RANGS R.K SQUARE - BOQ Fire 140719

This document provides a bill of quantities (BOQ) for a fire protection and detection system for a project located in Dhaka, Bangladesh. It includes 19 line items describing the supply, installation, testing, and commissioning of a fire alarm control panel, detectors, notification devices, isolator modules, emergency lighting, fire cables, fire accessories like suits and blankets, as well as documentation and testing. It also includes one line item for a public address speaker system. The high level goal is to provide a fully functioning fire detection, alarm, and notification system along with related equipment to protect the building and occupants.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
625 views30 pages

RANGS R.K SQUARE - BOQ Fire 140719

This document provides a bill of quantities (BOQ) for a fire protection and detection system for a project located in Dhaka, Bangladesh. It includes 19 line items describing the supply, installation, testing, and commissioning of a fire alarm control panel, detectors, notification devices, isolator modules, emergency lighting, fire cables, fire accessories like suits and blankets, as well as documentation and testing. It also includes one line item for a public address speaker system. The high level goal is to provide a fully functioning fire detection, alarm, and notification system along with related equipment to protect the building and occupants.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Fire Protection & Detection System

Client: RANGS PROPERTIES

Project: RANGS R.K SQUARE


Location: 13, Gulshan Avenue,
Circle-1,Dhaka

Date: 14.07.2019
Title: BOQ - Fire Protection & Detection
Rev No. :
Rv. Date:
Supply, Installation, Testing & Commissioning of the following with all accessories complete including integratio

SL No. Description of items

1 Addressable Type Fire Alarm Control Panel :


Supply & Installation of Addressable type Fire Alarm Control Panel complete
with following basic options. Master Controller Assembly / CPU shall be suitable
with port to add Voice alarm system / Fire Fighter Telephone system / Printer /
Remote Annunciator etc. FACP must be comply with internationally accepted
standard. Control units for Fire Protective Signaling Systems. Product shall be
UL listed or FM Approved with Graphic Software Computer-3G. FACP for per
loop upto 225 Addressable Devices and 3 loops. Country of origin : USA
/UK/EU/JAPAN

2 Repeater Panel / Remote Annunciator :


Supply & Installation of Repeater Panel / Remote LCD Annunciator with the
same "look and feel" as the FACP operator interface. The Remote LCD
Annunciator shall use the same Primary Acknowledge, Silence, and Reset
Keys, Status LEDs and LCD Display as the FACP. Product shall be UL listed or
FM Approved.Country of origin : USA /UK/EU/JAPAN

3 Addressable Type Heat Detector :


Supply & Installation of Addressable type Heat Detector / Thermal Sensor:
Combination fixed-temperature and rate-of-rise unit with plug-in base and alarm
indication lamp; 135° F fixed-temperature setting except as indicated. Product
shall be UL listed or FM Approved. Country of origin : USA /UK/EU/JAPAN

4 Multi Detector / Multi Sensors :


Supply & Installation of Multi-Sensors shall be combined with photoelectric
smoke sensing and heat sensing technologies complete with standard base.
An alarm shall be determined by either smoke detection, with selectable
sensitivity from 0.2 to 3.7 %/ft obscuration; or heat detection, selectable as fixed
temperature or fixed with selectable rate-of-rise; or based on an analysis of the
combination of smoke and heat activity. Product shall be UL listed or FM
Approved. Country of origin : USA /UK/EU/JAPAN

5 Addressable Type Smoke Detector :

Supply & Installation of Addressable type Smoke Detector c/w Standard Base.
Comply with internationally accepted standard "Smoke Detectors for Fire
Protective Signaling Systems." Include the following features:

The detector shall be Self-Restoring: Detectors do not require resetting or


readjustment after actuation to restore normal operation. Product shall be UL
listed or FM Approved. Country of origin : USA /UK/EU/JAPAN

6 Addressable Manual Pull Station :


Supply & Installation of Addressable type Manual Call Station of red LEXAN,
with molded, raised-letter operating instructions of contrasting color. Station will
mechanically latch upon operation and remain so until manually reset by
opening with a key common with the control units. Product shall be UL listed or
FM Approved Country of origin : USA /UK/EU/JAPAN

Addressable Manual Pull Station

7 Fire Alarm Bell :


Supply & Installation of Wall / Ceilling mounted type alarm bell of 150mm dia
shall be suitable to produce 72 dB of sound at a distance of 3 meter. Bell shall
be pressed steel gong with robust striker mechanism complete monitor module
and all other accessories. Power supply shall be 24V DC.
Installation of Alarm Bell shall be at location shown in the drawing and shall be
as per recommendation of the manufacturer. Product shall be UL listed or FM
Approved. Country of origin : USA /UK/EU/JAPAN/TAIWAN

8 Notification Device ( Horn with Strobe) :


Supply & Installation of Horn with Strobe for Audible & Visible application,
combination of Audible & Visible (A/V) Notification Appliance . Product shall be
UL listed or FM Approved.Country of origin : USA /UK/EU/JAPAN

9 Isolator Module / Fault Isolator Module :


Supply & Installation of Addressable type Isolator / Fault Isolator Module shall
be used in the field wiring between the devices (contractor shall propose the
quantity and location in the system required) to detect & isolate the devices at
the time short cirtuit in SLC. Product shall be UL listed or FM Approved.

Addressable Relay / Control Module / Out put Module and Input


10 Module :

10.1 Out put Module


Supply & Installation of Addressable Relay / Control Module shall be used in the
field wiring to connect the conventional Initiating devices with the Addressable
FACP interfaces to control / operate dampers, motors or similar appliances on
receiving signal from the FACP as when as required (configured by the service
provider). Product shall be UL listed or FM Approved.

10.2 In put Module


Supply and installation of addressable input module shall be used in the field
wiring to connect the conventional initiating devices with the addressable FACP
interfaces to control /operate dampers ,motors or similar apliances on reciving
signal from the FACP as when as Required ( configure by the service provider).
Temperature Range 0ᴼC to 50ᴼC. Product shall be UL listed/FM/LPCB
approved

11 Firemen Telephone Outlet:

Firemen telephone outlet shall be concealed type mounted on wall suitable to


adopt mail socket of the firemen telephone jack. Front cover shall be S.S plat.

12 Firemen Telephone Set :


Handheld type Firemen Telephone set shall be complete with portable box,
suitable to jack with outlet, communicate upto central panle.

Fireman Teiphone Cable (China)

13 Emergency / Indicating Light :


Supply & Installation of Emergency or indicating light to indicate way of exit.
Surface mounted type Emergency light shall be 24V, DC complete with
rechargeable battery and charger. Light shall be suitable for AC/DC. Power
supply shall be 220V single phase power supply from Fire Panel. Country of
origin China.

Evacuation Light / Exit Sign With Light :


14
Supply & Installation of Evacuation light shall be used during fire or emergency
at power interruption to facilitate the occupants to evacuate the building safety.
Light shall be double fittings type, with reflector, battery operated, 100watt, 24V,
DC power supply. Set shall be with auto charger, battery shall be good to
provide power for 30 minutes at least. Installation of Evacuation / Exit Sign with
light shall be at location shown in the drawing and shall be as per
recommendation of the manufacturer. Country of origin: China.

15 Fire Resistance Cable :


Supply and Installation of Fire retardant type twin core multi strend PVC
insulated, PVC sheathed electrical cable of copper conductor of required size
as per drawing and direction. Cable shall be complete with supply & return
lope .The work shall be complete with water grade PVC conduit, conduit bends,
tees etc. complete as per direction and standard. Cutting of wall, floor, roof etc.
mending good the damage shall be as per direction. All vertical cable work
through PVC conduits shall be concealed, necessary cutting (if any) shall be
done as required in walls & all horizontal cable work throgh PVC conduits shall
be surface. Cable work shall be done as per drawing and direction. The
Authority shall supply required power up to panel. the cable shall be able to with
stand fire temperature 400ºC for at least two hours.
Installation of Fire resistance Cable shall be as per recommendation of the
manufacturer. Approved type of metal conduit shall be used.

a) 1C X 1.5 mm FR
b) 1C x2.5 rm FR
16 Fire Accessories:
16.1 Fire Protected Suit :
Fire protected suit shall be suitable to withstand 150°C temperature for two
hours. Suit shall be suitable to cover total body of the fire fighter including shoe,
hand globs, transparent eye cover etc.

16.2 Fire Protected Breathing Mask


Fire protected Breathing Mask shall be suitable to withstand 150°C temperature
with breathing arrangement inside fire and smoke and of Standard size with all
accessories complete in all respect.

16.3 Fire Protected Blanket


Fire protected Blanket shall be suitable to withstand 150°C temperature for 30
minutes. Blanket shall be of standard size to cover hole body of the.

17.0 Maintenance Tools:


18.0 Spare Parts :
Spare parts for the fire detection system shall be suitable for 5 years trouble
free operation of the system. Detail of spare parts including its name and unit
rate shall be submitted.
19.0 Documentation :
Documentation after complete installation with as built drawing shall be as per
specification.
20.0 Testing Commissioning :
Testing and commissioning of the total fire detection system shall be done as per NFPA
standard. All test result shall have Owner’s approval.

B PA (Public Address) SYSTEM

SL No. Description of items

1 PA System Speaker :
Supply and Installation of surface mounted type speaker of capacity 15 watt
operable on 100 volt line. The speaker shall be housed within insect proof
metallic housing which is resistant to moisture. Country of origin: China/
Equivalent, Brand : Toa/Bosch

2 Cable For PA System Speaker :


Supply & Installation of two core audio cable with high quality sheathing
complete with PVC water grade conduit. Conduit shall be along pipe work for
PA system. All vertical cable work through PVC conduits shall be concealed,
necessary cutting (if any) shall be done as required in walls & all horizontal
cable work throgh PVC conduits shall be surface.

3 PA System Amplifier :
Supply & Installation of heavy duty amplifier for 9 Nos. of 15W speakers.
Amplifier capacity (240 x1) 240 watts. Country of origin : China/ Equivalent,
Brand : Toa/Bosch

4 PA Panel Microphone :
Supply & Installation of PA Panel suitable for announcement of fire status to the
occupants in the building. PA Panel shall be complete with self contained
speaker, goose neck microphone, zone selection switch, common
announcement switch and pre-selected and recorded fire announcement
system. Country of origin : China/ Equivalent, Brand : Toa/Bosch

5 Documentation :
Documentation after complete installation with as built drawing shall be as per
specification.

Balancing, Testing & Commissioning of Public Address System.


6
After completion of Installation : Balancing, Testing & commissioning of the
system shall be done as per recommendation of the Manufacturer and as per
NFPA. All the individual items shall be tested separately upto the satisfaction of
the Consultant/PD

C FIRE PROTECTION SYSTEM

SL No. Description of items

1 Fire Water Pump (Engine Driven) :


Supply & Installation of Diesel Engine Driven Fire Pump complete with all
related & essential accessories. The pump shall be designed and installed in
accordance with globally accepted international standard. Pumps shall be of
the non-overloading, centrifugal, volute type, horizontally split, double suction
type with suction and discharge connections in the lower half of the casing,
allowing removal of the rotating element without disturbing the pipe connections
and operating at not over 3000 rpm. Pumps shall be selected for a total
efficientcy of not less than 65%. Pump performance curves shall be submitted
for approval together with the pump technical data. The pump shall have a
capacity to handle 500 US GPM of water against a head of 90 Meter of water.
Each unit shall be tested and NFPA approved. Product shall be UL listed or
FM approved. Country of origin : USA /UK/EU/JAPAN

2 Fire Water Pump (Motor Driven) :


Supply & installation of electrically driven centrifugal type end suction, vertical
discharge Fire Water Pump manufactured according to globally accepted
international standard shall be complete with skid mounted, coupled with motor,
safety cover etc. Motor shall be 420V/3 phase/ 50 HZ/ 2900 rpm / Class F
insulation / Encloser IP55 [ as per pump manufacturer's recommendation /
performance curve of the pump ]. The pump shall have a capacity to handle 500
US GPM of water against a head of 90 Meter of water. Each unit shall be tested
and NFPA approved. Product shall be UL listed or FM approved. Country
of origin: USA /UK/EU/JAPAN

3 Jocky Pump (Pressure Maintenance Pump) :


Supply, installation of multistage jockey pump manufactured according to
globally accepted international standard for Fire Hydrant system to keep a
certain pressure in water distribution system. Capacity of the pump shall be 20
US GPM against a Head of 100 m of water. Pump shall be complete with motor
suitable to meet performance curve of the pump. The Motor shall be 420V/3
phase/ 50 HZ/ 2900 rpm. Country of Origin:
USA/UK/Germany/Denmark/Singapore.

4 Valve & Fittings :


Supply, Installation and testing of Valves & Fittings of manufactured according
to confirm ANSI B16, BS, ISO-9001starndard. different sizes of valves shall be
suitable to withstand a working pressure of 150 psi and complete in all respect
with all accessories such as Flanges, Nut – Bolts, Gaskets etc. Valves 80mm
dia and above shall be Cast Iron body flanged end type, smaller than those
shall be Brass / Bronze body Screwed end type. Country of Origin: Japan /
Germany / Italy / Denmark / Poland /Turkey / Malaysia OR Liscenced
Manufacturing units located Globally.

4.1 Gate Valve :


It shall be anti corrosive cast iron body flanged end type complete with
companion flanges, nut-bolt gasket etc above 80 mm dia.

a) 250 mm dia

b) 200 mm dia

b) 100 mm dia

c) 75 mm dia

d) 65 mm dia

e) 50 mm dia

f)50 mm dia (Ball Valve)

g) 40 mm dia Drain valve ( Gate / Ball Valve)

h)1000 mm dia Drain valve (Gate / Ball Valve)


4.2 Check /Non Return Valve (Disk Type) :
Non-return valves shall be re-grind able seat, screwed cap, lift type disk, integral
seal and flanges end type. Material: Cast iron, Joints: Threaded (upto 65mm),
flanged (above 65 mm).

a) 250 mm dia.

a) 200 mm dia.
b) 150 mm dia.

c) 100 mm dia.

d)75 mm dia.

e) 65 mm dia.

f) 50 mm dia.

4.3 Flexible Joint :


Flexible joint shall be suitable to absorb shock and system hammering and to
reduce vibration transmission. Flexible joint shall be ss construction, flanged
end type.

a250 mm dia.

b) 200 mm dia.

c) 65 mm dia.

c) 50 mm dia.

4.4 Foot Valve :


a) 250 mm dia.
b) 50 mm dia.
4.5 Y-Strainer :
Strainer shall be Y type with SS screen, flanged end type, cast iron body.

a) 250 mm dia.
a) 200 mm dia.
b) 65 mm dia.
b) 50 mm dia.
4.6 Pressure Release Valve :
Supply, installation and testing of Pressure Release valve of 4" inch (100mm)
dia of cast iron / brass body with adjustable knob to adjust set pressure for
release excess pressure from the sytem to safe the fire fighting system network
to drain. The valve shall be installed at pump house in discharge header. The
valve shall be suitable to withstand pressure of 12kg/cm². Inlet / outlet shall be
flanged / threaded end type.

4.7 Pressure Gauge :


Supply and installation of 4” dial type Pressure Gauges including supply of all
accessories and consumable. The range shall be 0-250 psi.

4.8 Pressure Switch :


Supply, installation and testing of Pressure Switch complete with sensing
element, enclosure material, 15 mm NPT pressure connection, direct mounting
electrical connection, other material etc.accepted/approved by the Consultant.

4.9 Auto Air - Vent Valve :


Supply & Installation of Auto Air vent valve of 1 inch (25mm) dia of 1" dia inlet
BSP, bronze made with rubber ball and seat. The valve shall be suitable to
release air from the fire hydrant pipes. Shall be suitable to withstand pressure
upto 10kg/cm².

4.10 Butterfly Valve :


Supply & installation of Butterfly valve shall be made of cast iron body, high
corrosion resistant bronze disc, liner, stainless steel stem, self locking lever with
locking mechanism showing degree of opening by pointer and calibrated notch
plate. having arrangement for flange connection with pipes.

a) 90mm dia.
b)65mm dia.

4.11 Flow Switch :


Supply & Installation of Flow Switch of leaf type suitable for installation within
65mm and 40mm dia water hydrant pipe. The flow shall sense flow of water
within pipe and send signal to water flow monitoring panel. Flow switch shall be
under control of water flow supervisory Panel to ensure the hydrant operation.
Power supply shall be 24VDC.

a) 90mm dia.
b) 65mm dia.
4.12 Pressure Reducing Valve :
Supply & Installation of Pressure Reducing valve of 1½" (40mm) and 2½"
(65mm) dia, brass body, screwed end type, shall be used with 40mm dia
internal Hydrant unit (where to reduce high pressure is necessary). Valve body
shall be made with hot pressed brass, seat of stainless steel ANSI304. Shall be
suitable for 80°C. Initial pressure shall be 15 bar, adjustable final pressure shall
be 0.5bar (min), 7bar (max).

a) 40mm dia.
b) 65mm dia.
5 Fire Hydrant Unit (1½" dia):
Each 1½" dia Fire Hydrant Unit shall be complete with the following
Components and accessories. The Fire Hydrant unit shall be Country of Origin
& shipment : Australia/USA/Japan/Malayasia/EU countries/or their liscenced
manufacturing units located Globally.
5.1 Hose Angle Valve (Landing valve): 1½" dia

Supply and installation of Hose Angle valve / Landing valve of 1½" (40mm)
shall be made with brass / bronze with instantaneous female outlet. The valve
shall be BS standard .

5.2 Ball Valve: 1½" dia


Supply and installation of Hose Ball valve of 1½" (63mm) shall be made with
brass / bronze/ cast iron with instantaneous female outlet. The valve shall be
BS standard.

5.3 Fire Hose : 1½" dia


Supply & installation of Fire Hose of 40mm dia 30 meter long suitable to install
inside the Hydrant cabinet. The hose shall confirming to BS standard .

5.4 Jet / Spray Nozzle : 1½" dia


Supply & installation of Jet / Spray Nozzle having 40mm dia male instantaneous
coupling.
5.5
Steel Cabinet for Double Compartment Type Hydrant Unit :

Locally Fabrication, Supply & Installation of double compartment type Hydrant


cabinet of suitble size : 30" X 72" X 12" (wide x height x depth) or as per site
measurement and requirement / Rrecommendation of Consultant/PD.

5.6 Hose Angle Valve (Landing valve): 2½" dia


Supply and installation of Hose Angle valve / Landing valve of 2½" (63mm)
shall be made with brass / bronze/ cast iron with instantaneous female outlet.
The valve shall be BS standard.

5.7 Ball Valve: 2½" dia


Supply and installation of Hose Ball valve of 2½" (63mm) shall be made with
brass / bronze/ cast iron with instantaneous female outlet. The valve shall be
BS standard.

6 Pillar Hydrant (Double Headed)


Supply and installation of cast iron body Double Headed Pillar Hydrant
complete with two nos. cast brass made controllabale outlet of 2½" (63mm) dia
with female instanteneous outlet, inlet shall be 4" (100mm) dia flanged end. The
Hydrant Shall be suitable to withstand test pressure of 300 psi (min). Color of
the units shall be red/apprdoved by the manufacturer or as per code. Country of
Origin: Australia/USA/Japan/Malayasia/EU countries/or their liscenced
manufacturing units located Globally.

7 Fire Brigade Connection : 2 - Way


Supply and installation of 2-Way Fire Brigade Connection with Cabinet,
complete in all respect with all accessories. The unit shall have two Inlet
connections of 2½" (63mm) male instanteneous with non-return valve and
having 6" dia (150mm) flanged type outlet directly connected with stand pipe. It
will have also one 25mm dia drain valve for drainage of water, rubber blank cap
and chain for protection. Outlet 150mm dia shall be as per ANSI-B-16B-16.5B.
or equivalent and Shall be suitable to withstand pressure of 20kg/cm². It shall
be manufactured according to BS standard & suitable for using with fire service
& civil defence department of Bangladesh.Country of Origin:
Australia/USA/Japan/Malayasia/EU countries/or their liscenced manufacturing
units located Globally.

8 Sprinkler Head :
Supply & Installation of Sprinklar head of 1/2" in diameter nominal orifice, K-
Factor 5.6 chrome finish glass bulb type. Temparature rating 680 C for general
area others area shall be specified as per requirement. Sprinklar head shall be
UL Listed / FM Approved..Country of Origin: USA/UK/ Equivalent

a ) Pendent type
b ) Up-Right type
c ) Side wall type

9 Automatic Alarm Check Valve :


Supply, Installation, Testing and commissioning of 150mm dia Alarm Check
Valve complete with retarded chamber, trim assemble, alarm gong, control,
drain & test valve as per manufacturer's specifications.Product shall be UL
listed or FM Approved. Origin: USA/UK/ Equivalent

10 Portable Fire Extinguisher :


a) Dry Chemical Powder Type:
Supply & fixing the following capacities multi purpose ABC&E dry chemical
powder stored pressure type with manometer system Fire Extinguisher suitable
for repeated use complete with wall bracket, CO Cartridge, easy refilling
system etc. as per sample accepted/approved by the Consultant.Country of
Origin: China or Equivalent

5 Kg. capacity.
b) Carbon-Di-Oxide (CO2) Type
Supply & fixing the following capacities Carbon-di-Oxide type Fire Extinguisher
suitable for repeated use complete with wall bracket, discharge nozzle etc. as
per sampleaccepted/approved by the Consultant. Country of Origin: China or
Equivalent

5 Kg. capacity.
11 Wet Chemical Fire Suppression System :
Wet chemical fire suppression system shall be complete with wet chemical
storage cylinder with discharge valve, wall bracket, mechanical control head,
discharge nozzle, remote control box, reset level assembly, SPDP micro switch,
vent plug, fusable link detector, EMT conduit, cable etc. complete in all respect.

4 gallon cylinder with all accessories.

2.5 gallon cylinder with all accessories

12 FM 200 Fire Suppression System :


FM 200 fire suppression system shall be complete with control center with
24VDC battery back up, FM gas cylinder with discharge valve, nipple, victualic
coupling and mounting, abort switch, release valve, low pressure switch,
warning signal, 150mm dia alarm bell, strobe light, high pressure flexible hose,
cable, conduit complete in all respect.

215 lbs. FM 200 for server room

60 lbs. FM 150 system for Generator Room


80 lbs. FM 150 system for for Sub-station
Auto Mechanical Foam System for Generator Room
13
Mechanical foam system shall be complete with foam chamber, deluze valve,
FFF 3% foam, Nozzle, sensors etc.

Pre Action System for Lift


14
Preaction shall be double inter lock type with deluze valve, compressure, valves
and other accessories for Lift Machine Room

15 Black Steel Pipe ERW, 40 Schedule:


Supply and Installation of Black steel pipe ERW, 40 schedule . The Pipe work
shall be included with welded type Tee, Elbow, Reducer etc., and also
hangers / supports etc completed. Pipe work (over ground) shall be painted with
red oxide primer. Underground pipes should be layed after wrapping with pvc
tape after using approved priver. Pipe wall thickness shall be as per mentioned
for different diameters.Origin: Korea/Vietnam/ Equivalent

a). 250 mm dia


a). 200 mm dia
b). 150 mm dia
c). 100 mm dia
d). 90 mm dia
e). 75 mm dia,
f). 65 mm dia,
g). 50 mm dia,
h). 40 mm dia,
i). 32 mm dia,
j). 25 mm dia,
k). 20 mm dia,
l).100 mm dia.Drain MS pipe riser(Origin:Bangladesh)
m).40 mm dia.Drain MS pipe riser(Origin:Bangladesh)

n).50 mm dia drain MS pipe (Origin: Bangladesh)


16 Pump Controler Panels :
Supply, installation of Fire pump (engine & motor driven) & Jockey Pump
Control Panel complete with MCCB / MCB / Magnetic Contactor / On-Off Push
switch / Indication Lamp for phase indication, run, trip mode / Ampere meter /
Volt meter / Overload Selector switch / Phase failure protection device / Dry
Operation Protection Device / Volt Guard / Connector Block / Bus-bar / CT of
rated capacity / Ventilation fan / Buzzer / Cable lugs / and all other accessories.
The Panel shall be well dressed in side for safety purpose and for looking good.
Product shall be UL/ FM Listed. Country of origin : USA /UK/EU/JAPAN

17
Electrical Cabling Work :
Supply and Installation of single/multi core Fire rated PVC insulated, PVC
sheathed electrical cable of copper conductor of following size as direction The
work shall be complete with water grade PVC conduit, required ECC, conduit
bends, tees, junction box, pull box etc. complete as per direction and standard.
Cutting of wall, floor, roof etc. mending good the damage shall be as per
direction. All horizontal cable work through PVC conduits shall be concealed
between RCC floor slab and floor tiles,necessary cutting (if any) shall be done
as required in walls and in floors.Termination and cable jointing shall be done
as per standard practise.The authority shall supply required power up to pump
house. Cable shall be BRB/Paradise.

18 Testing, Commissioning and Balancing :


After complete proper installation the system shall be tested, commissioned and
balanced of the system shall be done as per direction and recommendation of
the Manufacturer & NFPA. Pipe work system shall be tested at 250 psi/ 15 bar
pressure for 24 hours without any leakage. All the individual items shall be
tested separately upto the satisfaction of the Consultant/PD. After proper
testing, commissioning and balancing the system shall run for seven days upto
the satisfaction of the Owner.

19 Documentation :
After complete installation, testing commissioning and balancing the system the
contractor shall have to provide as built drawing as per specification.

20 Training & Fire Drill :


After complete installation, testing commissioning and balancing the system the
contractor shall have to provide training programme to the representatives of
the Client. Fire drill shall be performed before handing over the system to the
Owner. Fire Drill shall be performed at least once in a month for 12 months
defect liability period.

D FIRE DOOR :

1 Fire Rated Door


Supply & Installation of Fire Rated Door complete with UL Listed /FM approved
Panic Bar. The door shall be made with 1.5mm thick sheet steel painted with
approved red colour over a coat of primer. Thickness of the leaf shall be 40mm
and filled with fire proof / resisting materials of minimum two hours rated. Door
size shall be 60" (wide) X 84" (height).Country of Origin : Locally Fabricated /
China.

Gra

Grand Total Taka in word:


System

RANGS R.K
SQUARE

all accessories complete including integration with IBMS system:

Total Rate (Tk) Amount


Unit
Qty. (Tk)

Set 1

Set 49

Set 95

Set 13
Set 113

Set 59

No. 59

No. 59

Set 34
Set 59

Set 59

No 34

Set 34

RFT 1000

No. 100

No. 59
Rft. 1000
Rft. 2000

Set. 34

Set 34

Set 34

Lot. 1
Lot 1
Job. 1

Job. 1

Total Rate (Tk) Amount


Unit
Qty. (Tk)

No. 59

Rft. 2000

Set 1

No. 1

Job. 1

Job 1
Total Rate (Tk) Amount
Unit
Qty. (Tk)

Set 1

Set 1

Set 1
-

No 2

No 2

No 2

No 0

No 2

No 1

No 1

No 1

No 34

-
No 2

No 2
No 0

No 0

No 3

No 25

No 1

No 1

No 1

No 1

No 1

No 1
No 0

No 1
No 1
No 1
No 1
No 1

No 38

No 38
No 1

-
No 6
No 28

No 6
No 28

No 9
No 0
33
No 33

33

Set 33

No 33

-
33
No

No 33

33

No 1

No 1
No 205
No 245
No
Set 1

No 59

No 59 -
Set 0

Set 0

Set

Set 1
Set 1

Set 1

Set 0

Rft. 350
Rft. 350
Rft. 0
Rft. 0
Rft. 90
Rft. 950
Rft. 1850
Rft. 350
Rft. 675
Rft. 450
Rft. 2051
Rft.
Rft. 350
Rft. 0

Rft. 0
Set 1

Lot 1

Job 1

-
Rate (Tk) Amount
Unit QTY
(Tk)
Sqft 1050

Total Taka = -
Grand Total in Taka :