Dynamic Modeling of Microgrid For Grid Connected and Intentional Islanding Operation
Dynamic Modeling of Microgrid For Grid Connected and Intentional Islanding Operation
Vabc_ grid
islanding mode. Iabc_inverter
2) Development of an algorithm for intentional islanding
detection and synchronization controller required CONTROLLER
Gate signals
POWER SYSTEMS are experiencing tremendous growth intentional islanding detection algorithm [4]. After islanding
operation, the DGs are connected back to grid. At this instant
in the field of distributed generation because of economic of grid reconnection, re-closure algorithm has to be established
benefits, environmental concern, reliability requirement etc. to achieve synchronization [4], [9].
Mainly the DGs include wind turbines, photovoltaic cells,
micro turbines and fuel cells. The DG is a voltage source
inverter with an output low pass filter supplying the load [1]. II. CONTROL TECHNIQUES FOR INVERTER
The microgrid configuration [2] with the control strategy is The voltage and current control loop has been implemented
shown in Fig. 1. by using PI controllers working on the D-Q synchronous
reference frame. AC quantities are converted in to DC
synchronous reference frame by Parks Transformation.
Rinu J Vijayan is currently doing MTech in Power electronics and
Electrical drives in Electrical Engineering Dept in National Institute of Correspondingly all reference quantities become DC in nature,
Technology, Surat, (Phone: 08891771200 e-mail: [email protected]). so that simple PI controllers would be sufficient to yield zero
Subrahmanyam Ch is doing MTech in Power electronics and Electrical steady state error.
Drives in Electrical engineering Dept in National Institute of Technology,
Surat, Gujarat (e-mail: [email protected]). A. DQ- PLL structure
Dr. Ranjit Roy is working as Associate Professor with Electrical
Engineering Dept, National Institute of technology, Surat, Gujarat. For unity power factor operation i.e. Grid current reference
(e-mail: [email protected]). to be in phase with grid voltage, estimation of phase angle is a
-
voltage controlled oscillator, an integrator and a phase detector ia
+ va
CURRENT
[6], [7]. Phase estimation is achieved by synchronization of the ib abc
to
ID REGULATOR vq
DQ vb
IQ PLL
oscillating waveform generated by oscillator with the measured ic dqo Synchronization
controller
Vd vc
Ѳ new Ѳ old
waveform. Ѳ new
Kp
ωf
Fig. 3. Block diagram of current controller
+ + + ^
Ki 1 Ѳ
Vq=0
- s + + s Finally the DC reference quantities added with terminal
Vq
voltages are transformed back to stationary frame by Inverse
αβ Park’s Transformation. Thereafter it is used to generate the gate
Vd To
dq pulses by SPWM technique [4].
Va Vα Vβ
Abc
Vb To
αβ
C. Voltage control
Vc
In this control the microgrid will provide constant voltage to
Fig. 2. DQ-PLL structure the load [10]. This control scheme makes use of both current
regulator as well as voltage regulator. The control works on the
The DQ-PLL structure consists of a Clarke’s transformation, principle of voltage regulation through current compensation
[12], [13]. Fig. 4 represents the voltage control scheme. The
Park’s transformation, PI regulator and an integrator. The
converter output voltage is controlled by a synchronous
expression for the d- axis component and the q-axis component
reference frame closed loop voltage controller. Its output is
fed to the PI controller is given as
transferred in to a closed loop current regulator which is further
transformed in to stationary frame, and then the space vector
̂ ̂ PWM generates the gating signals of the IGBTs.
̂ ̂
Ѳ new
+
̂ va
+
- Vd Idref Id Vdref
+
vb DQ + -
+
PLL
̂ vc - Vq Iqref
+ Iq Vqref
+
+ -
Ѳ old 0
The realization of lock in PLL relies on regulating the SYNCHRONIZATION
1
abc
quadrature component (3) of rotating reference frame to zero CONTROLLER to
Ѳ new dqo
using the PI controller. When generated by oscillator Ѳ new
approximates ̂, the PLL will be locked. The value of as Ia Ib Ic
shown in (4) will become V i.e. At the instant, when lock is Fig. 4. Block diagram of voltage controller
realized, the direct axis component gives the magnitude of the
voltage [8]. As shown in Fig. 4, the filter output line voltage is
B. Current control transformed in to dc quantities by DQ-PLL structure. The
direct and quadrature quantities are forced to follow their
In grid connected mode the magnitude and frequency of the corresponding reference values by using voltage regulator. The
microgrid terminal voltages are imposed by the grid voltage. current references generated by voltage regulator are compared
Current controller is designed to provide constant current with the dc values of load currents and the error is
output during grid connected operation [12], [13]. Control compensated by current regulator. The output of current
System shown in Fig. 3 is used to accomplish current control. regulator provides the reference voltage signal.
In the strategy proposed here, the VSC line current is made
controllable by a dedicated scheme and through the control of D. Intentional islanding detection algorithm
VSC terminal voltage. The inverter AC output current is Parameters which are used to determine the state of grid is
transformed in to DC quantity in synchronous rotating frame voltage and frequency. Fig. 5 indicates the algorithm
by Park’s transformation. The direct and quadrature developed to accomplish the detection of intentional islanding.
components are compared with the reference quantities and the Under deficient grid voltage conditions, the main switch is
error signal is passed to the PI controller to generate the turned off and disconnects the main grid from the utility. This
switching causes transients in voltage and frequency [11].
voltage references [10]. The inverter terminal voltage is
Therefore tracking of system voltage magnitude and frequency
considered as a disturbance and hence fed forward to
indicates the transition switching between grid connected and
compensate it [1].
islanding mode, and vice versa.
Va
Vdpu ≤ 1.1 inverter voltages is given by
3 phase
Vb
sequence
analyzer
AND - (5)
Vc
Vdpu ≥ 0.88
Voltage
measurement
AND
Va
f ≥ 59.3
Vb 3 phase
AND
(7)
PLL
Vc
f ≤ 60.5
frequency
measurement
( )
When paralleling microgrid with utility grid, it is necessary to III. DESIGN OF PI CONTROLLER
have the same phase angle for both of them. By closing the A. Current control transfer function
breaker at PCC, the two individual systems begin to have
Current control scheme is needed during grid connected
parallel operation. In order to achieve stiff synchronization
operation. The block diagram of current controlled operation is
with the utility grid during grid reconnection, synchronization
shown in Fig. 7. The inverter is modeled with an ideal gain
controller is used. The algorithm used here [4] is to determine
GI=1. In order to obtain the transfer function of the filter and
the new phase angle at which both the microgrid and utility
the load block, the designed LCL filter and RLC load circuit
grid have to operate.
must be taken in to consideration. Fig. 8 depicts the circuit
The algorithm is as follows diagram of LCL filter and RLC load. The transfer function of
1 150
0.9
100
0.8
50
0.7
voltage
logical value
0.6 0
0.5
-50
0.4
-100
0.3
0.2 -150
0.1
-200
0.25 0.3 0.35 0.4 0.45
0
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 time
time
Fig. 11. Transition from grid connected to islanding mode. Fig. 14(b). Line Voltage with voltage controller
200
150
60
100
59.9
50
59.8
voltage
0
frequency
59.7
-50
59.6
-100
59.5
-150
59.4
-200
59.3
-250
59.2 0.5 0.55 0.6 0.65 0.7
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
time
time
200
1.4
150
1.2
100
magnitude (pu)
1
50
voltage
0.8
0
0.6
-50
0.4
-100
0.2
-150
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 -200
0.5 0.55 0.6 0.65 0.7
time
time
200
80
150
60 100
50
voltage
40
0
20
current
-50
0
-100
-20 -150
-40 -200
-250
-60 0.2 0.3 0.4 0.5 0.6 0.7 0.8
time
-80
0.25 0.3 0.35 0.4 0.45
time
150
250
100
200
150 50
voltage
100
0
50
voltage
-50
0
-100
-50
-100 -150
-150 -200
0.3 0.4 0.5 0.6 0.7 0.8
-200 time
-250
0.25 0.3 0.35
time
0.4 0.45
Fig. 16. Synchronization for grid reconnection (a) without re-
Fig.14(a). Line Voltage without Voltage controller closure algorithm (b) with re-closure algorithm
B. Without and with synchronization controller V. CONCLUSION
At first, simulation was conducted when the microgrid is Current and voltage Control techniques have been developed
connected to the utility grid without any synchronization for grid connected and intentional islanding modes of operation
controller. The grid was disconnected by setting the status in using PI controllers. An intentional islanding detection
three phase circuit breaker as closed initially and transition algorithm responsible for switching between current control
time at 0.3s. Fig. 13 and Fig. 14(a) show the inverter currents and voltage control is developed using logical operations and
and voltages at the point of common coupling. The occurrence proved to be effective. The reconnection algorithm coupled
of transients at 0.3s is seen clearly. Occurrence of large with the synchronization controller enabled the DG to
transient during the instant of grid reconnection is undesirable. synchronize itself with the grid during grid reconnection. The
Fig. 15(a) shows the phase voltage at PCC without the performance of the microgrid with the proposed controllers and
implementation of any resynchronization algorithm. Fig. 16(a) algorithms has been analyzed by conducting simulation on
shows per phase voltage at both sides of PCC in the absence of dynamic model using SIMULINK. The simulation results
presented here confirms the effectiveness of the control
resynchronization controller. It can be observed that the system
scheme.
takes longer duration to achieve the synchronization, which is
quite undesirable for the loads. Grid current doesn’t get
influenced under the effect of synchronous controller, as there
REFERENCES
will not be any supply of current to the load from the utility
[1] L. Shi, M.Y. Lin Chew. “A review on sustainable design of renewable
grid during standalone mode. energy systems,” science direct journal present in Renewable and
Sustainable Energy Reviews, Vol. 16, Issue 1, 2012, pp. 192–207.
The grid was then reconnected at 0.6s. The microgrid [2] Q. Lei, Fang Zheng Peng, Shuitao Yang. “Multi loop control method
for high performance microgrid inverter through load voltage and
continuous to operate in synchronous islanding mode until both current decoupling with only output voltage feedback,” IEEE Trans.
the utility system and the microgrid system is resynchronized. power. Electron, vol. 26, no. 3, 2011, pp. 953–960.
Fig. 16(b) shows the synchronization of voltage at both sides of [3] J. Selvaraj and N. A. Rahim, “Multilevel inverter for grid-connected PV
system employing digital PI controller,” IEEE Trans. Ind. Electron.,
the PCC in the presence of resynchronization controller. On vol. 56, no. 1, 2009, pp. 149–158.
investigating from the beginning of intentional islanding mode, [4] I. J. Balaguer, Fang Zheng Peng, Shuitao Yang, Uthane Supatti Qin
the system achieves synchronization in much less time Lei. “Control for grid connected and intentional islanding modes of
operations of distributed power generation,” IEEE Trans. Ind.
comparing with that system without synchronization controller. Electron., vol. 56, no. 3, 2009, pp. 726–736.
With the implementation of resynchronization controller [5] R. J. Azevedo, G.I. Candela, R. Teodorescu, P.Rodriguez , I.E-Otadui
algorithm, the DG voltage is forced to track the voltage at the “Microgrid connection management based on an intelligent connection
agent,” 36th annual conference on IEEE industrial electronics
grid. On completion of the synchronization, the DG is society, 2010, pp. 3028–3033.
reconnected to the grid, and the controller will be switched [6] V. Kaura and V. Blasko “Operation of a Phase Locked Loop System
from the voltage to the current control mode. Fig. 15(b) shows under Distorted Utility Conditions,” IEEE Trans. on Ind. Applications,
vol. 33. no. 1,1997, pp. 58–63.
the phase voltage with the synchronization algorithm [7] S.A.O. Silva. and E.A.A. Coelho, “Analysis and Design of a Three-
implemented. This graph depicts the effectiveness of Phase PLL Structure for Utility Connected Systems under Distorted
resynchronization algorithm in avoiding hard transients during Utility Conditions,” in Proc. Conf. Rec. IEEE-CIEP, 2004, pp. 218–
223.
grid reconnection. [8] L.N. Aruddha “PLL structure for utility connected systems,” in IEEE
36th IAS annual meeting in industry applications conference vol.
TABLE I 4,2001, pp. 2655–2660.
DESIGNED VALUES OF PARAMETERS USED FOR SIMULATION [9] C.Cho, J-HongJeon, J-YulKim, S. Kwon, K. Park, S. Kim “Active
synchronizing control of a microgrid,” IEEE Trans. power. Electron,
Symbol Value Description vol. 26, no. 12, 2009, pp. 3707–3719.
[10] I.Vechiu, A.Llaria, O.Curea, and H.C. Technopôle Izarbel “
1mH Filter inductance Control of power converters for microgrid” in 4th international
31µF Filter capacitance conference on EVER MONACO ecological vehicles and renewable
energies , EVER09-181, RE 4 session, 2009.
0.5 mH Filter inductance [11] J. Rocabert, G.Azevedo, I. Candela, R.Teoderescu, P.Rodriguez, J.M.
1.535mF Load capacitance Guerrero, “Intelligent control agent for transient to an island grid,” in
4.585mH Load inductance IEEE international symposium on Ind. Electron, 2009, pp. 2223–
2228.
4.33Ώ Load resistance [12] Sao, C.K. Lehn, P.W, “Intentional islanding operation of converter fed
microgrid,” in IEEE power engineering society general meeting 2006,
Vdc 400V Dc voltage source pp. 6.
Rgrid 0.1 Ώ Grid resistance [13] Sao, C.K. Lehn, P.W, “Islanding control of DG in microgrid,” in IEEE
power engineering society general meeting 2006, pp. 6.
Lgrid 0.1mH Grid inductance [14] M.-T ho, H.zen Wang, “PID controller design with guaranteed gain
Kp, Ki 1.24, 0.02 Voltage loop PI constant and phase margins,” ASIAN Journal of control, vol. 5, no. 3, 2003,
values pp. 374–381.
Kp, Ki 0.8, 50 Current loop PI constant [15] D. Xue, Yang. Chen, and D.P. Atherton, Linear Feedback Control
values 2007 chapter 6, pp. 183–225.
System frequency [16] M.B. Delghavi, A. Yazdani, “A control strategy for islanded operation
f 60hz of a Distributed Resource (DR) unit,” Power & Energy Society
General- Meeting, 2009, PES '09, IEEE 2009, pp. 1–8.
fs 1Khz Switching frequency