Data sheet 6EP1961-2BA21

SITOP PSE200U SELECTIVITY MODULE 10A


SITOP PSE200U 10 A Selectivity module 4-channel input: 24 V
DC/40 A output: 24 V DC/4x 10 A Level adjustable 3-10 A with
common signaling contact

Input
Type of the power supply network Controlled DC voltage
Supply voltage / at DC / Rated value 24 V
Input voltage / at DC 22 ... 30 V
Overvoltage overload capability 35 V
Input current / at rated input voltage 24 V / Rated 40 A
value

Output
Voltage curve / at output controlled DC voltage
Formula for output voltage Vin - approx. 0.2 V
Relative overall tolerance / of the voltage / Note In accordance with the supplying input voltage
Number of outputs 4
Output current / up to 60 °C / per output / rated value 10 A
Adjustable pick-up value current / of the current- 3 ... 10 A
dependent overload release
Type of response value setting via potentiometer
Product feature / parallel switching of outputs No

6EP1961-2BA21 Subject to change without notice


Page 1/3 10/31/2018 © Copyright Siemens
Product feature / bridging of equipments Yes
Type of outputs connection Simultaneous connection of all outputs after power up of the
supply voltage > 20 V, delay time of 25 ms, 100 ms or adjustable
"load optimised" via DIP switch for sequential connection

Efficiency
Efficiency in percent 99 %
Power loss [W] / at rated output current / for rated 10 W
value of the output current / typical

Switch-off characteristic per output


Switching characteristic
● of the excess current Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s
● of the current limitation Iout = 1.5 x set value, switch-off after typ. 100 ms
● of the immediate switch-off Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
Design of the reset device/resetting mechanism via sensor per output
Remote reset function Non-electrically isolated 24 V input (signal level "high" at > 15 V)

Protection and monitoring


Display version / for normal operation Three-color LED per output: green LED for "Output switched
through"; yellow LED for "Output switched off manually"; red LED
for "Output switched off due to overcurrent"
Design of the switching contact / for signaling Common signal contact (changeover contact, rating 0.1 A/24 V
function DC)

Safety
Galvanic isolation / between input and output at No
switch-off
Operating resource protection class Class III
Certificate of suitability
● CE marking Yes
● as approval for USA UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508,
CSA C22.2 No. 107.1) File E197259
Standard / for safety according to EN 60950-1 and EN 50178
Certificate of suitability / relating to ATEX IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc;
cCSAus Class I, Div. 2, Group ABCD, T4
Shipbuilding approval DNV GL, ABS
Protection class IP IP20

EMC
Standard
● for emitted interference EN 55022 Class B
● for interference immunity EN 61000-6-2

Operating data
Ambient temperature
● during operation -25 ... +60 °C
— Note with natural convection

6EP1961-2BA21 Subject to change without notice


Page 2/3 10/31/2018 © Copyright Siemens
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Environmental category / acc. to IEC 60721 Climate class 3K3, no condensation

Mechanics
Type of electrical connection screw-type terminals
● at input +24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals
for 0.5 ... 4 mm²
● at output Output 1 ... 4: 1 screw terminal each for 0.5 ... 4 mm²
● for signaling contact 3 screw terminals for 0.5 ... 4 mm²
● for auxiliary contacts Remote reset: 1 screw terminal for 0.5 ... 4 mm²
Width / of the enclosure 72 mm
Height / of the enclosure 80 mm
Depth / of the enclosure 72 mm
Installation width 72 mm
Mounting height 180 mm
Net weight 0.2 kg
Mounting type Snaps onto DIN rail EN 60715 35x7.5/15
Mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-
1SB20
MTBF / at 40 °C 540 979 h
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)

6EP1961-2BA21 Subject to change without notice


Page 3/3 10/31/2018 © Copyright Siemens