0% found this document useful (0 votes)
287 views21 pages

1900 65a General Purpose Equipment Monitor Data Sheet PDF

Uploaded by

Thaynar Barbosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
287 views21 pages

1900 65a General Purpose Equipment Monitor Data Sheet PDF

Uploaded by

Thaynar Barbosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

1900/65A General Purpose Equipment Monitor

Bently Nevada* Asset Condition Monitoring


Description
The 1900/65A General Purpose Equipment Monitor is designed to continuously
monitor and protect equipment that is used in a variety of applications and
industries. The monitor’s low cost makes it an ideal solution for general-purpose
machines and processes that can benefit from continuous monitoring and
protection.
Inputs
The 1900/65A provides four transducer inputs and four temperature inputs.
Software can configure each transducer input to support 2- and 3-wire
accelerometers, velocity sensors or proximity sensors. Each temperature input
supports Type E, J, K, and T thermocouples, and 2- or 3-wire RTDs.
Outputs
The 1900/65A provides six relay outputs, four 4-20 mA recorder outputs, and a
dedicated buffered output. The user can use the 1900 Configuration software to
configure the relay contacts to open or close according to the OK, Alert and
Danger statuses of any channel or combination of channels, and to provide data
from any variable from any channel on any recorder output. The dedicated
buffer output can provide the signal for each transducer input.
A Modbus Gateway option allows the monitor to provide static variables,
statuses, event list, time and date information directly to any Modbus client,
including Distributed Control Systems (DCSs), Supervisory Control and Data
Acquisition (SCADA) systems, Programmable Logic Controllers (PLCs), or System
1 software. The monitor uses an internal counter and a Modbus client/master
time reference to generate time and date information. Users can upgrade
monitors without the Modbus Gateway by ordering the 1900/01
Communications Upgrade (see the Ordering Information section). The 1900/65A
supports Modbus communications via Ethernet and a software-configurable
RS232/485 serial port.
Configuration
The user defines monitor operation and the Modbus Gateway register map by
using software running on a laptop or PC to create a configuration file and
download the file to the monitor through the built-in Ethernet connection. The
1900/65A permanently stores configuration information in non-volatile memory,
and can upload this information to the PC for changes.
Display Module
The 1900/65A supports an optional display/keypad to view channel information
or make minor configuration changes. This allows the 1900/65A to operate as a
stand-alone package. If desired, the user can mount the display up to 75 metres
(250 feet) from the Monitor Module

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 1 of 21
Feature List Specifications
Inputs
• Continuous monitoring and protection is suitable
for auto-shutdown applications
Transducer Inputs
• Stand-alone operation on general-purpose Users can configure Channels 1
equipment through 4 to accept input from
acceleration, velocity or
• Optional Modbus communications via displacement transducers.
10BaseT/100BaseTX Ethernet, or
software-configurable 485/232 serial port Transducer Channel Types
• Small package. Monitor Module: 196.9 mm x Channel Types define the
149.4 mm x 74.4 mm (7.75” x 5.88” x 2.93”). functionality for processing that
Monitor Module with attached Display Module: will be applied to an input signal
196.9 mm x 149.4 mm x 97.8 mm (7.75” x 5.88” x and the kind of variables or
3.85)” measurement values that will be
derived from this input. Channel
• DIN rail or bulkhead mounting options Types also define the kind of
sensor that must be used.
• 18 to 36 Vdc power input. (optional 110-220 Vac Transducer Channel Types
external supply) include:
• 24-bit ADC conversion • Acceleration or Reciprocating
Acceleration
• Four vibration/position/speed inputs
• Velocity or Reciprocating
• Four temperature inputs Velocity
• Configurable scale factors and full scale ranges • Radial Vibration (shaft
vibration)
• Up to four processed variables per channel with
independent integration and filter control • Thrust (shaft axial
displacement)
• Internal OK checking with status
• Position
• Independent Alert and Danger setpoints
• Speed
• 200-entry event list
Acceleration and
• Six relay outputs. Relay operation is Reciprocating
programmable Acceleration
Channel Types
• Buffered outputs for each transducer channel
The Acceleration Channel Type
• Four configurable 4-20 mA recorder outputs and Reciprocating Acceleration
Channel Type support two- and
• Optional NEMA 4X/IP66 fiberglass housing with three-wire acceleration sensors.
window for display The Reciprocating Acceleration
• Painted or stainless steel weatherproof door for channel type has timed OK
panel-mount display channel defeat disabled.

• Hazardous area approvals


• Maritime Approvals

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 2 of 21
Acceleration Variables Filters
and Reciprocating
Vibration
Acceleration Variables
Variable:
Acceleration Variables and
0.5 Hz – 25 kHz configurable
Reciprocating Acceleration
4-pole high-pass, 4-pole low-pass
Variables are filtered and
processed measurements from Enveloping
raw transducer signals. The High-Pass:
Acceleration Channel Type and
25 Hz to 5 kHz, configurable
Reciprocating Acceleration
4-pole
Channel Type continuously
processes up to four variables per Enveloping
channel. Low-Pass:
Vibration: 125 Hz to 25 kHz, configurable
2-pole
Up to three bandpass filtered
amplitude measurements. Enveloped
Variable High-
Acceleration
Pass:
Enveloping:
0.1 Hz min., but greater than
Users can apply the acceleration
Enveloped Variable low-pass
enveloping algorithm to one
2-pole
Acceleration or Reciprocating
Acceleration Variable. Enveloped
Variable Low-
Bias Voltage:
Pass:
Users may assign the value of the
Greater than Enveloped Variable
transducer bias voltage to any of
high-pass and less than
the variables.
Enveloping high-pass 4-pole
Configuration
Bias Filter:
Options
0.01 Hz 1-pole low-pass
Each variable is independently
configured with the following OK Filter:
options.
2.4 kHz 1-pole low-pass
Vibration
Full Scale Range
Variables:
Vibration:
Peak or RMS
20 to 500 m/s2 (2 to 50 g) peak
Metric or English units
and RMS
Filter corner frequencies
Enveloped:
Full scale range
20 to 500 m/s2 (2 to 50 g) peak
Acceleration integrated to and RMS
velocity
Integrated:
Enveloped
10 to 100 mm/s (0.4 to 4 in/s)
Variable:
peak and RMS
Filter corner frequencies
Bias Voltage:
Standard or Enhanced
-24 V
demodulation

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 3 of 21
Accuracy Filter corner frequencies
Vibration Full-scale range
Variables:
Velocity integrated to
±1% of full scale range displacement
Input Filters
Impedance
Vibration
3-wire Voltage Variables:
Mode:
0.5 Hz to 5.5 kHz, configurable
10 kΩ 8-pole high-pass, 4-pole low-pass
Velocity and Bias Filter:
Reciprocating Velocity
0.09 Hz 1-pole low-pass
Channel Type
OK Filter:
The Velocity Channel Type and
Reciprocating Velocity Channel 2.4 kHz 1-pole low-pass
Type support two-wire and three-
Full Scale Range
wire piezo-velocity sensors.
Vibration:
Velocity Variables
and Reciprocating 10 to 50 mm/s (0.5 to 2 in/s) peak
Velocity Variables and RMS
Velocity Variables and Integrated:
Reciprocating Velocity Variables
100 to 500 μm (5 to 20 mils) peak
are filtered and processed
to peak
measurements from raw
transducer signals. The Velocity Bias Voltage:
Channel Type and Reciprocating
-24 V
Velocity Channel Type support up
to four continuously calculated Accuracy
variables per channel.
Vibration
Vibration: Variables:
Up to three bandpass filtered ±1% of full scale range
amplitude measurements.
Input
Bias Voltage: Impedance
Users may assign the value of the 3-Wire Voltage
transducer bias voltage to any of Mode:
the variables.
10 kΩ
Configurable
Radial Vibration
Options
Channel Type
Each variable is independently
The Radial Vibration Channel Type
configured with the following
measures radial shaft motion
options.
using proximity sensors.
Vibration
Radial Vibration
Variables:
Variables
Peak or RMS
Radial Vibration Variables are
Metric or English units filtered and processed
measurements from raw
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 4 of 21
transducer sensors. The Radial OK Filter:
Vibration Channel Type supports
2.4 kHz 1-pole low-pass
up to four continuously calculated
variables per channel.

Direct: Full Scale Range


Up to three bandpass filtered Direct:
amplitude measurements
100 to 500 μm (3 to 20 mils) peak-
Gap: to-peak
Gap voltage Gap:
Vibration: -24 V
Up to three bandpass filtered Accuracy
amplitude measurements
Vibration
Configurable Variables:
Options
±1% of full-scale range
Each variable is independently
Input
configured with the following
Impedance
options.
Non-
Vibration
configurable:
Variables:
10 kΩ
Metric or English units
Thrust Channel
Filter corner frequencies
Type
Number of filter poles
The Thrust Channel Type
Full-cale range measures axial shaft motion
using proximity sensors.
Filters
Thrust Variables
Direct Filter 1:
Thrust Variables are filtered and
4 to 4000 Hz (240 to 240,000 RPM)
processed measurements from
Direct Filter 2: raw transducer signals.
1 to 600 Hz (60 to 36,000 RPM) Position:
Direct Filter Axial position of shaft
Characteristics:
Gap:
High-pass set by attack and
Gap, voltage or position
decay, 1-pole low-pass
Configurable
Gap Filter:
Options
0.09 Hz 1-pole low-pass
Each variable is independently
Vibration configured with the following
Variables: options.
0.5 Hz to 4 kHz, configurable Position
Variables:
1-, 2-, or 4-pole high-pass and
low-pass, configurable Metric or English units

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 5 of 21
Full-scale range Configurable
Options
Filters
Each variable is independently
Direct Filter:
configured with the following
1.2 Hz 1-pole low-pass options.
Gap Filter: Position
Variables:
0.41 Hz 1-pole low-pass
Metric or English units
OK Filter:
Full scale range
2.4 kHz 1-pole low-pass
Filters
Full Scale Range
Direct Filter:
Position:
1.2 Hz 1-pole low-pass
1 to 4 mm (50 to 150 mils) span
with adjustable zero position Gap Filter:
Gap: 0.41 Hz 1-pole low-pass
–24 V OK Filter:
Accuracy 2.4 kHz 1-pole low-pass
Position Full Scale Range
Variables:
Position:
±1% of full-scale range
1 to 28 mm (50 to 1100 mils) span
Input with adjustable zero position
Impedance
Gap:
Non-
-24 V
configurable:
Accuracy
10 kΩ
Position
Position
Variables:
Channel Type
±1% of full scale range
The Position Channel Type
measures mechanical motion Input
using proximity sensors. Impedance
Position Non-
Variables configurable:
Position Variables are filtered and 10 kΩ
processed measurements from
Speed Channel
raw transducer signals.
Type
Position:
The Speed Channel Type
Mechanical position measures speed using proximity
sensors.
Gap:
Speed Variables
Gap, voltage or position
Speed Variables are filtered and
processed measurements from
raw transducer signals.

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 6 of 21
Speed: Configurable
Options
Up to four speed measurements
Each Variable is independently
Gap:
configured with the following
Gap, voltage options.
Configurable Units:
Options
°C or °F
Each variable is independently
Filters
configured with the following
options. Analog Filter:
Gap Filter: 50 Hz 1-pole, low-pass
0.09 Hz 1-pole low-pass Digital Filter:
OK Filter: Notch filter will attenuate the first 5
orders of 50 Hz and 60 Hz (49 Hz
2.4 kHz 1-pole low-pass to 61 Hz) by a minimum of 100
Full Scale Range dB.

Speed: Full Scale Range

100 - 100,000 rpm Type E:

Events Per -200 to 1000 ºC (-328 to 1832 ºF)


Revolution Type J:
EPR: -210 to 1200 ºC (-346 to 2192 ºF)
0.001 to 1000 Type K:
Accuracy -200 to 1370 ºC (-328 to 2498 ºF)
Speed Type T:
Variables:
-200 to 400 ºC (-328 to 752 ºF)
± 0.5 RPM + 0.015% of reading
10 Ω Cu
Input α=0.00427:
Impedance
-200°C to 260 °C (-328 to 500 ºF)
Non-
configurable: 120 Ω Ni
α=0.00672:
10 kΩ
-80°C to 260 °C (-112 to 500 ºF)
Temperature Inputs (Ch. 5 – 8) 100 Ω Pt
Channels 5 through 8 support α=0.00385:
Type E, J, K, and T thermocouples,
-200 to 850 °C (-328 to 1562 ºF)
and 2- and 3-wire RTDs.
100 Ω Pt
Temperature
α=0.00392:
Variable
-200°C to 700 °C (-328 to1292 ºF)
Temperature variables are
processed measurements from
raw transducer signals. The
temperature channel type
processes one temperature
variable per channel.
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 7 of 21
Accuracy Temperature / Speed Inputs
All Thermocouple Minimum
Types: 1 second
±1 °C (±1.8 °F) typical @ 25 °C (77 Maximum
°F)
60 seconds
±2.5 °C (±4.5 °F) maximum for
thermocouple measurements Adjustment
over –100 °C (148 °F) Resolution
±5 °C (±9 °F) maximum for 0.1 second
thermocouple measurements
Relays
below –100 °C (-148 °F)
3-Wire RTD Relay Logic
(except 10 Ω The 1900/65A monitor has six
Cu): relay outputs that users can
±1.5 °C (±2.7 °F) + 0.5 % full scale program to open or close
contacts according to user-
3-Wire RTD 10 defined logic statements. Logic
Ω Cu: statements use the OK, Alert and
±3 °C (±5.4 °F) + 0.5 % full scale Danger statuses of any channel,
or combination of channels as
2-wire RTD inputs.
Types:
Logical
2-wire RTDs have additional Operators
errors due to field wire resistance
and variations in the field wire AND (bypassed channels ignored)
resistance due to changes in True AND (bypassed channels
ambient temperature. included)
Input OR
Impedance
Logical
Thermocouple Operands
Inputs:
Monitor inhibit
>1 MΩ
Monitor Not OK
Monitor Danger
Alarm Status Time Delays
Monitor Alert
Position / Vibration Inputs Channel Not OK
Minimum Channel Danger
0.1 second Channel Alert
Maximum Variable Danger
60 seconds Variable Alert
Adjustment Maximum
Resolution Operands
0.1 second 50 per relay

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 8 of 21
Relay Configuration Inhibit, Reset, and Trip Multiply Inputs
The following configuration
options are independent of the Inhibit/Trip Multiply
relay logic and can be configured Users can use software to
for each relay: configure the Inhibit/Trip Multiply
input as either Inhibit or Trip
 Latching or non-latching
Multiply.
independent of alarm status
 Normally energized or normally de- When configured for Trip Multiply
energized short-circuiting the Inhibit/Trip
Multiply contact to RTN will
 Normally open and normally closed increase Alert and Danger set
via contacts points.

Relay Specifications When configured for Inhibit the


Inhibit input will inhibit (bypass or
Type inactivate) Alert and Danger
Single pole, double throw (SPDT) statuses. Short circuiting the
INHIBIT contact to INHIBIT RTN
Max switched will:
Voltage:
 Set all Variable Danger Statuses to
dc: 300V logic 0
ac: 400V  Set all Variable Alert Statuses to
Max switched logic 0
current:  Set Bypass and Inhibit Statuses to
dc: 5A logic 1

ac: 6A Modbus Note: Monitor Alarm


Inhibit switch, and Monitor Trip
Max switched Multiply switch mapped in the
VA: Modbus Gateway will remotely
dc: 150VA inhibit Alert and Danger statuses
or activate Trip Multiply
ac: 1500VA respectfully.
Min switched Electrical
Current:
Activate Inhibit
dc: 100mA / 12V
50 kΩ or less (shorted)
Contact Life
De-activate
100,000 cycles @ 5 A, 250 Vac Inhibit
200,000 cycles @ 1 A, 24 Vdc 500 kΩ or greater (open)
Sealing
Reset
Epoxy
Use the Reset input to reset all
Insulation latched alarms and latched
Resistance relays. If the condition driving the
status no longer exists, short-
1000 MΩ minimum @ 500 Vdc
circuiting the RESET contact to
RESET RTN will:
 Reset all latched Alert statuses
 Reset all latched Danger statuses
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 9 of 21
 Reset all latched Not OK statuses 4 to 20 mA values are
proportional to the channel full-
 Reset all latched relays
scale.
Modbus Note: Writing a non-zero
value to the Modbus register Loop Supply
Reset Latched Statuses mapped in Voltage
the Modbus Gateway will reset 18 to 36 Vdc
the monitor remotely.
Loop Resistance
Electrical
600 Ω maximum
Activate Reset
Accuracy
50 kΩ or less (shorted)
2% over operating temperature
De-activate range
Reset
Update Rate
500 kΩ or greater (open)
100 mS
Transducer Supplies Resolution
All outputs are short-circuit protected.
10 µA
Two-Wire Current Mode
Current Source Clamp Current
3.3 mA ± 5% 2 mA ± 10% (configurable for Not
Open Circuit OK and Bypass)
Voltage
Buffered Outputs
21 to 24 Vdc
Display Module
Three-Wire Voltage Mode A single buffered output on the
Supply Voltage Display Module provides access
to input Channels 1 through 4.
-24.02 Vdc to –23.47 Vdc The signal does not have gain,
Maximum Rated and is not scaled. This output is
Current buffered to provide short circuit
and EMI protection.
15 mA
Output
Short Circuit Impedance
Current
550 Ω
15.1 mA to 23.6 mA
Bandwidth
4-20 mA Interface
40 kHz minimum (Display Module
Number of
attached directly to Monitor)
Outputs
8 kHz minimum (75 m (250 ft.) of
Four outputs, any of which may
cable)
be configured to provide data
from any channel and any
variable. Monitor Module
Each input for channels 1 through
Proportional 4 has a dedicated buffered
Value output. The signal does not have
gain, and is not scaled. Each

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 10 of 21
output is buffered to provided Operating
short circuit and EMI protection. Current
Output 0.35 A typical, 1.0 A maximum
Impedance
Operating
550 Ω Power
Bandwidth 8.5 W typical, 14 W maximum
40 kHz minimum Physical
Indicators Monitor Module
Monitor Module Dimensions (L x
W x H)
Status LED
196.9 mm x 149.4 mm x 74.4 mm
Indicates when the monitor is
functioning properly (7.75 in x 5.88 in x 2.93 in)
Weight
Display Module
OK LED 0.77 kg (1.70 lb)

Indicates when the monitor is Display Module


functioning properly
Dimensions (L x
Alert LED W x H)
Indicates an Alert condition 196.9 mm x 149.4 mm x 32.8 mm
Danger LED (7.75 in x 5.88 in x 1.29 in)
Indicates a Danger condition Weight
Bypass LED 0.40 kg (0.89 lb)
Indicates that the monitor is in
Bypass mode Mounting
DIN Rail Option
Trip Multiply
LED 35 mm DIN rail
Indicates that the monitor is in Bulkhead
Trip Multiply mode Option
Channel LED Bulkhead mounting plate
Indicates channel is active Weatherproof
Enclosure
Option
Display NEMA 4X/IP66 Fiberglass Housing
Liquid Crystal Display (LCD) with with window, 300.2 mm x 249.4
backlight mm x 209.8 mm (11.82 in x 9.82 in
x 8.26 in)
68.6 mm (2.7 in) wide x 35.6 mm
(1.4 in) high The 1900 Configuration
Software package contains
Power Requirements everything necessary to install,
Input Voltage configure, and maintain the
Range 1900/65A monitor.
18 to 36 Vdc
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 11 of 21
• FeaturesTools for installing and Environmental
troubleshooting
Temperature
• Simple display to help with
configuration Operating
• Ability to browse network for -20 to +70 ºC
1900 monitors (-4 to +158 ºF)
• Network configuration Storage
• Configuration for channels, -30 to +90 ºC
variables, setpoints, tag names,
recorders and filters (-22 to +194 ºF)
• Configuration for the optional
Modbus Gateway Humidity
• Configuration for relays and Operating
relay voting logic 95% non-condensing, maximum
• Off-line configuration allowing
use of software when Storage
hardware is not available 95% non-condensing, maximum
• Firmware upgrade function
and diagnostics Supported Transducers
• Change bypass modes and Channel Type Bently Nevada Transducer
setpoints on the fly Acceleration and 200350 Accelerometer
Reciprocating 330400 Accelerometer
• Display component for Acceleration 330425 Accelerometer
statuses and variables Velocity and 190501 Velomitor*
• Display Hardware Identification Reciprocating 330500 Velomitor
and manufacturing information Velocity 330525 Velomitor
330750 Velomitor
• Context-specific help Radial Vibration, 3300 5 & 8 mm Proximitor*
• System Requirements Thrust, and Speed System
3300 XL 8mm Proximitor System
• Users may install software on a 3300 XL 11mm Proximitor System
notebook or desktop computer 3300 XL NSv* Proximitor System
that meets these minimum
7200 5 & 8mm Proximitor System
requirements:
7200 11mm Proximitor System
• Microsoft ® Windows® 2000 or 7200 14 mm Proximitor System
Windows XP or Windows Position 3300 5 & 8 mm Proximitor
Server 2003 Operating System System
• 800 MHz Pentium® III class 3300 XL 8mm Proximitor System
processor 3300 XL 11mm Proximitor System
3300 XL 25mm Proximitor System
• 256 MB RAM 3300 XL 50mm Proximitor System
• 8 MB video card 3300 XL NSv* Proximitor System
7200 5 & 8mm Proximitor System
• 8x or faster CD-ROM drive 7200 11mm Proximitor System
• 100 MB available hard drive 7200 14 mm Proximitor System
space
Note: The 1900/65A provides default configuration
• 10/100BaseT Ethernet settings for Bently Nevada* transducers. The user can
interface (10 or 100 Mb/s)
configure the 1900/65A to accept other transducers.
• 1024 x 768 screen resolution
recommended

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 12 of 21
Compliance and Certifications Ordering Information
EMC Country specific approvals may be available.
Standards: Please consult your local Customer Care
Representative for more information.
EN 61000-6-2 Immunity for Industrial
Environments
EN 61000-6-4 Emissions for Industrial
Environments 1900/65A General Purpose Equipment Monitor
1900/65A-AXX-BXX-CXX-DXX-EXX
European Community Directives:
A: Power Option
EMC Directive 2004/108/EC
00 18 to 36 Vdc
Electrical Safety 01 110 to 220 Vac @ 50 to 60 Hz
(external supply)
Standards:
B: Display Option
EN 61010-1
00 No display
01 Attached display (no cable)
European Community Directives:
02 Display with 10’ PVC cable
2006/95/EC Low Voltage
03 Display with 10’ unassembled
For further certification and approvals information please visit the PVC cable
following website: 04 Display with 10’ TEF cable
www.ge-mcs.com/bently 05 Display with 10’ unassembled
TEF cable
Hazardous Area Approvals
06 Display with 50’ PVC cable
This monitor is not certified for 07 Display with 50’ unassembled
installation in Class 1 Div 1 locations, PVC cable
but it will support transducers installed 08 Display with 50’ TEF cable
in Div 1 locations via the use of 09 Display with 50’ unassembled
galvanic isolators and barriers. If TEF cable
galvanic isolators are used, no change 10 Display with 100’ PVC cable
is necessary to the installation. A 11 Display with 100’ unassembled
removable ground jumper allows the PVC cable
monitor to support zener barrier 12 Display with 100’ TEF cable
installations. Removing the jumper will 13 Display with 100’ unassembled
disconnect circuit common from TEF cable
chassis at the monitor so that chassis 14 Display with 250’ PVC cable
can be connected at the barrier. 15 Display with 250’ unassembled
PVC cable
North American 16 Display with 250’ TEF cable
Ex/AEx nA [L] IIC 17 Display with 250’ unassembled
Class I Division 2 Groups A B C D TEF cable
T4 @ -20 °C ≤ Ta ≤ 70 ºC C: Mounting Option
00 None
Vn = 18 to 36 Vdc @ Imax = 1A per 01 DIN rail mount (see Figure 1)
drawing 173089
European
II 3G Ex nA [nL] IIC T4
@-20 °C ≤ Ta ≤ 70 °C
Sira 06 ATEX 4053X
IECEx SIR 06.0012X per drawing
173089
Maritime
DNV Cert A-12794
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 13 of 21
Figure 1: DIN Rail Mount Figure 4: 1900/55 Replacement Kit

02 Bulkhead Mount (see Figure 2) 07 ProTIM Housing, Wiring and


Mounting Hardware (See
Figure on page 21)

D: Approvals Option
00 None
Figure 2: Bulkhead Mount 01 Multiple approvals. See
Hazardous Area Approvals
03 Fiberglass NEMA 4X/IP66 WP section for specific
housing with window in door certifications.
(see Figure 3) 02 Maritime Cert (DNV)
E: Communications Option
00 None
01 Modbus communications

1900/01 – 1900/65A General Communications Monitor,


Communications Upgrade
1900/01-AXX-BXX-CXX-DXX
A: Order Type Option
01 New order (CD, key, and
binder)
Figure 3: NEMA 4X/IP66 WP Housing 98 Replacement licenses (key)
99 Configuration Software
only(CD)
04 1900/55 replacement kit (see B: Communications Option
Figure 4) 01 Modbus communications
Note: Uses existing 1900/55 weather-
proof housing and requires power option
C: License Key Type Option
A01 (110/220 Vac to 24 Vdc external 00 None
power supply) 01 USB license key
02 Floppy disk license key
D: License Quantity Option
XX Total licenses (1 to 99)

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 14 of 21
Accessories 168547-0050-02-02
15 m (50 ft) TEF cable,
167699-02
unassembled
1900/65A Display Module
168547-0100-01-01
173400-01
30 m (100 ft) PVC cable,
1900/65A Product Manual assembled
172250-01 168547-0100-01-02
1900/65 Modbus Gateway Users 30 m (100 ft) PVC cable,
Guide unassembled
173089-01 168547-0100-02-01
1900/65A Field Wiring Diagrams 30 m (100 ft) TEF cable,
assembled
02200794
168547-0100-
Power supply, 110/220 Vac to 24
02-02
Vdc 2.5 A DIN rail mount
30 m (100 ft) TEF cable,
02200121
unassembled
DIN rail end bracket
168547-0250-
168374 01-01
35mm DIN rail mounting clip for 75 m (250 ft) PVC cable,
1900/65A Monitor Module assembled
168495 168547-0250-
01-02
Bulkhead mounting plate
75 m (250 ft) PVC cable,
168547-0010-01-01
unassembled
3 m (10 ft) PVC cable, assembled

168547-0250-
168547-0010-01-02 02-01
3 m (10 ft) PVC cable, 75 m (250 ft) TEF cable,
unassembled assembled
168547-0010-02-01 168547-0250-
02-02
3 m (10 ft) TEF cable, assembled
75 m (250 ft) TEF cable,
168547-0010-02-02
unassembled
3 m (10 ft) TEF cable,
168628
unassembled
Stainless steel NEMA 4X
168547-0050-01-01
weatherproof door for panel-
15 m (50 ft) PVC cable, assembled mount display assembly
168547-0050-01-02 168629
15 m (50 ft) PVC cable, Painted steel NEMA 4
unassembled weatherproof door for panel-
mount display assembly
168547-0050-02-01
15 m (50 ft) TEF cable, assembled
Specifications and Ordering Information
Part Number 173401-01
Rev. L (11/14)

Page 15 of 21
168944 172555
Fiberglass NEMA 4X/IP66 Modbus/TCP (Ethernet) to
weatherproof housing with Modbus/RTU (Serial) Converter
window in door
169825-01
02295055
Training CD
MTL 728(-) barrier
02245002
MTL 796(-) barrier

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 16 of 21
Dimensions
Note: All dimensions shown in millimeters (inches) except as noted.

Figure 5: Monitor Module Dimensions

Figure 6: Display Module Dimensions

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 17 of 21
Figure 7: Combined Dimensions

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 18 of 21
Figure 8: Weatherproof Housing Dimensions

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 19 of 21
Figure 9: Weatherproof Door Drill Pattern

Figure 10: Weatherproof Door Dimensions

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 20 of 21
Figure 11: ProTIM Housing Dimensions

* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Company.

Microsoft and Windows are registered trademarks of Microsoft Corporation in the United States and other countries.
Modbus is a trademark of Modbus-IDA.

© 2006 – 2014 Bently Nevada, Inc. All rights reserved.

Printed in USA. Uncontrolled when transmitted electronically.

1631 Bently Parkway South, Minden, Nevada USA 89423


Phone: 775.782.3611 Fax: 775.215.2873
www.ge-mcs.com/bently

Specifications and Ordering Information


Part Number 173401-01
Rev. L (11/14)

Page 21 of 21

You might also like