Ni-Cad Battery Sizing Calculation (IEEE 1115) Rev Date: Page 1 of 2

This document contains inputs and results for sizing a nickel-cadmium battery system. The inputs include load profiles, voltage requirements, temperature parameters, and design factors. Based on the inputs, the possible number of cells that can be connected in series is calculated to be between 362 to 545 cells per string. 545 cells in series is selected. The results include the maximum and minimum system voltages as well as the end of discharge voltage and selected cell size.

Uploaded by

MK
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views2 pages

Ni-Cad Battery Sizing Calculation (IEEE 1115) Rev Date: Page 1 of 2

This document contains inputs and results for sizing a nickel-cadmium battery system. The inputs include load profiles, voltage requirements, temperature parameters, and design factors. Based on the inputs, the possible number of cells that can be connected in series is calculated to be between 362 to 545 cells per string. 545 cells in series is selected. The results include the maximum and minimum system voltages as well as the end of discharge voltage and selected cell size.

Uploaded by

MK
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ni-Cad Battery Sizing Calculation(IEEE Rev

1115) Date : Page 1 of 2

Ni-Cad Battery Sizing Calculation(IEEE 1115)

Project
Project No:

Project Title:

Document No:

Revision No:

Date :

Inputs
Minimum System Voltage 412.5 V

Maximum System Voltage 600 V

Nominal System Voltage 450 V

Load Profile

Known Loads

Load Tag Load Unit Begin(min) End(min)

L1 20000 Amps 30 30

L2 280 Amps 30 30

L3 40000 Amps 30 30

L4 100 Amps 30 30

L5 10000 Amps 30 30

L6 80 Amps 30 30

Random
Loads

Load Tag Load Unit Duration(min)

L7 100 Amps 1

Maximum Charge 1.10 V


Voltage/Cell

For single level charging max chargin voltage is typically 1.43-1.5V/cell. For two level charging typically 1.47 to 1.7V/cell

Maximum Temperature 40 °C

Minimum Temperature 0 °C

Nominal Temperature 25 °C

Maximum, minimum and nominal temperatures pertain to site ambient/installation conditions.

Design Margin 1.1

Aging Factor 1.25

Cell Range Series M (30min to 3hr backup periods)

Cells in Series based on max possible for economic selection

Results
Possible No of cells in series 362 (min) to 545 (max) per string

No of cells in series selected 545

Maximum System Voltage 599.5 V

Minimum System Voltage 545.0 V

End of Discharge Voltage 1.0 V

Cell Strings/Arrays in parallel 1

Cell Sizing Data

Cell Section Size (for Known Loads) 0 AH

Cell Section Size (for Random Loads) 47.9 AH

Calculation Performed at www.codecalculation.com

www.codecalculation.com
Ni-Cad Battery Sizing Calculation(IEEE Rev
1115) Date : Page 2 of 2

Cell Section Size (Uncorrected) 47.9 AH

Cell Section Size (Corrected for 65.8 AH


Design Margin and Aging Factor)

Cell Selected 70 AH

Calculation Performed at www.codecalculation.com

www.codecalculation.com