SIA Event Block Data Code Definitions: Data Code Short Description Long Description Address Field AA

This document defines data codes used for event block data in an SIA system. It provides the short description, long description, and address field for each data code. Some of the codes relate to alarms, troubles, and restorals for burglary, fire, access control, and general system events. Others indicate user actions like arming, disarming, granting access, or denying access. The codes provide details on the type of event, involved zone or point, and relevant area, user, or door number.

Uploaded by

jhuenup
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views10 pages

SIA Event Block Data Code Definitions: Data Code Short Description Long Description Address Field AA

This document defines data codes used for event block data in an SIA system. It provides the short description, long description, and address field for each data code. Some of the codes relate to alarms, troubles, and restorals for burglary, fire, access control, and general system events. Others indicate user actions like arming, disarming, granting access, or denying access. The codes provide details on the type of event, involved zone or point, and relevant area, user, or door number.

Uploaded by

jhuenup
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

SIA Event Block Data Code Definitions

Data Short Long Address


Code Description Description Field
AA Alarm – Panel Substitution An attempt to substitute an alternate alarm panel for a secure Condition number
panel has been made
AB Abort An event message was not sent due to User action Zone or point
AN Analog Restoral An analog fire sensor has been restored to normal operation Zone or point
AR AC Restoral AC power has been restored Unused
AS Analog Service An analog fire sensor needs to be cleaned or calibrated Zone or point
AT AC Trouble AC power has been failed Unused
BA Burglary Alarm Burglary zone has been violated while armed Zone or point
BB Burglary Bypass Burglary zone has been bypassed Zone or point
BC Burglary Cancel Alarm has been cancelled by authorized user User number
BD Swinger Trouble A non-fire zone has been violated after a Swinger Shutdown on Zone or point
the zone
BE Swinger Trouble Restore A non-fire zone restores to normal from a Swinger Trouble state Zone or point
BG Unverified Event - Burglary A point assigned to a Cross Point group has gone into alarm Zone or point
but the Cross Point remained normal
BH Burglary Alarm Restore Alarm condition eliminated Zone or point
BJ Burglary Trouble Restore Trouble condition eliminated Zone or point
BM Burglary Alarm - Burglary alarm w/cross point also in alarm - alarm verified Zone or point
Cross Point
BR Burglary Restoral Alarm/trouble condition has been eliminated Zone or point
BS Burglary Supervisory Unsafe intrusion detection system condition Zone or point
BT Burglary Trouble Burglary zone disabled by fault Zone or point
BU Burglary Unbypass Zone bypass has been removed Zone or point
BV Burglary Verified A burglary alarm has occurred and been verified within Area number
programmed conditions. (zone or point not sent)
BX Burglary Test Burglary zone activated during testing Zone or point
BZ Missing Supervision A non-fire Supervisory point has gone missing Zone or point
CA Automatic Closing System armed automatically Area number
CD Closing Delinquent The system has not been armed for a programmed amount of Area number
time
CE Closing Extend Extend closing time User number
CF Forced Closing System armed, some zones not ready User number
CG Close Area System has been partially armed Area number
CI Fail to Close An area has not been armed at the end of the closing window Area number
Data Short Long Address
Code Description Description Field
CJ Late Close An area was armed after the closing window User number
CK Early Close An area was armed before the closing window User number
CL Closing Report System armed, normal User number
CM Missing Alarm - Recent Closing A point has gone missing within 2 minutes of closing Zone or point
CO Command Sent A command has been sent to an expansion/peripheral device Condition number
CP Automatic Closing System armed automatically User number
CQ Remote Closing The system was armed from a remote location User number
CR Recent Closing An alarm occurred within five minutes after the system was User number
closed
CS Closing Keyswitch Account has been armed by keyswitch Zone or point
CT Late to Open System was not disarmed on time Area number
CW Was Force Armed Header for a force armed session, forced point msgs may follow Area number
CX Custom Function Executed The panel has executed a preprogrammed set of instructions Custom Function
number
CZ Point Closing A point, as opposed to a whole area or account, has closed Zone or point
DA Card Assigned An access ID has been added to the controller User number
DB Card Deleted An access ID has been deleted from the controller User number
DC Access Closed Access to all users prohibited Door number
DD Access Denied Access denied, unknown code Door number
DE Request to Enter An access point was opened via a Request to Enter device Door number
DF Door Forced Door opened without access request Door number
DG Access Granted Door access granted Door number
DH Door Left Open - Restoral An access point in a Door Left Open state has restored Door number
DI Access Denied – Passback Access denied because credential has not exited area before Door number
attempting to re-enter same area
DJ Door Forced - Trouble An access point has been forced open in an unarmed area Door number
DK Access Lockout Access denied, known code Door number
DL Door Left Open - Alarm An open access point when open time expired in an armed area Door number
DM Door Left Open - Trouble An open access point when open time expired in an unarmed Door number
area
DN Door Left Open An access point was open when the door cycle time expired Door number
(non-alarm, non-trouble)
DO Access Open Access to authorized users allowed Door number
DP Access Denied - An access request was denied because the request is occurring Door number
Unauthorized Time outside the user’s authorized time window(s)
DQ Access Denied An access request was denied because the user was not Door number
Unauthorized Arming State authorized in this area when the area was armed
DR Door Restoral Access alarm/trouble condition eliminated Door number
DS Door Station Identifies door for next report Door number
Data Short Long Address
Code Description Description Field
DT Access Trouble Access system trouble Unused
DU Dealer ID Dealer ID number Dealer ID
DV Access Denied An access request was denied because the user is not Door number
Unauthorized Entry Level authorized in this area
DW Access Denied - An access request was denied because the doors associated Door number
Interlock Interlock point is open
DX Request to Exit An access point was opened via a Request to Exit device Door number
DY Door Locked The door’s lock has been engaged Door number
DZ Access Denied - An access request was denied because the door has been Door number
Door Secured placed in an Access Closed state
EA Exit Alarm An exit zone remained violated at the end of the exit delay Zone or point
period
EE Exit Error An exit zone remained violated at the end of the exit delay User number
period
EJ Expansion Tamper Restore Expansion device tamper restoral Expansion device
number
EM Expansion Device Missing Expansion device missing Expansion device
number
EN Expansion Missing Restore Expansion device communications re-established Expansion device
number
ER Expansion Restoral Expansion device trouble eliminated Expander number
ES Expansion Device Tamper Expansion device enclosure tamper Expansion device
number
ET Expansion Trouble Expansion device trouble Expander number
EX External Device Condition A specific reportable condition is detected on an external device Device number
EZ Missing Alarm - Exit Error A point remained missing at the end of the exit delay period Point number
FA Fire Alarm Fire condition detected Zone or point
FB Fire Bypass Zone has been bypassed Zone or point
FC Fire Cancel A Fire Alarm has been cancelled by an authorized person Zone or point
FG Unverified Event – Fire A point assigned to a Cross Point group has gone into alarm Zone or point
but the Cross Point remained normal
FH Fire Alarm Restore Alarm condition eliminated Zone or point
FI Fire Test Begin The transmitter area's fire test has begun Area number
FJ Fire Trouble Restore Trouble condition eliminated Zone or point
FK Fire Test End The transmitter area's fire test has ended Area number
FL Fire Alarm Silenced The fire panel’s sounder was silenced by command Zone or point
FM Fire Alarm - Cross Point Fire Alarm with Cross Point also in alarm verifying the Fire Point number
Alarm
FQ Fire Supervisory Trouble A fire supervisory zone that was in trouble condition has now Zone or point
Restore restored to normal
FR Fire Restoral Alarm/trouble condition has been eliminated Zone or point
Data Short Long Address
Code Description Description Field
FS Fire Supervisory Unsafe fire detection system condition Zone or point
FT Fire Trouble Zone disabled by fault Zone or point
FU Fire Unbypass Bypass has been removed Zone or point
FV Fire Supervision Restore A fire supervision zone that was in alarm has restored to normal Zone or point
FW Fire Supervisory Trouble A fire supervisory zone is now in a trouble condition Zone or point
FX Fire Test Fire zone activated during test Zone or point
FY Missing Fire Trouble A fire point is now logically missing Zone or point
FZ Missing Fire Supervision A Fire Supervisory point has gone missing Zone or point
GA Gas Alarm Gas alarm condition detected Zone or point
GB Gas Bypass Zone has been bypassed Zone or point
GH Gas Alarm Restore Alarm condition eliminated Zone or point
GJ Gas Trouble Restore Trouble condition eliminated Zone or point
GR Gas Restoral Alarm/trouble condition has been eliminated Zone or point
GS Gas Supervisory Unsafe gas detection system condition Zone or point
GT Gas Trouble Zone disabled by fault Zone or point
GU Gas Unbypass Bypass has been removed Zone or point
GX Gas Test Zone activated during test Zone or point
HA Holdup Alarm Silent alarm, user under duress Zone or point
HB Holdup Bypass Zone has been bypassed Zone or point
HH Holdup Alarm Restore Alarm condition eliminated Zone or point
HJ Holdup Trouble Restore Trouble condition eliminated Zone or point
HR Holdup Restoral Alarm/trouble condition has been eliminated Zone or point
HS Holdup Supervisory Unsafe holdup system condition Zone or point
HT Holdup Trouble Zone disabled by fault Zone or point
HU Holdup Unbypass Bypass has been removed Zone or point
IA Equipment Failure Condition A specific, reportable condition is detected on a device Point number
IR Equipment Fail - Restoral The equipment condition has been restored to normal Point number
JA User Code Tamper Too many unsuccessful attempts have been made to enter a Area number
user ID
JD Date Changed The date was changed in the transmitter/receiver User number
JH Holiday Changed The transmitter's holiday schedule has been changed User number
JK Latchkey Alert A designated user passcode has not been entered during a User number
scheduled time window
JL Log Threshold The transmitter's log memory has reached its threshold level Unused
JO Log Overflow The transmitter's log memory has overflowed Unused
JP User On Premises A designated user passcode has been used to gain access to User number
the premises.
Data Short Long Address
Code Description Description Field
JR Schedule Executed An automatic scheduled event was executed Area number
JS Schedule Changed An automatic schedule was changed User number
JT Time Changed The time was changed in the transmitter/receiver User number
JV User Code Changed A user's code has been changed User number
JX User Code Deleted A user's code has been removed User number
JY User Code Added A user’s code has been added User number
JZ User Level Set A user’s authority level has been set User number
KA Heat Alarm High temperature detected on premise Zone or point
KB Heat Bypass Zone has been bypassed Zone or point
KH Heat Alarm Restore Alarm condition eliminated Zone or point
KJ Heat Trouble Restore Trouble condition eliminated Zone or point
KR Heat Restoral Alarm/trouble condition has been eliminated Zone or point
KS Heat Supervisory Unsafe heat detection system condition Zone or point
KT Heat Trouble Zone disabled by fault Zone or point
KU Heat Unbypass Bypass has been removed Zone or point
LB Local Program Begin local programming Unused
LD Local Program Denied Access code incorrect Unused
LE Listen-in Ended The listen-in session has been terminated Unused
LF Listen-in Begin The listen-in session with the RECEIVER has begun Unused
LR Phone Line Restoral Phone line restored to service Line number
LS Local Program Success Local programming successful Unused
LT Phone Line Trouble Phone line trouble report Line number
LU Local Program Fail Local programming unsuccessful Unused
LX Local Programming Ended A local programming session has been terminated Unused
MA Medical Alarm Emergency assistance request Zone or point
MB Medical Bypass Zone has been bypassed Zone or point
MH Medical Alarm Restore Alarm condition eliminated Zone or point
MI Message A canned message is being sent Message number
MJ Medical Trouble Restore Trouble condition eliminated Zone or point
MR Medical Restoral Alarm/trouble condition has been eliminated Zone or point
MS Medical Supervisory Unsafe system condition exists Zone or point
MT Medical Trouble Zone disabled by fault Zone or point
MU Medical Unbypass Bypass has been removed Zone or point
NA No Activity There has been no zone activity for a programmed amount of Zone number
time
NC Network Condition A communications network has a specific reportable condition Network number
NF Forced Perimeter Arm Some zones/points not ready Area number
Data Short Long Address
Code Description Description Field
NL Perimeter Armed An area has been perimeter armed Area number
NM Perimeter Armed, User A user defined area has been perimeter armed Area number
Defined
NR Network Restoral A communications network has returned to normal operation Network number
NS Activity Resumed A zone has detected activity after an alert Zone number
NT Network Failure A communications network has failed Network number
OA Automatic Opening System has disarmed automatically Area number
OC Cancel Report Untyped zone cancel User number
OG Open Area System has been partially disarmed Area number
OH Early to Open from Alarm An area in alarm was disarmed before the opening window User number
OI Fail to Open An area has not been armed at the end of the opening window Area number
OJ Late Open An area was disarmed after the opening window User number
OK Early Open An area was disarmed before the opening window User number
OL Late to Open from Alarm An area in alarm was disarmed after the opening window User number
OP Opening Report Account was disarmed User number
OQ Remote Opening The system was disarmed from a remote location User number
OR Disarm From Alarm Account in alarm was reset/disarmed User number
OS Opening Keyswitch Account has been disarmed by keyswitch Zone or point
OT Late To Close System was not armed on time User number
OU Output State – Trouble An output on a peripheral device or NAC is not functioning Output number
OV Output State – Restore An output on a peripheral device or NAC is back to normal Output number
operation
OZ Point Opening A point, rather than a full area or account, disarmed Zone or point
PA Panic Alarm Emergency assistance request, manually activated Zone or point
PB Panic Bypass Panic zone has been bypassed Zone or point
PH Panic Alarm Restore Alarm condition eliminated Zone or point
PJ Panic Trouble Restore Trouble condition eliminated Zone or point
PR Panic Restoral Alarm/trouble condition has been eliminated Zone or point
PS Panic Supervisory Unsafe system condition exists Zone or point
PT Panic Trouble Zone disabled by fault Zone or point
PU Panic Unbypass Panic zone bypass has been removed Zone or point
QA Emergency Alarm Emergency assistance request Zone or point
QB Emergency Bypass Zone has been bypassed Zone or point
QH Emergency Alarm Restore Alarm condition has been eliminated Zone or point
QJ Emergency Trouble Restore Trouble condition has been eliminated Zone or point

QR Emergency Restoral Alarm/trouble condition has been eliminated Zone or point


Data Short Long Address
Code Description Description Field
QS Emergency Supervisory Unsafe system condition exists Zone or point
QT Emergency Trouble Zone disabled by fault Zone or point
QU Emergency Unbypass Bypass has been removed Zone or point
RA Remote Programmer Transmitter failed to communicate with the remote programmer Unused
Call Failed
RB Remote Program Begin Remote programming session initiated Unused
RC Relay Close A relay has energized Relay number
RD Remote Program Denied Access passcode incorrect Unused
RN Remote Reset A TRANSMITTER was reset via a remote programmer Unused
RO Relay Open A relay has de-energized Relay number
RP Automatic Test Automatic communication test report Unused
RR Power Up System lost power, is now restored Unused
RS Remote Program Success Remote programming successful Unused
RT Data Lost Dialer data lost, transmission error Line number
RU Remote Program Fail Remote programming unsuccessful Unused
RX Manual Test Manual communication test report User number
RY Test Off Normal Test signal(s) indicates abnormal condition(s) exist Zone or point
SA Sprinkler Alarm Sprinkler flow condition exists Zone or point
SB Sprinkler Bypass Sprinkler zone has been bypassed Zone or point
SC Change of State An expansion/peripheral device is reporting a new condition or Condition number
state change
SH Sprinkler Alarm Restore Alarm condition eliminated Zone or point
SJ Sprinkler Trouble Restore Trouble condition eliminated Zone or point
SR Sprinkler Restoral Alarm/trouble condition has been eliminated Zone or point
SS Sprinkler Supervisory Unsafe sprinkler system condition Zone or point
ST Sprinkler Trouble Zone disabled by fault Zone or point
SU Sprinkler Unbypass Sprinkler zone bypass has been removed Zone or point
TA Tamper Alarm Alarm equipment enclosure opened Zone or point
TB Tamper Bypass Tamper detection has been bypassed Zone or point
TC All Points Tested All point tested Unused
TE Test End Communicator restored to operation Unused
TH Tamper Alarm Restore An Expansion Device’s tamper switch restores to normal from Unused
an Alarm state
TJ Tamper Trouble Restore An Expansion Device’s tamper switch restores to normal from a Unused
Trouble state
TP Walk Test Point This point was tested during a Walk Test Point number
TR Tamper Restoral Alarm equipment enclosure has been closed Zone or point
TS Test Start Communicator taken out of operation Unused
Data Short Long Address
Code Description Description Field
TT Tamper Trouble Equipment enclosure opened in disarmed state Zone or point
TU Tamper Unbypass Tamper detection bypass has been removed Zone or point
TW Area Watch Start Area watch feature has been activated Unused
TX Test Report An unspecified (manual or automatic) communicator test Unused
TZ Area Watch End Area watch feature has been deactivated Unused
UA Untyped Zone Alarm Alarm condition from zone of unknown type Zone or point
UB Untyped Zone Bypass Zone of unknown type has been bypassed Zone or point
UG Unverified Event – Untyped A point assigned to a Cross Point group has gone into alarm Zone or point
but the Cross Point remained normal
UH Untyped Alarm Restore Alarm condition eliminated Zone or point
UJ Untyped Trouble Restore Trouble condition eliminated Zone or point
UR Untyped Zone Restoral Alarm/trouble condition eliminated from zone of unknown type Zone or point
US Untyped Zone Supervisory Unsafe condition from zone of unknown type Zone or point
UT Untyped Zone Trouble Trouble condition from zone of unknown type Zone or point
UU Untyped Zone Unbypass Bypass on zone of unknown type has been removed Zone or point
UX Undefined An undefined alarm condition has occurred Unused
UY Untyped Missing Trouble A point or device which was not armed is now logically missing Zone or point
UZ Untyped Missing Alarm A point or device which was armed is now logically missing Zone or point
VI Printer Paper In TRANSMITTER or RECEIVER paper in Printer number
VO Printer Paper Out TRANSMITTER or RECEIVER paper out Printer number
VR Printer Restore TRANSMITTER or RECEIVER trouble restored Printer number
VT Printer Trouble TRANSMITTER or RECEIVER trouble Printer number
VX Printer Test TRANSMITTER or RECEIVER test Printer number
VY Printer Online RECEIVER’S printer is now online Unused
VZ Printer Offline RECEIVER’S printer is now offline Unused
WA Water Alarm Water detected at protected premises Zone or point
WB Water Bypass Water detection has been bypassed Zone or point
WH Water Alarm Restore Water alarm condition eliminated Zone or point
WJ Water Trouble Restore Water trouble condition eliminated Zone or point
WR Water Restoral Water alarm/trouble condition has been eliminated Zone or point
WS Water Supervisory Water unsafe water detection system condition Zone or point
WT Water Trouble Water zone disabled by fault Zone or point
WU Water Unbypass Water detection bypass has been removed Zone or point
XA Extra Account Report CS RECEIVER has received an event from a non-existent Unused
account
XE Extra Point Panel has sensed an extra point not specified for this site Point number
XF Extra RF Point Panel has sensed an extra RF point not specified for this site Point number
Data Short Long Address
Code Description Description Field
XH RF Interference Restoral A radio device is no longer detecting RF Interference Receiver number
XI Sensor Reset A user has reset a sensor Zone or point
XJ RF Receiver Tamper A Tamper condition at a premises RF Receiver has been Receiver number
Restoral restored
XL Low Received Signal The RF signal strength of a reported event is below minimum Receiver number
Strength level
XM Missing Alarm - Cross Point Missing Alarm verified by Cross Point in Alarm (or missing) Zone or point
XQ RF Interference A radio device is detecting RF Interference Receiver number
XR Transmitter Battery Restoral Low battery has been corrected Zone or point
XS RF Receiver Tamper A Tamper condition at a premises receiver is detected Receiver number
XT Transmitter Battery Trouble Low battery in wireless transmitter Zone or point
XW Forced Point A point was forced out of the system at arm time Zone or point
XX Fail to Test A specific test from a panel was not received Unused
YA Bell Fault A trouble condition has been detected on a Local Bell, Siren, or Unused
Annunciator
YB Busy Seconds Percent of time receiver's line card is on-line Line card number
YC Communications Fail RECEIVER and TRANSMITTER Unused

YD Receiver Line Card Trouble A line card identified by the passed address is in trouble Line card number

YE Receiver Line Card A line card identified by the passed address is restored Line card number
Restored
YF Parameter Checksum Fail System data corrupted Unused
YG Parameter Changed A TRANSMITTER’S parameters have been changed Unused
YH Bell Restored A trouble condition has been restored on a Local Bell, Siren, or Unused
Annunciator
YI Overcurrent Trouble An Expansion Device has detected an overcurrent condition Unused
YJ Overcurrent Restore An Expansion Device has restored from an overcurrent Unused
condition
YK Communications Restoral TRANSMITTER has resumed communication with a Unused
RECEIVER
YM System Battery Missing TRANSMITTER/RECEIVER battery is missing Unused
YN Invalid Report TRANSMITTER has sent a packet with invalid data Unused
YO Unknown Message An unknown message was received from automation or the Unused
printer
YP Power Supply Trouble TRANSMITTER/RECEIVER has a problem with the power Unused
supply
YQ Power Supply Restored TRANSMITTER’S/RECEIVER’S power supply has been Unused
restored
YR System Battery Restoral Low battery has been corrected Unused
YS Communications Trouble RECEIVER and TRANSMITTER Unused
Data Short Long Address
Code Description Description Field
YT System Battery Trouble Low battery in control/communicator Unused
YU Diagnostic Error An expansion/peripheral device is reporting a diagnostic error Condition number
YW Watchdog Reset The TRANSMITTER created an internal reset Unused
YX Service Required A TRANSMITTER/RECEIVER needs service Unused
YY Status Report This is a header for an account status report transmission Unused
YZ Service Completed Required TRANSMITTER / RECEIVER service completed Mfr defined
ZA Freeze Alarm Low temperature detected at premises Zone or point
ZB Freeze Bypass Low temperature detection has been bypassed Zone or point
ZH Freeze Alarm Restore Alarm condition eliminated Zone or point
ZJ Freeze Trouble Restore Trouble condition eliminated Zone or point
ZR Freeze Restoral Alarm/trouble condition has been eliminated Zone or point
ZS Freeze Supervisory Unsafe freeze detection system condition Zone or point
ZT Freeze Trouble Zone disabled by fault Zone or point
ZU Freeze Unbypass Low temperature detection bypass removed Zone or point