Model: 1600REOZM
4-Cycle
380-480 V Diesel
Tier 1 EPA-Certified for Standard Features
Stationary Emergency Kohler Co. provides one-source responsibility for the
Applications generating system and accessories.
The generator set and its components are prototype-
Ratings Range tested, factory-built, and production-tested.
60 Hz 50 Hz
The generator set complies with ISO 8528-5, Class G3
Standby: kW 1625-1630 1380-1480
requirements for transient performance.
kVA 2031-2038 1725-1850
Prime: kW 1480 1280-1420 The generator set accepts rated load in one step.
kVA 1850 1600-1775 A standard one-year limited warranty covers all systems and
DCC : kW 1480 1280-1420 components. Two-, five-, and ten-year extended warranties are
kVA 1850 1600-1775 also available.
Alternator features:
o The pilot-excited, permanent magnet (PM) alternator
provides superior short-circuit capability
o The brushless, rotating-field generator has broad range
reconnectability.
t�-::1-W-n-=_.....E
:fl 1t1====i=1
.. Other features:
� :JI'� o Kohler designed controllers for guaranteed system
"\ - -�
\'\ integration and remote communication. See Controllers on
page 3
o The low coolant level shutdown prevents overheating
(standard on radiator models only).
o An electronic, isochronous governor delivers precise
frequency regulation.
• o Multiple circuit breaker configurations.
Generator Ratings
150°C Rise 125°C Rise 125°C Rise
Standby Rating Prime Rating DCC Rating
Alternator Voltage Ph Hz kW / kVA Amps kW / kVA Amps kW /kVA Amps
220/380 3 50 1480/1850 2811 1420/1775 2696 1420/1775 2696
7M4052 230/400 3 50 1448/1810 2613 1348/1685 2432 1348/1685 2432
240/415 3 50 1380/1725 2400 1280/1600 2226 1280/1600 2226
277/480 3 60 1630/2038 2451 1480/1850 2225 1480/1850 2225
7M4174 220/380 3 60 1625/2031 3086 1480/1850 2810 1480/1850 2810
RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is
available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. DCC :
Data Center Continuous Power ratings apply to Data Center installations where a reliable utility power is available and comply with Uptime institute Tier III and IV
requirements. At constant or varying load, the number of generator set operating hours is unlimited. Average load: ≤ 100%. For limited running time and base load ratings,
consult the factory. Obtain technical information bulletin (TIB-101) for rating guidelines and complete ratings definitions. GENERAL GUIDELINES FOR DERATION :
Altitude: Derate 5.0 % per 500 m (1640 ft) elevation above 1000 m (3280 ft) up to maximum altitude of 4000 m (13120 ft). Temperature: Derate 6.0 % per 10°C (18°F)
temperature above 40°C (104°F) up to maximum temperature of 60° C (140° F). The generator set manufacturer reserves the right to change the design and specifications
without notice and without any obligation or liability whatsoever.
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GSD5-09005 (1600REOZM) 03/18
Alternator Specifications
Specifications Generator
NEMA MG1, IEEE, and ANSI standards compliance for
Type 4-Pole, Rotating-Field temperature rise and motor starting.
Exciter type Brushless, Permanent-
Magnet Pilot Exciter Sustained short-circuit current of up to 300% of the
Voltage regulator Solid State, Volts/Hz rated current for up to 10 seconds.
Insulation: NEMA MG1
Sustained short-circuit current enabling downstream
Material . . . . . . . . . . . . . . . . . . . Class H, Synthetic, circuit breakers to trip without collapsing the
Nonhygroscopic
generator field.
Temperature rise . . . . . . . . . . . . 125°C Prime, 150°C Standby
Bearing: quantity, type 1, Sealed Self-ventilated and dripproof construction.
Coupling Flexible Disc
Superior voltage waveform from two-thirds pitch
Amortisseur windings Full
Rotor balancing 125% 60 Hz, 150% 50Hz
windings and skewed stator.
Voltage regulation, no-load to full-load Digital solid-state, volts-per-hertz voltage regulator
(with <0.5% drift due to temp Variation) 3-Phase Sensing, ±0.25% with ±0.25% no-load to full-load regulation.
One-step load acceptance 100% of Rating
Unbalanced load capability 100% of Rated Standby Brushless alternator with brushless pilot exciter for
Current excellent load response.
Peak motor starting kVA: (35% dip for voltages below)
480 V, 380 V 7M4052 (4 bus bar) . . 5500 (60Hz), 4000 (50Hz)
380 V 7M4174 (4 bus bar) . . 4200 (60Hz)
Application Data
Engine Engine Electrical
Engine Specifications 60 Hz 50 Hz Engine Electrical System 60 Hz 50 Hz
Engine model S16R-Y1 PTA-2 S16R-Y1 PTA-4 Battery charging alternator:
Ground (negative/positive) . . . . . . . Negative
Engine type 4-Cycle, Volts (DC) . . . . . . . . . . . . . . . . . . . . . 24
Ampere rating . . . . . . . . . . . . . . . . . 30
Turbocharged, Intercooled Starter motor rated voltage (DC) Dual, 24
Cylinder arrangement 16-V Battery, recommended cold cranking
Displacement, L (cu. in.) 65.4 (3989) amps (CCA):
Bore and stroke, mm (in.) 170 x 180 (6.69 x 7.09) Qty., CCA rating 4, 1000
Compression ratio 15.0:1 Battery voltage (DC) 12
Piston speed, m/min. (ft./min.) 648 (2126) 540 (1772)
Main bearings: quantity, type - Fuel
Rated rpm 1800 1500 Fuel System 60 Hz 50 Hz
Max. power at rated rpm, kWm (BHP) 1750 (2346) 1701 (2280) Fuel supply line, min. ID, mm (in.) 25 (1.0)
Cylinder head material Cast Iron Fuel return line, min. ID, mm (in.) 19 (0.75)
Crankshaft material Forged Steel Max. lift, engine-driven fuel pump, m (ft.) 1 (3)
Governor: type, make/model Electronic, Woodward Max. fuel flow, Lph (gph) 560 (148) 510 (135)
PROACT II
Max. fuel pump restriction, kPa (in. Hg) 10 (3.0)
Frequency regulation, no-load to full-load Isochronous
Fuel filter: quantity, type 4, Secondary
Frequency regulation, steady state ±0.25%
Recommended fuel #2 Diesel
Frequency Fixed
Air cleaner type, all models Dry Lubrication
Exhaust Lubricating System 60 Hz 50 Hz
Exhaust System 60 Hz 50 Hz Type Full Pressure
Exhaust manifold type Dry Oil pan capacity, L (qt.) 200 (211)
3
Exhaust flow at rated kW, m /min. 404 (14265) 385 (13594)
Oil pan capacity with filter, L (qt.) 230 (243)
(cfm) Oil filter: quantity, type 4, Cartridge
Exhaust temperature at rated kW,
Oil Cooler Water-Cooled
dry exhaust, C ( F)
520 (968) 519 (966)
Maximum allowable back pressure,
kPa (in. Hg) 5.9 (1.7)
Exhaust outlet size at engine hookup,
mm (in.) See ADV drawing
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GSD5-09005 (1600REOZM) 03/18
Application Data Controllers
Cooling
Radiator System 60 Hz 50 Hz
Ambient temperature 40 (104)
Engine jacket water capacity, L (gal.) 170 (44.9)
Radiator system capacity, including
engine, L (gal.) 250 (66.1) 315 (83.3)
Engine jacket water flow, Lpm (gpm) 1850 (489) 1650 (436)
®
Heat rejected to cooling water at rated Decision-Maker 550 Controller
Audiovisual annunciation with NFPA 110 Level 1 capability.
kW, dry exhaust, kW (Btu/min.) 1135 (64532) 1063 (60452)
Programmable microprocessor logic and digital display features.
Water pump type Centrifugal Generator safeguard circuit protection.
Fan diameter, including blades, mm (in.) 1800 (70.9) 12- or 24-volt engine electrical system capability.
Fan, kWm (HP) 45 ( 60) 45 ( 60) Remote start, remote annunciation, and remote communication options.
Refer to G6-46 for additional controller features and accessories.
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
Operation Requirements Additional Standard Features
®
Air Requirements 60 Hz 50 Hz Alternator Protection (standard with Decision-Maker 550)
Radiator-cooled cooling air, Electronic, Isochronous Governor
3
m /min. (scfm) ~ 2435 (86000) 2311 (81600) Oil Drain Extension
3
Combustion air, m /min. (cfm) 155 (5473) 146 (5155) Operation and Installation Literature
Heat rejected to ambient air:
Pilot-Excited, Permanent Magnet Generator (PMG)
Engine, kW (Btu/min.) . . . . . . . . 135 (7744) 127 (7254)
Generator, kW (Btu/min.) . . . . . . 82 (4663)
3
~ Air density = 1.20 kg/m (0.075 lbm/ft )
3
Dimensions and Weights
Overall Size, L x W x H, mm (in.): 5768 x 2212 x 2516
Fuel Consumption 60 Hz 50 Hz (227.1 x 87.1 x 99.05)
Diesel, Lph (gph) at % load Standby Rating W eight (radiator model), wet, max., kg (lb.): 13 300 (29296)
100% 430 (113.7) 383 (101.4)
75% 321 (84.9) 283 (74.8)
50% 224 (59.1) 195 (51.5)
25% 127 (33.6) 109 (28.8)
Diesel, Lph (gph) at % load Prime Rating
100% 389 (102.8) 344 (91.1)
75% 295 (77.9) 258 (68.3)
50% 209 (55.2) 180 (47.7)
25% 124 (32.8) 105 (27.7)
NOTE: This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-565-3381, Fax 920-459-1646 North Asia, S.E.Asia & Australasia
For the nearest sales and service outlet in the 7 Jurong Pier Road Singapore 619159
US and Canada, phone 1-800-544-2444 Phone (65) 6264-6422, Fax (65) 6264-6455
www.KohlerPowerSystems.com www.kohlerPower.com.sg
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.