100% found this document useful (1 vote)
1K views4 pages

V-LFP48100 (48V100Ah) : Vision Technology Delivers Safe Lithium Iron Phosphate Battery Solutions For Telecom Application

This document provides information on the V-LFP48100 48V100Ah lithium iron phosphate battery system from Vision Technology for telecom backup applications. The system features include built-in battery management system (BMS) for monitoring, protection from over/under voltage, temperature and current conditions. The battery has a 48V nominal voltage, 100Ah capacity, 15 cells, and dimensions of 440mm x 440mm x 177mm. It is suitable for telecom equipment backup when main power fails and recharges when power is restored.

Uploaded by

Mai Linh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views4 pages

V-LFP48100 (48V100Ah) : Vision Technology Delivers Safe Lithium Iron Phosphate Battery Solutions For Telecom Application

This document provides information on the V-LFP48100 48V100Ah lithium iron phosphate battery system from Vision Technology for telecom backup applications. The system features include built-in battery management system (BMS) for monitoring, protection from over/under voltage, temperature and current conditions. The battery has a 48V nominal voltage, 100Ah capacity, 15 cells, and dimensions of 440mm x 440mm x 177mm. It is suitable for telecom equipment backup when main power fails and recharges when power is restored.

Uploaded by

Mai Linh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

V-LFP48100 (48V100Ah)

Vision Technology delivers safe lithium iron phosphate


Battery solutions for Telecom application.

Overview Features
The V-LFP 48V100Ah back-up lithium iron  RS485 communication output for monitoring
phosphate battery system is developed for backup  Built-in BMS with Charging current limitation
of Telecom equipment. Under normal condition,  Built-in automatic protection for over-charge,
grid AC power supply to rectifier module and the Over - discharge and over-temperature
Telecom loads and charge battery pack; When conditions
the AC power fail, rectifier module stop power  State of charge and state of health indication
supply, the battery serves for Telecom equipment,  Built-in battery control for efficient operation
to ensure the Telecom equipment runs normally;  Internal cell balancing
when the AC power is switched on again, power  Compatible with standard Telecom rectifiers
rectifier module for Telecom equipment recover  Maintenance free
to while charge the battery pack.

Specifications V-LFP48100
Voltage 48 V
Number of cell 15 cell
Nominal Capacity (40°C , 0.5C) 100 Ah
Weight (Approximate) 42.6±0.3Kg
Normal energy (40°C , 0.5C) 4800 Wh
Energy Volumetric energy density 153Wh/L
Gravimetric energy density 112Wh/kg
Dimensions (W*D*H) Width*Depth* Height 440mm*440mm*177mm
Impedance (Max, at 1000Hz.) ≤25mΩ

Standard Discharge Max. constant current 100A


25°C Cut-off voltage 42V
Charge Voltage 54-55V
Standard charge Max. constant current 100A
25℃ Recommended charging
20A(0.2C) for5.2 hours
current and time
Round trip efficiency (%) >96%
Calendar life 25°C >12 years
Cycle life (0.2C, 25°C) 80% DOD 4000 cycles
Charging: 0°C ~60°C
Recommend operating temperature
Discharging: -20°C ~ 60°C
Recommend storage temperature Recommended range: 0℃ ~ 60℃

www.vision-tech.vn
BMS Parameters.
Setting value
NO. Type Function Remarks
V-LFP48100 48V100Ah

1 Cell Voltage Protection 3.90V Protection Recover at 3.6V


Charge
2 Total Voltage Protection 57V Protection Recover at 54.0V
Voltage
3 Cell Voltage Protection 2.3V Protection Recover at 3.1V
Discharge
4 Total Voltage Protection 42V Protection Recover at 46.5V

5 charge Normal ≤100A

6 Normal ≤100A
Delay 30s ,recovery in
7 Current Over Current Protection 1 >100A and <150A
every 60s
Discharge
Delay 3s ,recovery in
Over Current Protection 2 >150A and <300A
every 60s
8 Short Circuit Protection ≥300A Delay 300uS
Charging < -10℃
9 Cell Temp 1 Low temp protection Delay 1~2S
Discharging <- 20℃
Charging >70℃
10 Temp Cell Temp 2 High temp protection Delay 1~2S
Discharging >75℃
11 PCB Range ≥95℃ Recovery at 75℃
All cell voltages<3.4V
Make all cells be balance
Cell VMax.≥3.40V and VMax. - VMin≥40mV, or VMax. - VMin ≤40mV,
12 Balance during charging process.
Balance Start balance or discharge Stop
Current: 150mA
balance

Battery Status.
1. Stop/Transport Mode. In working mode, turn off air switch, battery will go to STOP mode with low
self-discharge. In STOP mode, charging MOS and discharging MOS are turn off, battery cannot charge, discharge
or communicate.

2. Working Mode. In STOP mode, connect the battery to SMPS, turn on air switch, battery will go to working mode.
In working mode, BMS will monitor battery voltage, current, and temp and communication is available, charging
MOS and discharging MOS are closed, Battery will operate as the settings.

3. Sleep Mode. After turn on the battery, if the battery voltage below low voltage protection, BMS will go to sleep
mode in 1 minute. In sleep mode, charging MOS and discharging MOS are closed; BMS will check the
current in every 1 min, if there is charging current connecting; battery will turn to working mode.

4. Error Mode. In working mode, if there is: ①.Battery cells, ΔU>1V, or ②.Any cell voltage>3.9V or <2.3V,
or ③. Battery temp is <-20℃ or +75℃. BMS will go to error mode, ALM will bright and other LED will shut
down, and go to STOP mode, charging MOS and discharging MOS are turn off. Need to make troubleshoot.

www.vision-tech.vn
Performance Curve.

Discharge Performance at 40℃ Temperature effects on capacity at 0.5C


58 110

54 100

50 90
Capacity (%)
Voltage (V)

46 80

42 70
0.5C 0.1C
0.2C
38 60
0 20 40 60 80 100 120 -30 -20 -10 0 10 20 30 40 50 60 70
Capacity (%) 0.1C 0.2C 0.5C Temperature (℃)

Charge and Discharge at 40℃,0.5C Self-discharge at different temperature


110
54 Charge 100
Capacity (%)

50 90
Voltage (V)

80
46 70
60 45℃ 35℃ 25℃
42 55℃
50
Discharge
38 40
30
0 20 40 60 80 100 120 0 2 4 6 8 10 12 14 16 18 20 22 24
Capacity (%) Storage time (months)

www.vision-tech.vn
Discharge Performance at 45 ℃ Temperature effects on capacity at 0.2C
58 110

54 100

50 90

Capacity (%)
Voltage (V)

46 80

42 70
1C 0.1C
0.5C 0.2C
38 60
0 20 40 60 80 100 120 -30 -20 -10 0 10 20 30 40 50 60 70
Capacity (%) 0.1C 0.2C 0.5C 1.0C Temperature ( ℃)

Performance may vary depending on, but not limited to cell usage and application. If cell is used outside specifications, performance will
diminish. All specifications are subject to change without notice. All information provided herein is believed, but not guaranteed, to be
current and accurate.

www.vision-tech.vn