Flow Calc Manual
Flow Calc Manual
ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
For use with Chemetron FM-200 Flow Calculation Program
CHEM-200 Version 4.2.3
Contents
LIST OF ILLUSTRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
LIST OF TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
REVISION PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
GENERAL COMMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Agent Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 The Piping System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 The Discharge Nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 FLOW CALCULATIONS 12
APPENDIX 53
Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Example 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Example 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Example 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Example 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page i
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
LIST OF ILLUSTRATIONS
FIGURE NUMBER DESCRIPTION OF ILLUSTRATION PAGE NO.
1.2.4.1A Graph: FM-200 Calculated cylinder Pressure vs.
Percent of Agent Supply Discharged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2.4.1B Graph: FM-200 Cylinder Discharge Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.2 Graph: FM-200 Pipiline Densities vs. Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.3 Graph: FM-200 Agent Temperature vs. Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.7A Graph: Sample Bull Head Tee Test - No Correction for
Mechanical Separation Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3.7B Graph: Sample Side-thru Tee Tests - Effect of Mechanical
Phase Separation on side Branch Discharge . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4.1 Graph: FM-200 Specific Nozzle Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4.2 Graph: Chemetron FM-200 8 Port Nozzle Efficiencies . . . . . . . . . . . . . . . . . . . . . . 9
1.4.5 Graph: FM-200 Cylinder Pressure Recession . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.4.6 Graph: FM-200 Mid-Discharge Storage Pressure vs.
Percent of Agent in Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.1.5 Graph: Minimum Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.1.6A Orientation of Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.1.1.6B Minimum Distance From Elbow to Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3A Plan View - Above Floor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.3B Plan View - Underfloor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.4.1 Flow Calc Program Screen View - System Commands . . . . . . . . . . . . . . . . . . . . 20
2.4.1.1.A Flow Calc Program Screen View - Project Data . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.4.1.1.B Flow Calc Program Screen View - Revision Version . . . . . . . . . . . . . . . . . . . . . . 22
2.4.1.1.C Flow Calc Program Screen View - Cylinder Data . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4.1.1.D2 Flow Calc Program Screen View - Configuration Variables - Altitude . . . . . . . . . 24
2.4.1.1.D3 Flow Calc Program Screen View - Configuration Variables - Calc Increment . . . 25
2.4.1.2 Flow Calc Program Screen View - Hazard Data . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.4.1.3 Flow Calc Program Screen View - Piping Data . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.4.1.3.A7 Flow Calc Program Screen View - Piping Data - Type . . . . . . . . . . . . . . . . . . . . . 29
2.4.1.3.A8 Flow Calc Program Screen View - Piping Data - Size . . . . . . . . . . . . . . . . . . . . . 30
2.4.1.3.C Flow Calc Program Screen View - Piping Data - Fixed Pounds & Orifices . . . . . 33
2.4.1.4.A Flow Calc Program Screen View - Calculation Results . . . . . . . . . . . . . . . . . . . . 35
2.4.1.4.B Flow Calc Program Screen View - Nozzle Performance . . . . . . . . . . . . . . . . . . . 36
2.4.1.4.C Flow Calc Program Screen View - Hazard Concentration Results . . . . . . . . . . . . 41
2.4.1.4.D Flow Calc Program Screen View - Error Messages . . . . . . . . . . . . . . . . . . . . . . . 42
2.4.1.4.D1 Flow Calc Program Screen View - Error Screen Examples . . . . . . . . . . . . . . . . . 45
2.4.1.5 Flow Calc Program Screen View - Print Data and Results
or Print Output Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.4.1.5.C Flow Calc Program Screen View - Configure Printer . . . . . . . . . . . . . . . . . . . . . . 47
2.4.1.5.D Flow Calc Program Screen View - Printer Font Selection . . . . . . . . . . . . . . . . . . 48
2.4.3.1 Flow Calc Program Screen View - Load Data File . . . . . . . . . . . . . . . . . . . . . . . . 49
2.4.5 Flow Calc Program Screen View - Volume/Weight/Concentration
Calculator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page ii
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
LIST OF TABLES
TABLE NUMBER DESCRIPTION PAGE NO.
2.4.1.1.C Cylinder Capacity Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4.1.3A8 Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fitting Equivalent Length Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Cylinder/Check Valve Equivalent Length Table . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3/8" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 37
1/2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 37
3/4" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 38
1" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . . 38
1-1/4" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . 39
1-1/2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . 39
2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . . 40
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page iii
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
REVISION SHEET
Date of issue for original and revised pages is:
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page iv
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
REVISION SHEET
Section Number Page Numbers Revision Date
Section 2.3.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 - 17 . . . . . . . . . . . . . . . . June 26, 2001
Section 2.3 (Figures 2.3A & 2.3B) . . . . . . . . . . . . 18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Section 2.3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 . . . . . . . . . . . . . . . November 1, 1997
Section 2.3.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 . . . . . . . . . . . . . . . . . . June 26, 2001
Section 2.3.4 - 2.3.5 . . . . . . . . . . . . . . . . . . . . . . 18 - 19 . . . . . . . . . . . . . November 1, 1997
Section 2.4 - 2.4.1.1.C . . . . . . . . . . . . . . . . . . . . 19 - 22 . . . . . . . . . . . . . . . January 5, 2001
Section 2.4.1.1.C . . . . . . . . . . . . . . . . . . . . . . . . . . 23 . . . . . . . . . . . . . . . . October 15, 2001
Section 2.4.1.1.C - 2.4.1.2 . . . . . . . . . . . . . . . . . . 24 - 28 . . . . . . . . . . . . . . . . June 26, 2001
Section 2.4.1.3. - 2.4.1.3.A . . . . . . . . . . . . . . . . . 28 - 32 . . . . . . . . . . . . . . . January 5, 2001
Section 2.4.1.3.B . . . . . . . . . . . . . . . . . . . . . . . . . . 32 . . . . . . . . . . . . . . . . October 15, 2001
Section 2.4.1.3.B - 2.4.1.3.C . . . . . . . . . . . . . . . 33 - 34 . . . . . . . . . . . . . . . January 5, 2001
Section 2.4.1.4.A1 . . . . . . . . . . . . . . . . . . . . . . . . 34 . . . . . . . . . . . . . . . . . . June 26, 2001
Section 2.4.1.4.A2 - 2.4.1.4.C . . . . . . . . . . . . . . 35 - 41 . . . . . . . . . . . . . . . January 5, 2001
Nozzle Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 - 40 . . . . . . . . . . . . . . . . June 26, 2001
Section 2.4.1.4.D . . . . . . . . . . . . . . . . . . . . . . . . 42 - 44 . . . . . . . . . . . . . . . . June 26, 2001
Section 2.4.1.4.D1 - 2.5.1.4 . . . . . . . . . . . . . . . . 45 - 52 . . . . . . . . . . . . . . . January 5, 2001
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 . . . . . . . . . . . . . . . November 1, 1997
Appendix - Example #1 . . . . . . . . . . . . . . . . . . . 54 - 63 . . . . . . . . . . . . . . January 23, 2003
Appendix - Example #2 . . . . . . . . . . . . . . . . . . . 64 - 71 . . . . . . . . . . . . . . January 23, 2003
Appendix - Example #3 . . . . . . . . . . . . . . . . . . . 72 - 81 . . . . . . . . . . . . . . January 23, 2003
Appendix - Example #4 . . . . . . . . . . . . . . . . . . . 82 - 90 . . . . . . . . . . . . . . January 23, 2003
Appendix - Example #5 . . . . . . . . . . . . . . . . . . 91 - 100 . . . . . . . . . . . . . . January 23, 2003
Appendix - Example #6 . . . . . . . . . . . . . . . . . . 101 - 109 . . . . . . . . . . . . . January 23, 2003
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page v
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Foreword
Chemetron Fire Systems reserves the right to revise and improve its products as it deems necessary without
notification. This publication is intended to describe the state of this product at the time of its publication, and
may not reflect the product at all times in the future. The software screen prints depicted in this manual are
presented for reference and example purposes only and may not reflect the most current version of the FM-200
Flow Calculation software (CHEM-200.exe and support files).
This technical manual provides the necessary information for designing and performing flow calculations for
a Chemetron FM-200 Engineered System. This is a single volume technical manual arranged in 2 sections,
followed by an Appendix.
This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose, without
the express written consent of Chemetron Fire Systems.
Any questions concerning the information presented in this manual should be addressed to the Matteson Office.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page vi
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
General Comments
Factory Mutual Research Corporation does not accept metric unit calculations. They will not be approved
for Factory Mutual installations.
FM-200 Systems using concentrations below 7.0% are not UL & ULC Listed nor Factory Mutual Approved.
UL, ULC & FMRC require multiple tiers of nozzles for heights above 16' 0" (4.88 M).
The calculation method used by Chemetron Fire systems has been investigated using A-53, Schedule 40
pipe and 300 lb malleable iron fittings for test installations.
When specified limitations noted in this manual and in the Chemetron software are not maintained, there
is the risk that the system will not supply the required amount of extinguishing agent.
For installation, design, operation and maintenance of Chemetron Fire Systems FM-200 Fire Suppression
Systems, please refer to the Beta & Gamma Series Engineered Systems Design, Installation,
Operation and Maintenance Manual, Part Number 30000030, and the Sigma Series Engineered
Systems Design, Installation, Operation and Maintenance Manual, Part Number 30000049.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page vii
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page viii
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
1.1 Introduction
1.1.1 Decomposition
An adverse characteristic of FM-200 is that it will decompose into toxic and corrosive byproducts if
exposed to fire or to objects heated above 1,300°F (704°C). Such decomposition is kept at a negligible
level by rapidly discharging the agent so as to extinguish the flames promptly. This minimizes the quantity
of agent that passes through a flame front at concentrations too low for flame extinguishment. The
problem of FM-200 decomposition has led to a requirement in NFPA 2001 that discharge of 95 percent
of the agent mass needed to achieve minimum design concentration be discharged within 10 seconds.
This 10 second discharge time requirement is very important in hazards where flammable liquids are
likely to be the fuel.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 1
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 2
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
400
350
300
250
PRESSURE (PSIA)
200
150
100
50
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
PERCENT DISCHARGED
Figure 1.2.4.1A Calculated pressure in the storage container versus the percent of agent supply discharged from the container is
plotted for the 360 psig system.
Figure 1.2.4.1B Pressure versus time data taken during an actual FM-200 discharge at 70 lbs/cu.ft. fill density.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 3
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
90
80
70
50% 78% 97% LEAVING CYLINDER
0% 28% 47% IN PIPE
60
DENSITY LB/CU FT
50
40
30
20
10
0
250 200 150 100 50 0
PRESSURE PSIA
Figure 1.3.2 Calculated pipeline densities plotted versus pipeline pressure for increments of liquid leaving the cylinder at
various stages during a discharge.
The density of the two-phase mixture in the pipeline can be calculated on the basis of the thermodynamic
properties of the agent taking into account the effects of the nitrogen used for superpressurization. The
density of the agent as it leaves the cylinder varies from the start to the completion of the liquid phase
of the discharge. The starting density is lowest for the first portion of liquid to leave the cylinder and
becomes progressively greater until the final portion of liquid leaves the cylinder. Figure 1.3.2 shows
the density-pressure curves for increments of liquid leaving the cylinder at various stages during the
discharge of a 360 psig (25.8 bar) storage container. Curves are shown for the 50th percentile to leave
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 4
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
the cylinder (pipe holds 0% of the agent supply) and the 97th percentile to leave the cylinder (pipe holds
approximately 50% of the agent supply during discharge). The pipeline pressure density condition is
calculated based on the actual percent agent held in the pipe during discharge. If necessary, “percent
in the pipe” values other than 0% and 50% are found by extrapolation.
1.3.3 Temperature
Figure 1.3.3 Calculated agent temperature versus pressure as agent flows through pipeline.
As the agent flows from the cylinder into the pipeline, the drop in cylinder pressure is accompanied by
a drop in temperature. Figure 1.3.3 is a plot of agent temperature versus pressure in the cylinder during
the discharge of a 360 psig (25.8 bar) storage container filled to 70 lb/ft3 (1121.3 kg/m3). As the agent
flows down the pipeline, the additional drop in pressure is likewise accompanied by a further drop in
the agent temperature. The net effect is the introduction of a cold liquid into the pipeline at ambient
temperature.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 5
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 6
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
130%
125%
115%
110%
105%
100%
95%
90%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
% FLOW
Figure 1.3.7A The effects of “mechanical” separation as reflected in the quantity of agent discharged from nozzles
supplied by a bullhead tee.
100%
98%
96%
SIDE BRANCH WT ACT/WT CALC (%)
94%
92%
90%
88%
86%
84%
82%
80%
0 5 10 15 20 25 30 35 40
% FLOW
Figure 1.3.7B The effect of “mechanical” separation on the quantity of agent discharged from nozzles fed by a side-
thru tee.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 7
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
50
45
40
35
SPECIFIC RATE (LB/SEC/SQ IN)
25
20
15
10
0
0 50 100 150 200 250
PRESSURE (PSIA)
Figure 1.4.1
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 8
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
NOTE
THE 1/4" NOZZLES ARE NOT UL LISTED OR FMRC APPROVED.
100%
90%
80%
70%
60%
EFFICIENCY (%)
50%
40%
30%
1/4" NPT NOZZLE
20%
10%
0%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90%
PERCENT PIPE AREA
Figure 1.4.2 Nozzle efficiencies for the Chemetron 8 port nozzle are related to the ratio of total orifice area to feed-pipe area. See
Note in Paragraph 1.4.2.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 9
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
350
300
MID-DISCHARGE PRESSURE
250
PRESSURE (PSIA)
IN CYLINDER
200
150
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
PERCENT DISCHARGED FROM CYLINDER
Figure 1.4.5
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 10
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
1.4.6 Percent-in-the-Pipeline
The calculated average cylinder pressures during discharge are based on the above consideration. Figure
1.4.6 shows the relationship between the average pressure in the cylinder during nozzle discharge and
the ratio of the pipe volume to the volume of the agent supply expanded under flowing conditions.
This latter quantity shall be referred to simply as the Percent-in-the-Pipe.
300
280
FILL DENSITY
240
40 LB/CU. FT.
220
50 LB/CU.FT.
200
60 LB/CU.FT.
180
70 LB/CU.FT.
160
140
120
100
0.0% 10.0% 20.0% 30.0% 40.0% 50.0% 60.0% 70.0% 75% 80.0%
MAX
% IN PIPE
Figure 1.4.6 The mid-discharge pressure in the cylinder during nozzle discharge is a function of the percent of agent supply
needed to fill the pipeline.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 11
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
2 Flow Calculations
2.1.1 Limitations
Any distribution system that does not employ exactly the same actual and equivalent lengths of pipe
from the storage cylinder to each nozzle, and the same orifice sizes for each nozzle has some degree
of system imbalance. Such systems are, however, the rule rather than the exception. Due to structural
components present at the job site, it is often impossible to install perfectly balanced piping systems.
However, it is desirable to maintain balanced piping whenever possible.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 12
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Pipe ID (mm)
0 20 40 60 80 100 120 140 160 180
350 160
120
250
5" 100
200
80
150 4"
60
100 1 1/2"
1/2" 1" 3" 40
NOTE: Branches leading to discharge nozzles with
no intervening flow splits may use flow rates no
2 1/2"
50 1 1/4" lower than 60% of the plotted minimum rates.
3/4" 2" 20
3/8"
0 0
0 1 2 3 4 5 6 7
Pipe ID (inches)
Figure 2.1.1.5 Minimum Flow Rates. The pipe that can be used for a given flow rate is based upon the minimum flow rate
required to maintain complete turbulence.
There must be a minimum of 10 nominal pipe diameters between an elbow and the inlet to any tee (does
not apply in manifolds where flow is combining).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 13
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Figure 2.1.1.6A - Orientation of Tees: Tee outlets should be placed in the horizontal plane to minimize gravitational effects
on liquid - vapor separation
Figure 2.1.1.6B - Minimum Distance From Elbow to Tee: Minimizes centripetal effects on liquid - vapor separation before
entering a flow split.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 14
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
If the program is used to calculate an “as-built” system, it will calculate lower nozzle pressures - an error
or warning message will result if pressures below the pressures required for the approval agencies are
calculated.
A second limitation on nozzle orifice sizing is a limit on the ratio of flow through the nozzle to the theoretical
maximum flow that the feed pipe branch could carry under the calculated pressure, density and
temperature conditions. This limit is 65% of the maximum feed pipe flow. The computer checks this.
This limitation serves two purposes: 1) it insures that the nozzle, and not the equivalent length of the
pipe run, will control the amount of discharge from that nozzle; and 2) it provides an automatic check
against calculating systems having nozzle flow rates that cannot be achieved under the calculated terminal
pressure conditions.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 15
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
When the elevation difference between outlet tees is in excess of 30 feet (9.1 m), consideration should
be given to rerouting piping to reduce the elevation difference between tees. Even though sound
engineering theory is used to predict pressure changes due to elevation, no actual testing has been
performed incorporating the combination of maximum and/or minimum limits with elevations.
1. If nozzles are located above the container outlet, then the maximum elevation difference between
the container outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest)
shall not exceed 30 feet (9.1 m).
2. If nozzles are only located below the container outlet, then the maximum elevation difference between
the container outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest)
shall not exceed 30 feet (9.1 m).
3. If nozzles are located both above and below the container outlet, then the maximum elevation
difference between the furthest horizontal pipe runs or discharge nozzles (whichever is furthest)
shall not exceed 30 feet (9.1 m).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 16
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
The 360° nozzle cannot be mounted in a corner or against a wall. The maximum discharge radius
is 26.6 ft (8.1 m). A single nozzle may be used to flood a rectangular area of a nominal 1,412
ft2 (131.2 m2), with the longest side of this rectangle not to exceed 37 feet 7 inches (11.45 m).
Nozzles must be oriented so that a pair of orifice holes parallels the wall of the enclosure.
These nozzles should be centered in the area of protection when multiple nozzles are discharged
into the same hazard.
The maximum throw distance of the 180° nozzle is 37.0 ft (11.3 m). The maximum distance between
180° nozzles is 37.6 feet (11.5 m). The maximum coverage distance from the nozzle to a wall is
18.8 feet (5.7 m). The 180° nozzle must be installed at no more than 6 inches (15.2 cm) from the
enclosure wall and at a maximum of 9.25 inches (23.5 cm) down from the ceiling.
For UL, ULC, and FMRC, the maximum enclosure height that may be flooded by a single tier
of nozzles is 16 feet (4.88 m) with the nozzle located no more than 9.25 inches (23.5 cm) below
the ceiling.
Before using a single nozzle at the maximum area or volume rating, consideration should be given to
whether the contents of the hazard might be damaged by the resultant high velocity discharge. In hazards
such as computer rooms or areas where fragile apparatus is stored, the number of nozzles used to flood
an area should be increased so as to limit discharge velocities to a safe level. After considering possible
damage to the hazard by the FM-200 discharge and determining a reasonable area [not to exceed 1,412
ft2 (131.2 m2)] to be covered by each nozzle, the nozzles should be located. The Chemetron 8 port nozzles
must be placed in the center of each area. The discharge rate for each nozzle should be based upon
flooding the volume protected by that nozzle within the design discharge time.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 17
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Figure 2.3A Plan View - Above Floor System Figure 2.3B Plan View - Underfloor System
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 18
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
The Chemetron FM-200 flow calculation program has been divided into four main areas: Commands
Available, Output and File Utilities, and Units. By clicking the system of units, either English (En-
gineering units of pounds and feet) or Metric (Units of kilograms and meters) may be used in the data
input file. Note that available cylinder sizes, pipe sizes and nozzle orifice sizes are the same regardless
of the unit of measure chosen. Available pipe sizes are given in Table 2.4.1.3.A8. Available cylinder
sizes are given in Table 2.4.1.1.C. Available nozzles can be found in the nozzle tables following section
2.4.1.4.B.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 19
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
System Information
Hazard Information
Piping Model Data
Calculate and Display Results
Clear All Current Data
For reference only, a Vol/Lbs/% calculator, a CARDOX valve equivalent length chart, and a minimum
flow rate chart have been included.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 20
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Project Data
Revision
Cylinder Data
Configuration Variables
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 21
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
B. Revision: This data field is used to track versions/changes on a specific data file and/or submittal.
1. Pounds/Cylinder (Kilograms/Cylinder): This data field is used to input the actual amount of
FM-200 required per cylinder.
2. Number of Cylinders: The number of cylinders required to contain the amount of FM-200
required for a discharge. This value may be entered by one of two means: the value may be
directly entered into this field or a value may be selected from the pop-down window, which can
be accessed by clicking onto the arrow at the right of the data field.
3. Cylinder Capacity: This data field is used to input the description of the actual type of cylinders
to be used. The nominal cylinder capacity is displayed for the chosen FM-200 cylinder assembly
along with its minimum and maximum FM-200 cylinder capacity. By clicking on the arrow at
the right of the field, additional cylinder choices may be viewed. User Specified Beta and
Gamma can be selected from the list for special cylinder capacities, in which case the cylinder
volume capacity will need to be inputted and either the Beta or Gamma valve selected.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 22
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
WARNING
WHEN THE CYLINDER CAPACITY FIELD FOR “USER SPECIFIED” BETA AND GAMMA CYLINDERS IS USED, FACTORY
MUTUAL RESEARCH CORPORATION APPROVAL AND UL LISTING HAVE BEEN VOIDED.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 23
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
4. Max Capacity: This is a read only field and is intended to inform the user of the maximum
capacity of FM-200 to which the cylinder selected may be filled.
5. Pipe Temp: The initial average pipe temperature shall be inputted here to accurately calculate
the vapor portion of the discharge. UL listing and FMRC approval is based upon a temperature
of 70°F ±10°F (21.1°C ±5.5°C). Calculations performed on systems where the cylinders are
not maintained within this range may not be accurate and the required quantities of agent may
not be discharged from one or more discharge nozzles.
6. Cylinder Volume [ft3 (m3)]: This heading will only appear when either the Beta User Specified
or the Gamma User Specified cylinder option is selected. This shall be used to accurately com-
pute the minimum and maximum fills for a unique cylinder.
7. Main/Reserve: Automatically adds the equivalent length of a required check valve for main and
reserve systems.
1. Report Title: The data entered here will appear in the general heading area on all printouts.
The intended use is to allow Chemetron distributors to incorporate their company name into
the printouts.
2. Altitude: This data field allows for the installation of a system from -3000 feet (-.914 km) below
sea level up to 10000 feet (3.05 km) above sea level. These values may be selected from the
pop-down window. Other values may be input as required.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 24
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3. Calc Increment (sec): The calculation increment is the method in which the calculation portion
of the program adjusts the discharge flow rate. The program is designed to perform calculations
by adjusting the rate of discharge to achieve the desired pounds to each nozzle within 10
seconds. In order to optimize the pipe sizes, the program begins at a slower flow rate, a time
nearer to 10 seconds. If it finds that the data file does not compute results within known
parameters, the rate will be adjusted and the calculation will be run again. The increments in
which the program will adjust the rate is directly related to the time the program assumes for
the next calculation run. This data field allows the user to select the incremental time for the
recalculation process. The more problematic the system design is, the lower the increment
should be set. By adjusting the time to a smaller increment, and therefore the discharge rate
to a smaller amount for each calculation run, the better the chance for the difficult system to
produce satisfactory results. However, the normal system design will calculate properly with
an incremental time of 0.2 seconds. The range is predefined. Additional time increments are
not available to the user.
4. Calculation: The calculation may be performed by either Automatic or Manual means. The
automatic mode will not allow the user to view the current attempt to solve the data into a
satisfactory result and does not require any user interface during the calculation. The manual
mode will pause after each attempt to solve the system design parameters. This will allow the
user to view the results - acceptable or not - of the previous calculation run. This manual mode
may aid the user in troubleshooting a problematic design.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 25
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
6. Exclude Pipe Sizes: When selected, it will force the flow calculation module to ignore a given
pipe size(s).
NOTE
DUE TO PRESSURE AND FLOW RATE LIMITATIONS, THIS MAY INCREASE THE DIFFICULTY IN GETTING VALID
CALCULATION RESULTS.
Hazard Data
Area Data
Area Nozzle List
An example of an area would be a room. All nozzles must be in the same room. Individual data must
be entered for each area to ensure that the appropriate amount of FM-200 is divided accordingly. This
portion of the program will model the data for each area. In the example shown in Figure 2.4.1.2, the
concentration selected was 7.44%. UL and FMRC will accept no less than a 7% design concentration
in any application.
Additional areas may be added to the data list to calculate more than one area simultaneously. Example:
room area, underfloor and false ceiling.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 26
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
A. Hazard Data
The first section is used to input the hazard area name(s) for reference, concentration required and
the temperature.
4. Total Volume: This field is provided for information only and may not be modified. This field
will indicate the total volume of the area as input into the Area Data section below.
B. Area Data
Enter the appropriate values in the Length, Width and Height fields and the program will compute
the correct room volume. As you will note, the Width and Height fields are both set to a default of
1. If the volume is known, enter it into the Length data field and leave the Width and Height fields
as 1. Data is input into the Current field line located directly below the columns heading line. Once
the data has been entered, clicking on the Add button will place the data into the grid just under the
Current line.
Each area will have one or more nozzles within it. This section is intended to model the nozzles
for a particular area. Each nozzle has a unique ID number. These numbers are automatically
assigned and are incremental. Two types of nozzles are included in the program: the 8 Port 360°
discharge pattern (Style F) nozzle and the 8 Port 180° discharge pattern (Style G) nozzle.
1. Add: Once the correct values have been entered into the editing (Current) line, clicking on the
Add button within that section will temporarily save the data to the screen. Another line of data
may then be entered. As you will note, while the data line just added has been placed into the
grid below, the values still remain on the editing line. If the next line of input is similar to the
previous, change the values requiring modification and click on the Add button again. Clicking
on any line in the data grid will cause its values to appear in the editing line. Therefore, if your
next line of input contains similar data to a previously entered line, clicking on that line will place
its values into the editing line where they can be modified as necessary. Click on the Add button
to add the data to the grid in the next available line position.
2. Edit: The name of the area you wish to modify must appear in the Current line of the Hazard
Data section. Clicking on the appropriate area name with the mouse will place this information
on the Current line. As you will note, the appropriate corresponding data will appear in the Area
Data and Area Nozzle List sections. Move the mouse to the field requiring editing and click on
the item to be modified. This data should now be reflected on the editing line where values can
be modified as necessary. Once the modification is complete, click on the Edit button to
temporarily save the modifications to the screen.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 27
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3. Delete: To delete a line of data from the data file, the name of the area containing the data to
be deleted must appear in the Current line of the Hazard Data section. Click on the area name
with the mouse so that the appropriate information is reflected on the Current line. Again, the
corresponding data will appear in the Area Data and Area Nozzle List sections. Move the mouse
to the appropriate field and click on the line to be deleted. This data should now be reflected on
the editing line. Clicking on the Delete button will delete this data.
1. Nodes: These points identify the section of pipe, nozzle or a cylinder that is being modeled.
4. Cyl Qty: The quantity of cylinders flowing through this specific section of piping.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 28
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
6. Elev: Change of elevation within the pipe section, expressed in feet or meters.
7. Type: Type of pipe to be installed. There are several types available, accessible through the
pop-down, for use:
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 29
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
8. Size: The size of pipe in the section. By accessing the pop-down window, choices from zero
(0) (no fixed pipe size) to 6" (150 mm) are available.
NOTE
BOTH THE INTERNAL PIPE DIAMETER AND THE MASS OF THE PIPE ARE USED IN THE HYDRAULIC CALCULATION.
IT IS ESSENTIAL THAT THE PIPE USED FOR INSTALLATION HAVE A DIAMETER AND WALL THICKNESS (WITHIN
TOLERANCES SPECIFIED IN ANSI AND ASTM STANDARD) USED IN THE CALCULATION. THE WEIGHT PER UNIT
LENGTH OF THE PIPE IS DIRECTLY RELATED TO THE INTERNAL DIAMETER AND WALL THICKNESS. THE FOLLOWING
TABLE GIVES THE NOMINAL PIPE SIZES WITH THE PIPE DIAMETER AND WEIGHT PER UNIT LENGTH USED IN THE
HYDRAULIC CALCULATION.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 30
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 31
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
c. Thru: The beginning of the pipe section begins with a thru tee. The default of zero (0)
indicates no tee and 1 indicates a thru tee. If the side branch of a tee is used to provide
pressure for tripping a pressure switch or pressure release, it is treated as an equivalent
number of elbows. In this case, 0.6 should be included in the 90's field.
d. Side: The beginning of the pipe section begins with a side tee. The default of zero (0)
indicates no tee and 1 indicates a side tee. If one of the thru branches of a tee is used to
provide pressure for tripping a pressure switch or pressure release, it is treated as an
equivalent number of elbows. In this case, 2.0 should be included in the 90's field.
11. Pounds (Kgs) Req'd: The number of pounds (kilograms) required to be discharged from this
particular nozzle, when the option Fixed Pounds is selected. If the Fixed Orifice option
is selected, the value in this field will represent the nozzle orifice drill diameter.
NOTE
THE ALPHA CYLINDER/VALVE ASSEMBLIES ARE CURRENTLY NOT UL & ULC LISTED NOR FMRC APPROVED.
HOWEVER, THE EQUIVALENT LENGTH NOTED ABOVE FOR THE ALPHA VALVE HAS BEEN DETERMINED BY UL AND
FMRC AFTER WITNESSING TESTING.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 32
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3. Insert: The Insert button is used to insert a line of data into the data grid in a specific location
other than at the next available position at the bottom of the grid. In order to insert a line, click
onto the highest line in the data grid that must be moved down. This data line will be highlighted
in the grid as well as be copied into the edit line above. Modify the data within the edit line. You
may use Reset to Defaults to remove the existing values from the edit line. Once the data on
the edit line is correct, click on the Insert button and the lines in the data grid will be relocated
down one line position and the data in the edit line will be placed into the open position.
4. Delete: The Delete button is used to delete a line of data in the data grid. Highlight the data
line within the data grid by clicking on it with the mouse. Click on the delete button. A verification
message will appear to validate the request. Should you confirm the request, the data line will
be deleted and any data lines below it will be moved up to compensate for the deleted line of
data.
It is possible to input either the pounds or kilograms required for each nozzle or the existing nozzle
orifice drill diameter. The program has the flexibility to calculate an existing system model by allowing
the nozzle orifice diameter to be input as data. The combination of both weight required from one
nozzle and the orifice diameter of the second nozzle is not permitted and cannot be calculated.
Figure 2.4.1.3.C Flow Calc Program - Piping Data - Fixed Pounds & Fixed Orifices
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 33
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
1. Fixed Pounds (Kgs): This radio button should be on when the values in the Pounds (Kgs)
Required column indicate the quantity of pounds (Kgs) required to be discharged from a particular
nozzle.
2. Fixed Orifices: This radio button should be on when the values in the Pounds (Kgs) Required
column indicate the actual nozzle drill diameter in inches (mm) for a particular nozzle.
Calculation Results
Nozzle Performance
Hazard Concentration Results
Error Messages
A. Calculation Results
The calculation results screen depicts the cylinder information and the piping model information.
1. Conditions
a. Storage Pressure: The starting pressure just prior to the cylinder actuation.
b. Average Cylinder Pressure: The average cylinder pressure during the discharge.
c. Average Initial Pipe Temp: The average ambient pipe temperature at the beginning of the
discharge.
d. Fill Density: The fill density [lbs/ft3 (kgs/m3)] of the cylinder. For all systems, the range is
35 to 70 lb/ft3 (560.7 to 1121.4 kg/m3).
e. Percent of Agent in Pipe: Based on the volume of discharge pipe. This value represents
what percentage of the total amount of FM-200 is in the piping network during the discharge.
f. Average Discharge Time: This value represents the average discharge time of all of the
nozzles.
i. Total Lbs (Kgs) of FM-200: The total amount of FM-200 within all the cylinders.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 34
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
2. Piping Results
a. Section Nodes: The starting and ending nodes for a particular section of the pipe model.
b. Nominal Pipe Size: The computed or inputted pipe size and schedule.
e. EQL: Total equivalent length of the section of pipe. This includes pipe, elbows, tees, coup-
lings, unions, valves, and any additional information inputted into the equivalent length column
of the data file.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 35
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
B. Nozzle Performance
3. Stock Number: The Chemetron Fire Systems’ stock number for the particular nozzle.
4. Style: The manufacturing designation for the particular configuration of the nozzle.
5. Drill Diameter: The specific drill diameter in inches (mm) for each of the nozzle ports.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 36
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3/8 inch 8-Port Styles F & G Nozzle 1/2 inch 8-Port Styles F & G Nozzle
DRILL DRILL DRILL DRILL DRILL DRILL DRILL DRILL
DRILL DRILL DRILL DRILL
DIA DIA DIA DIA DIA DIA DIA DIA
# # # #
inches mm inches mm inches mm inches mm
48 0.0760 1.930 33 0.1130 2.870 41 0.0960 2.438 23 0.1540 3.912
5/64 0.0781 1.984 32 0.1160 2.946 40 0.0980 2.489 5/32 0.1562 3.967
47 0.0785 1.994 31 0.1200 3.048 39 0.0995 2.527 22 0.1570 3.988
46 0.0810 2.057 1/8 0.1250 3.175 38 0.1015 2.578 21 0.1590 4.039
45 0.0820 2.083 30 0.1285 3.264 37 0.1040 2.642 20 0.1610 4.089
44 0.0860 2.184 29 0.1360 3.454 36 0.1065 2.705 19 0.1660 4.216
43 0.0890 2.261 28 0.1405 3.569 7/64 0.1094 2.779 18 0.1695 4.305
42 0.0935 2.375 9/64 0.1406 3.571 35 0.1100 2.794 11/64 0.1719 4.366
3/32 0.0938 2.383 27 0.1440 3.658 34 0.1110 2.819 17 0.1730 4.394
41 0.0960 2.438 26 0.1470 3.734 33 0.1130 2.870 16 0.1770 4.496
40 0.0980 2.489 25 0.1495 3.797 32 0.1160 2.946 15 0.1800 4.572
39 0.0995 2.527 24 0.1520 3.861 31 0.1200 3.048 14 0.1820 4.623
38 0.1015 2.578 23 0.1540 3.912 1/8 0.1250 3.175 13 0.1850 4.699
37 0.1040 2.642 5/32 0.1562 3.967 30 0.1285 3.264 3/16 0.1875 4.763
36 0.1065 2.705 22 0.1570 3.988 29 0.1360 3.454 12 0.1890 4.801
7/64 0.1094 2.779 21 0.1590 4.039 28 0.1405 3.569 11 0.1910 4.851
35 0.1100 2.794 20 0.1610 4.089 9/64 0.1406 3.571 10 0.1935 4.915
34 0.1110 2.819 27 0.1440 3.658 9 0.1960 4.978
26 0.1470 3.734 8 0.1990 5.055
25 0.1495 3.797 7 0.2010 5.105
24 0.1520 3.861 13/64 0.2031 5.159
NOTE
NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS
PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS
ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES TOGETHER
WITH EQUIVALENT MILLIMETERS FOR REFERENCE PURPOSES ONLY. EVEN THOUGH THE METRIC OPTION IS CHOSEN
AND THE NOZZLE ORIFICES ARE SELECTED USING METRIC UNITS, THE CALCULATION WILL BE PERFORMED IN
ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 37
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3/4 inch 8-Port Styles F & G Nozzle 1 inch 8-Port Styles F & G Nozzle
DRILL DRILL DRILL DRILL DRILL DRILL DRILL DRILL DRILL DRILL
DRILL DRILL
# DIA DIA # DIA DIA DIA DIA DIA DIA
# #
inches mm inches mm inches mm inches mm
1/8 0.1250 3.175 11 0.1910 4.851 21 0.1590 4.039 A 0.2340 5.944
30 0.1285 3.264 10 0.1935 4.915 20 0.1610 4.089 15/64 0.2344 5.954
29 0.1360 3.454 9 0.1960 4.978 19 0.1660 4.216 B 0.2380 6.045
28 0.1405 3.569 8 0.1990 5.055 18 0.1695 4.305 C 0.2420 6.147
9/64 0.1406 3.571 7 0.2010 5.105 11/64 0.1719 4.366 D 0.2460 6.248
27 0.1440 3.658 13/64 0.2031 5.159 17 0.1730 4.394 E 0.2500 6.350
26 0.1470 3.734 6 0.2040 5.182 16 0.1770 4.496 F 0.2570 6.528
25 0.1495 3.797 5 0.2055 5.220 15 0.1800 4.572 G 0.2610 6.629
24 0.1520 3.861 4 0.2090 5.309 14 0.1820 4.623 17/64 0.2656 6.746
23 0.1540 3.912 3 0.2130 5.410 13 0.1850 4.699 H 0.2660 6.756
5/32 0.1562 3.967 7/32 0.2188 5.558 3/16 0.1875 4.763 I 0.2720 6.909
22 0.1570 3.988 2 0.2210 5.613 12 0.1890 4.801 J 0.2770 7.036
21 0.1590 4.039 1 0.2280 5.791 11 0.1910 4.851 K 0.2810 7.137
20 0.1610 4.089 A 0.2340 5.944 10 0.1935 4.915 9/32 0.2812 7.142
19 0.1660 4.216 15/64 0.2344 5.954 9 0.1960 4.978 L 0.2900 7.366
18 0.1695 4.305 B 0.2380 6.045 8 0.1990 5.055 M 0.2950 7.493
11/64 0.1719 4.366 C 0.2420 6.147 7 0.2010 5.105 19/64 0.2969 7.541
17 0.1730 4.394 D 0.2460 6.248 13/64 0.2031 5.159 N 0.3020 7.671
16 0.1770 4.496 E 0.2500 6.350 6 0.2040 5.182 5/16 0.3125 7.938
15 0.1800 4.572 F 0.2570 6.528 5 0.2055 5.220 O 0.3160 8.026
14 0.1820 4.623 G 0.2610 6.629 4 0.2090 5.309 P 0.3230 8.204
13 0.1850 4.699 17/64 0.2656 6.746 3 0.2130 5.410 21/64 0.3281 8.334
3/16 0.1875 4.763 H 0.2660 6.756 7/32 0.2188 5.558 Q 0.3320 8.433
12 0.1890 4.801 2 0.2210 5.613 R 0.3390 8.611
1 0.2280 5.791
NOTE
NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS
PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS
ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES TOGETHER
WITH EQUIVALENT MILLIMETERS FOR REFERENCE PURPOSES ONLY. EVEN THOUGH THE METRIC OPTION IS CHOSEN
AND THE NOZZLE ORIFICES ARE SELECTED USINGMETRIC UNITS, THE CALCULATION WILL BE PERFORMED IN
ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 38
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
1-1/4 inch 8-Port Styles F & G Nozzle 1-1/2 inch 8-Port Styles F & G Nozzle
DRILL DRILL DRILL DRILL DRILL DRILL DRILL DRILL
DRILL DRILL DRILL DRILL
DIA DIA DIA DIA DIA DIA DIA DIA
# # # #
inches mm inches mm inches mm inches mm
4 0.2090 5.309 N 0.3020 7.671 D 0.2460 6.248 11/32 0.3438 8.733
3 0.2130 5.410 5/16 0.3125 7.938 E 0.2500 6.350 S 0.3480 8.839
7/32 0.2188 5.558 O 0.3160 8.026 F 0.2570 6.528 T 0.3580 9.093
2 0.2210 5.613 P 0.3230 8.204 G 0.2610 6.629 23/64 0.3594 9.129
1 0.2280 5.791 21/64 0.3281 8.334 17/64 0.2656 6.746 U 0.3680 9.347
A 0.2340 5.944 Q 0.3320 8.433 H 0.2660 6.756 3/8 0.3750 9.525
15/64 0.2344 5.954 R 0.3390 8.611 I 0.2720 6.909 V 0.3770 9.576
B 0.2380 6.045 11/32 0.3438 8.733 J 0.2770 7.036 W 0.3860 9.804
C 0.2420 6.147 S 0.3480 8.839 K 0.2810 7.137 25/64 0.3906 9.921
D 0.2460 6.248 T 0.3580 9.093 9/32 0.2812 7.142 X 0.3970 10.084
E 0.2500 6.350 23/64 0.3594 9.129 L 0.2900 7.366 Y 0.4040 10.262
F 0.2570 6.528 U 0.3680 9.347 M 0.2950 7.493 13/32 0.4062 10.317
G 0.2610 6.629 3/8 0.3750 9.525 19/64 0.2969 7.541 Z 0.4130 10.490
17/64 0.2656 6.746 V 0.3770 9.576 N 0.3020 7.671 27/64 0.4219 10.716
H 0.2660 6.756 W 0.3860 9.804 5/16 0.3125 7.938 7/16 0.4375 11.113
I 0.2720 6.909 25/64 0.3906 9.921 O 0.3160 8.026 29/64 0.4531 11.509
J 0.2770 7.036 X 0.3970 10.084 P 0.3230 8.204 15/32 0.4688 11.908
K 0.2810 7.137 Y 0.4040 10.262 21/64 0.3281 8.334 31/64 0.4844 12.304
9/32 0.2812 7.142 13/32 0.4062 10.317 Q 0.3320 8.433 1/2 0.5000 12.700
L 0.2900 7.366 Z 0.4130 10.490 R 0.3390 8.611 33/64 0.5156 13.096
M 0.2950 7.493 27/64 0.4219 10.716
19/64 0.2969 7.541 7/16 0.4375 11.113
NOTE
NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS
PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS
ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES TOGETHER
WITH EQUIVALENT MILLIMETERS FOR REFERENCE PURPOSES ONLY. EVEN THOUGH THE METRIC OPTION IS CHOSEN
AND THE NOZZLE ORIFICES ARE SELECTED USING METRIC UNITS, THE CALCULATION WILL BE PERFORMED IN
ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 39
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
NOTE
NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS
PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS
ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES TOGETHER
WITH EQUIVALENT MILLIMETERS FOR REFERENCE PURPOSES ONLY. EVEN THOUGH THE METRIC OPTION IS CHOSEN
AND THE NOZZLE ORIFICES ARE SELECTED USING METRIC UNITS, THE CALCULATION WILL BE PERFORMED IN
ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 40
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
3. Pounds (Kgs) Discharged: The quantity of FM-200 that was discharged into a particular hazard
area.
5. Concentration Achieved: Based on the results of the calculation, the concentration that was
achieved.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 41
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
D. Error Messages
This screen will display various piping model input errors and/or system calculation errors. The
following is a list of system design errors that may appear.
5. FIXED PIPE SIZE IN NOZZLE SECTION ## - ##. NOZZLE SECTION MAY NOT BE GREATER
THAN 2 INCH (50 MM) PIPE.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 42
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
8. ERROR--PIPE DIAMETER CODE MUST BE >0 AND <=15 IN SEC ## - ##. PIPE DIAMETER
CODE FOR THIS SECTION IS ###. DATA FILE IS CORRUPTED.
21. PRESSURE DROPS BELOW 59 PSI (4.1 BAR) IN SEC ## - ## (Fatal error during iterative
calculating process -- not a system limit. System limit is 125 PSIA minimum nozzle pressure.)
22. PERCENT IN PIPE CALCULATED AS ###. CHECK FOR FIXED PIPE SIZES, EXTREME
PIPE LENGTHS.
23. ####### ITERATIONS COMPLETED. NOZZLE PRESSURES AND FLOW RATES DO NOT
CONVERGE. ALL PIPE SIZES LEADING TO NOZZLE ### ARE MAXIMUM.
25. PRESSURE ENTERING TEE SEC ## TO ## EXCEEDS UL LIMIT OF 91% AND FM LIMIT
OF 90% OF AVERAGE CYLINDER PRESSURE. TEE BRANCH IS TOO CLOSE TO CYLINDER
MANIFOLD OR PIPE LEADING TO TEE IS TOO LARGE (for systems using only Style F nozzles;
no Style G nozzles).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 43
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
26. PRESSURE ENTERING TEE SEC ## TO ## IS LESS THAN FM LIMIT OF 67.5% OF AVERAGE
CYLINDER PRESSURE. TEE BRANCH IS TOO FAR FROM CYLINDER MANIFOLD.
REDESIGN TO REDUCE PRESSURE DROP FROM MANIFOLD TO TEE INLET (for systems
using Style G nozzles or a combination of Style F & Style G nozzles).
27. PRESSURE ENTERING TEE SEC ## TO ## IS LESS THAN UL LIMIT OF 63% AND FM LIMIT
OF 67.5% OF AVERAGE CYLINDER PRESSURE. TEE BRANCH IS TOO FAR FROM
CYLINDER MANIFOLD. REDESIGN TO REDUCE PRESSURE DROP FROM MANIFOLD TO
TEE INLET (for systems using only Style F nozzles; no Style G nozzles).
28. SEC ## TO ## BULLHEAD TEE MINOR FLOW BRANCH CARRIES ## PERCENT OF FLOW.
MINIMUM BRANCH FLOW FROM BULLHEAD TEE IS 30 PERCENT.
29. SIDE OUTLET TEE BRANCH CARRIES ## PERCENT FLOW. MAXIMUM SIDE OUTLET
BRANCH FLOW IS 35 PERCENT.
30. SEC ## TO ## SIDE OUTLET TEE BRANCH CARRIES ## PERCENT OF FLOW. MAXIMUM
SIDE OUTLET BRANCH FLOW IS 10 PERCENT.
31. NOZZLE ## AREA EQUALS ## % FEED PIPE AREA (LIMIT 1/4 NPT=75%).
34. NOZZLE PRESSURE FOR ### IS BELOW 125 PSIA (7.60 BAR).
38. PERCENT AGENT IN PIPE IS ###. THIS IS OVER MAXIMUM OF 75 PERCENT PERMITTED.
39. PERCENT AGENT IN PIPE IS ##.##%. THIS MEETS UL & ULC LISTING CRITERIA OF 75%
OR LESS BUT EXCEEDS FM APPROVAL LIMIT OF 70%.
40. FLOW RATE IN SEC ## - ## IS LESS THAN ##.# MINIMUM REQUIRED FOR PIPE SIZE.
42. FIXED ORIFICE SYSTEM FAILS TO CONVERGE WITHIN ±3.5%. CONVERGENCE WAS
WITHIN ± ### PERCENT. SYSTEM MUST BE REDESIGNED OR INSTALLATION MUST BE
SUBJECT TO A FULL DISCHARGE TEST TO PROVE PROPER AGENT CONCENTRATION
AND DISTRIBUTION.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 44
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Figure 2.4.1.4.D1 Additional examples of error screens that may appear while running the Flow Calc Software program.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 45
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
Figure 2.4.1.5 Flow Calc Program - Print Data and Results or Print Output Results
A. Items to Print
1. Input Data Listing: When this option is selected, clicking on the adjacent option box will output
the data file.
2. Calculation Results: The selection of this option will output the results of the calculation.
3. BOM: The mechanical FM-200 system Bill of Material, including pipe and pipe fittings.
B. Output Units
1. English: This option will output the required information with standard English units.
NOTE
THE INPUT DATA FILE WILL BE OUTPUT IN THE SAME UNITS OF MEASUREMENT AS THAT SELECTED FOR THE DATA
INPUT. THE UNITS USED TO CREATE THE INPUT DATA FILE WILL BE DESIGNATED AS "(CURRENT)" AFTER THE
APPROPRIATE UNITS. HOWEVER, THE CALCULATION RESULTS MAY BE PRINTED IN EITHER UNITS OF MEASURE,
REGARDLESS OF WHICH UNITS WERE USED FOR THE INPUT DATA FILE.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 46
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
C. Configure Printer
There are numerous types of printers on the market and the program is designed to incorporate
a wide range of printers. It is advisable to click on Configure Printer to verify the current WindowsTM
selected printer.
D. Printer Font
There are virtually hundreds of fonts available in the industry today. Even though the program will
accept and use a number of them, the suggested font is ARIAL. This font is commonly found within
the WindowsTM list of available fonts. However, there are a number of acceptable fonts and by
selecting and trying these fonts, based on the numerous styles and types of printers, Chemetron
cannot assure you of satisfactory results. The printout uses various configurations and sizes to
produce its hard copy printout.
E. Print To File
Should this option be selected, the data requested will be sent to a file on the selected disk drive.
The user will be asked to verify the drive, path, and filename prior to the data being written to the
file. The outputted data will be in Standard ASCII format and may be imported into various programs
for incorporation into drawings, manuals, etc.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 47
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
F. Print
Clicking on this command will start the printing or writing of the selected data.
2.4.2 Output
This area will allow the user to export either the data file or calculation results.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 48
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
2.4.3.1 Load
An existing data file, stored on a disk drive, may be loaded into the program for modifications or recal-
culation.
2.4.3.2 Save
The current data file may be saved to a disk drive for historical information.
2.4.3.3 Delete
A data file may be erased from a disk drive. However, please note that once the data file has been
deleted, it cannot be retrieved.
2.4.4 Exit
The exit button will unload the program and return you to the previous WindowsTM system screen.
In addition, two of the remaining three fields must be inputted and the third will be solved. The remaining
three fields are:
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 49
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
C. Volume
D. Weight
E. Concentration
For example, if the quantity of agent and the volume are known, the concentration may be computed.
If the volume and the concentration are known, the amount of FM-200 can be computed. Should the
concentration and the amount of FM-200 be known, the calculator will determine the volume in which
these parameters will fit.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 50
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
(1)
Normally, the change in elevation head is zero, so it can be dropped from the above equation. When
a change in elevation is present in a system, the resultant loss or gain in pressure can be calculated
separately from the basic two-phase flow equation. The basic flow equation is as follows:
(2)
(3)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 51
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
(4)
The total terminal pressure must be used since it is the measure of energy available to drive the flowing
media from the orifice(s). (See Sections 1.4.1 and 1.4.2).
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 52
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX
This appendix documents six calculation examples. Examples 1 & 6 utilize a Beta cylinder and
Examples 2, 3, 4, & 5 utilize Gamma cylinders. Example 6 was calculated using Metric units
of measure. Preceding each program example are the initial data acquisition worksheets.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 53
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
VOLUME
Lx W = Sq Ft x H= Cu Ft
Lx W = Sq Ft x H= Cu Ft
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 54
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 55
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
0'-6"
301
18'-0"
7'-0"
OUTLET OF
DISCHARGE TUBE
BASE OF
DIB TUBE
Isometric Drawing for the system flow calculation detailed in Example 1.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 56
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 57
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
EXAMPLE #1 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. At the completion and verification
of the inputted data, the current data should be saved (refer to Section 2.4.3.2 - Save). The data is then
ready to Calculate and Display (refer to Section 2.4.1.4 - Calculate and Display Results). The next 5 screens
illustrate the results of the calculation.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 58
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 59
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
EXAMPLE #1 - Figure 8 Refer to Section 2.4.1.5 - Print Data and Results or Print Output Results.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 60
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
System Information
Storage Pressure (psig): 360.0 Average Cyl Pressure (psia): 240
Ave Initial Pipe Temp (°F): 70 Fill Density (lbs/cu.ft.): 45.9
Percent Agent in Pipe: 19.7 Average Discharge Time (sec): 9.5
Quantity of Cylinders: 1 Type of Cylinder: Beta 95
Amount per Cylinder (lbs): 63 Total Amount of Agent (lbs): 63
Altitude Relative to Sea (ft): 0
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.ft.) (lbs) Requested Achieved
ROOM 1,823 63 7 7.08
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID (in) Number Style (in) Size (lbs)
301 3/4-SCH 40 10371362 F 0.2187 7/32 63.00
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 61
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
Error Messages
FM200FLC
NO ERRORS
Time and date of calculation 18:26:17 01-31-2003
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 62
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #1
Cylinder Information
Amount of FM-200 per Cylinder (lbs): 63.0 Type of Cylinder: Beta 95
Quantity of Cylinders: 1 Cylinder Maximum Capacity (lbs) 96
Cylinder Initial Temperature (°F) 70 Altitude Relative to Sea (ft): 0
Hazard Information
Hazard: ROOM Concentration Required: 7.00 Temperature (°F): 70.0
Nozzle(s): 301 8 Port Style F Dimensions (ft): 13.50 X 13.50 X 10.00
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 3.2 40T 1-1/4 0 0 0 0 801 60.0
2 3 25.0 7.0 40T 0 1 0 0 0 0 0.0
3 301 0.5 -0.5 40T 0 1 0 0 0 62.16 0.0
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803 = 3 cylinders, etc...).
This data file has fixed agent amount specified for the nozzle.
1 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 63
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
VOLUME
Lx W = Sq Ft x H= Cu Ft
Lx W = Sq Ft x H= Cu Ft
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 64
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 65
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 66
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 67
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
EXAMPLE #2 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. At the completion and verification of
the inputted data, the current data should be saved (refer to Section 2.4.3.2 - Save). The data is then ready
to Calculate and Display (refer to Section 2.4.1.4 - Calculate and Display Results). The next 5 screens
illustrate the results of the calculation.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 68
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
System Information
Storage Pressure (psig): 360 Average Cyl Pressure (psia): 193
Ave Initial Pipe Temp (°F): 70 Fill Density (lbs/cu.ft.): 50.3
Percent Agent in Pipe: 57.8 Average Discharge Time (sec): 7.2
Quantity of Cylinders: 1 Type of Cylinder: Gamma 250
Amount per Cylinder (lbs): 197.0 Total Amount of Agent (lbs): 197.0
Altitude Relative to Sea (ft): 0
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.ft.) (lbs) Requested Achieved
ROOM 5775 197.0 7 7
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 69
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID (in) Number Style (in) Size (lbs)
301 1-SCH 40 10371418 F 0.3230 P 98.50
302 1-SCH 40 10371418 F 0.3230 P 98.50
Error Messages
FM200FLC
Nozzle pressure for 301 meets FM approval limit but is below UL listing limit of 125 psia (8.58 bar)
Nozzle pressure for 302 meets FM approval limit but is below UL listing limit of 125 psia (8.58 bar)
Time and date of calculation 08:12:09 01-31-2003
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 70
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #2
Cylinder Information
Amount of FM-200 per Cylinder (lbs): 197.0 Type of Cylinder: Gamma 250
Quantity of Cylinders: 1 Cylinder Maximum Capacity (lbs) 274
Cylinder Initial Temperature (°F) 70 Altitude Relative to Sea (ft): 0
Hazard Information
Hazard: ROOM Concentration Required: 7.00 Temperature (°F): 70.0
Nozzle(s): 301 8 Port Style F Dimensions (ft): 25.00 X 23.10 X 10.00
302 8 Port Style F
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 3.5 40T 2 0 0 0 0 801 51.0
2 3 100.0 5.0 40T 0 1 0 0 0 0 0.0
3 4 8.0 0.0 40T 0 0 0 1 0 0 0.0
4 301 1.0 -1.0 40T 0 1 0 0 0 98.475 0.0
3 5 8.0 0 40T 0 0 0 1 0 0 0.0
5 302 1.0 -1.0 40T 0 1 0 0 0 98.475 0.0
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803= 3 cylinders, etc...).
This data file has fixed agent amount specified for the nozzle.
Note 2: The data input file shown here may not agree with the data used for the flow calculation.
The data input file may have been changed since the calculation was performed.
1 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 71
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
VOLUME
Lx W = Sq Ft x H= 20590 Cu Ft
Lx W = Sq Ft x H= Cu Ft
Lx W = Sq Ft x H= Cu Ft
Total = Sq Ft 20590 Cu Ft
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 72
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 73
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 74
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 75
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
EXAMPLE #3 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. At the completion and verification of
the inputted data, the current data should be saved (refer to Section 2.4.3.2 - Save). The data is then ready
to Calculate and Display (refer to Section 2.4.1.4 - Calculate and Display Results). The next 5 screens
illustrate the results of the calculation.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 76
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 77
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
System Information
Storage Pressure (psig): 360 Average Cyl Pressure (psia): 197
Ave Initial Pipe Temp (°F): 70 Fill Density (lbs/cu.ft.): 60.0
Percent Agent in Pipe: 30.2 Average Discharge Time (sec): 9.6
Quantity of Cylinders: 3 Type of Cylinder: Gamma 250
Amount per Cylinder (lbs): 235.0 Total Amount of Agent (lbs): 705.0
Altitude Relative to Sea (ft): 0
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 78
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.ft.) (lbs) Requested Achieved
ROOM 20590 705.0 7 7.02
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID (in) Number Style (in) Size (lbs)
301 1-1/2-SCH 40 10371365 F 0.4375 7/16 176.25
302 1-1/2-SCH 40 10371365 F 0.4375 7/16 176.25
303 1-1/2-SCH 40 10371365 F 0.4375 7/16 176.25
304 1-1/2-SCH 40 10371365 F 0.4375 7/16 176.25
Error Messages
FM200FLC
NO ERRORS
Time and date of calculation 8:13:22 01-31-2003
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 79
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
Cylinder Information
Amount of FM-200 per Cylinder (lbs): 235.0 Type of Cylinder: Gamma 250
Quantity of Cylinders: 3 Cylinder Maximum Capacity (lbs) 274
Cylinder Initial Temperature (°F) 70 Altitude Relative to Sea (ft): 0
Hazard Information
Hazard: ROOM Concentration Required: 7.00 Temperature (°F): 70.0
Nozzle(s): 301 8 Port Style F Dimensions (ft): 20590.00 X 1.00 X 1.00
302 8 Port Style F
303 8 Port Style F
304 8 Port Style F
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 3.5 40T 2 0 0 0 0 801 64.0
2 3 6.0 0.0 40T 0 0 0 0 0 803 0.0
3 4 24.0 4.0 40T 0 2 0 0 0 0 0.0
4 5 8.0 0.0 40T 0 0 0 1 0 0 0.0
5 6 8.0 0.0 40T 0 0 0 1 0 0 0.0
6 301 1.0 -1.0 40T 0 1 0 0 0 175.5525 0.0
5 7 8.0 0.0 40T 0 0 0 1 0 0 0.0
7 302 1.0 -1.0 40T 0 1 0 0 0 175.5525 0.0
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 80
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #3
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803 = 3 cylinders, etc...).
This data file has fixed agent amount specified for the nozzle.
Note 2: The data input file shown here may not agree with the data used for the flow calculation.
The data input file may have been changed since the calculation was performed.
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 81
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
VOLUME
Lx W = Sq Ft x H= Cu Ft
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 82
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 83
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 84
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 85
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
EXAMPLE #4 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. At the completion and verification of
the inputted data, the current data should be saved (refer to Section 2.4.3.2 - Save). The data is then ready
to Calculate and Display (refer to Section 2.4.1.4 - Calculate and Display Results). The next 5 screens
illustrate the results of the calculation.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 86
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 87
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
System Information
Storage Pressure (psig): 360 Average Cyl Pressure (psia): 253
Ave Initial Pipe Temp (°F): 70 Fill Density (lbs/cu.ft.): 46.8
Percent Agent in Pipe: 9.5 Average Discharge Time (sec): 9.4
Quantity of Cylinders: 1 Type of Cylinder: Gamma 250
Amount per Cylinder (lbs): 183.0 Total Amount of Agent (lbs): 183.0
Altitude Relative to Sea (ft): 0
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.ft.) (lbs) Requested Achieved
ROOM 4800 163.9 7.00 7.00
SUBFLOOR 480 19.1 7.00 8.08
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 88
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID (in) Number Style (in) Size (lbs)
301 1-1/4-SCH 40 10371364 F 0.3480 S 163.86
302 1/2-SCH 40 10371361 F 0.1406 9/64 19.14
Error Messages
FM200FLC
Orifice diameters and pipe sizes are fixed in input data.
NO ERRORS
Time and date of calculation 18:35:09 01-30-2003
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 89
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #4
Cylinder Information
Amount of FM-200 per Cylinder (lbs): 183.0 Type of Cylinder: Gamma 250
Quantity of Cylinders: 1 Cylinder Maximum Capacity (lbs) 274
Cylinder Initial Temperature (°F) 70 Altitude Relative to Sea (ft): 0
Hazard Information
Hazard: ROOM Concentration Required: 7.00 Temperature (°F): 70.0
Nozzle(s): 301 8 Port Style F Dimensions (ft): 24.00 X 20.00 X 10.00
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 3.5 40T 2 0 0 0 0 801 51.0
2 3 3.0 1.0 40T 1-1/4 1 0 0 0 0 0.0
3 4 4.0 3.0 40T 1-1/4 1 1 0 0 0 0.0
4 301 10.5 -1.0 40T 1-1/4 1 0 0 0 0.348 0.0
3 5 8.0 -7.0 40T 1/2 1 0 1 0 0 0.0
5 302 11.0 -1.0 40T 1/2 2 0 0 0 0.1406 0.0
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803 = 3 cylinders, etc.).
This data file has fixed agent amount specified for the nozzle.
Note 2: The data input file shown here may not agree with the data used for the flow calculation.
The data input file may have been changed since the calculation was performed.
1 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 90
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
VOLUME
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 91
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 92
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 93
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 94
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
EXAMPLE #5 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. At the completion and verification of
the inputted data, the current data should be saved (refer to Section 2.4.3.2 - Save). The data is then ready
to Calculate and Display (refer to Section 2.4.1.4 - Calculate and Display Results). The next 5 screens
illustrate the results of the calculation.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 95
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 96
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
System Information
Storage Pressure (psig): 360 Average Cyl Pressure (psia): 265
Ave Initial Pipe Temp (°F): 70 Fill Density (lbs/cu.ft.): 42.7
Percent Agent in Pipe: 21.5 Average Discharge Time (sec): 9.9
Quantity of Cylinders: 1 Type of Cylinder: Gamma 550
Amount per Cylinder (lbs): 343.0 Total Amount of Agent (lbs): 343.0
Altitude Relative to Sea (ft): 0
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 97
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.ft.) (lbs) Requested Achieved
STORAGE ROOM 1440 49.1 7.00 7.00
LABORATORY 3200 109.1 7.00 7.00
OFFICE AREA 3600 123.3 7.00 7.02
CONTROL ROOM 1800 61.5 7.00 7.00
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID (in) Number Style (in) Size (lbs)
304 3/4-SCH 40 10371362 F 0.2344 15/64 49.13
303 1-SCH 40 10371363 F 0.2950 M 109.15
301 1-1/4-SCH 40 10371364 F 0.3480 S 123.26
302 3/4-SCH 40 10371362 F 0.2380 B 61.46
Error Messages
FM200FLC
Orifice diameters and pipe sizes are fixed in input data.
No Errors
Time and date of calculation 12:35:05 02-03-2003
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 98
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
Cylinder Information
Amount of FM-200 per Cylinder (lbs): 343.0 Type of Cylinder: Gamma 550
Quantity of Cylinders: 1 Cylinder Maximum Capacity (lbs) 563
Cylinder Initial Temperature (°F) 70 Altitude Relative to Sea (ft): 0
Hazard Information
Hazard: STORAGE ROOM Concentration Required: 7.00 Temperature (°F): 70.0
Nozzle(s): 304 8 Port Style F Dimensions (ft): 9.00 X 16.00 X 10.00
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 3.5 40T 2 0 0 0 0 801 51.0
2 3 6.0 4.0 40T 2 1/2 1 0 0 0 801 0.0
3 4 2.0 0.0 40T 2 1/2 1 0 0 0 0 0.0
4 5 10.0 0.0 40T 3/4 0 0 1 0 0 0.0
5 304 1.0 -1.0 40T 3/4 1 0 0 0 0.2344 0.0
4 6 10.0 0.0 40T 2 0 1 0 0 0 0.0
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 99
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #5
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803 = 3 cylinders, etc...).
This data file has fixed agent amount specified for the nozzle.
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 100
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
VOLUME
Lx W = Sq M x H= Cu M
Lx W = Sq M x H= Cu M
FM-200 REQUIRED (REFER TO TABLES BELOW AND/OR THE EQUATION AS NOTED ON PAGE 2)
STORAGE REQUIRED
Qty Cylinder Minimum Fill Maximum Fill Qty Cylinder Minimum Fill Maximum Fill
Used Size Lbs (Kgs) Lbs (Kgs) Used Type Lbs (Kgs) Lbs (Kgs)
ALPHA BETA
10 Lb 6 (2.7) 12 (5.4) 40 Lb 21 (9.5) 41 (18.6)
20 Lb 12 (5.4) 23 (10.4) 55 Lb 28 (12.7) 55 (24.9)
GAMMA 95 Lb 48 (21.8) 96 (43.5)
150 Lb 82 (37.2) 163 (73.9) SIGMA
250 Lb 138 (62.6) 274 (124.3) 600 Lb 304 (137.9) 607 (275.3)
400 Lb 211 (95.7) 421 (191.0) 750 Lb 455 (206.4) 910 (412.8)
500 Lb 282 (127.9) 500 (226.8) 1000 Lb 620 (281.2) 1,000 (562.0)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 101
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
Ft Km PSIA cm Hg
FM-200
Specific -3,000 -0.92 16.25 84.0 1.11
(t)
40 5.0 2.0678 0.1294 0.0364 0.5816 0.0421 0.6719 0.0478 0.7642 2,000 0.61 13.64 70.5 0.93
3,000 0.92 13.12 67.8 0.89
50 10.0 2.1146 0.1320 0.0356 0.5700 0.0411 0.6585 0.0468 0.7490
4,000 1.22 12.58 65.0 0.86
60 15.0 2.1612 0.1347 0.0348 0.5589 0.0402 0.6457 0.0458 0.7344
5,000 1.52 12.04 62.2 0.82
70 20.0 2.2075 0.1373 0.0341 0.5483 0.0394 0.6335 0.0448 0.7205 6,000 1.83 11.53 59.6 0.78
80 25.0 2.2538 0.1399 0.0334 0.5382 0.0386 0.6217 0.0439 0.7071 7,000 2.13 11.03 59.6 0.75
90 30.0 2.2994 0.1425 0.0327 0.5284 0.0378 0.6104 0.0430 0.6943 8,000 2.44 10.64 55.0 0.72
9,000 2.74 10.22 52.8 0.69
100 35.0 2.3452 0.1450 0.0321 0.5190 0.0371 0.5996 0.0422 0.6819
10,000 3.05 9.77 50.5 0.66
110 40.0 2.3912 0.1476 0.0315 0.5099 0.0364 0.5891 0.0414 0.6701
NOTE: Multiply the correction factor by the
120 45.0 2.4366 0.1502 0.0309 0.5012 0.0357 0.5790 0.0406 0.6586
sea level design quantity of FM-200 to
130 50.0 2.4820 0.1527 0.0303 0.4929 0.0350 0.5694 0.0398 0.6476 obtain the correct quantity for a given alti-
tude.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 102
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
.2 m
5m
2m
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 103
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
EXAMPLE #6 - Figure 1 Refer to Section 2.4.1.1 - System Information. UNITS OF MEASURE SHOWN ARE METRIC
DESIGNATIONS.
EXAMPLE #6 - Figure 2 Refer to Section 2.4.1.2 - Hazard Data. UNITS OF MEASURE SHOWN ARE METRIC
DESIGNATIONS.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 104
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
EXAMPLE #6 - Figure 3 Refer to Section 2.4.1.3 - Piping Information. UNITS OF MEASURE SHOWN ARE METRIC
DESIGNATIONS. At the completion and verification of the inputted data, the current data should be saved
(refer to Section 2.4.3.2 - Save). The data is then ready to Calculate and Display (refer to Section 2.4.1.4 -
Calculate and Display Results). The next 5 screens illustrate the results of the calculation.
EXAMPLE #6 - Figure 4 Refer to Section 2.4.1.4.A - Calculation Results. UNITS OF MEASURE SHOWN ARE METRIC
DESIGNATIONS.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 105
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
EXAMPLE #6 - Figure 5 Refer to Section 2.4.1.4.B - Nozzle Performance. UNITS OF MEASURE SHOWN ARE METRIC
DESIGNATIONS.
EXAMPLE #6 - Figure 6 Refer to Section 2.4.1.4.C - Hazard Concentration Results. UNITS OF MEASURE SHOWN
ARE METRIC DESIGNATIONS.
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 106
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
System Information
Storage Pressure (bar): 25.80 Average Cyl Pressure (bar): 16.7
Ave Initial Pipe Temp (°C): 21 Fill Density (lbs/cu.m.): 746.7
Percent Agent in Pipe: 17.9 Average Discharge Time (sec): 9.5
Quantity of Cylinders: 1 Type of Cylinder: Beta 95
Amount per Cylinder (kgs): 29 (63.9 lb) Total Amount of Agent (kgs): 29 (63.9 lb)
Altitude Relative to Sea (m): 0
Concentration Results
Volume Discharged Concentration
Hazard Area (cu.m.) (kgs) Requested Achieved
ROOM 52.1 29.0 7.00 7.10
Nozzle Information
Nozzle Size Stock Drill Dia Drill Discharged
ID mm (in) Number Style in (mm) Size (kg)
301 20 mm (3/4) 10371362 F 0.2210 (5.613) 2 29.0
1 (Continued)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 107
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
Error Messages
FM200FLC
NO ERRORS
Time and date of calculation 08/09/07 01-31-2003
PIPING NOTICE: This flow calculation is only listed and approved for Schedule 40 and Schedule 80
pipe meeting the specifications of American National Standards Institute (ANSI) B36.10 for steel
pipe. Millimeter pipe diameter equivalents are given for reference only. See Chemetron Design
and Flow Calculation Manual Part Number 30000034, Revision H, dated 1/23/03 for details.
2 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 108
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
APPENDIX - EXAMPLE #6
Cylinder Information
Amount of FM-200 per Cylinder (kg): 29.0000 Type of Cylinder: Beta 95
Quantity of Cylinders: 1 Cylinder Maximum Capacity (kgs) 43.5456
Cylinder Initial Temperature (°C) 21 Altitude Relative to Sea (m): 0
Hazard Information
Hazard: ROOM Concentration Required: 7.00 Temperature (°C): 21.1
Nozzle(s): 301 8 Port Style F Dimensions (m): 4.10 X 4.10 X 3.10
Piping Model
Section Pipe Tees Cplng/
Start End Lgth Elev Sch Size 90's Thru Side Union Note 1 EQL
1 2 0.0 0.98 40T 32 0 0 0 0 801 18.29
2 3 7.00 2.00 40T 0 1 0 0 0 0 0.00
3 301 0.20 -0.20 40T 0 1 0 0 0 28.53 0.00
Note 1: This column is used to indicate either a manifold, fixed agent amount or fixed nozzle
orifice diameter. The 800 Series numbers indicate either a single cylinder (801) or
multiple cylinders (802 = 2 cylinders, 803 = 3 cylinders, etc...).
This data file has fixed agent amount specified for the nozzle.
Note 2: The data input file shown here may not agree with the data used for the flow calculation.
The data input file may have been changed since the calculation was performed.
1 (End of Printout)
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 109
FM-200™ ENGINEERED SYSTEMS
DESIGN & FLOW CALCULATION MANUAL
S/N 30000034
ISSUED: 11/15/95 REVISED: 1/23/2003 Page 110