Reinforced Concrete Footing Types: Home Structural Engineering Foundation Design
Reinforced Concrete Footing Types: Home Structural Engineering Foundation Design
Reinforced concrete footing are designed based on column loads and moments at base and the
soil data. This article shed light on the design of reinforced concrete footing.
The brick wall footings can also be designed. Often plinth beams are provided to support brick
walls and also to act as earthquake ties in each principal direction.
If these loads are to be properly transmitted, footings must be designed to prevent excessive
settlement or rotation, to minimize differential settlement and to provide adequate safety against
sliding and overturning.
Depth of footing
As per clause 34.1.3 of IS456: 2000 and section 15.7 of ACI 318-14 the thickness of
footing at its edge shall not be less than 15cmm on soils, or less than 30cm for footings
on piles.
Depth of foundation below ground level can be obtained by using Rankine’s formula:
: density of soil
Dimension of pedestal
In the case of plain cement concrete pedestals, the angle between the plane passing through the
bottom edge of the pedestal and the corresponding junction edge of the column with pedestal and
the horizontal plane shall be governed by the expression.
Where:
Fig.1: dimension of pedestal
According to ACI 318- 14 section 15.4.1 and 15.4.2, and IS 456: 2000 clause 34.2.3.1 and
34.2.3.2, The bending moment will be considered at the face of column, pedestal or wall and
shall be determined by passing through the section a vertical plane which extends completely
across the footing, and over the entire area of the footing or one side of the said plane.
Fig.2: Maximum bending moment in footing
1. The footing acting basically as a wide beam, with a potential diagonal crack intending in
a plane across the entire width, the critical section for this condition shall be assumed as a
vertical section located from the face of the column, pedestal or wall at a distance equal
to the effective depth of the footing in case of footings on soils. For one way shear
action, the nominal shear stress in calculated as:
Where:
: shear stress
d: effective depth
, where :design shear strength of concrete based on % longitudinal tensile reinforcement.
Refer table 61 of SP -16)
2. For two way shear (or two way bending action or punching shear) of foundation, the following
should be checked in punching shear. Punching shear shall be around the perimeter 0.5 times the
effective depth away from the face of the column or pedestal.
For two way shear action, the nominal shear stress is calculated in accordance with clause
31.6.2 of IS456: 2000 as follows:
Where
: shear stress
When shear reinforcement is not provided, the nominal shear stress at the critical section should
not exceed
Where:
Note: It is general practice to make the base deep enough so that shear reinforcement is not
required.
According to ACI 318-14 section 15.6 and IS 456: 2000 clause 34.2.4.3, the critical section for
checking the development length in a footing shall be assumed at the following planes:
At the face of the column, pedestal or wall, for footings supporting a concrete column,
pedestal or wall.
Halfway between the centre-line and the edge of the wall, for footings under masonry
walls.
Halfway between the face of the column or pedestal and the edge of the gussetted base,
for footings under gussetted bases.
All other vertical planes where abrupt changes in section occur.
Reinforcement in footings
The minimum reinforcement in footing slab specified by the code is 0.12% and maximum
spacing specified is 3 times the effective depth or 450mm whichever is less. (clause 34.3).
In one-way reinforced footing; two-way reinforced square footing; and long direction of two way
rectangular footing, the-reinforcement extending in each direction shall be distributed uniformly
across the full width of the footing.
However, there shall be a central band, equal to the width of the footing for short direction of
two way rectangular footings. The reinforcement in the central band shall be provided in
accordance with the following equation.
Where B is the ratio of long side of the footing to its short side.
The bearing pressure on the loaded area shall not exceed the permissible bearing stress in direct
compression multiplied by a value equal to but not greater than 2.
Where:
: supporting are for bearing of footing, which is sloped or stepped footing may be taken as the
area of the lower base of the largest frustum of a pyramid or cone contained wholly within the
footing and having its upper base, the area actually loaded and having side slope of one vertical
to two horizontal.
For limit state design, the permissible bearing stress specified is 45 fck.
If the permissible bearing stress is exceeded either in the column concrete or in footing concrete,
reinforcement must be provided for developing the excess force. The reinforcement may be
provided either extending the longitudinal bars into the footing or by providing dowels in
accordance with the code as given by the following: