1
2
MAT /RAFT FOOTING
3
➢ These types of footings consist of large concrete slabs of (0.75m to
2m) thick and continuous two-way reinforcing at top and bottom that
support several lines of columns or walls.
➢ Mat foundation may be supported by piles in situations such as high
groundwater table to control buoyancy or where the base soil is
susceptible to large settlements.
➢ In general, the critical point to design a mat foundation is the total
settlement but not the bearing capacity failure.
➢ Hence, as a rule for rafts, the maximum permissible total settlement is
about (2.0 inches) and the maximum permissible differential
settlement is about (1.5 inches).
4
USES OF MAT FOUNDATIONS
➢When the base soil has a low bearing capacity.
➢The column loads are so large such that the use of conventional
spread footings covers more than 50% of the total area.
➢When the soil strata are erratic or there is a soft layers of soil within
the subsoil profile.
➢When there is a large differential settlements expected to occur, and
➢If there is a basement and groundwater table problems and there is
a need to eliminate water infiltration into basement-type installations.
5
TYPES OF MAT FOUNDATIONS
(1) Flat-plate: this type is most
common, less labour effort,
easy to construct, more
economical, and has a constant
thickness for all the raft; see
Figure below.
6
(2) Plate thickened under the
columns: this is to increase the
punching shear capacity, without
increasing the thickness for the
entire mat; see Figure below.
7
3) Waffle-plate: this type is
designed as a grid of beams and
slabs in one or two directions to
provide rigidity with a
minimum concrete thickness;
see Figure below.
8
(4) Wall-plate: this type consists
of slab-wall interaction resulting
in a stiffer mat foundation; in this
case, check wide-beam shear of
walls in each direction; see
Figure below.
9
(5) Plate with pedestals: this
type consists of pedestals as
part of mat; to connect steel
columns with the mat slab;
see Figure below.
10
6) Basement walls as part
of mat; see Figure below.
11
DESIGN STEPS OF MAT FOUNDATIONS
BY CONVENTIONAL RIGID METHOD
Step 1: Calculate the total column loads
∑ P = (DL + LL)col.1 + (DL + LL)col.2 + (DL + LL)col.3 +………..
Pu1 = [1.2D.L +1.5L.L].col.1 ; Pu2 = [1.2D.L
+1.5L.L].col.2 ; Pu3 = [1.2D.L +1.5L.L].col.3
∑ Pu lt. = Pu1 + Pu2 + Pu3 + …………..
12
Fig 1. Conventional
rigid mat foundation
design.
13
Step 2: Determine the load eccentricities.
Refer to the diagram on the previous slide.
14
Step 3: Determine the soil reactions
15
Step 4: Compare the Soil pressure
Compare the values of the soil pressures determined in
step (3) with the allowable net soil pressure to
determine whether q ≤ qall (net).
Step 5: Determine the Depth
Determine the depth (d) of the mat by checking the
punching shear failure at (d/2) from faces of various
columns.
16
Depending on the location of the column, calculate bo
(punching perimeter)
Punching area for mat foundation design
17
Step 6: Divide the mat into several strips in x and y directions.
For example, referring to Fig.(1) mentioned previously, take 4
strips in y-direction with B1, B2, B2, and B1 widths,
respectively, and 3 strips in x-direction with B3, B4, and B3
widths, respectively.
Step 7
Draw shear, V, and moment, M, diagrams for each individual strip
using the modified loading (in the x and y directions).
Step 8
From the moment diagrams of all strips in one direction (x or y),
obtain the maximum positive and negative moments per unit
width (i.e., M = M / B3 ).
18
Step 9: Design the Longitudinal and Transverse Reinforcement
Compare As with As,min and take the larger value for design.
Step 10: Design spacing for steel distribution.
19