D/E Remote Relay Panel User Guide: This Manual Should Remain With The Unit
D/E Remote Relay Panel User Guide: This Manual Should Remain With The Unit
Relay Outputs
Each channel will provide one pair of Normally
Open/Normally Closed contacts. See Figure 2.
The relay status is fail-safe when using the NC con-
tacts as the alarm output i.e.:
Alarm OFF = Relay ON = NC contact OPEN
Alarm ON = Relay OFF = NC contact CLOSED
Figure 2
Figure 4 — S2
NOTE:
So a DC supply failure will reset the relay to Off = If a unit is wired up and then subsequently an
alarm ON - N/C Closed. additional DIP is selected or deselected all the
relay outputs will be re-assigned sequentially and
therefore may require re-wiring.
RS485 Communication
There are no options available, the jumpers J1 & J2
must both be set to positions 1-2.
Communication Jumper Position
RS485 J1 1-2
(default) J2 1-2
EXAMPLE 1
A single RRP is connected to a D panel (Figure 6).
S3.1, 3.2 Address 0, S3.1 and S3.2 OFF
S3.2 Unused is OFF
S3.4 RS485 termination resistor is ON
EXAMPLE 2
If subsequently DIP1-3 is removed, and DIP2-5 is
added, then relays will be re-assigned as (Figures 9
and 10).
DIP Parameter Relay
1, 1 RPM Sensor Loss 1
1, 5 High Water Temp 2
1, 10 Pre-Low Fuel 3
2, 5 Generator Power 4
Figure 9 — S1
4
1
4 5
7
4
1
2
8
5