom ceiling
Calibration of the TMV (Thermostatic Mixing
44 P A Shower Room Valve) for the shower. Provide the calibration
certificate from the contractor.

TEAD (Toilet Exhaust Air Duct) not yet


45 M A Toilet Room
functional.

46 M A All Areas FAD (Fresh Air Duct) not yet


functional.

47 M A Vestibule No vibration isolator installed for the FCU.


Verify as per design.
48 O B All Areas Provide the approved T&C for the MEPF
system.
Photo Reference Closed-out signed off Remarks
Date
HCC FM
FM/BU/ODT/CM/Designer/Consultant/Contractor Representative(s):
Company Name Sign
Date
Item Trade Category Specific/Area/ Description Photo Reference
No. Room/Gridline

Legend:
Trade
C- Civil F - Fire Pro A - Arch'l B - BMS
S - Str'l P- Plumbing M - Mech'l/MVAC E - Electrical
Category
A - Major snag which may affect functionality and safety B - Minor snag which can be rectified after handover
Photo Reference Closed-out signed off Remarks
Date
HCC FM

O-
Others
L-
Landsc
ape
snag which can be rectified after handover