This document provides the guaranteed technical particulars for 96kV 10kA class-3 lightning arresters manufactured by Lamco Industries Private Limited. It lists 22 key specifications such as the manufacturer, reference standard, rated voltage, nominal discharge current, maximum switching impulse residual voltage, and mounting details. The arresters have a rated voltage of 96kV, nominal discharge current of 10kA, and can dissipate energy of 9kJ/kV.

Uploaded by

kapil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views5 pages

Ct-Pt-Lighting Arrester

This document provides the guaranteed technical particulars for 96kV 10kA class-3 lightning arresters manufactured by Lamco Industries Private Limited. It lists 22 key specifications such as the manufacturer, reference standard, rated voltage, nominal discharge current, maximum switching impulse residual voltage, and mounting details. The arresters have a rated voltage of 96kV, nominal discharge current of 10kA, and can dissipate energy of 9kJ/kV.

Uploaded by

kapil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

FUARANTEED TECHNICAL PARTICULARS FOR 11OW_CT

'' RATIO":20~-=m1-1-1-1 A
ISI. No. I
I

ITEM DESCRIPTION I
I

UNIT I
I

I
GUARANTEEDVALUES
1 NAME OF THE MANUFACTURER I LAMCO INDUSTRIES PVT. LTD
2 COUNTRY OF ORIGIN " INDIA

I SINGLE PHASE, OIL IMMERSED, DEAD


TANK,OUT DOOR TYPE

FOR LAMCO INDUSTRIES PVT. LTD.

DATE :
11 CLASS OF INSULATION A
ONE MINUTE POWER FREQUENCY WITH STAND
l2 KVms 230
VOLTAGE (DRY & WET)
13 LIGHTNING IMPULSE WITHSTAND VOLTAGE KVp 550

ONE MINUTE POWER FREQUENCY WITH STAND


l4 KVms 3
VOLTAGE ON SECONDARY WINDING
1.5 MINIMUM CREEPAGE DISTANCE mmKV 3813
16 STANDARD TO WHICH OIL CONFORMS IS - 335
17 WEIGHT OF OIL Kg 120&10%
18 TOTAL WEIGHT Kg 450i10%
19 MOUNTlNG DIMENSION mm 400x400
20 OVER ALL DIMENSION AS PER APPROVED G.A DRAWING
21 TANK FINISH PAINTING
22 TERMINAL CONNECTORS ACSR RIGID TYPE

FOR LAMCO INDUSTRIES PVT. LTD.

3
DATE:.@ /? ((I DATE :
I
GUARANTEED TECHNICAL PARTICULARS FOR
96KV lOKA CLASS-3 LIGHTNING ARRESTERS

1. Name of the Manufacturer : LAMCO INDUSTRIES PRIVATE LIMITED.,


B-39, I.E.SanathnagarrHYDERABAD-018 ( A m

2. Type : Heavy Duty Station Class Metal Oxide gapless


Lightning Arrester "MORESTER" type 'LMA.5'-

3. Reference Standard : IEC 99-4 of 2006/ IS 3070(Part-3)1993.


C".?

4. Model (Drg. No.) : 2210969

5. Nc, cf Units : TWO (48KVx2Nosj

6. Rated Voltage
++,
I 7. Nominal discharge current

8. Reference current : 3mA

9. Reference voltage : Greater than the rated


Arrester voltage at
reference current

10. Leakage Current at COV : less than 0.8 mA

! 11. Max. continuous operating voltage : 76.8 KVrms

12. Maximum resldual voltage for discharge


current of (8/20 micro sec. wave)
i. 5000 Amps : 260 KVpeak
ii. 10000 Amps : 273 KVpeak
iii. 20000 Amps : 360 KVpeak

13. Max. steep front residual voltage at


P lOKA with one micro sec. rise time : 360 KVpeak

14. Max. switching impulse residual voltage


with 40/80 micro sec. wave at 500A : 272 KVpeak

15. Energy dissipation capability : 9 KJ/KV


(cumulative of 3 sequential shots)

16. High current 4/10 micro sec. test value: 100 KApeak

17. Long duration current tests


i) Current peak : As per discharge Class-3
of IEC 99-4 (Table-4).
ii) Virtual duration : 2400 us

Continued on page..2
:: 2 ::
(2210969) \ b ..
18. Pressure relief class : Class 'A'

19. Short circuit current capability : 40 KA rms

20. Partial discharge at 1.05 times MCOV : Less than 10 pC

21. Temporary over voltage withstam


value for
a. 0.1 Second : 110 KVrms
b. 1.0 Second : 106 KVrns
c. 10.0 Second : 101 KVrms

22. Insulation withstand strength of


Arrester housing
i) One minute 50 Hz dry & wet : 230 KVrms
ii) Lightning impulse voltage withstand : 550 KVpeak

23. Creepage distance : 3900 mrn

24. Weight of complete unit : 113 5~10%kgs

25. Height of complete unit from base to


the line side : Refer Drg No. 2210969

26. Minimum recommended centre to centre


spacing between Arresters : 1800 rnm

27. Clearance required from ground


equipment at various heights of
Arrester unit : 1500 mrn

28. Earthing arrangement provided for : Ground Terminal Bracket


earthing side of Arrester provided for connecting earth
strip (Drg. No.6220154)

29. Mounting flange dimensional details : End castings,3 holes (12.5mm dia)
120 deg apart at 250 mm PCD.

for LAMCO INDUSTRIES PRIVATE LIMITED.

(B.RAJAIAH)
MANAGER (D&D)
31 q l r t
LlNE TERMINAL CONNECTOR

LlNE TERMINAL BRACKET

UNlT - A, NAME PLATE

GRADING RlNG

PORCELAIN BUSHING

UNlT - B, NAME PLATE

NAME PLATE

GROUND TERMINAL BRACKET

SUPPORT INSLILATOR 078


3 Nos. PLACED 120" APART.

3 MOUNTING HOLES 012.5 ON


250 PCD FOR M I 2 BOLTS.
I I NOTE :
1. FOR SURGE MONITOR REFER Drg. No. : 4249001A.
1500
2. FOR INSTALLATION AND INTERCONNECTION
I -- . REFER Drg. No. : 4320010.
A
3. TOTAL CREEPAGE DISTANCE 3900 mm (NOM).
1500 < 4. ARRESTER VENT PORTS SHOULD BE D!RECTED
E-p p-p 1 p-p TOWARDS SAFE DIRECTION.

- 1500 - 1800 -- 1800 - 1500 - 5. WEIGHT OF THE ARRESTER 1 13k1O%Kgs.

3 P H A S E INSTALLATION

01. GRADING RING DIMENSION MODIFIED & MATERIAL CHANGED TO ALUMINIUM


I REV. No. I BREIF DESCRIPTION I SIGNATURE DATE I

LAMCO
INDUSTRIES PRIVATE LIMITED,
TOLERANCE
AS
INDICATED

Y
B - 38,39,40, SANATHNAGAR I.E,
HYDERABAD-500018,A.P, INDIA.
ALL DIMENSIONS
ARE IN mm
SCALE . NTS APPROVED cG$$b-"&\ 1
121f1q~
TITLE :
96KV, 1OK, LIGHTNING ARRESTER (C.D. : 3900mm)
DRAWING NUMBER
ISSUE - ,
(MORESTER TYPE LMAS) 22 10969 REV - 1

You might also like