YDV Modular DC Inverter R-410A 60 HZ PDF
YDV Modular DC Inverter R-410A 60 HZ PDF
___________________________________________________________________________________
-1-
Contents
___________________________________________________________________________________
Contents
Part 5 Installation…………………………………………………………………………………………………………260
1. Summarize of Installation ……………………………………...........................…………………..…………262
2. Installation of Outdoor unit………………………………………………………………………………………. .266
3. Installation of Indoor unit ……………………………………………………….....………………….….…….…271
4. Installation of Refrigerant Pipe ……………………………....…………….……………………..….………. .273
5. Processing & Installation of drainage pipe……………………………………………………………………310
6. Installation work………………………………………………………………………………………………………..313
7. Pipeline Installation……………………………………………………………………………………………………316
8. Electric installation………………………………………………………………………………….…………………321
___________________________________________________________________________________
-2-
Contents
___________________________________________________________________________________
___________________________________________________________________________________
-3-
General information
_______________________________________________________________________________________________
_______________________________________________________________________________________________
-4-
General information
_______________________________________________________________________________________________
Contents
1. Features………………………………………………………………………………………….……………………….6
2. Nomenclature……………………………….…………………………………………………………………………19
3. YDV Products Lineup………………….………………………………………...………………………………….20
_______________________________________________________________________________________________
-5-
General information
_______________________________________________________________________________________________
1. Features
1.1) Environment friendly
DC Inverter Smart adopts High tech brushless DC motor, Neodymium material permanent
magnet of rotor, New Design for Magnet Arranging, concentrate Magnetic Lines, reduce the
New DC Motor central winding motor owns high efficiency comparing with normal DC motor.
New DC Motor
Efficiency
High-
perfor
manc
e Normal DC Motor
20 40 60 80 100 Speed(S-1)
_______________________________________________________________________________________________
-6-
General information
_______________________________________________________________________________________________
1.3) Vector Control Technology
System stepless Vector Adjust Vector Drive Technology:
1. The units can adjust capacity according the ambient temperature.
2. The system can be stepless adjusted with vector driving tech in the operation range from 60Hz
to 180Hz; it means the output can actually meet your requirement to make you feel more
comfortable.
C a p a c i t y — — F re q u e n c y c u r v e :
Frequency (Hz)
180
DC stepless vector adjust
Capacity (%)
0 20 40 60 80 100
_______________________________________________________________________________________________
-7-
General information
_______________________________________________________________________________________________
_______________________________________________________________________________________________
-8-
General information
_______________________________________________________________________________________________
1.4) High efficiency
The efficiency of DC Inverter Smart is increased 25% compared with AC Inverter Smart at
least.
Cooling EER
4.15
3.18 3.62 3.39 3.26 3.15 3.20 Average EER 3.53
4.0 3.09 3.01 3.08
3.0
2.0
DC
1.0 AC
0
8HP 10HP 12HP 14HP 16HP
Heating COP
4.35 4.12 Average COP3.97
4.08 3.88
3.60 3.39 3.79
4.0 3.21 3.20 3.15
3.0
DC AC
2.0
1.0
0
8HP 10HP 12HP 14HP 16HP
_______________________________________________________________________________________________
-9-
General information
_______________________________________________________________________________________________
The max. pipe length between indoor unit and outdoor unit is 175m.
The max. height difference between indoor unit and outdoor unit is 70m.
The max. distance between the first branch to the farthest indoor unit is 40m.
The max. height difference between indoor units is 15m.
_______________________________________________________________________________________________
- 10 -
General information
_______________________________________________________________________________________________
1.6) Free combination, wide capacity range
1.7) Patented design, running reliable, and oil return to the system better.
1.7.1 Oil Control technology
Suction pipe
Discharge pipe
Oil basin
Oil balance between modules, special oil balance vector control equipment ensured oil
reasonable distribution between modules, and make sure the compressor operate more stable
and reliable
_______________________________________________________________________________________________
- 11 -
General information
_______________________________________________________________________________________________
Refrigerant flow
direction Enter
condenser
Oil separator
Oil balance
Refrigerant flow
From evaporator
DC Inverter Smart adopts oil balance technology, which can balance the refrigerant lubricant
distribution among different modules.
Adopts high efficient centrifugal-type oil separator, which separate the lubricant from
diDCN1harge refrigerant with up to 99% effect to make all the lubricant diDCN1harged from
compressor can be returned in time.
New designed low pressure liquid receiver with high efficiency of oil-return effect.
Oil balance ensures sufficient refrigerant lubricant supply. Elaborately designed oil-return hole,
which ensure reliable oil-return for every compressor.
_______________________________________________________________________________________________
- 12 -
General information
_______________________________________________________________________________________________
_______________________________________________________________________________________________
- 13 -
General information
_______________________________________________________________________________________________
1.10) Patented double four way valve designs.
The combination of one main and one auxiliary four way valve can control the outdoor heat
exchanger and outdoor air flow independently. And according to the load adjust the heat
exchange volume of outdoor unit accurately and prevent wasting the capacity in part load time.
_______________________________________________________________________________________________
- 14 -
General information
_______________________________________________________________________________________________
Installation by stages can avoid the no installment for the new project
Convenient installation is realized for the rebuilt project.
1.12.3 No need special maintenance work
Simple refrigerant piping system without any complicated maintenance work
Compared with the water-cooled system:
Without water-cooled system, there is no need to clean the water pipe
No full-time person is needed to do the maintenance work
Module construction enables the system to be free from large-DCN1ale repair regularly
_______________________________________________________________________________________________
- 15 -
General information
_______________________________________________________________________________________________
_______________________________________________________________________________________________
- 16 -
General information
_______________________________________________________________________________________________
27 52
℃ ℃
-20 -15
℃ ℃
Low-ambient cooling function
Thanks to the low ambient kit built-in with the outdoor unit, even when the outdoor temp. is as
_______________________________________________________________________________________________
- 17 -
General information
_______________________________________________________________________________________________
low as -15 o C, the system can also work in cooling mode.
The lowest heating temperature can reach -20 o C.
The system (not cold area type) will operation normally under low ambient temperature, but
the heating capacity and efficiency will be reduced:
110%
100% 100%
Heating Capacity(%)
90%
83%
80%
76%
70%
62%
60%
50% 49%
40%
-15℃ -10℃ -5℃ 0℃ 2℃ 7℃
Outdoor Temperature(℃)
Select the cold area type units or according heating capacity for the cold area.
_______________________________________________________________________________________________
- 18 -
General information
_______________________________________________________________________________________________
2. Nomenclature
YDV YORK AC/DC Inverter - E High wall Everest B R407C 2 220-240V-3-50Hz / 200-230V-3-60Hz
K 4-Way Cassette
Q 1-Way Cassette
T Hi ESP Ducted
U Me ESP Ducted
F Fifth generation
Example
YDS-280WA35A - York Digital Scroll Outdoor unit 28 kW, R-22, 3 Ph 50 Hz, 1st generation
YDS-22KA15IA - York Digital Scroll Cassette type 2.2 kW, R-22, 1 Ph 50 Hz, EXV. fixed on
unit, 1st generation
_______________________________________________________________________________________________
- 19 -
General information
_______________________________________________________________________________________________
25.2 25.2 13
28.0 28.0 16
33.5 33.5 16
40.0 40.0 16
45.0 45.0 16
53.2 25.2+28.0 20
56.0 28.0+28.0 20
61.5 28.0+33.5 20
68.0 28.0+40.0 20
73.0 28.0+45.0 20
78.5 33.0+45 20
85.0 40.0+45 32
90.0 45.0+45.0 32
96.0 28.0x2+40.0 32
3 Ph, 230 V, 60 Hz
101.0 R-410A 28.0x2+45.0 32
3 Ph, 380 V, 60 Hz
106.5 28.0+33.5+45.0 32
113.0 28.0+40.0+45.0 40
118.0 28.0+45.0x2 40
123.5 33.5+45.0x2 40
130.0 40.0+45.0x2 40
135.0 45.0x3 40
140.5 28.0x3+40.0 50
145.5 28.0x3+45.0 50
152.0 28.0x2+40.0+45.0 50
157.0 28.0x2+45.0x2 50
163.0 28.0+45.0x3 50
168.5 33.5+45.0x3 64
175.0 40.0+45.0x3 64
180.0 45.0x4 64
_______________________________________________________________________________________________
- 20 -
General information
_______________________________________________________________________________________________
3.2) Indoor Units
Capacity 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 28.0
YDS Product
Refrigerant kW kW kW kW kW kW kW kW kW kW kW
One-Way Cassette
Four-way Cassette
R-410A
Floor ceiling
_______________________________________________________________________________________________
- 21 -
Unit selection
___________________________________________________________________________________
- 22 -
Unit selection
___________________________________________________________________________________
1. General Instruction
Note:
Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be
calculated according to the combination by using outdoor unit capacity table.
- 23 -
Unit selection
___________________________________________________________________________________
- 24 -
Unit selection
___________________________________________________________________________________
2. Unit selection (Based on Cooling Load)
Determine correct table according to the outdoor unit model and combination ratio.
Enter the table at given indoor and outdoor temperature and find the outdoor unit capacity and
power input.
The individual indoor unit capacity (power input) can by calculated as follows.
IUC=OUC × INX/TNX
Then, correct the indoor unit capacity according to the piping length.
If the corrected capacity is smaller than the load, the size of indoor unit has to be increased and
repeat the same selection procedure.
- 25 -
Unit selection
___________________________________________________________________________________
- 26 -
Unit selection
___________________________________________________________________________________
Notes: These figures assume the following operation conditions (Indoor and outdoor units):
1. Equivalent pipe length: 10 m
2. Height difference: 0 m
- 27 -
Unit selection
___________________________________________________________________________________
1) Given condition
[1] Design condition (Cooling: Indoor 19°C (WB), Outdoor 35°C (DB))
[2] Cooling load
Select the suitable capacity for condition of ‘Indoor 19°C (WB), Outdoor 35°C (DB)’ using
indoor unit capacity table. The selected result is as follows. (Assuming the indoor unit type is
duct)
- 28 -
Unit selection
___________________________________________________________________________________
c. Capacity change factor with pipe length (50m) and height difference (30m): 0.958
d. Each cooling capacity
[4] Conclusion: Generally, we think this result is acceptable, so we can think we have
accomplished the calculation. But if you think this result is not acceptable, you can repeat the
over process.
Remark: In these samples, we don’t consider the other capacity modification index and assume
them is 1.
- 29 -
Outdoor
30
Outdoor
Contents
1. Specifications………………………………..…………………………………………………………………………….32
2. Capacity table……………………………………………………………………………………..…….……………..…34
3. Dimensions………………………………………………………………………………………..……………………....54
4. Service space…………………………………………………………………………………….………………….......56
5. Piping diagrams...……………………….……………………………………………………..………………………..57
6. Wiring diagrams…………………………………………………….…………………………..………………………..59
7. Electric characteristics………………………………………………………………………..……………………..…61
8. Operation limits…………………………………………………………………………………..………………….……62
9. Noise Levels………………..……………………………………………………………………..……………….….……63
10. Trouble-shooting ………………………………………………………………………………..………………….....64
11. Accessories ………..……………………………………………………………………………..………………………77
12. Explode view and spare part list …………….………………………………………….……………...…………78
31
Outdoor
1. Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and
outdoor temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor
temperature: 7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
32
Outdoor
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and
outdoor temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor
temperature: 7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
33
Outdoor
___________________________________________________________________________________
2. Capacity table
YDS-252WC26/36 COOLING TC: total capacity, PI: power input
Indoor temperature(°CWB/DB)
Combination, Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
%(Capacity temperature(°C
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
index) DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 17.45 2.03 20.60 2.52 23.75 3.02 25.20 3.28 26.65 3.47 27.23 3.57 27.81 3.71
12 17.45 2.06 20.60 2.57 23.75 3.08 25.20 3.34 26.65 3.54 27.23 3.63 27.81 3.77
14 17.45 2.10 20.60 2.62 23.75 3.13 25.20 3.40 26.65 3.60 27.23 3.70 27.81 3.84
16 17.45 2.14 20.60 2.66 23.75 3.19 25.20 3.46 26.65 3.67 27.23 3.76 27.81 3.91
18 17.45 2.18 20.60 2.71 23.75 3.25 25.20 3.52 26.65 3.73 27.23 3.83 27.81 3.98
19 17.45 2.21 20.60 2.76 23.75 3.30 25.20 3.58 26.65 3.80 27.23 3.90 27.81 4.04
21 17.45 2.37 20.60 2.96 23.75 3.54 25.20 3.84 26.65 4.07 27.23 4.18 27.81 4.37
23 17.45 2.54 20.60 3.17 23.75 3.79 25.20 4.11 26.65 4.36 27.23 4.47 27.81 4.65
25 17.45 2.72 20.60 3.39 23.75 4.06 25.20 4.40 26.65 4.66 27.23 4.80 27.81 4.99
27 17.45 2.91 20.60 3.62 23.75 4.34 25.20 4.70 26.65 4.99 27.23 5.13 27.81 5.32
100% 29 17.45 3.10 20.60 3.87 23.75 4.63 25.20 5.02 26.65 5.32 27.23 5.45 27.81 5.73
31 17.45 3.31 20.60 4.12 23.75 4.94 25.20 5.36 26.65 5.68 27.23 5.86 27.81 6.06
33 17.45 3.53 20.60 4.39 23.75 5.26 25.20 5.71 26.65 6.05 27.23 6.22 27.81 6.45
35 17.45 3.75 20.60 4.67 23.75 5.60 25.20 6.07 26.65 6.43 27.23 6.58 27.81 6.74
37 17.45 3.99 20.60 4.97 23.75 5.95 25.20 6.46 26.65 6.84 27.23 7.01 27.81 7.17
39 17.45 4.01 20.60 4.99 23.75 5.98 25.20 6.48 26.65 6.87 27.23 7.03 27.81 7.20
41 17.45 4.03 20.60 5.02 23.75 6.01 25.20 6.51 26.65 6.90 27.23 7.08 27.81 7.23
43 17.45 4.04 20.60 5.04 23.75 6.03 25.20 6.54 26.65 6.94 27.23 7.10 27.81 7.26
45 17.45 4.06 20.60 5.06 23.75 6.06 25.20 6.57 26.65 6.97 27.23 7.14 27.81 7.30
47 17.45 4.08 20.60 5.09 23.75 6.09 25.20 6.60 26.65 7.00 27.23 7.17 27.81 7.33
48 17.45 4.10 20.60 5.11 23.75 6.12 25.20 6.63 26.65 7.03 27.23 7.19 27.81 7.36
10 15.71 1.75 18.54 2.18 21.38 2.61 22.68 2.83 23.98 3.00 24.51 3.08 25.03 3.20
12 15.71 1.78 18.54 2.22 21.38 2.66 22.68 2.89 23.98 3.06 24.51 3.14 25.03 3.26
14 15.71 1.82 18.54 2.26 21.38 2.71 22.68 2.94 23.98 3.11 24.51 3.20 25.03 3.32
16 15.71 1.85 18.54 2.30 21.38 2.76 22.68 2.99 23.98 3.17 24.51 3.25 25.03 3.38
18 15.71 1.88 18.54 2.34 21.38 2.81 22.68 3.04 23.98 3.23 24.51 3.31 25.03 3.44
19 15.71 1.91 18.54 2.38 21.38 2.85 22.68 3.10 23.98 3.28 24.51 3.37 25.03 3.49
21 15.71 2.05 18.54 2.56 21.38 3.06 22.68 3.32 23.98 3.52 24.51 3.61 25.03 3.78
23 15.71 2.20 18.54 2.74 21.38 3.28 22.68 3.56 23.98 3.77 24.51 3.86 25.03 4.02
25 15.71 2.35 18.54 2.93 21.38 3.51 22.68 3.80 23.98 4.03 24.51 4.15 25.03 4.31
27 15.71 2.51 18.54 3.13 21.38 3.75 22.68 4.07 23.98 4.31 24.51 4.43 25.03 4.60
90% 29 15.71 2.68 18.54 3.34 21.38 4.00 22.68 4.34 23.98 4.60 24.51 4.71 25.03 4.95
31 15.71 2.86 18.54 3.57 21.38 4.27 22.68 4.63 23.98 4.91 24.51 5.06 25.03 5.24
33 15.71 3.05 18.54 3.80 21.38 4.55 22.68 4.93 23.98 5.23 24.51 5.37 25.03 5.58
35 15.71 3.24 18.54 4.04 21.38 4.84 22.68 5.25 23.98 5.56 24.51 5.69 25.03 5.82
37 15.71 3.45 18.54 4.30 21.38 5.15 22.68 5.58 23.98 5.92 24.51 6.06 25.03 6.20
39 15.71 3.46 18.54 4.32 21.38 5.17 22.68 5.61 23.98 5.94 24.51 6.08 25.03 6.22
41 15.71 3.48 18.54 4.34 21.38 5.19 22.68 5.63 23.98 5.97 24.51 6.12 25.03 6.25
43 15.71 3.50 18.54 4.36 21.38 5.22 22.68 5.66 23.98 6.00 24.51 6.13 25.03 6.28
45 15.71 3.51 18.54 4.38 21.38 5.24 22.68 5.68 23.98 6.02 24.51 6.17 25.03 6.31
47 15.71 3.53 18.54 4.40 21.38 5.26 22.68 5.71 23.98 6.05 24.51 6.19 25.03 6.34
48 15.71 3.54 18.54 4.42 21.38 5.29 22.68 5.74 23.98 6.08 24.51 6.21 25.03 6.37
10 13.96 1.52 16.48 1.89 19.00 2.26 20.16 2.45 21.32 2.60 21.78 2.67 22.25 2.77
12 13.96 1.54 16.48 1.92 19.00 2.30 20.16 2.50 21.32 2.65 21.78 2.72 22.25 2.82
14 13.96 1.57 16.48 1.96 19.00 2.35 20.16 2.54 21.32 2.70 21.78 2.77 22.25 2.87
16 13.96 1.60 16.48 1.99 19.00 2.39 20.16 2.59 21.32 2.74 21.78 2.82 22.25 2.92
18 13.96 1.63 16.48 2.03 19.00 2.43 20.16 2.63 21.32 2.79 21.78 2.86 22.25 2.98
19 13.96 1.66 16.48 2.06 19.00 2.47 20.16 2.68 21.32 2.84 21.78 2.91 22.25 3.03
21 13.96 1.78 16.48 2.21 19.00 2.65 20.16 2.87 21.32 3.05 21.78 3.13 22.25 3.27
23 13.96 1.90 16.48 2.37 19.00 2.84 20.16 3.08 21.32 3.26 21.78 3.34 22.25 3.48
25 13.96 2.04 16.48 2.54 19.00 3.04 20.16 3.29 21.32 3.49 21.78 3.59 22.25 3.73
27 13.96 2.18 16.48 2.71 19.00 3.25 20.16 3.52 21.32 3.73 21.78 3.84 22.25 3.98
80% 29 13.96 2.32 16.48 2.89 19.00 3.47 20.16 3.76 21.32 3.98 21.78 4.08 22.25 4.29
31 13.96 2.48 16.48 3.09 19.00 3.70 20.16 4.01 21.32 4.25 21.78 4.38 22.25 4.54
33 13.96 2.64 16.48 3.29 19.00 3.94 20.16 4.27 21.32 4.53 21.78 4.65 22.25 4.83
35 13.96 2.81 16.48 3.50 19.00 4.19 20.16 4.54 21.32 4.82 21.78 4.92 22.25 5.04
37 13.96 2.99 16.48 3.72 19.00 4.46 20.16 4.83 21.32 5.12 21.78 5.24 22.25 5.36
39 13.96 3.00 16.48 3.74 19.00 4.47 20.16 4.85 21.32 5.14 21.78 5.26 22.25 5.39
41 13.96 3.01 16.48 3.75 19.00 4.49 20.16 4.87 21.32 5.17 21.78 5.30 22.25 5.41
43 13.96 3.03 16.48 3.77 19.00 4.52 20.16 4.90 21.32 5.19 21.78 5.31 22.25 5.44
45 13.96 3.04 16.48 3.79 19.00 4.54 20.16 4.92 21.32 5.22 21.78 5.34 22.25 5.46
47 13.96 3.05 16.48 3.81 19.00 4.56 20.16 4.94 21.32 5.24 21.78 5.36 22.25 5.49
48 13.96 3.07 16.48 3.82 19.00 4.58 20.16 4.97 21.32 5.26 21.78 5.38 22.25 5.51
34
Outdoor
___________________________________________________________________________________
10 12.22 1.31 14.42 1.63 16.63 1.95 17.64 2.12 18.65 2.24 19.06 2.30 19.47 2.39
12 12.22 1.33 14.42 1.66 16.63 1.99 17.64 2.16 18.65 2.29 19.06 2.34 19.47 2.44
14 12.22 1.36 14.42 1.69 16.63 2.02 17.64 2.20 18.65 2.33 19.06 2.39 19.47 2.48
16 12.22 1.38 14.42 1.72 16.63 2.06 17.64 2.23 18.65 2.37 19.06 2.43 19.47 2.52
18 12.22 1.41 14.42 1.75 16.63 2.10 17.64 2.27 18.65 2.41 19.06 2.47 19.47 2.57
19 12.22 1.43 14.42 1.78 16.63 2.13 17.64 2.31 18.65 2.45 19.06 2.51 19.47 2.61
21 12.22 1.53 14.42 1.91 16.63 2.29 17.64 2.48 18.65 2.63 19.06 2.70 19.47 2.82
23 12.22 1.64 14.42 2.05 16.63 2.45 17.64 2.66 18.65 2.82 19.06 2.88 19.47 3.00
25 12.22 1.76 14.42 2.19 16.63 2.62 17.64 2.84 18.65 3.01 19.06 3.10 19.47 3.22
27 12.22 1.88 14.42 2.34 16.63 2.80 17.64 3.04 18.65 3.22 19.06 3.31 19.47 3.44
70% 29 12.22 2.00 14.42 2.50 16.63 2.99 17.64 3.24 18.65 3.44 19.06 3.52 19.47 3.70
31 12.22 2.14 14.42 2.66 16.63 3.19 17.64 3.46 18.65 3.67 19.06 3.78 19.47 3.92
33 12.22 2.28 14.42 2.84 16.63 3.40 17.64 3.69 18.65 3.91 19.06 4.01 19.47 4.17
35 12.22 2.42 14.42 3.02 16.63 3.61 17.64 3.92 18.65 4.16 19.06 4.25 19.47 4.35
37 12.22 2.58 14.42 3.21 16.63 3.84 17.64 4.17 18.65 4.42 19.06 4.52 19.47 4.63
39 12.22 2.59 14.42 3.22 16.63 3.86 17.64 4.19 18.65 4.44 19.06 4.54 19.47 4.65
41 12.22 2.60 14.42 3.24 16.63 3.88 17.64 4.21 18.65 4.46 19.06 4.57 19.47 4.67
43 12.22 2.61 14.42 3.25 16.63 3.90 17.64 4.23 18.65 4.48 19.06 4.58 19.47 4.69
45 12.22 2.62 14.42 3.27 16.63 3.91 17.64 4.25 18.65 4.50 19.06 4.61 19.47 4.71
47 12.22 2.64 14.42 3.28 16.63 3.93 17.64 4.27 18.65 4.52 19.06 4.63 19.47 4.73
48 12.22 2.65 14.42 3.30 16.63 3.95 17.64 4.28 18.65 4.54 19.06 4.64 19.47 4.76
10 10.47 1.11 12.36 1.39 14.25 1.66 15.12 1.80 15.99 1.91 16.34 1.96 16.68 2.04
12 10.47 1.13 12.36 1.41 14.25 1.69 15.12 1.84 15.99 1.95 16.34 2.00 16.68 2.07
14 10.47 1.15 12.36 1.44 14.25 1.72 15.12 1.87 15.99 1.98 16.34 2.03 16.68 2.11
16 10.47 1.18 12.36 1.46 14.25 1.75 15.12 1.90 15.99 2.02 16.34 2.07 16.68 2.15
18 10.47 1.20 12.36 1.49 14.25 1.78 15.12 1.94 15.99 2.05 16.34 2.10 16.68 2.19
19 10.47 1.22 12.36 1.52 14.25 1.82 15.12 1.97 15.99 2.09 16.34 2.14 16.68 2.22
21 10.47 1.30 12.36 1.63 14.25 1.95 15.12 2.11 15.99 2.24 16.34 2.30 16.68 2.40
23 10.47 1.40 12.36 1.74 14.25 2.08 15.12 2.26 15.99 2.40 16.34 2.45 16.68 2.56
25 10.47 1.49 12.36 1.86 14.25 2.23 15.12 2.42 15.99 2.56 16.34 2.64 16.68 2.74
27 10.47 1.60 12.36 1.99 14.25 2.38 15.12 2.59 15.99 2.74 16.34 2.82 16.68 2.93
60% 29 10.47 1.71 12.36 2.13 14.25 2.55 15.12 2.76 15.99 2.93 16.34 2.99 16.68 3.15
31 10.47 1.82 12.36 2.27 14.25 2.71 15.12 2.94 15.99 3.12 16.34 3.22 16.68 3.33
33 10.47 1.94 12.36 2.42 14.25 2.89 15.12 3.14 15.99 3.32 16.34 3.42 16.68 3.55
35 10.47 2.06 12.36 2.57 14.25 3.08 15.12 3.34 15.99 3.54 16.34 3.62 16.68 3.70
37 10.47 2.19 12.36 2.73 14.25 3.27 15.12 3.55 15.99 3.76 16.34 3.85 16.68 3.94
39 10.47 2.20 12.36 2.74 14.25 3.29 15.12 3.56 15.99 3.78 16.34 3.86 16.68 3.96
41 10.47 2.21 12.36 2.76 14.25 3.30 15.12 3.58 15.99 3.80 16.34 3.89 16.68 3.97
43 10.47 2.22 12.36 2.77 14.25 3.32 15.12 3.60 15.99 3.81 16.34 3.90 16.68 3.99
45 10.47 2.23 12.36 2.78 14.25 3.33 15.12 3.61 15.99 3.83 16.34 3.92 16.68 4.01
47 10.47 2.24 12.36 2.80 14.25 3.35 15.12 3.63 15.99 3.85 16.34 3.94 16.68 4.03
48 10.47 2.25 12.36 2.81 14.25 3.36 15.12 3.65 15.99 3.87 16.34 3.95 16.68 4.05
10 8.73 0.93 10.30 1.15 11.88 1.38 12.60 1.50 13.32 1.59 13.61 1.63 13.90 1.69
12 8.73 0.94 10.30 1.17 11.88 1.41 12.60 1.53 13.32 1.62 13.61 1.66 13.90 1.72
14 8.73 0.96 10.30 1.20 11.88 1.43 12.60 1.55 13.32 1.65 13.61 1.69 13.90 1.76
16 8.73 0.98 10.30 1.22 11.88 1.46 12.60 1.58 13.32 1.68 13.61 1.72 13.90 1.79
18 8.73 0.99 10.30 1.24 11.88 1.48 12.60 1.61 13.32 1.71 13.61 1.75 13.90 1.82
19 8.73 1.01 10.30 1.26 11.88 1.51 12.60 1.64 13.32 1.73 13.61 1.78 13.90 1.85
21 8.73 1.08 10.30 1.35 11.88 1.62 12.60 1.75 13.32 1.86 13.61 1.91 13.90 2.00
23 8.73 1.16 10.30 1.45 11.88 1.73 12.60 1.88 13.32 1.99 13.61 2.04 13.90 2.12
25 8.73 1.24 10.30 1.55 11.88 1.85 12.60 2.01 13.32 2.13 13.61 2.19 13.90 2.28
27 8.73 1.33 10.30 1.66 11.88 1.98 12.60 2.15 13.32 2.28 13.61 2.34 13.90 2.43
50% 29 8.73 1.42 10.30 1.77 11.88 2.12 12.60 2.30 13.32 2.43 13.61 2.49 13.90 2.62
31 8.73 1.51 10.30 1.88 11.88 2.26 12.60 2.45 13.32 2.59 13.61 2.68 13.90 2.77
33 8.73 1.61 10.30 2.01 11.88 2.40 12.60 2.61 13.32 2.76 13.61 2.84 13.90 2.95
35 8.73 1.71 10.30 2.14 11.88 2.56 12.60 2.77 13.32 2.94 13.61 3.01 13.90 3.08
37 8.73 1.82 10.30 2.27 11.88 2.72 12.60 2.95 13.32 3.13 13.61 3.20 13.90 3.27
39 8.73 1.83 10.30 2.28 11.88 2.73 12.60 2.96 13.32 3.14 13.61 3.21 13.90 3.29
41 8.73 1.84 10.30 2.29 11.88 2.74 12.60 2.98 13.32 3.16 13.61 3.23 13.90 3.30
43 8.73 1.85 10.30 2.30 11.88 2.76 12.60 2.99 13.32 3.17 13.61 3.24 13.90 3.32
45 8.73 1.86 10.30 2.31 11.88 2.77 12.60 3.00 13.32 3.18 13.61 3.26 13.90 3.33
47 8.73 1.87 10.30 2.32 11.88 2.78 12.60 3.02 13.32 3.20 13.61 3.27 13.90 3.35
48 8.73 1.87 10.30 2.33 11.88 2.80 12.60 3.03 13.32 3.21 13.61 3.29 13.90 3.37
35
Outdoor
___________________________________________________________________________________
36
Outdoor
___________________________________________________________________________________
10 13.57 1.65 16.02 2.06 18.47 2.47 19.60 2.67 20.73 2.84 21.18 2.91 21.63 3.02
12 13.57 1.68 16.02 2.10 18.47 2.51 19.60 2.72 20.73 2.89 21.18 2.96 21.63 3.08
14 13.57 1.71 16.02 2.14 18.47 2.56 19.60 2.77 20.73 2.94 21.18 3.02 21.63 3.13
16 13.57 1.74 16.02 2.17 18.47 2.60 19.60 2.82 20.73 2.99 21.18 3.07 21.63 3.19
18 13.57 1.78 16.02 2.21 18.47 2.65 19.60 2.87 20.73 3.05 21.18 3.12 21.63 3.24
19 13.57 1.81 16.02 2.25 18.47 2.69 19.60 2.92 20.73 3.10 21.18 3.18 21.63 3.30
21 13.57 1.94 16.02 2.41 18.47 2.89 19.60 3.13 20.73 3.32 21.18 3.41 21.63 3.57
23 13.57 2.07 16.02 2.58 18.47 3.09 19.60 3.36 20.73 3.56 21.18 3.64 21.63 3.79
25 13.57 2.22 16.02 2.77 18.47 3.31 19.60 3.59 20.73 3.81 21.18 3.92 21.63 4.07
27 13.57 2.37 16.02 2.96 18.47 3.54 19.60 3.84 20.73 4.07 21.18 4.19 21.63 4.34
70% 29 13.57 2.53 16.02 3.16 18.47 3.78 19.60 4.10 20.73 4.35 21.18 4.44 21.63 4.67
31 13.57 2.70 16.02 3.37 18.47 4.03 19.60 4.37 20.73 4.63 21.18 4.78 21.63 4.95
33 13.57 2.88 16.02 3.59 18.47 4.29 19.60 4.66 20.73 4.94 21.18 5.07 21.63 5.27
35 13.57 3.06 16.02 3.81 18.47 4.57 19.60 4.95 20.73 5.25 21.18 5.37 21.63 5.50
37 13.57 3.26 16.02 4.06 18.47 4.86 19.60 5.27 20.73 5.58 21.18 5.72 21.63 5.85
39 13.57 3.27 16.02 4.07 18.47 4.88 19.60 5.29 20.73 5.61 21.18 5.74 21.63 5.87
41 13.57 3.28 16.02 4.09 18.47 4.90 19.60 5.32 20.73 5.63 21.18 5.78 21.63 5.90
43 13.57 3.30 16.02 4.11 18.47 4.92 19.60 5.34 20.73 5.66 21.18 5.79 21.63 5.93
45 13.57 3.32 16.02 4.13 18.47 4.95 19.60 5.36 20.73 5.69 21.18 5.82 21.63 5.95
47 13.57 3.33 16.02 4.15 18.47 4.97 19.60 5.39 20.73 5.71 21.18 5.84 21.63 5.98
48 13.57 3.35 16.02 4.17 18.47 4.99 19.60 5.41 20.73 5.74 21.18 5.87 21.63 6.01
10 11.63 1.41 13.73 1.75 15.83 2.10 16.80 2.28 17.77 2.41 18.15 2.48 18.54 2.57
12 11.63 1.43 13.73 1.79 15.83 2.14 16.80 2.32 17.77 2.46 18.15 2.52 18.54 2.62
14 11.63 1.46 13.73 1.82 15.83 2.18 16.80 2.36 17.77 2.50 18.15 2.57 18.54 2.67
16 11.63 1.49 13.73 1.85 15.83 2.22 16.80 2.40 17.77 2.55 18.15 2.61 18.54 2.71
18 11.63 1.51 13.73 1.88 15.83 2.25 16.80 2.45 17.77 2.59 18.15 2.66 18.54 2.76
19 11.63 1.54 13.73 1.92 15.83 2.29 16.80 2.49 17.77 2.64 18.15 2.70 18.54 2.81
21 11.63 1.65 13.73 2.05 15.83 2.46 16.80 2.67 17.77 2.83 18.15 2.90 18.54 3.04
23 11.63 1.77 13.73 2.20 15.83 2.63 16.80 2.86 17.77 3.03 18.15 3.10 18.54 3.23
25 11.63 1.89 13.73 2.35 15.83 2.82 16.80 3.06 17.77 3.24 18.15 3.33 18.54 3.46
27 11.63 2.02 13.73 2.52 15.83 3.01 16.80 3.27 17.77 3.46 18.15 3.56 18.54 3.70
60% 29 11.63 2.16 13.73 2.69 15.83 3.22 16.80 3.49 17.77 3.70 18.15 3.78 18.54 3.98
31 11.63 2.30 13.73 2.87 15.83 3.43 16.80 3.72 17.77 3.94 18.15 4.07 18.54 4.21
33 11.63 2.45 13.73 3.05 15.83 3.65 16.80 3.96 17.77 4.20 18.15 4.32 18.54 4.48
35 11.63 2.61 13.73 3.25 15.83 3.89 16.80 4.22 17.77 4.47 18.15 4.57 18.54 4.68
37 11.63 2.77 13.73 3.45 15.83 4.13 16.80 4.48 17.77 4.75 18.15 4.87 18.54 4.98
39 11.63 2.78 13.73 3.47 15.83 4.15 16.80 4.50 17.77 4.77 18.15 4.88 18.54 5.00
41 11.63 2.80 13.73 3.48 15.83 4.17 16.80 4.52 17.77 4.80 18.15 4.92 18.54 5.02
43 11.63 2.81 13.73 3.50 15.83 4.19 16.80 4.55 17.77 4.82 18.15 4.93 18.54 5.05
45 11.63 2.82 13.73 3.52 15.83 4.21 16.80 4.57 17.77 4.84 18.15 4.96 18.54 5.07
47 11.63 2.83 13.73 3.53 15.83 4.23 16.80 4.59 17.77 4.86 18.15 4.97 18.54 5.09
48 11.63 2.85 13.73 3.55 15.83 4.25 16.80 4.61 17.77 4.88 18.15 4.99 18.54 5.12
10 9.70 1.17 11.45 1.46 13.20 1.75 14.00 1.89 14.81 2.01 15.13 2.06 15.45 2.14
12 9.70 1.19 11.45 1.48 13.20 1.78 14.00 1.93 14.81 2.04 15.13 2.10 15.45 2.18
14 9.70 1.21 11.45 1.51 13.20 1.81 14.00 1.96 14.81 2.08 15.13 2.13 15.45 2.22
16 9.70 1.23 11.45 1.54 13.20 1.84 14.00 2.00 14.81 2.12 15.13 2.17 15.45 2.26
18 9.70 1.26 11.45 1.57 13.20 1.87 14.00 2.03 14.81 2.15 15.13 2.21 15.45 2.30
19 9.70 1.28 11.45 1.59 13.20 1.91 14.00 2.07 14.81 2.19 15.13 2.25 15.45 2.33
21 9.70 1.37 11.45 1.71 13.20 2.04 14.00 2.22 14.81 2.35 15.13 2.41 15.45 2.53
23 9.70 1.47 11.45 1.83 13.20 2.19 14.00 2.37 14.81 2.52 15.13 2.58 15.45 2.68
25 9.70 1.57 11.45 1.96 13.20 2.34 14.00 2.54 14.81 2.69 15.13 2.77 15.45 2.88
27 9.70 1.68 11.45 2.09 13.20 2.50 14.00 2.72 14.81 2.88 15.13 2.96 15.45 3.07
50% 29 9.70 1.79 11.45 2.23 13.20 2.67 14.00 2.90 14.81 3.07 15.13 3.14 15.45 3.31
31 9.70 1.91 11.45 2.38 13.20 2.85 14.00 3.09 14.81 3.28 15.13 3.38 15.45 3.50
33 9.70 2.04 11.45 2.54 13.20 3.04 14.00 3.29 14.81 3.49 15.13 3.59 15.45 3.73
35 9.70 2.17 11.45 2.70 13.20 3.23 14.00 3.51 14.81 3.72 15.13 3.80 15.45 3.89
37 9.70 2.30 11.45 2.87 13.20 3.44 14.00 3.73 14.81 3.95 15.13 4.04 15.45 4.14
39 9.70 2.31 11.45 2.88 13.20 3.45 14.00 3.74 14.81 3.97 15.13 4.06 15.45 4.16
41 9.70 2.32 11.45 2.90 13.20 3.47 14.00 3.76 14.81 3.99 15.13 4.09 15.45 4.17
43 9.70 2.34 11.45 2.91 13.20 3.48 14.00 3.78 14.81 4.01 15.13 4.10 15.45 4.19
45 9.70 2.35 11.45 2.92 13.20 3.50 14.00 3.80 14.81 4.02 15.13 4.12 15.45 4.21
47 9.70 2.36 11.45 2.94 13.20 3.52 14.00 3.81 14.81 4.04 15.13 4.14 15.45 4.23
48 9.70 2.37 11.45 2.95 13.20 3.53 14.00 3.83 14.81 4.06 15.13 4.15 15.45 4.25
37
Outdoor
___________________________________________________________________________________
38
Outdoor
___________________________________________________________________________________
10 16.24 1.96 19.17 2.44 22.10 2.93 23.45 3.17 24.80 3.36 25.34 3.45 25.88 3.59
12 16.24 2.00 19.17 2.49 22.10 2.98 23.45 3.23 24.80 3.43 25.34 3.52 25.88 3.65
14 16.24 2.03 19.17 2.53 22.10 3.03 23.45 3.29 24.80 3.49 25.34 3.58 25.88 3.72
16 16.24 2.07 19.17 2.58 22.10 3.09 23.45 3.35 24.80 3.55 25.34 3.64 25.88 3.78
18 16.24 2.11 19.17 2.62 22.10 3.14 23.45 3.41 24.80 3.61 25.34 3.71 25.88 3.85
19 16.24 2.14 19.17 2.67 22.10 3.20 23.45 3.47 24.80 3.68 25.34 3.77 25.88 3.91
21 16.24 2.30 19.17 2.86 22.10 3.43 23.45 3.72 24.80 3.94 25.34 4.04 25.88 4.23
23 16.24 2.46 19.17 3.07 22.10 3.67 23.45 3.98 24.80 4.22 25.34 4.32 25.88 4.50
25 16.24 2.63 19.17 3.28 22.10 3.93 23.45 4.26 24.80 4.52 25.34 4.65 25.88 4.83
27 16.24 2.81 19.17 3.51 22.10 4.20 23.45 4.55 24.80 4.83 25.34 4.97 25.88 5.15
70% 29 16.24 3.01 19.17 3.74 22.10 4.48 23.45 4.86 24.80 5.16 25.34 5.27 25.88 5.55
31 16.24 3.21 19.17 3.99 22.10 4.78 23.45 5.19 24.80 5.50 25.34 5.67 25.88 5.87
33 16.24 3.41 19.17 4.25 22.10 5.09 23.45 5.52 24.80 5.86 25.34 6.02 25.88 6.25
35 16.24 3.63 19.17 4.53 22.10 5.42 23.45 5.88 24.80 6.23 25.34 6.37 25.88 6.52
37 16.24 3.86 19.17 4.81 22.10 5.76 23.45 6.25 24.80 6.63 25.34 6.78 25.88 6.94
39 16.24 3.88 19.17 4.83 22.10 5.79 23.45 6.28 24.80 6.65 25.34 6.81 25.88 6.97
41 16.24 3.90 19.17 4.86 22.10 5.81 23.45 6.31 24.80 6.68 25.34 6.85 25.88 7.00
43 16.24 3.92 19.17 4.88 22.10 5.84 23.45 6.34 24.80 6.72 25.34 6.87 25.88 7.03
45 16.24 3.93 19.17 4.90 22.10 5.87 23.45 6.37 24.80 6.75 25.34 6.91 25.88 7.07
47 16.24 3.95 19.17 4.92 22.10 5.90 23.45 6.39 24.80 6.78 25.34 6.93 25.88 7.10
48 16.24 3.97 19.17 4.95 22.10 5.92 23.45 6.42 24.80 6.81 25.34 6.96 25.88 7.13
10 13.92 1.67 16.43 2.08 18.94 2.49 20.10 2.70 21.26 2.86 21.72 2.94 22.18 3.05
12 13.92 1.70 16.43 2.12 18.94 2.54 20.10 2.75 21.26 2.92 21.72 2.99 22.18 3.11
14 13.92 1.73 16.43 2.16 18.94 2.58 20.10 2.80 21.26 2.97 21.72 3.05 22.18 3.16
16 13.92 1.76 16.43 2.20 18.94 2.63 20.10 2.85 21.26 3.02 21.72 3.10 22.18 3.22
18 13.92 1.79 16.43 2.23 18.94 2.68 20.10 2.90 21.26 3.08 21.72 3.15 22.18 3.28
19 13.92 1.82 16.43 2.27 18.94 2.72 20.10 2.95 21.26 3.13 21.72 3.21 22.18 3.33
21 13.92 1.96 16.43 2.44 18.94 2.92 20.10 3.16 21.26 3.35 21.72 3.44 22.18 3.60
23 13.92 2.09 16.43 2.61 18.94 3.12 20.10 3.39 21.26 3.59 21.72 3.68 22.18 3.83
25 13.92 2.24 16.43 2.79 18.94 3.34 20.10 3.63 21.26 3.84 21.72 3.96 22.18 4.11
27 13.92 2.40 16.43 2.99 18.94 3.57 20.10 3.88 21.26 4.11 21.72 4.23 22.18 4.39
60% 29 13.92 2.56 16.43 3.19 18.94 3.82 20.10 4.14 21.26 4.39 21.72 4.49 22.18 4.72
31 13.92 2.73 16.43 3.40 18.94 4.07 20.10 4.41 21.26 4.68 21.72 4.82 22.18 5.00
33 13.92 2.91 16.43 3.62 18.94 4.34 20.10 4.70 21.26 4.98 21.72 5.12 22.18 5.32
35 13.92 3.09 16.43 3.85 18.94 4.61 20.10 5.00 21.26 5.30 21.72 5.42 22.18 5.55
37 13.92 3.29 16.43 4.10 18.94 4.91 20.10 5.32 21.26 5.64 21.72 5.77 22.18 5.91
39 13.92 3.30 16.43 4.11 18.94 4.93 20.10 5.34 21.26 5.66 21.72 5.79 22.18 5.93
41 13.92 3.32 16.43 4.13 18.94 4.95 20.10 5.37 21.26 5.69 21.72 5.83 22.18 5.96
43 13.92 3.33 16.43 4.15 18.94 4.97 20.10 5.39 21.26 5.72 21.72 5.85 22.18 5.99
45 13.92 3.35 16.43 4.17 18.94 4.99 20.10 5.42 21.26 5.74 21.72 5.88 22.18 6.01
47 13.92 3.36 16.43 4.19 18.94 5.02 20.10 5.44 21.26 5.77 21.72 5.90 22.18 6.04
48 13.92 3.38 16.43 4.21 18.94 5.04 20.10 5.47 21.26 5.80 21.72 5.92 22.18 6.07
10 11.60 1.39 13.69 1.73 15.79 2.07 16.75 2.25 17.71 2.38 18.10 2.44 18.48 2.54
12 11.60 1.41 13.69 1.76 15.79 2.11 16.75 2.29 17.71 2.42 18.10 2.49 18.48 2.59
14 11.60 1.44 13.69 1.79 15.79 2.15 16.75 2.33 17.71 2.47 18.10 2.53 18.48 2.63
16 11.60 1.46 13.69 1.83 15.79 2.19 16.75 2.37 17.71 2.51 18.10 2.58 18.48 2.68
18 11.60 1.49 13.69 1.86 15.79 2.22 16.75 2.41 17.71 2.56 18.10 2.62 18.48 2.72
19 11.60 1.52 13.69 1.89 15.79 2.26 16.75 2.45 17.71 2.60 18.10 2.67 18.48 2.77
21 11.60 1.63 13.69 2.03 15.79 2.43 16.75 2.63 17.71 2.79 18.10 2.86 18.48 3.00
23 11.60 1.74 13.69 2.17 15.79 2.60 16.75 2.82 17.71 2.99 18.10 3.06 18.48 3.19
25 11.60 1.86 13.69 2.32 15.79 2.78 16.75 3.02 17.71 3.20 18.10 3.29 18.48 3.42
27 11.60 1.99 13.69 2.48 15.79 2.97 16.75 3.22 17.71 3.42 18.10 3.51 18.48 3.65
50% 29 11.60 2.13 13.69 2.65 15.79 3.17 16.75 3.44 17.71 3.65 18.10 3.73 18.48 3.92
31 11.60 2.27 13.69 2.83 15.79 3.38 16.75 3.67 17.71 3.89 18.10 4.01 18.48 4.15
33 11.60 2.42 13.69 3.01 15.79 3.60 16.75 3.91 17.71 4.14 18.10 4.26 18.48 4.42
35 11.60 2.57 13.69 3.20 15.79 3.83 16.75 4.16 17.71 4.41 18.10 4.51 18.48 4.62
37 11.60 2.73 13.69 3.41 15.79 4.08 16.75 4.42 17.71 4.69 18.10 4.80 18.48 4.91
39 11.60 2.75 13.69 3.42 15.79 4.10 16.75 4.44 17.71 4.71 18.10 4.82 18.48 4.93
41 11.60 2.76 13.69 3.44 15.79 4.11 16.75 4.46 17.71 4.73 18.10 4.85 18.48 4.95
43 11.60 2.77 13.69 3.45 15.79 4.13 16.75 4.48 17.71 4.75 18.10 4.86 18.48 4.98
45 11.60 2.78 13.69 3.47 15.79 4.15 16.75 4.50 17.71 4.77 18.10 4.89 18.48 5.00
47 11.60 2.80 13.69 3.48 15.79 4.17 16.75 4.52 17.71 4.80 18.10 4.91 18.48 5.02
48 11.60 2.81 13.69 3.50 15.79 4.19 16.75 4.55 17.71 4.82 18.10 4.93 18.48 5.05
39
Outdoor
___________________________________________________________________________________
40
Outdoor
___________________________________________________________________________________
10 19.39 2.44 22.89 3.03 26.39 3.63 28.00 3.94 29.61 4.18 30.25 4.29 30.90 4.46
12 19.39 2.48 22.89 3.09 26.39 3.70 28.00 4.01 29.61 4.25 30.25 4.36 30.90 4.54
14 19.39 2.53 22.89 3.15 26.39 3.77 28.00 4.09 29.61 4.33 30.25 4.44 30.90 4.62
16 19.39 2.57 22.89 3.20 26.39 3.84 28.00 4.16 29.61 4.41 30.25 4.52 30.90 4.70
18 19.39 2.62 22.89 3.26 26.39 3.90 28.00 4.23 29.61 4.49 30.25 4.60 30.90 4.78
19 19.39 2.66 22.89 3.32 26.39 3.97 28.00 4.31 29.61 4.56 30.25 4.68 30.90 4.86
21 19.39 2.85 22.89 3.55 26.39 4.26 28.00 4.62 29.61 4.89 30.25 5.02 30.90 5.26
23 19.39 3.06 22.89 3.81 26.39 4.56 28.00 4.94 29.61 5.24 30.25 5.37 30.90 5.59
25 19.39 3.27 22.89 4.07 26.39 4.88 28.00 5.29 29.61 5.61 30.25 5.77 30.90 5.99
27 19.39 3.50 22.89 4.36 26.39 5.21 28.00 5.66 29.61 6.00 30.25 6.17 30.90 6.40
70% 29 19.39 3.73 22.89 4.65 26.39 5.57 28.00 6.04 29.61 6.40 30.25 6.55 30.90 6.89
31 19.39 3.98 22.89 4.96 26.39 5.94 28.00 6.44 29.61 6.83 30.25 7.04 30.90 7.29
33 19.39 4.24 22.89 5.28 26.39 6.33 28.00 6.86 29.61 7.27 30.25 7.47 30.90 7.76
35 19.39 4.51 22.89 5.62 26.39 6.73 28.00 7.30 29.61 7.74 30.25 7.91 30.90 8.10
37 19.39 4.80 22.89 5.98 26.39 7.16 28.00 7.76 29.61 8.23 30.25 8.42 30.90 8.62
39 19.39 4.82 22.89 6.00 26.39 7.19 28.00 7.80 29.61 8.26 30.25 8.45 30.90 8.65
41 19.39 4.84 22.89 6.03 26.39 7.22 28.00 7.83 29.61 8.30 30.25 8.51 30.90 8.69
43 19.39 4.86 22.89 6.06 26.39 7.25 28.00 7.87 29.61 8.34 30.25 8.53 30.90 8.73
45 19.39 4.88 22.89 6.09 26.39 7.29 28.00 7.90 29.61 8.38 30.25 8.58 30.90 8.77
47 19.39 4.91 22.89 6.11 26.39 7.32 28.00 7.94 29.61 8.42 30.25 8.61 30.90 8.81
48 19.39 4.93 22.89 6.14 26.39 7.35 28.00 7.98 29.61 8.46 30.25 8.64 30.90 8.85
10 16.62 2.07 19.62 2.58 22.62 3.09 24.00 3.35 25.38 3.56 25.93 3.65 26.48 3.79
12 16.62 2.11 19.62 2.63 22.62 3.15 24.00 3.42 25.38 3.62 25.93 3.72 26.48 3.86
14 16.62 2.15 19.62 2.68 22.62 3.21 24.00 3.48 25.38 3.69 25.93 3.78 26.48 3.93
16 16.62 2.19 19.62 2.73 22.62 3.26 24.00 3.54 25.38 3.75 25.93 3.85 26.48 4.00
18 16.62 2.23 19.62 2.77 22.62 3.32 24.00 3.60 25.38 3.82 25.93 3.92 26.48 4.07
19 16.62 2.26 19.62 2.82 22.62 3.38 24.00 3.66 25.38 3.88 25.93 3.98 26.48 4.14
21 16.62 2.43 19.62 3.03 22.62 3.62 24.00 3.93 25.38 4.16 25.93 4.27 26.48 4.47
23 16.62 2.60 19.62 3.24 22.62 3.88 24.00 4.21 25.38 4.46 25.93 4.57 26.48 4.76
25 16.62 2.78 19.62 3.47 22.62 4.15 24.00 4.50 25.38 4.77 25.93 4.91 26.48 5.10
27 16.62 2.98 19.62 3.71 22.62 4.44 24.00 4.81 25.38 5.10 25.93 5.25 26.48 5.45
60% 29 16.62 3.18 19.62 3.96 22.62 4.74 24.00 5.14 25.38 5.45 25.93 5.57 26.48 5.86
31 16.62 3.39 19.62 4.22 22.62 5.05 24.00 5.48 25.38 5.81 25.93 5.99 26.48 6.21
33 16.62 3.61 19.62 4.50 22.62 5.38 24.00 5.84 25.38 6.19 25.93 6.36 26.48 6.61
35 16.62 3.84 19.62 4.78 22.62 5.73 24.00 6.21 25.38 6.58 25.93 6.73 26.48 6.89
37 16.62 4.08 19.62 5.09 22.62 6.09 24.00 6.61 25.38 7.00 25.93 7.17 26.48 7.33
39 16.62 4.10 19.62 5.11 22.62 6.12 24.00 6.64 25.38 7.03 25.93 7.19 26.48 7.37
41 16.62 4.12 19.62 5.13 22.62 6.15 24.00 6.67 25.38 7.06 25.93 7.24 26.48 7.40
43 16.62 4.14 19.62 5.16 22.62 6.17 24.00 6.70 25.38 7.10 25.93 7.26 26.48 7.43
45 16.62 4.16 19.62 5.18 22.62 6.20 24.00 6.73 25.38 7.13 25.93 7.30 26.48 7.47
47 16.62 4.18 19.62 5.20 22.62 6.23 24.00 6.76 25.38 7.16 25.93 7.33 26.48 7.50
48 16.62 4.20 19.62 5.23 22.62 6.26 24.00 6.79 25.38 7.20 25.93 7.36 26.48 7.54
10 13.85 1.72 16.35 2.15 18.85 2.57 20.00 2.79 21.15 2.96 21.61 3.03 22.07 3.15
12 13.85 1.76 16.35 2.19 18.85 2.62 20.00 2.84 21.15 3.01 21.61 3.09 22.07 3.21
14 13.85 1.79 16.35 2.23 18.85 2.67 20.00 2.89 21.15 3.07 21.61 3.14 22.07 3.27
16 13.85 1.82 16.35 2.27 18.85 2.71 20.00 2.94 21.15 3.12 21.61 3.20 22.07 3.32
18 13.85 1.85 16.35 2.31 18.85 2.76 20.00 3.00 21.15 3.17 21.61 3.26 22.07 3.38
19 13.85 1.88 16.35 2.35 18.85 2.81 20.00 3.05 21.15 3.23 21.61 3.31 22.07 3.44
21 13.85 2.02 16.35 2.52 18.85 3.01 20.00 3.27 21.15 3.46 21.61 3.55 22.07 3.72
23 13.85 2.16 16.35 2.69 18.85 3.23 20.00 3.50 21.15 3.71 21.61 3.80 22.07 3.96
25 13.85 2.31 16.35 2.88 18.85 3.45 20.00 3.74 21.15 3.97 21.61 4.08 22.07 4.24
27 13.85 2.47 16.35 3.08 18.85 3.69 20.00 4.00 21.15 4.24 21.61 4.36 22.07 4.53
50% 29 13.85 2.64 16.35 3.29 18.85 3.94 20.00 4.27 21.15 4.53 21.61 4.63 22.07 4.87
31 13.85 2.82 16.35 3.51 18.85 4.20 20.00 4.56 21.15 4.83 21.61 4.98 22.07 5.16
33 13.85 3.00 16.35 3.74 18.85 4.48 20.00 4.85 21.15 5.15 21.61 5.29 22.07 5.49
35 13.85 3.19 16.35 3.98 18.85 4.76 20.00 5.16 21.15 5.47 21.61 5.60 22.07 5.73
37 13.85 3.39 16.35 4.23 18.85 5.06 20.00 5.49 21.15 5.82 21.61 5.96 22.07 6.10
39 13.85 3.41 16.35 4.25 18.85 5.09 20.00 5.52 21.15 5.85 21.61 5.98 22.07 6.12
41 13.85 3.42 16.35 4.27 18.85 5.11 20.00 5.54 21.15 5.87 21.61 6.02 22.07 6.15
43 13.85 3.44 16.35 4.29 18.85 5.13 20.00 5.57 21.15 5.90 21.61 6.04 22.07 6.18
45 13.85 3.46 16.35 4.31 18.85 5.16 20.00 5.59 21.15 5.93 21.61 6.07 22.07 6.21
47 13.85 3.47 16.35 4.33 18.85 5.18 20.00 5.62 21.15 5.96 21.61 6.09 22.07 6.24
48 13.85 3.49 16.35 4.35 18.85 5.20 20.00 5.64 21.15 5.98 21.61 6.12 22.07 6.27
41
Outdoor
___________________________________________________________________________________
42
Outdoor
___________________________________________________________________________________
10 21.81 2.81 25.75 3.50 29.69 4.19 31.50 4.55 33.31 4.82 34.04 4.95 34.76 5.14
12 21.81 2.86 25.75 3.57 29.69 4.27 31.50 4.63 33.31 4.91 34.04 5.04 34.76 5.24
14 21.81 2.91 25.75 3.63 29.69 4.35 31.50 4.72 33.31 5.00 34.04 5.13 34.76 5.33
16 21.81 2.97 25.75 3.70 29.69 4.43 31.50 4.80 33.31 5.09 34.04 5.22 34.76 5.42
18 21.81 3.02 25.75 3.76 29.69 4.50 31.50 4.88 33.31 5.18 34.04 5.31 34.76 5.52
19 21.81 3.07 25.75 3.83 29.69 4.58 31.50 4.97 33.31 5.27 34.04 5.40 34.76 5.61
21 21.81 3.29 25.75 4.10 29.69 4.91 31.50 5.33 33.31 5.65 34.04 5.79 34.76 6.07
23 21.81 3.53 25.75 4.39 29.69 5.26 31.50 5.71 33.31 6.05 34.04 6.20 34.76 6.45
25 21.81 3.77 25.75 4.70 29.69 5.63 31.50 6.11 33.31 6.47 34.04 6.66 34.76 6.92
27 21.81 4.03 25.75 5.03 29.69 6.02 31.50 6.53 33.31 6.92 34.04 7.12 34.76 7.39
70% 29 21.81 4.31 25.75 5.37 29.69 6.43 31.50 6.97 33.31 7.39 34.04 7.56 34.76 7.95
31 21.81 4.59 25.75 5.72 29.69 6.85 31.50 7.43 33.31 7.88 34.04 8.12 34.76 8.41
33 21.81 4.89 25.75 6.10 29.69 7.30 31.50 7.92 33.31 8.39 34.04 8.62 34.76 8.96
35 21.81 5.20 25.75 6.48 29.69 7.76 31.50 8.42 33.31 8.93 34.04 9.13 34.76 9.35
37 21.81 5.54 25.75 6.90 29.69 8.26 31.50 8.96 33.31 9.49 34.04 9.72 34.76 9.94
39 21.81 5.56 25.75 6.93 29.69 8.29 31.50 9.00 33.31 9.54 34.04 9.75 34.76 9.99
41 21.81 5.58 25.75 6.96 29.69 8.33 31.50 9.04 33.31 9.58 34.04 9.82 34.76 10.03
43 21.81 5.61 25.75 6.99 29.69 8.37 31.50 9.08 33.31 9.62 34.04 9.85 34.76 10.08
45 21.81 5.64 25.75 7.02 29.69 8.41 31.50 9.12 33.31 9.67 34.04 9.90 34.76 10.12
47 21.81 5.66 25.75 7.06 29.69 8.45 31.50 9.16 33.31 9.71 34.04 9.94 34.76 10.17
48 21.81 5.69 25.75 7.09 29.69 8.49 31.50 9.21 33.31 9.76 34.04 9.97 34.76 10.22
10 18.70 2.39 22.07 2.98 25.45 3.57 27.00 3.87 28.55 4.10 29.17 4.21 29.79 4.38
12 18.70 2.44 22.07 3.04 25.45 3.63 27.00 3.94 28.55 4.18 29.17 4.29 29.79 4.46
14 18.70 2.48 22.07 3.09 25.45 3.70 27.00 4.01 28.55 4.25 29.17 4.36 29.79 4.54
16 18.70 2.53 22.07 3.15 25.45 3.77 27.00 4.09 28.55 4.33 29.17 4.44 29.79 4.61
18 18.70 2.57 22.07 3.20 25.45 3.83 27.00 4.16 28.55 4.41 29.17 4.52 29.79 4.69
19 18.70 2.61 22.07 3.26 25.45 3.90 27.00 4.23 28.55 4.48 29.17 4.60 29.79 4.77
21 18.70 2.80 22.07 3.49 25.45 4.18 27.00 4.53 28.55 4.81 29.17 4.93 29.79 5.16
23 18.70 3.00 22.07 3.74 25.45 4.48 27.00 4.86 28.55 5.15 29.17 5.27 29.79 5.49
25 18.70 3.21 22.07 4.00 25.45 4.79 27.00 5.20 28.55 5.51 29.17 5.67 29.79 5.89
27 18.70 3.43 22.07 4.28 25.45 5.12 27.00 5.56 28.55 5.89 29.17 6.06 29.79 6.29
60% 29 18.70 3.67 22.07 4.57 25.45 5.47 27.00 5.93 28.55 6.29 29.17 6.43 29.79 6.76
31 18.70 3.91 22.07 4.87 25.45 5.83 27.00 6.33 28.55 6.71 29.17 6.91 29.79 7.16
33 18.70 4.16 22.07 5.19 25.45 6.21 27.00 6.74 28.55 7.14 29.17 7.34 29.79 7.62
35 18.70 4.43 22.07 5.52 25.45 6.61 27.00 7.17 28.55 7.60 29.17 7.77 29.79 7.96
37 18.70 4.71 22.07 5.87 25.45 7.03 27.00 7.62 28.55 8.08 29.17 8.27 29.79 8.46
39 18.70 4.73 22.07 5.90 25.45 7.06 27.00 7.66 28.55 8.12 29.17 8.30 29.79 8.50
41 18.70 4.75 22.07 5.92 25.45 7.09 27.00 7.69 28.55 8.15 29.17 8.36 29.79 8.54
43 18.70 4.78 22.07 5.95 25.45 7.12 27.00 7.73 28.55 8.19 29.17 8.38 29.79 8.58
45 18.70 4.80 22.07 5.98 25.45 7.16 27.00 7.76 28.55 8.23 29.17 8.43 29.79 8.62
47 18.70 4.82 22.07 6.01 25.45 7.19 27.00 7.80 28.55 8.27 29.17 8.46 29.79 8.66
48 18.70 4.84 22.07 6.03 25.45 7.22 27.00 7.83 28.55 8.30 29.17 8.49 29.79 8.70
10 15.58 1.99 18.39 2.48 21.21 2.97 22.50 3.22 23.79 3.41 24.31 3.50 24.83 3.64
12 15.58 2.03 18.39 2.52 21.21 3.02 22.50 3.28 23.79 3.47 24.31 3.56 24.83 3.70
14 15.58 2.06 18.39 2.57 21.21 3.08 22.50 3.34 23.79 3.54 24.31 3.63 24.83 3.77
16 15.58 2.10 18.39 2.62 21.21 3.13 22.50 3.40 23.79 3.60 24.31 3.69 24.83 3.84
18 15.58 2.14 18.39 2.66 21.21 3.19 22.50 3.46 23.79 3.66 24.31 3.76 24.83 3.90
19 15.58 2.17 18.39 2.71 21.21 3.24 22.50 3.52 23.79 3.73 24.31 3.82 24.83 3.97
21 15.58 2.33 18.39 2.90 21.21 3.48 22.50 3.77 23.79 4.00 24.31 4.10 24.83 4.29
23 15.58 2.50 18.39 3.11 21.21 3.72 22.50 4.04 23.79 4.28 24.31 4.38 24.83 4.56
25 15.58 2.67 18.39 3.33 21.21 3.98 22.50 4.32 23.79 4.58 24.31 4.71 24.83 4.89
27 15.58 2.85 18.39 3.56 21.21 4.26 22.50 4.62 23.79 4.90 24.31 5.04 24.83 5.23
50% 29 15.58 3.05 18.39 3.80 21.21 4.55 22.50 4.93 23.79 5.23 24.31 5.35 24.83 5.62
31 15.58 3.25 18.39 4.05 21.21 4.85 22.50 5.26 23.79 5.57 24.31 5.75 24.83 5.95
33 15.58 3.46 18.39 4.31 21.21 5.16 22.50 5.60 23.79 5.94 24.31 6.10 24.83 6.34
35 15.58 3.68 18.39 4.59 21.21 5.49 22.50 5.96 23.79 6.32 24.31 6.46 24.83 6.61
37 15.58 3.92 18.39 4.88 21.21 5.84 22.50 6.34 23.79 6.72 24.31 6.88 24.83 7.04
39 15.58 3.93 18.39 4.90 21.21 5.87 22.50 6.37 23.79 6.75 24.31 6.90 24.83 7.07
41 15.58 3.95 18.39 4.92 21.21 5.90 22.50 6.39 23.79 6.78 24.31 6.95 24.83 7.10
43 15.58 3.97 18.39 4.95 21.21 5.92 22.50 6.42 23.79 6.81 24.31 6.97 24.83 7.13
45 15.58 3.99 18.39 4.97 21.21 5.95 22.50 6.45 23.79 6.84 24.31 7.01 24.83 7.16
47 15.58 4.01 18.39 4.99 21.21 5.98 22.50 6.48 23.79 6.87 24.31 7.03 24.83 7.20
48 15.58 4.03 18.39 5.02 21.21 6.01 22.50 6.51 23.79 6.90 24.31 7.06 24.83 7.23
43
Outdoor
___________________________________________________________________________________
44
Outdoor
___________________________________________________________________________________
-15 -15 17.82 5.08 17.31 5.07 16.04 4.93 15.45 4.90 14.77 4.78 13.49 4.50
-13 -13 18.59 5.21 17.31 5.05 16.04 4.85 15.45 4.71 14.77 4.62 13.49 4.29
-11 -11 18.59 5.12 17.31 4.85 16.04 4.68 15.45 4.57 14.77 4.45 13.49 4.12
-10 -10 18.59 5.06 17.31 4.82 16.04 4.59 15.45 4.48 14.77 4.39 13.49 4.07
-9 -9 18.59 5.00 17.31 4.74 16.04 4.53 15.45 4.41 14.77 4.35 13.49 4.03
-7 -8 18.59 4.92 17.31 4.64 16.04 4.46 15.45 4.30 14.77 4.23 13.49 3.92
-5 -6 18.59 4.78 17.31 4.56 16.04 4.32 15.45 4.18 14.77 4.05 13.49 3.79
-3 -4 18.59 4.63 17.31 4.40 16.04 4.20 15.45 4.16 14.77 3.98 13.49 3.65
60%
0 -1 18.59 4.44 17.31 4.27 16.04 4.03 15.45 3.89 14.77 3.74 13.49 3.42
3 2 18.59 4.34 17.31 4.09 16.04 3.81 15.45 3.68 14.77 3.53 13.49 3.27
5 4 18.59 4.20 17.31 3.94 16.04 3.68 15.45 3.56 14.77 3.41 13.49 3.17
7 6 18.59 4.11 17.31 3.84 16.04 3.58 15.45 3.44 14.77 3.30 13.49 3.02
9 8 18.59 3.97 17.31 3.70 16.04 3.45 15.45 3.33 14.77 3.21 13.49 2.96
11 10 18.59 3.85 17.31 3.62 16.04 3.38 15.45 3.26 14.77 3.13 13.49 2.87
13 12 18.59 3.68 17.31 3.44 16.04 3.20 15.45 3.11 14.77 2.98 13.49 2.74
15 14 18.59 3.62 17.31 3.39 16.04 3.14 15.45 3.04 14.77 2.94 13.49 2.71
-15 -15 15.45 4.36 14.43 4.18 13.41 4.08 12.81 4.03 12.31 3.92 11.29 3.72
-13 -13 15.45 4.31 14.43 4.15 13.41 4.00 12.81 3.88 12.31 3.82 11.29 3.54
-11 -11 15.45 4.24 14.43 4.01 13.41 3.88 12.81 3.77 12.31 3.68 11.29 3.39
-10 -10 15.45 4.16 14.43 3.98 13.41 3.81 12.81 3.69 12.31 3.60 11.29 3.36
-9 -9 15.45 4.11 14.43 3.92 13.41 3.75 12.81 3.59 12.31 3.58 11.29 3.32
-7 -8 15.45 4.05 14.43 3.84 13.41 3.69 12.81 3.54 12.31 3.49 11.29 3.23
-5 -6 15.45 3.94 14.43 3.77 13.41 3.57 12.81 3.44 12.31 3.33 11.29 3.14
-3 -4 15.45 3.83 14.43 3.65 13.41 3.49 12.81 3.44 12.31 3.31 11.29 3.04
50%
0 -1 15.45 3.66 14.43 3.51 13.41 3.34 12.81 3.20 12.31 3.10 11.29 2.86
3 2 15.45 3.57 14.43 3.38 13.41 3.17 12.81 3.05 12.31 2.93 11.29 2.72
5 4 15.45 3.45 14.43 3.25 13.41 3.05 12.81 2.94 12.31 2.84 11.29 2.61
7 6 15.45 3.37 14.43 3.17 13.41 2.98 12.81 2.85 12.31 2.75 11.29 2.52
9 8 15.45 3.26 14.43 3.07 13.41 2.87 12.81 2.76 12.31 2.66 11.29 2.46
11 10 15.45 3.19 14.43 2.99 13.41 2.79 12.81 2.67 12.31 2.58 11.29 2.37
13 12 15.45 3.05 14.43 2.86 13.41 2.67 12.81 2.57 12.31 2.48 11.29 2.28
15 14 15.45 2.99 14.43 2.80 13.41 2.61 12.81 2.50 12.31 2.42 11.29 2.23
45
Outdoor
___________________________________________________________________________________
46
Outdoor
___________________________________________________________________________________
-15 -15 20.79 6.31 20.20 6.30 18.71 6.13 18.02 6.09 17.23 5.94 15.74 5.60
-13 -13 21.68 6.48 20.20 6.28 18.71 6.03 18.02 5.86 17.23 5.74 15.74 5.34
-11 -11 21.68 6.37 20.20 6.04 18.71 5.82 18.02 5.69 17.23 5.53 15.74 5.12
-10 -10 21.68 6.29 20.20 5.99 18.71 5.71 18.02 5.57 17.23 5.45 15.74 5.06
-9 -9 21.68 6.21 20.20 5.90 18.71 5.63 18.02 5.48 17.23 5.41 15.74 5.01
-7 -8 21.68 6.12 20.20 5.77 18.71 5.55 18.02 5.35 17.23 5.26 15.74 4.87
-5 -6 21.68 5.95 20.20 5.67 18.71 5.37 18.02 5.19 17.23 5.03 15.74 4.71
-3 -4 21.68 5.76 20.20 5.48 18.71 5.22 18.02 5.17 17.23 4.95 15.74 4.54
60%
0 -1 21.68 5.52 20.20 5.31 18.71 5.01 18.02 4.84 17.23 4.65 15.74 4.25
3 2 21.68 5.40 20.20 5.08 18.71 4.74 18.02 4.58 17.23 4.39 15.74 4.06
5 4 21.68 5.22 20.20 4.90 18.71 4.58 18.02 4.42 17.23 4.24 15.74 3.94
7 6 21.68 5.11 20.20 4.77 18.71 4.45 18.02 4.28 17.23 4.10 15.74 3.75
9 8 21.68 4.93 20.20 4.60 18.71 4.29 18.02 4.14 17.23 3.99 15.74 3.67
11 10 21.68 4.79 20.20 4.50 18.71 4.20 18.02 4.05 17.23 3.89 15.74 3.56
13 12 21.68 4.57 20.20 4.28 18.71 3.98 18.02 3.86 17.23 3.71 15.74 3.41
15 14 21.68 4.51 20.20 4.21 18.71 3.90 18.02 3.78 17.23 3.65 15.74 3.37
-15 -15 18.02 5.42 16.83 5.19 15.64 5.07 14.95 5.01 14.36 4.87 13.17 4.63
-13 -13 18.02 5.35 16.83 5.16 15.64 4.97 14.95 4.82 14.36 4.75 13.17 4.40
-11 -11 18.02 5.27 16.83 4.99 15.64 4.82 14.95 4.68 14.36 4.57 13.17 4.22
-10 -10 18.02 5.18 16.83 4.95 15.64 4.74 14.95 4.59 14.36 4.48 13.17 4.17
-9 -9 18.02 5.10 16.83 4.87 15.64 4.66 14.95 4.46 14.36 4.45 13.17 4.12
-7 -8 18.02 5.03 16.83 4.78 15.64 4.59 14.95 4.41 14.36 4.33 13.17 4.01
-5 -6 18.02 4.90 16.83 4.69 15.64 4.44 14.95 4.28 14.36 4.14 13.17 3.90
-3 -4 18.02 4.76 16.83 4.54 15.64 4.33 14.95 4.28 14.36 4.12 13.17 3.78
50%
0 -1 18.02 4.54 16.83 4.37 15.64 4.16 14.95 3.98 14.36 3.86 13.17 3.56
3 2 18.02 4.44 16.83 4.20 15.64 3.94 14.95 3.79 14.36 3.65 13.17 3.38
5 4 18.02 4.29 16.83 4.05 15.64 3.79 14.95 3.65 14.36 3.53 13.17 3.25
7 6 18.02 4.19 16.83 3.94 15.64 3.71 14.95 3.55 14.36 3.42 13.17 3.14
9 8 18.02 4.05 16.83 3.82 15.64 3.56 14.95 3.43 14.36 3.30 13.17 3.06
11 10 18.02 3.96 16.83 3.71 15.64 3.47 14.95 3.32 14.36 3.21 13.17 2.95
13 12 18.02 3.79 16.83 3.56 15.64 3.32 14.95 3.20 14.36 3.09 13.17 2.83
15 14 18.02 3.71 16.83 3.48 15.64 3.24 14.95 3.11 14.36 3.00 13.17 2.77
47
Outdoor
___________________________________________________________________________________
48
Outdoor
___________________________________________________________________________________
-15 -15 24.75 7.44 24.05 7.43 22.28 7.23 21.45 7.18 20.51 7.00 18.74 6.60
-13 -13 25.81 7.64 24.05 7.40 22.28 7.10 21.45 6.90 20.51 6.77 18.74 6.29
-11 -11 25.81 7.51 24.05 7.11 22.28 6.86 21.45 6.70 20.51 6.52 18.74 6.03
-10 -10 25.81 7.41 24.05 7.06 22.28 6.73 21.45 6.57 20.51 6.43 18.74 5.97
-9 -9 25.81 7.32 24.05 6.95 22.28 6.64 21.45 6.46 20.51 6.38 18.74 5.90
-7 -8 25.81 7.21 24.05 6.80 22.28 6.54 21.45 6.30 20.51 6.20 18.74 5.74
-5 -6 25.81 7.01 24.05 6.68 22.28 6.32 21.45 6.12 20.51 5.93 18.74 5.55
-3 -4 25.81 6.79 24.05 6.45 22.28 6.16 21.45 6.09 20.51 5.83 18.74 5.36
60%
0 -1 25.81 6.50 24.05 6.26 22.28 5.90 21.45 5.71 20.51 5.48 18.74 5.01
3 2 25.81 6.36 24.05 5.99 22.28 5.59 21.45 5.40 20.51 5.18 18.74 4.79
5 4 25.81 6.15 24.05 5.77 22.28 5.40 21.45 5.21 20.51 5.00 18.74 4.65
7 6 25.81 6.03 24.05 5.63 22.28 5.24 21.45 5.05 20.51 4.83 18.74 4.42
9 8 25.81 5.82 24.05 5.43 22.28 5.06 21.45 4.88 20.51 4.71 18.74 4.33
11 10 25.81 5.65 24.05 5.30 22.28 4.95 21.45 4.78 20.51 4.59 18.74 4.20
13 12 25.81 5.39 24.05 5.05 22.28 4.69 21.45 4.55 20.51 4.37 18.74 4.02
15 14 25.81 5.31 24.05 4.96 22.28 4.60 21.45 4.46 20.51 4.30 18.74 3.97
-15 -15 21.45 6.39 20.04 6.12 18.62 5.98 17.80 5.90 17.09 5.74 15.68 5.45
-13 -13 21.45 6.31 20.04 6.08 18.62 5.86 17.80 5.68 17.09 5.60 15.68 5.18
-11 -11 21.45 6.22 20.04 5.88 18.62 5.68 17.80 5.52 17.09 5.39 15.68 4.97
-10 -10 21.45 6.10 20.04 5.83 18.62 5.59 17.80 5.41 17.09 5.28 15.68 4.92
-9 -9 21.45 6.02 20.04 5.74 18.62 5.49 17.80 5.26 17.09 5.24 15.68 4.86
-7 -8 21.45 5.93 20.04 5.63 18.62 5.40 17.80 5.19 17.09 5.11 15.68 4.73
-5 -6 21.45 5.78 20.04 5.53 18.62 5.24 17.80 5.04 17.09 4.88 15.68 4.60
-3 -4 21.45 5.61 20.04 5.35 18.62 5.11 17.80 5.04 17.09 4.85 15.68 4.46
50%
0 -1 21.45 5.36 20.04 5.15 18.62 4.90 17.80 4.69 17.09 4.55 15.68 4.19
3 2 21.45 5.23 20.04 4.96 18.62 4.64 17.80 4.47 17.09 4.30 15.68 3.99
5 4 21.45 5.06 20.04 4.77 18.62 4.46 17.80 4.31 17.09 4.16 15.68 3.83
7 6 21.45 4.94 20.04 4.64 18.62 4.37 17.80 4.18 17.09 4.03 15.68 3.70
9 8 21.45 4.78 20.04 4.50 18.62 4.20 17.80 4.04 17.09 3.89 15.68 3.61
11 10 21.45 4.67 20.04 4.37 18.62 4.09 17.80 3.92 17.09 3.79 15.68 3.48
13 12 21.45 4.47 20.04 4.20 18.62 3.92 17.80 3.77 17.09 3.64 15.68 3.34
15 14 21.45 4.38 20.04 4.10 18.62 3.82 17.80 3.67 17.09 3.54 15.68 3.27
49
Outdoor
___________________________________________________________________________________
50
Outdoor
___________________________________________________________________________________
-15 -15 29.70 9.31 28.85 9.30 26.73 9.05 25.74 8.99 24.61 8.76 22.49 8.26
-13 -13 30.98 9.56 28.85 9.26 26.73 8.89 25.74 8.64 24.61 8.47 22.49 7.88
-11 -11 30.98 9.39 28.85 8.90 26.73 8.58 25.74 8.39 24.61 8.16 22.49 7.55
-10 -10 30.98 9.27 28.85 8.83 26.73 8.43 25.74 8.22 24.61 8.04 22.49 7.47
-9 -9 30.98 9.17 28.85 8.70 26.73 8.31 25.74 8.09 24.61 7.98 22.49 7.39
-7 -8 30.98 9.02 28.85 8.51 26.73 8.19 25.74 7.89 24.61 7.76 22.49 7.18
-5 -6 30.98 8.77 28.85 8.37 26.73 7.92 25.74 7.66 24.61 7.42 22.49 6.94
-3 -4 30.98 8.50 28.85 8.08 26.73 7.71 25.74 7.63 24.61 7.30 22.49 6.70
60%
0 -1 30.98 8.14 28.85 7.83 26.73 7.39 25.74 7.14 24.61 6.86 22.49 6.28
3 2 30.98 7.96 28.85 7.49 26.73 6.99 25.74 6.75 24.61 6.48 22.49 5.99
5 4 30.98 7.70 28.85 7.22 26.73 6.75 25.74 6.53 24.61 6.26 22.49 5.81
7 6 30.98 7.54 28.85 7.04 26.73 6.56 25.74 6.32 24.61 6.05 22.49 5.53
9 8 30.98 7.28 28.85 6.79 26.73 6.33 25.74 6.11 24.61 5.89 22.49 5.42
11 10 30.98 7.07 28.85 6.63 26.73 6.19 25.74 5.98 24.61 5.74 22.49 5.26
13 12 30.98 6.75 28.85 6.32 26.73 5.87 25.74 5.70 24.61 5.47 22.49 5.03
15 14 30.98 6.65 28.85 6.21 26.73 5.76 25.74 5.58 24.61 5.38 22.49 4.97
-15 -15 25.74 8.00 24.05 7.66 22.35 7.48 21.36 7.39 20.51 7.18 18.81 6.82
-13 -13 25.74 7.90 24.05 7.61 22.35 7.34 21.36 7.11 20.51 7.00 18.81 6.49
-11 -11 25.74 7.78 24.05 7.36 22.35 7.11 21.36 6.91 20.51 6.74 18.81 6.23
-10 -10 25.74 7.64 24.05 7.30 22.35 6.99 21.36 6.78 20.51 6.61 18.81 6.16
-9 -9 25.74 7.53 24.05 7.18 22.35 6.87 21.36 6.59 20.51 6.56 18.81 6.08
-7 -8 25.74 7.42 24.05 7.05 22.35 6.76 21.36 6.50 20.51 6.39 18.81 5.92
-5 -6 25.74 7.23 24.05 6.92 22.35 6.55 21.36 6.31 20.51 6.11 18.81 5.76
-3 -4 25.74 7.03 24.05 6.69 22.35 6.39 21.36 6.31 20.51 6.07 18.81 5.58
50%
0 -1 25.74 6.70 24.05 6.45 22.35 6.13 21.36 5.86 20.51 5.69 18.81 5.25
3 2 25.74 6.55 24.05 6.20 22.35 5.81 21.36 5.59 20.51 5.38 18.81 4.99
5 4 25.74 6.33 24.05 5.97 22.35 5.59 21.36 5.39 20.51 5.21 18.81 4.79
7 6 25.74 6.18 24.05 5.81 22.35 5.47 21.36 5.23 20.51 5.04 18.81 4.63
9 8 25.74 5.98 24.05 5.64 22.35 5.26 21.36 5.06 20.51 4.87 18.81 4.52
11 10 25.74 5.85 24.05 5.48 22.35 5.11 21.36 4.90 20.51 4.74 18.81 4.35
13 12 25.74 5.60 24.05 5.25 22.35 4.90 21.36 4.72 20.51 4.55 18.81 4.18
15 14 25.74 5.48 24.05 5.13 22.35 4.78 21.36 4.59 20.51 4.43 18.81 4.09
51
Outdoor
___________________________________________________________________________________
52
Outdoor
___________________________________________________________________________________
-15 -15 33.00 10.48 32.06 10.47 29.70 10.18 28.60 10.12 27.35 9.86 24.99 9.30
-13 -13 34.42 10.76 32.06 10.43 29.70 10.01 28.60 9.73 27.35 9.54 24.99 8.87
-11 -11 34.42 10.57 32.06 10.02 29.70 9.66 28.60 9.44 27.35 9.19 24.99 8.50
-10 -10 34.42 10.44 32.06 9.94 29.70 9.48 28.60 9.26 27.35 9.05 24.99 8.41
-9 -9 34.42 10.32 32.06 9.79 29.70 9.35 28.60 9.10 27.35 8.99 24.99 8.31
-7 -8 34.42 10.16 32.06 9.58 29.70 9.21 28.60 8.88 27.35 8.73 24.99 8.08
-5 -6 34.42 9.87 32.06 9.42 29.70 8.91 28.60 8.62 27.35 8.35 24.99 7.82
-3 -4 34.42 9.56 32.06 9.09 29.70 8.68 28.60 8.58 27.35 8.22 24.99 7.54
60%
0 -1 34.42 9.16 32.06 8.81 29.70 8.32 28.60 8.04 27.35 7.72 24.99 7.06
3 2 34.42 8.96 32.06 8.43 29.70 7.87 28.60 7.60 27.35 7.29 24.99 6.75
5 4 34.42 8.66 32.06 8.13 29.70 7.60 28.60 7.34 27.35 7.05 24.99 6.54
7 6 34.42 8.49 32.06 7.93 29.70 7.39 28.60 7.11 27.35 6.81 24.99 6.23
9 8 34.42 8.19 32.06 7.64 29.70 7.13 28.60 6.87 27.35 6.63 24.99 6.10
11 10 34.42 7.95 32.06 7.47 29.70 6.97 28.60 6.73 27.35 6.46 24.99 5.92
13 12 34.42 7.60 32.06 7.11 29.70 6.61 28.60 6.42 27.35 6.16 24.99 5.66
15 14 34.42 7.48 32.06 6.99 29.70 6.48 28.60 6.28 27.35 6.06 24.99 5.60
-15 -15 28.60 9.00 26.72 8.62 24.83 8.42 23.73 8.31 22.79 8.08 20.90 7.68
-13 -13 28.60 8.89 26.72 8.57 24.83 8.26 23.73 8.00 22.79 7.88 20.90 7.30
-11 -11 28.60 8.76 26.72 8.29 24.83 8.00 23.73 7.78 22.79 7.59 20.90 7.01
-10 -10 28.60 8.60 26.72 8.22 24.83 7.87 23.73 7.63 22.79 7.44 20.90 6.93
-9 -9 28.60 8.47 26.72 8.08 24.83 7.74 23.73 7.41 22.79 7.39 20.90 6.85
-7 -8 28.60 8.35 26.72 7.94 24.83 7.61 23.73 7.32 22.79 7.20 20.90 6.66
-5 -6 28.60 8.14 26.72 7.79 24.83 7.38 23.73 7.10 22.79 6.87 20.90 6.48
-3 -4 28.60 7.91 26.72 7.53 24.83 7.20 23.73 7.10 22.79 6.83 20.90 6.28
50%
0 -1 28.60 7.55 26.72 7.26 24.83 6.90 23.73 6.60 22.79 6.40 20.90 5.90
3 2 28.60 7.37 26.72 6.98 24.83 6.54 23.73 6.30 22.79 6.05 20.90 5.62
5 4 28.60 7.13 26.72 6.72 24.83 6.29 23.73 6.07 22.79 5.87 20.90 5.39
7 6 28.60 6.96 26.72 6.54 24.83 6.16 23.73 5.89 22.79 5.67 20.90 5.21
9 8 28.60 6.73 26.72 6.35 24.83 5.92 23.73 5.69 22.79 5.49 20.90 5.09
11 10 28.60 6.58 26.72 6.16 24.83 5.76 23.73 5.52 22.79 5.33 20.90 4.90
13 12 28.60 6.30 26.72 5.91 24.83 5.52 23.73 5.31 22.79 5.12 20.90 4.70
15 14 28.60 6.16 26.72 5.77 24.83 5.38 23.73 5.17 22.79 4.99 20.90 4.61
53
Outdoor
3. Dimensions
3.1) 25.2-28.0 kW
(Unit: mm)
54
Outdoor
3.2) 33.5-45.0 kW
(Unit: mm)
55
Outdoor
4. Service Space
4.1) Power supply equipment is preferred to be installed by the side of the outdoor unit;
4.2) Ensure there is sufficient space for the maintenance of the outdoor unit. The modules in the
same system must be on the same height.
56
Outdoor
5. Piping Diagram
EXV
EXV
Ф 28.6
ST1
SV5
Ф 6.4
5
SV2
Ф 19.1
4
SV4
1 2 3
Remark:
1: DC Inverter compressor
2/3: Fixed compressor
4: Gas-liquid separator
5: Oil separator
57
Outdoor
5) SV1: Opens when outdoor unit starts. Closes when unit stops.
6) SV2: For spraying a little refrigerant to cool compressor down.
Opens if any compressor discharge temp. is higher than 100℃.
7) SV3: for changing the heat-exchanged areas on heating mode.
Opens when the average temp. of all indoor evaporators is less than 46℃. Closes while
the average temp. of all indoor evaporators more than 52℃
OFF on cooling mode
8) SV4: oil returning valve.
Opens when the unit is running for every 20 minutes and last 3 minutes
9) SV5: for defrost.
In defrosting mode, the opening of SV5 can cut the refrigerant flowing circle, so the
defrosting process will takes less time.
10) SV6: for by-pass.
Closes when the unit stands by and system in heating mode.
Opens when the discharge temperature is too high in cooling mode.
58
Outdoor
6. Wiring Diagram
6.1) 3 Ph 380 V
59
Outdoor
6.2) 3 Ph 230 V
60
Outdoor
7. Electrical characteristic
Remark:
61
Outdoor
8. Operation Limits
Cooling Heating
55
50
45
40 35
30
35
Outdoor temperature(℃ DB)
30 25
25 20
Outdoor temperature(℃ WB)
20 15
5
10
0
5
-5
0
- 10
-5
- 15
-10
- 20
- 15
- 25
- 20
5 10 15 20 25 30
10 15 20 25 30
Indoor temperature(℃ DB)
Indoor temperature(℃ WB)
Notes: These figures assume the following operation conditions (Indoor and outdoor units):
1. Equivalent pipe length: 10m
2. Height difference: 0m
62
Outdoor
9. Sound Levels
9.1) Standard of testing
Note: H = (h+1) / 2
63
Outdoor
10. Trouble-shooting
10.1) Unit running control
10.1.1 Introduction of Stand-by after power on and power off
-Indoor unit: Running light flash slowly after power on, running light extinguish after power off
-Outdoor unit: Digital pipe can display online number of indoor units for two states as above
10.1.2 Starting process:
Outdoor unit power for the first time
Single
Outdoor unit power on for module SV1 close: SV4
the first time, EXV close to open, SV3, SV6,
700 pulse first then open ST1, ST2, fan,
to 350 pulse comp. close
Combination
64
Outdoor
65
Outdoor
66
Outdoor
NO
NO
Check address Set again and power on again
setting
OK
NO
Check wiring: Replace PCB, set
polarity is wrong? and power on again
NO
Check wiring:
short circuit?
NO
67
Outdoor
NO
Check address Reset address, power to
setting outdoor unit
OK NO
NO
Wrong wiring; Change PCB,
Wrong polarity resetting address
OK
Short circuit
OK
NO
Shield cable?
Earthling?
No
Change PCB
68
Outdoor
E2: Communication error between Indoor unit and master outdoor unit
E1 (Master unit),
Timer (Indoor unit)
flash quickly
NO
Short circuit
NO
NO
Shield cable?
Earthling?
69
Outdoor
E3:T3 outdoor coil sensor, T3>65 o C, 3 seconds, stops compressor, T3<52 o C compressor on
E3 (Master unit),
Indoor alarm flash slowly
Yes
No
No
Does sensor connector connect well? Fix connector
Yes
Is sensor defective? No
Change sensor
25℃, R=10K
Yes No
No Yes
Is pipe temp. More than Does the sensor have Change PCB
65degree? correct resistance?
Yes
Yes No
Yes
There is air in system,
recharge refrigerant
Change PCB or relay in
PCB
70
Outdoor
E4 (Master unit),
Indoor alarm flash slowly
Is sensor defective? No
Change
25℃, R=10K
sensor
Yes
Change PCB
E5 (Master unit),
Indoor unit alarm flash slowly
Yes
Is sensor defective? Change
25℃, R=10K sensor
No
Change PCB
71
Outdoor
E8 (Mater unit)
Master unit: 0,
Slave unit: 1-3
NO
Change PCB
72
Outdoor
H2 or H3 (master unit)
Indoor unit alarm flash slowly
Check wiring
Wrong polarity? Wrong wiring? Wrong earthling ? Short circuit?
Power the outdoor units again, does the problem solve?
No Yes
Disconnect one slave unit, Change the PCB in Reconnect the salve unit
power the units again, slave unit
does the problem solve? Yes
No
73
Outdoor
P1: High pressure protection (the code will disappear when protection recovery)
If code appears when powering on or keep for a long time, generally this is caused by high
pressure switch, main board or connecting line malfunction.
OK
High/low pressure stop Error disappear
valve opened
completely or not?
NO
Yes
Yes
Pressures switch No
Replace high pressure switch Error
work well? disappear
No
Piping (filter, Replace Error disappear
accumulator), 4-way
and EXV work well?
Yes
74
Outdoor
P2: Low pressure protection (the code will disappear when protection recovery)
If code appears when powering on or keep for a long time, generally this is caused by low
pressure switch, main board or connecting line malfunction.
High/low pressure OK
Error disappear
stop valve opened
completely or not?
NO
Yes
Yes
No
Pressures switch
Replace pressure switch Error
work well?
disappear
Yes
75
Outdoor
76
Outdoor
11. Accessories
11.1) Standard accessories
77
Outdoor unit
12. Explode view and spare part list
MODEL YDV-252-280WC R-410A 3 Ph 380-415V 60Hz
_______________________________________________________________________________________________
78
Outdoor unit
PART NO.
ITEM NO PART NAME QTY REMARK
25.2 kW 28.0 kW
1 201M100300203 Axial flow fan 1
2 202M400400025 Motor 1
3 201M295500304 Motor bracket 2
4 202M450200314 Temp sensor ass'y 1
5 201M595190001 Condenser ass'y 1
6 201M295100148 Fixing board ass'y 1
7 202M450200331 Temp sensor ass'y 1
8 202M450200313 Discharge temp sensor ass'y 1
9 202M395020902 Discharge temp sensor ass'y 1
10 201M400410480 201M400420100 Compressor 1
11 201M400410490 201M400420110 Compressor 1
12 202M403100170 202M495030816 Compressor electric heater 1
13 202M495030816 Compressor electric heater 1
14 201M195590003 Board 4
15 203M395190011 E-part box ass'y 1
- 201M295030803 E-part box 1
- 202M300100906 Resistor 2
- 202M300300109 Aluminum electroanalysis capacitor 2
- 201M395030801 Filter board ass'y 1
- 202M300130008 Resistance 2
- 202M401090058 Compressor capacitor 1
- 202M300900109 Transformer 1
- 202M300850043 Contactor 2
- 202M301000005 Magnetism loop 1
- 202M301450131 Wire joint 1
- 202M301450112 Wire joint, 4p 1
- 202M301450125 Wire joint 2
- 202M401000410 Compressor capacitor 1
- 201M395030802 Load transit board 1
- 202M300900150 Transformer 1
- 202M300800071 Relay 2
- 201M395190009 Main controller ass'y 1
- 201M319900562 201M319900566 Inverter module 1
- 202M301900048 Radiator 1
- 202M300500326 Three phase bridge 1
- 202M300500331 Single-phase bridge 1
16 201M295190026 Compressor base 1
17 201M295190024 Compressor base 3
18 201M295030839 E-part box cover board 1
19 201M295190022 Inductance cover 1
20 201M695190149 Solenoid valve ass'y 1
- 201M600600081 Solenoid valve 1
- 201M600600214 Solenoid valve winding 1
21 201M250200306 Inductance board 1
22 202M301000241 202M301000266 Electrical inductance 1
23 201M295100083 Inductance Holder 1
24 201M295100080 Duct 1
25 201M295500305 Front cover 1
26 201M148700009 Handle 1
27 201M695190004 Accumulator connection pipe ass'y 1
- 201M600600214 Solenoid valve winding 2
- 201M600600080 Solenoid valve 2
- 201M600810001 One way valve 1
28 201M695590087 High pressure valve ass'y 1
- 201M600720193 Low pressure valve 1
29 201M695590078 Pipe joint subassmbly 1
- 201M601200004 Pipe joint 1
30 201M695590224 Oil balance valve ass'y 1
- 201M600710108 Low pressure valve 1
31 201M695190055 Gas balance valve ass'y 1
- 201M600710109 Low pressure valve 1
_______________________________________________________________________________________________
79
Outdoor unit
32 201M695190048 Ball valve ass'y 1
- 201M600790123 Ball valve 1
33 201M695190000 201M695100102 Capillary ass'y 1
34 201M695190018 201M695100270 Suction pipe ass'y 1
- 202M301820028 Pressure controller 1
35 201M695190015 Capillary ass'y 1
- 201M600800033 One way valve 1
36 201M695190024 Electronic expansion valve ass'y 1
- 201M601300021 Electronic expansion valve 2
- 201M601390007 EEV solenoid 2
- 201M600800027 One way valve 3
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid valve winding 2
37 201M695190027 4-way valve ass'y 1
- 202M301820020 Pressure controller 1
- 201M600600113 4-Ways valve solenoid 2
- 201M600600110 4-way valve 2
38 201M695190008 201M695100268 Discharge pipe ass'y 1
- 201M600800027 One way valve 2
39 201M695190002 Capillary ass'y 1
- 201M600600081 Solenoid valve 1
- 201M600600214 Solenoid valve winding 1
40 201M695190016 Oil balance pipe ass'y 2
41 201M295190025 Base ass'y 1
42 201M295500306 201M295590074 Front-right supporting board 1
43 201M295500307 201M295590075 Front-left supporting board 1
44 201M295500298 Valve plate ass'y 1
45 201M295590025 E-part box installation board 1
46 201M295500309 Sealed board 2
47 201M601100031 Oil separator 1
48 201M601010007 Accumulator tank 1
49 201M295590024 E-part box installation board 1
50 201M601100042 Seporator 1
51 201M295500312 Net 2
52 201M295500311 Rear net 1
53 201M295500299 Rear-left supporting board 1
54 201M295590059 Cover board 2
55 201M295500308 Rear-right supporting board 1
56 201M295500297 Net 1
57 201M295190027 Installation board 1
58 201M295100147 Fixing board ass'y 1
59 201M295190028 Installation board 1
60 201M295500295 Condenser side board ass'y 1
61 201M295500313 Cover plate ass'y 1
62 201M295500310 Rear cover 1
63 201M195590004 Plastic top cover ass'y 1
_______________________________________________________________________________________________
80
Outdoor unit
_______________________________________________________________________________________________
81
Outdoor unit
_______________________________________________________________________________________________
82
Outdoor unit
44 202M495030816 Compressor electric heater 2
46 202M195020901 Sponge I 1
47 201M695100203 High pressure valve ass'y 1
- 201M600720193 Low pressure valve 1
48 201M695100187 Oil balance valve ass'y 1
- 201M600710108 Low pressure valve 1
49 201M695100185 Gas balance valve ass'y 1
- 201M600710109 Low pressure valve 1
50 201M695100205 Low pressure valve ass'y 1
- 201M600790123 Ball valve 1
51 201M695100272 Discharge pipe ass'y 1
- 201M600800027 One way valve 2
52 201M695100182 Oil balance pipe ass'y 1
- 201M600800033 One way valve 1
53 201M695190153 Suction pipe ass'y 1
- 201M600600081 Solenoid valve 2
- 201M600600225 Solenoid valve winding 2
- 202M301820028 Pressure controller 1
54 201M295100175 Compressor supporter ass'y III 1
55 201M295100174 Compressor supporter ass'y II 1
56 201M295100173 Compressor supporter ass'y I 2
57 201M695100162 Expansion valve ass'y 1
- 201M600800027 One way valve 3
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid valve winding 2
- 201M601300021 Electronic expansion valve 2
- 201M601390007 EEV solenoid 2
58 201M601010007 Accumulator tank 1
59 201M601100031 Oil separator 1
60 201M601100042 Seporator 1
61 201M195590003 Board 4
62 201M295100161 Ball valve supporter ass'y 1
63 201M295100166 Mid-front holder 1
64 201M295100163 Front-right supporting board 1
65 201M295100165 Rear-right supporting board 1
66 201M295100148 Fixing board ass'y I 1
67 201M295100157 Net 1
68 201M295100172 Rear net 2
69 201M295100158 Support board 1
70 201M295030810 Baffle ass'y 1
71 201M295100168 Motor bracket ass'y 1
72 201M295100169 Motor bracket ass'y 1
73 201M295030812 Rear clapboard ass'y 1
74 201M295100147 Fixing board ass'y II 3
75 201M695100212 4-way valve ass'y 1
- 201M600600110 4-way valve 2
- 201M600600113 4-Ways valve solenoid 2
- 202M301820020 Pressure controller 1
76 201M695100001 Accumulator connection pipe ass'y 1
- 201M600810001 One way valve 1
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid valve winding 2
77 201M695100207 Capillary ass'y 1
_______________________________________________________________________________________________
83
Outdoor unit
_______________________________________________________________________________________________
84
Outdoor unit
PART NO.
ITEM NO PART NAME QTY REMARK
40.0 kW 45.0 kW
1 201M195100000 Top cover 2
2 201M100300205 Axial flow fan 2
3 201M295100159 Covering plate 2
4 201M295030812 Rear clapboard ass'y 1
5 201M295100147 Fixing board ass'y 3
6 201M295030810 baffle ass'y 1
7 201M295100149 Cover board 2
8 201M295100158 Support board 1
9 201M295100172 Rear net 2
10 201M295100165 Rear-right supporting board 1
11 201M295100157 Net 1
12 201M295000076 E-part box Support board 1
13 201M295000013 Expansion valve bracket 1
14 201M295000011 E-part box Support board 1
15 201M295100166 Mid-front holder 1
16 201M295100163 Front-right supporting board 1
17 201M295100176 Base 1
18 201M195590003 Board 4
19 201M295100150 Valve plate 1
20 201M295100160 Valve plate cover 1
21 201M695190016 Oil balance pipe ass'y 3
22 201M695100176 Accumulator connection pipe ass'y 1
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid 2
- 201M600810001 One way valve 1
23 201M695100149 4-way valve ass'y 1
- 201M600600110 4-way valve 2
- 201M600600113 4-Ways valve solenoid 2
- 202M301820020 Pressure controller 1
24 201M695100162 Electronic expansion valve ass'y 1
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid 2
- 201M600800027 One way valve 3
- 201M601300021 Electronic expansion valve 2
- 201M601390007 EEV solenoid 2
25 201M695190151 201M695190152 Suction pipe ass'y 1
- 201M600600081 Solenoid valve 2
- 201M600600214 Solenoid 2
- 202M301820028 Pressure controller 1
26 201M695100169 201M695100276 Discharge pipe ass'y 1
- 201M600800027 One way valve 3
27 201M695100182 Oil balance pipe ass'y 1
- 201M600800033 One way valve 1
28 201M695100179 Capillary ass'y 1
29 201M295100170 Front-right board 1
30 201M695100188 Low pressure valve ass'y 1
- 201M600810007 Ball valve 1
31 201M295100161 Ball valve supporter ass'y 1
32 201M695100185 Gas balance valve ass'y 1
- 201M600710109 Low pressure valve 1
33 201M695100187 Oil balance valve ass'y 1
- 201M600710108 Low pressure valve 1
34 201M695590074 High pressure valve Ass'y 1
- 201M600710615 Low pressure valve 1
35 201M695590189 Pipe joint ass'y 1
- 201M601200004 Pipe joint 1
36 201M295100151 201M295190037 Front-left clapboard 1
37 201M295020911 Inductance Holder 1
38 202M301000241 Electrical inductance 1
39 201M250200306 Board 1
40 201M295190022 Inductance cover 1
_______________________________________________________________________________________________
85
Outdoor unit
41 201M295030839 E-part box cover board 1
42 201M295000061 201M295100008 Duct 1
43 203M395190013 E-part box ass'y 1
- 201M319900562 201M319900566 Inverter module 1
- 201M395190009 Main controller ass'y 1
- 202M300800071 Relay 2
- 201M395030802 Load transit board 1
- 202M401000303 Compressor capacitor 2
- 202M301000005 Magnetism loop 2
- 202M300900150 Transformer (TT2-D35+D15-1F) 1
- 202M301450125 Terminal block JX0-B6-D 2
- 202M301450112 Terminal 1
- 202M301450131 Wire joint 1
- 202M300850043 Contactor 3
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 201M395030801 Filter board ass'y 1
- 202M300130008 heat sense resistance 2
- 202M401090058 Compressor capacitor 1
- 202M300300109 Aluminium eletrolytic capacitor 2
- 202M300100906 Resistor 2
- 202M300500326 Three phase bridge 1
- 202M300500331 Single-phase bridge 1
- 202M301900048 Radiator 1
44 201M295100174 Compressor supporter ass'y II 1
45 201M295100175 Compressor supporter ass'y III 1
46 201M295100173 Compressor supporter ass'y I 2
47 201M400410490 201M400420100 Compressor 2
- 202M495030816 compressor electric heater 2
- 202M395020902 Discharge temp sensor Ass'y 2
48 201M400410480 201M400420110 Compressor 1
- 202M403100170 202M495030816 compressor electric heater 1
- 202M450200313 Discharge temp sensor Ass'y 1
49 201M295100148 Fixing board ass'y 1
50 201M595100140 Below condenser ass'y 1
- 202M450200331 evaporator temp sensor ass'y 1
51 201M595100141 Up condenser ass'y 1
- 202M450200314 202M301300198 ambient temp sensor ass'y 1
52 201M295100171 Motor bracket ass'y 1
53 201M295030828 Supporter 1
54 201M295030829 cover supporter 1
55 201M295100167 Middle supporting ass'y 2
56 201M295100168 Motor bracket ass'y 1
57 202M400400369 motor 2
58 201M295100169 Motor bracket ass'y 1
59 201M601100039 Seporator 1
60 201M601100031 Oil separator 1
61 201M601000027 Accumulator 1
62 201M295000079 condenser side board 2
63 201M295100162 Front-left supporting board 1
64 201M295030814 Wind baffle ass'y 1
65 201M295100156 Net 1
66 201M295100164 Rear-left supporting board 1
67 201M295030841 Support board 2
_______________________________________________________________________________________________
86
Outdoor unit
_______________________________________________________________________________________________
87
Outdoor unit
PART NO.
ITEM NO PART NAME QTY REMARK
25.2 kW 28.0 kW
1 201M195590004 Plastic top cover ass'y 1
2 201M295500310 Rear cover 1
3 201M295500295 Condenser side board ass'y 1
4 201M295190028 Installation board 1
5 201M295500297 Net 1
6 201M295500308 Rear-right supporting board 1
7 201M295500311 Rear net 1
8 201M295500312 Net 2
9 201M295590059 Cover board 2
10 201M295500309 Sealed board 2
11 201M295590074 Front-right supporting board 1
12 201M295190025 Base ass'y 1
13 201M195590003 Board 4
14 201M601100042 Seporator 1
15 201M601010007 Accumulator 1
16 201M601100031 Oil separator 1
17 201M695190002 Capillary ass'y 1
- 201M600600081 Solenoid valve 1
- 201M600600214 Solenoid 1
18 201M695100268 Discharge pipe ass'y 1
- 201M600800027 One way valve 2
19 201M695190027 4-way valve ass'y 1
- 201M600600110 4-way valve 2
- 201M600600113 4-way valve solenoid 2
- 202M301820020 Pressure controller 1
20 201M695190024 Electronic expansion valve ass'y 1
- 201M601300021 Electronic expansion valve 2
- 201M601390007 EEV solenoid 2
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid 2
- 201M600800027 One way valve 3
21 201M695100102 Capillary ass'y 1
22 201M695190167 Suction pipe ass'y 1
- 202M301820028 Pressure controller 1
23 201M695190015 Capillary ass'y 1
24 201M295190023 Ball valve inductance base ass'y 1
25 201M695190048 Ball valve ass'y 1
- 201M600790123 Ball valve 1
26 201M695190055 Gas balance valve ass'y 1
- 201M600710109 Low pressure valve 1
27 201M695590224 Oil balance valve ass'y 1
- 201M600710108 Low pressure valve 1
28 201M695590087 High pressure valve Ass'y 1
- 201M600720193 Low pressure valve 1
29 201M148700009 Handle 1
30 201M295590073 Front cover 1
31 201M295030839 E-part box cover board 1
32 201M295190024 Compressor base 3
33 201M295190026 Compressor base 1
34 201M400420160 201M400420170 Compressor 1
35 201M400420150 Compressor 1
36 201M295100148 Fixing board ass'y 1
37 201M595190001 Condenser ass'y 1
38 201M295500304 Motor bracket 2
39 202M400400025 motor 1
40 201M100300203 Axial flow fan 1
41 201M295190029 Installation board ass'y 1
42 201M295500313 Cover plate ass'y 1
43 201M295190027 Installation board 1
44 201M295100147 Fixing board ass'y 1
45 202M301300198 Room temp sensor ass'y 1
_______________________________________________________________________________________________
88
Outdoor unit
46 201M295500299 Rear-left supporting board 1
47 201M295590075 Front-left supporting board 1
48 201M295590024 E-part box installation board 1
49 201M295500298 Valve plate ass'y 1
50 202M395020902 Discharge temp sensor Ass'y 1
51 202M402150993 Grounding wire with jacket 2
52 202M495030816 compressor electric heater 2
53 202M495190001 Compressor wire joint ass'y 1
54 201M295020906 compressor gasket 8
55 202M450200313 Discharge temp sensor Ass'y 1
56 203M395190086 E-part box ass'y 1
- 201M295030803 E-part box 1
- 202M300100906 Resistor 2
- 202M300300109 Aluminium eletrolytic capacitor 2
- 201M395190015 Filter board ass'y 1
- 202M300130008 heat sense resistance 2
- 202M401090058 Compressor capacitor 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 202M300850050 AC contactor 1
- 202M301450131 Wire joint 1
- 202M301450110 Wire joint 1
- 202M301450125 Terminal block JX0-B6-D 2
- 202M401000410 Compressor capacitor for unit A 25UF/440-450V 1
- 201M395030802 Load transit board 1
- 202M300900150 Transformer (TT2-D35+D15-1F) 1
- 202M300800071 Relay 2
- 201M395190014 Main control board ass'y 1
- 201M319990010 Inverter module 1
- 202M301900008 Radiator 1
- 202M300500326 Three phase bridge 1
- 202M300500331 Single-phase bridge 1
57 201M295590025 E-part box installation board 1
58 201M295190039 Electric inductance cover ass'y 1
59 201M295190041 Inductance board 1
60 201M295190042 Inductance board 1
61 202M301000269 Electrical inductance 1
62 201M295190040 Inductance Holder 1
63 201M295100080 Duct 1
64 201M695190004 Accumulator connection pipe ass'y 1
- 201M600600214 Solenoid 2
- 201M600600080 Solenoid valve 2
- 201M600810001 One way valve 1
65 201M695190249 Solenoid valve ass'y 1
- 201M600600081 Solenoid valve 1
- 201M600600225 Solenoid valve winding 1
66 202M301000005 Magnetism loop 1
67 202M450200331 evaporator temp sensor ass'y 1
_______________________________________________________________________________________________
89
Outdoor unit
_______________________________________________________________________________________________
90
Outdoor unit
_______________________________________________________________________________________________
91
Outdoor unit
41 203M395190087 E-part box ass'y 1
- 201M319990010 Inverter module 1
- 201M395190014 Main control board ass'y 1
- 202M300800071 Relay 2
- 201M395030802 Load transit board 1
- 202M401000303 Compressor capacitor 2
- 202M300900150 Transformer (TT2-D35+D15-1F) 1
- 202M301450125 Terminal block JX0-B6-D 2
- 202M301450110 Wire joint 1
- 202M301450131 Wire joint 1
- 202M300850050 AC contactor 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 201M395190015 Filter board ass'y 1
- 202M300130008 heat sense resistance 2
- 202M401090058 Compressor capacitor 1
- 202M300300109 Aluminium eletrolytic capacitor 2
- 202M300100906 Resistor 2
- 202M300500326 Three phase bridge 1
- 202M300500331 Single-phase bridge 1
- 202M301900008 Radiator 1
42 201M295100174 Compressor supporter ass'y II 1
43 201M295100175 Compressor supporter ass'y III 1
44 201M295100173 Compressor supporter ass'y I 2
45 201M400420150 Compressor 1
- 202M495030816 compressor electric heater 2
- 202M450200313 Discharge temp sensor Ass'y 1
46 201M400420170 Compressor 1
- 202M395020902 Discharge temp sensor Ass'y 2
47 201M295100148 Fixing board ass'y 1
48 201M595100001 Condenser ass'y 1
- 202M450200331 evaporator temp sensor ass'y 1
- 202M301300198 Room temp sensor ass'y 1
49 201M601100042 Seporator 1
50 201M295100171 Motor bracket ass'y 1
51 201M295030828 Supporter 1
52 201M295030829 cover supporter 1
53 201M295100167 Middle supporting ass'y 2
54 201M295100168 Motor bracket ass'y 1
55 202M400400485 motor 2
56 201M295100169 Motor bracket ass'y 1
57 201M601100031 Oil separator 1
58 201M601010007 Accumulator 1
59 201M295100150 Valve plate 1
60 201M295000011 E-part box Support board 1
61 201M295100162 Front-left supporting board 1
62 201M295030814 Wind baffle ass'y 1
63 201M295100156 Net 1
64 201M295100164 Rear-left supporting board 1
65 201M295000076 E-part box Support board 1
66 201M295100147 Fixing board ass'y 3
67 202M301000005 Magnetism loop 1
_______________________________________________________________________________________________
92
Outdoor unit
_______________________________________________________________________________________________
93
Outdoor unit
PART NO.
ITEM NO PART NAME QTY REMARK
40.0 kW 45.0 kW
1 201M195100000 Top cover 2
2 201M100300205 Axial flow fan 2
3 201M295100159 Cover plate 2
4 201M295030812 Rear clapboard ass'y 1
5 201M295100147 Fixing board ass'y II 3
6 201M295030810 Baffle ass'y 1
7 201M295100149 Cover board 2
8 201M295100158 Support board 1
9 201M295100172 Rear net 2
10 201M295100165 Rear-right supporting board 1
11 201M295100157 Net 1
12 201M295000076 E-part box Support board 1
13 201M295000013 Expansion valve bracket 1
14 201M295000011 E-part box Support board 1
15 201M295100166 Mid-front holder 1
16 201M295100163 Front-right supporting board 1
17 201M295100176 Base 1
18 201M195590003 Board 4
19 201M295100150 Valve plate 1
20 201M295100160 Valve plate cover 1
21 201M295190031 Fresh air pipe ass'y 1
22 201M695100176 Accumulator connection pipe ass'y 1
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid valve winding 2
- 201M600810001 One way valve 1
23 201M695100149 4-way valve ass'y 1
- 201M600600110 4-way valve 2
- 201M600600113 4-Ways valve solenoid 2
- 202M301820020 Pressure controller 1
24 201M695100162 Expansion valve ass'y 1
- 201M600600080 Solenoid valve 2
- 201M600600214 Solenoid valve winding 2
- 201M600800027 One way valve 3
- 201M601300021 Electronic expansion valve 2
- 201M601390007 EEV solenoid 2
25 201M695190171 Suction pipe ass'y 1
- 201M600600081 Solenoid valve 2
- 201M600600225 Solenoid valve winding 2
- 202M301820028 Pressure controller 1
26 201M695100276 Discharge pipe ass'y 1
- 201M600800027 One way valve 3
27 201M695100182 Oil balance pipe ass'y 1
- 201M600800033 One way valve 1
28 201M695100179 Capillary ass'y 1
29 201M295100170 Front-right board 1
30 201M695100296 Low pressure valve ass'y 1
- 201M600810007 Ball valve 1
31 201M295100161 Ball valve supporter ass'y 1
32 201M695100185 Gas balance valve ass'y 1
- 201M600710109 Low pressure valve 1
33 201M695100187 Oil balance valve ass'y 1
- 201M600710108 Low pressure valve 1
34 201M695590074 High pressure valve ass'y 1
- 201M600710615 Low pressure valve 1
35 201M695590316 Pipe joint ass'y 1
- 201M601200004 Pipe joint 1
36 201M295190037 Front-left clapboard 1
37 201M295190043 Inductance Holder 1
38 202M301000269 Electrical inductance 1
39 201M295190041 Inductance board 1
- 201M295190042 Inductance board 1
_______________________________________________________________________________________________
94
Outdoor unit
40 201M295190039 Electric inductance cover ass'y 1
41 201M295030839 E-part box cover board 1
42 201M295100008 Duct 1
43 203M395190088 E-part box ass'y 1
- 201M319990010 Inverter module 1
- 201M395190014 Main control board ass'y 1
- 202M300800071 Relay 2
- 201M395030802 Load transit board 1
- 202M401000303 Compressor capacitor 2
- 202M300900150 Transformer 1
- 202M301450125 Wire joint 2
- 202M301450110 Wire joint 1
- 202M301450131 Wire joint 1
- 202M300850047 Contactor 1
- 202M300900109 Transformer 1
- 201M395190015 Filter board ass'y 1
- 202M300130008 Resistance 2
- 202M401090058 Compressor capacitor 1
- 202M300300109 Aluminum electroanalysis capacitor 2
- 202M300100906 Resistor 2
- 202M300500326 Three phase bridge 1
- 202M300500331 Single-phase bridge 1
- 202M301900008 Radiator 1
44 201M295100174 Compressor supporter ass'y II 1
45 201M295100175 Compressor supporter ass'y III 1
46 201M295100173 Compressor supporter ass'y I 2
47 201M400420160 201M400420170 Compressor 2
- 202M495030816 Compressor electric heater 3
- 202M395020902 Discharge temp sensor ass'y 1
48 201M400420150 Compressor 1
- 202M450200313 Discharge temp sensor ass'y 1
49 201M295100148 Fixing board ass'y I 1
50 201M595100140 Below condenser ass'y 1
- 202M450200331 Temp sensor ass'y 1
51 201M595100141 Up condenser ass'y 1
- 202M301300198 Room temp sensor ass'y 1
52 201M295100171 Motor bracket ass'y 1
53 201M295030828 Cover supporter 1
54 201M295030829 Cover supporter 1
55 201M295100167 Middle supporting ass'y 2
56 201M295100168 Motor bracket ass'y 1
57 202M400400369 Motor 2
58 201M295100169 Motor bracket ass'y 1
59 201M601100039 Seporator 1
60 201M601100031 Oil separator 1
61 201M601000027 Accumulator tank 1
62 201M295000079 Condenser side board 2
63 201M295100162 Front-left supporting board 1
64 201M295030814 Wind baffle ass'y 1
65 201M295100156 Net 1
66 201M295100164 Rear-left supporting board 1
67 201M295030841 Support board 2
68 202M301000005 Magnetism loop 2
_______________________________________________________________________________________________
95
Indoor unit introduction
___________________________________________________________________________________
___________________________________________________________________________________
- 96 -
Indoor unit introduction
___________________________________________________________________________________
Contents
1. Introduction…………………………..…………………………………………………………………………………98
2. One way cassette type………………………………………………………………………………………………99
3. Four-way cassette type……………………………………………………………………………………………..118
4. Wall mounted type…………………………………………………………………………..……………………....151
5. Ceiling &Floor type…………………………………………………………………………………………………...167
6. Hi ESP duct type....................................................................................................................192
7. Medium ESP slim duct type…………………………………………..……………………………………………218
8. Medium ESP duct type……………………………………………………………………………………………….241
___________________________________________________________________________________
- 97 -
Indoor unit introduction
___________________________________________________________________________________
1. Introduction
Refrigerant
Type Model Capacity (kW)
Type
One-way cassette type 2.8 3.6 4.5 5.6 7.1 R-410A
Cassette Four-way cassette type 2.8 3.6 4.5 5.6 7.1 8.0 0.0 11.2 14.0 R-410A
Medium ESP duct type 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 28.0 R-410A
Duct Slim Duct type 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 R-410A
Duct type 7.1 8.0 9.0 11.2 14.0 28.0 R-410A
Ceiling & floor type 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 R-410A
Wall-mounted type 2.2 2.8 3.6 4.5 5.6 7.1 R-410A
(1). Extreme low noise, 3 dB (A) lower compared with which put EXV into the indoor unit case.
(2). Easy maintenance. Being separated from indoor unit, fixed on the body or inside the indoor
unit independently, thus it can be replaced easily.
(3). Easy installation, just quick connection by flare nut.
Remark:
(1) One electronic Throttle Kit only can be applied to one indoor unit.
(2) Electronic Throttle Kit needn’t order separately, it has been packed with the indoor units
together in the factory.
___________________________________________________________________________________
- 98 -
1-Way Cassette
_____________________________________________________________________________________
- 99 -
1-Way Cassette
Contents
1. Feature………………………………………………………………………………………………..………………101
2. Specifications…………………………………………………………………………………………………….…102
3. Capacity Tables…………………………………………………………………………………………….……....103
4. Dimension……………………………………………………………………………………………………………107
5. Service space……………………………………………………………………………………………………….108
6. Piping diagrams…………………………………………………………………………………………………….108
7. Wiring diagrams……………………………………………………………………………………………………109
8. Velocity distribution………………………………………………………………………….……………….….110
9. Electric characteristics…………………………………………………………………………………………..111
10. Sound levels……………………………………………………………………………………………………….111
11. Accessories……………………………………………………………………………………………….……….113
12. Explored view……………………………………………………………………………………………..………114
_____________________________________________________________________________________
- 100 -
1-Way Cassette
1. Feature
1.1) Lower noise level
1.2) Smoother air flow with less turbulence
-Owing to the multiple-blade fan rotor and the air guide design, the airflow is getting
smoother and more comfortable
1.3) One direction air flow
-Quick cooling
- 101 -
1-Way Cassette
2. Specifications
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB,
and outdoor temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
_____________________________________________________________________________________
- 102 -
1-Way Cassette
3. Capacity table
3.1) Cooling TC: total capacity SHC: sensible capacity
Indoor temperature(°CWB)
Outdoor
Combination, %(Capacity 14 16 18 19 20 22 24
temperature(°C
index) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.70 2.10
12.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.10
14.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.10
16.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.00
18.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.50 2.00
20.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.40 1.90
21.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.40 1.90
23.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.10 3.40 1.90
2.80
25.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.00 3.30 1.90
27.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.00 3.30 1.90
29.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.20 1.90
31.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.20 1.90
33.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.10 2.00
35.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.10 2.90 1.90 3.10 2.00
37.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.10 2.90 1.90 2.90 1.90
39.00 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.80 2.00 2.90 1.90 2.90 1.90
10.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.80 2.80
12.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.60 2.70
14.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.60 2.70
16.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.50 2.70
18.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.50 2.70
20.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
21.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
23.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
3.60
25.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.10 2.70 4.20 2.60
27.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.10 2.70 4.20 2.60
29.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.10 2.50
31.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.10 2.40
33.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.00 2.40
35.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.60 4.00 2.40
37.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.60 3.90 2.30
39.00 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.70 3.90 2.40
10.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
12.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
14.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.80 3.30
16.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
18.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
20.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.50 3.20
21.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.40 3.10
23.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.40 3.10
4.50
25.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.30 3.00
27.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.30 3.00
29.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.10 2.90
31.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 5.10 3.00
33.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.90 2.90
35.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.80 2.80
37.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
39.00 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
_____________________________________________________________________________________
- 103 -
1-Way Cassette
Indoor temperature(°CWB)
Outdoor
Combination, %(Capacity 14 16 18 19 20 22 24
temperature(°C
index) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
12.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
14.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.20 4.10
16.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
18.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
20.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
21.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.00 4.10
23.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
5.60
25.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.50 4.10 6.80 3.90
27.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.40 4.00 6.50 3.80
29.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.30 4.00 6.40 3.70
31.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.20 3.90 6.30 3.70
33.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.00 3.80 6.30 3.70
35.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.70 6.20 3.60
37.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.90 6.10 3.50
39.00 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 5.70 3.80 5.80 3.80 6.00 3.50
10.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
12.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
14.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
16.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
18.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
20.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
21.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
23.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
7.10
25.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
27.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
29.00 5.30 4.70 6.10 5.10 6.90 5.40 7.30 5.60 7.70 5.80 8.50 6.00 9.30 6.20
31.00 5.20 4.60 6.00 5.00 6.80 5.30 7.20 5.50 7.60 5.70 8.40 5.90 9.20 6.10
33.00 5.20 4.60 6.00 5.00 6.80 5.30 7.20 5.50 7.60 5.70 8.40 5.90 9.20 6.10
35.00 5.20 4.60 6.00 5.00 6.80 5.30 7.10 5.50 7.60 5.70 8.40 5.90 9.20 6.10
37.00 5.20 4.60 6.00 5.00 6.80 5.30 7.10 5.50 7.60 5.70 8.40 5.90 9.20 6.10
39.00 5.20 4.60 6.00 5.00 6.80 5.30 7.10 5.50 7.60 5.70 8.40 5.90 9.20 6.10
_____________________________________________________________________________________
- 104 -
1-Way Cassette
_____________________________________________________________________________________
- 105 -
1-Way Cassette
_____________________________________________________________________________________
- 106 -
1-Way Cassette
4. Dimension
4.1) 2.8-3.6 kW
4.2) 4.5-5.6 kW
_____________________________________________________________________________________
- 107 -
1-Way Cassette
5. Service space
INSTALL SPACE
(Pipe side)
20 0mm
abo ve
Re frig era nt P ipe
1000 mm
abo ve
Ceiling
Obstacle
100mm 10 0mm
above abo ve
100 0mm
ab ove
245mm
Ce iling above
200mm
above
6. Piping diagrams
motor
fan
sensor2 flare nut
gas side
_____________________________________________________________________________________
- 108 -
1-Way Cassette
7. Wiring diagrams
CS
CN13
CN3
XS2 XP2
XS1 XP1
DM
GM
_____________________________________________________________________________________
- 109 -
1-Way Cassette
8. Velocity distribution
Airflow velocity
_____________________________________________________________________________________
- 110 -
1-Way Cassette
9. Electrical characteristic
Indoor Unit Power Supply IFM
Model
Hz Voltage Min. Max. MCA MFA KW FLA
YDS-28QC 60Hz 220V 198V 242V 0.3 5A 0.020 0.22
YDS-36QC 60Hz 220V 198V 242V 0.3 5A 0.020 0.22
YDS-45QC 60Hz 220V 198V 242V 0.6 5A 0.055 0.45
YDS-56QC 60Hz 220V 198V 242V 0.6 5A 0.055 0.45
1. 0m
Microphone
High airflow
Mid airflow
Low airflow
_____________________________________________________________________________________
- 111 -
1-Way Cassette
YDS-28,36QC YDS-45,56QC
Sound pressure level dB( 0dB=0.0002μ bar)
Octave band center frequency( Hz) Octave band center frequency( Hz)
_____________________________________________________________________________________
- 112 -
1-Way Cassette
12. Accessories
Standard accessories
Optional accessories
Number Item
1 Wired controller
2 Central controller
3 Network controller
_____________________________________________________________________________________
- 113 -
1-Way Cassette
PART NUMBER
ITEM NO PART NAME QTY REMARK
2.8 kW 3.6 kW
1 201M142090070 Panel ass'y 1
- 202M480200052 Motor ass'y 1
2 201M284100002 Base ass'y 1
3 201M280000052 Right cover ass'y 1
4 201M584040270 Evaporator ass'y 1
5 202M280000051 Foam ass'y 1
6 202M180200001 Insulation cover 1
7 201M280000060 Seal board ass'y 1
8 201M280000061 Cover plate ass'y 1
9 202M400600200 Drain pump 1
10 201M280000053 Partition board ass'y 1
11 202M480020050 Fan motor 1
12 202M280000050 Drainage pan ass'y 1
13 201M280000016 Separating board 1
14 201M280000007 Evaporator right cover 1
15 203M384090012 E-part box ass'y 1
- 201M280000068 E-part box 1
- 202M300900109 Transformer 1
- 201M385000007 Main controller ass'y 1
16 201M280000051 Left clapboard ass'y 1
17 201M280000008 Evaporator right cover 1
18 201M280000067 Water level switch holder 1
- 202M301310051 Water level sensor ass'y 1
19 201M280000057 Cover board 1
20 201M280000054 Motor bracket ass'y 1
21 201M180000011 Volute shell 2
_____________________________________________________________________________________
- 114 -
1-Way Cassette
_____________________________________________________________________________________
- 115 -
1-Way Cassette
PART NUMBER
ITEM NO PART NAME QTY REMARK
4.5 kW 5.6 kW
1 201M280200310 E-part box cover 1
2 201M280200013 E-part box joint board 1
3 201M609890068 201M684090106 Electric throttle ass'y 1
- 201M684290003 201M680090015 Connecting pipe ass'y 1
4 203M384290007 E-part box ass'y 1
- 202M300900109 Transformer 1
- 201M385000007 Main controller ass'y 1
- 202M301450042 Wire joint, 2p 1
- 202M301450125 Wire joint 1
5 201M280200309 Evaporate connect board 1
6 201M180200005 Pipe 1
7 201M180200006 Pipe 1
8 201M280200055 Motor cover ass'y 1
9 201M280200032 Cover board ass'y 1
10 201M280200060 Drainage pan cover ass'y 1
11 202M280200050 Drainage pan ass'y 1
12 201M584210230 201M584300140 Evaporator ass'y 1
13 201M280200053 Louver base ass'y 1
14 201M119890401 Panel 1
- 202M480200052 Motor ass'y 1
15 203M3550A1520 Remote controller 1
16 201M131390022 Remote controller holder ass'y 1
17 202M440500003 Room temp sensor ass'y 1
18 202M440500004 Temp.sensor ass'y 1
19 201M287000011 Bearing Fixing board 1
20 201M130000004 Bearing 1
_____________________________________________________________________________________
- 116 -
1-Way Cassette
_____________________________________________________________________________________
- 117 -
4-Way Cassette
___________________________________________________________________________________
- 118 -
4-Way Cassette
___________________________________________________________________________________
Contents
1. Features …………………………………………………………………………………………….……..…………120
2. Specifications……………………………………………………………………………………….….……………124
3. Capacity table…………………………………………………………………………………….…………………127
4. Dimensions………………………………………………………………………………………….……………….135
5. Service space…………………………………………………………………………………….………………….136
6. Wiring diagrams………………………………………………………………………………….…………………137
7. Electrical characteristic………………………………………………………………………….……………….139
8. Refrigerant system diagram…………………………………………………………………….………………139
9. Noise level…………………………………………………………………………………………………………….140
10. Velocity & temperature distribution………………………………………………………………………..142
11. Exploded view parts……………………………………………………………………………..………………143
- 119 -
4-Way Cassette
___________________________________________________________________________________
1. Feature
1.5) Adding digital tube displaying on the display board. LED can display the Error Code to make
the malfunction checking easier.
- 120 -
4-Way Cassette
___________________________________________________________________________________
1.6) Fresh air makes life healthier and more comfortable.
1.8) Ultra thin machine body to easy installation and maintenance: 2.8kW~8.0kW: 230mm,
9.0kW~11.2kW:300mm.
1.9) Different color panels for choose: White, Gray, Blue, Black
- 121 -
4-Way Cassette
___________________________________________________________________________________
1.11) More strengthening rib design around the panel, preventing the distortion for the panel.
1.12) New outlet frame design to make the phenomena of coagulation great improvement:
prevent the condensing water from damaging the air guide strip.
1.13) Adding rib on the panel of fan outlet, which can avoid the air outlet direct flow to people.
- 122 -
4-Way Cassette
___________________________________________________________________________________
1.14) 4 speeds available, optional super high fan speed design suitable for the large building over
3m high.
1.15) Reserve spaces for air side-outlet, it is available to connect duct pipe hence Air supplying
from the four sides to nearby small room.
1.16) Optimal design, smaller Control Box, Space saving and convenient for wiring,
Using fire resistance galvanized steel for E-box material. Metal box make the control part more
stable and prevent damaging
- 123 -
4-Way Cassette
___________________________________________________________________________________
2. Specifications
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB, and outdoor
temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB,
and equivalent ref. Piping: 8m (horizontal)
- 124 -
4-Way Cassette
___________________________________________________________________________________
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB,
19°CWB, and outdoor temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
- 125 -
4-Way Cassette
___________________________________________________________________________________
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB, and
outdoor temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
- 126 -
4-Way Cassette
___________________________________________________________________________________
3. Capacity table
- 127 -
4-Way Cassette
___________________________________________________________________________________
- 128 -
4-Way Cassette
___________________________________________________________________________________
- 129 -
4-Way Cassette
___________________________________________________________________________________
Indoor temperature(°CWB)
Outdoor
Indoor unit 14/20 16/23 18/26 19/27 20/28 22/30 24/32
temperatur
size (kW) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
e(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 18.20 10.20
12.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.90 10.00
14.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.80 10.00
16.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.50 9.80
18.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.10 9.60
20.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 16.80 9.40
21.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 16.50 9.30
23.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.40 10.20 16.40 9.20
14.0
25.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.20 10.10 16.20 9.10
27.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.10 10.00 16.10 9.20
29.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.00 9.90 16.00 9.10
31.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 15.80 9.80 15.40 8.80
33.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 15.70 9.70 15.40 8.80
35.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.70 9.70 15.10 9.40 15.10 8.80
37.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.60 9.60 15.10 9.40 15.00 8.70
39.0 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.30 9.40 14.60 9.20 15.00 8.80
- 130 -
4-Way Cassette
___________________________________________________________________________________
- 131 -
4-Way Cassette
___________________________________________________________________________________
- 132 -
4-Way Cassette
___________________________________________________________________________________
- 133 -
4-Way Cassette
___________________________________________________________________________________
- 134 -
4-Way Cassette
___________________________________________________________________________________
4 Dimensions
4.1 YDS-28-45GC
4.2 YDS-28-140KC
- 135 -
4-Way Cassette
___________________________________________________________________________________
5. Service Space
- 136 -
4-Way Cassette
___________________________________________________________________________________
6 Wiring diagram
6.1) YDS-28-45GC
- 137 -
4-Way Cassette
___________________________________________________________________________________
6.2) YDS-28-112KC
- 138 -
4-Way Cassette
___________________________________________________________________________________
7. Electrical characteristic
- 139 -
4-Way Cassette
___________________________________________________________________________________
9. Noise level
YDS-28,36GC/KC YDS-45,56GC/KC
- 140 -
4-Way Cassette
___________________________________________________________________________________
YDS-71,80KC YDS-45,56KC
- 141 -
4-Way Cassette
___________________________________________________________________________________
- 142 -
4-Way Cassette
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
2.8 kW 3.6 kW 4.5 kW
1 202M242400001 water collector 1
2 201M100110001 Centrifugal fan 1
3 201M242000402 Installation bracket 4
4 201M242000413 Evaporator fixing hanger 1
5 202M400410406 Motor 1
6 201M242000405 Motor base 1
7 201M242000401 Base ass'y 1
8 201M242000406 Board 1
9 201M242000411 Sealed board ass'y 1
10 203M384090008 E-part ass'y 1
- 202M301450125 201M140900018 Wire joint 1
11 201M242000407 E-Part box cover 1
12 201M242000409 Drain pump Holder 1
13 202M400600005 Drain pump 1
14 201M242000414 Right clapboard ass'y 1
15 201M242000404 Partition board 1
16 201M242000412 Evaporator fixing board ass'y 1
17 201M584090013 Evaporator ass'y 1
18 202M301300303 Temperature sensor 1
19 202M440500003 Room temp sensor ass'y 1
- 143 -
4-Way Cassette
___________________________________________________________________________________
20 202M300900109 Transformer 1
21 202M401190019 Motor capacitor 1
22 202M301310051 Water level sensor ass'y 1
23 201M384090002 Main controller ass'y 1
24 201M684090010 Connecting pipe ass'y 1
25 201M684090110 Electric throttle ass'y 1
26 203M3550A1520 Remote controller 1
- 201M131390022 Remote controller holder ass'y 1
27 201M142090078 Panel ass'y 1
28 202M400280001 Swing motor 1
29 203M342090008 Display board 1
- 144 -
4-Way Cassette
___________________________________________________________________________________
- 145 -
4-Way Cassette
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
2.8 kW 3.6 kW 4.5 kW
1 201M242800085 Electricity control box coping I 1
2 201M242800084 Electricity control box coping II 1
3 203M384090010 E-part box ass'y 1
- 201M242800091 E-part box 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 202M301310009 room temp sensor ass'y 1
- 201M385000000 Main controller ass'y 1
- 202M301450046 Wire joint,4p 1
- 202M301450044 Wire joint, 3p 2
4 201M142800075 Ring ass'y 1
5 202M242500075 Foam ass'y 1
6 201M142000003 Fan ass'y 1
7 201M242500082 Evaporator fixing board 1
8 201M584040340 201M584210350 Evaporator ass'y 1
- 201M584040133 201M542500076 Evaporator 1
- 201M684000003 201M684210223 Evaporator output pipe ass'y 1
- 201M684000001 201M684210220 Evaporator input pipe ass'y 1
- 201M600200001 Sleeve 1
9 201M242500079 Board ass'y 1
- 201M242500085 Hook 2
10 202M242500076 Foam ass'y 1
11 201M242500088 Board ass'y 1
12 202M400420012 Motor 1
13 201M242500080 Base 1
14 201M242500081 Clamp board 1
15 201M109990000 Panel 1
- 202M400100007 Stepper motor 2
- 203M342890005 Display control box ass'y 2
16 201M242800082 Wire clamp 1
17 201M102020216 Wire clip 1
18 201M242500083 Evaporator fixing hanger 3
19 201M242500084 Water pump board 1
20 202M400600200 Drain pump 1
21 201M242000003 Water Pump installation bracket ass'y 1
22 201M242500089 Board ass'y 1
23 201M242000013 Water pipe clamp 1
24 201M242000008 fan clip 1
25 201M242800092 Water cover ass'y 1
26 201M242500078 Board ass'y 1
- 201M242500085 Hook 2
27 201M142000002 water pipe 1
28 201M242800078 Sealed board ass'y 1
29 202M742000002 pump Rubber washer 3
30 203M3550A1500 Wireless remote,R91 HP,York brand,White 1
31 201M155090070 Remote holder,R91,York brand,White 1
32 202M301300303 Evaporator temp. sensor 1
33 202M401100353 Motor capacitor 1
- 146 -
4-Way Cassette
___________________________________________________________________________________
- 147 -
4-Way Cassette
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
5.6 kW 7.1 kW 8.0 kW
1 201M242800085 Electricity control box coping I 1
2 201M242800084 Electricity control box coping II 1
3 203M384090010 E-part box ass'y 1
- 201M242800091 E-part box 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 202M301310009 room temp sensor ass'y 1
- 201M385000000 Main controller ass'y 1
- 202M301450046 Wire joint,4p 1
- 202M301450044 Wire joint, 3p 2
4 201M142800075 Ring ass'y 1
5 202M242500075 Foam ass'y 1
6 201M142000003 Fan ass'y 1
7 201M242500082 Evaporator fixing board 1
8 201M584300270 Evaporator ass'y 1
- 201M542500076 Evaporator 1
- 201M684090303 Evaporator distributor ass'y 1
- 201M642090102 Evaporator distributor 1
- 201M600200001 Sleeve 1
9 201M242500079 Board ass'y 1
- 201M242500085 Hook 2
10 202M242500076 Foam ass'y 1
11 201M242500088 Board ass'y 1
12 202M400420012 202M400400490 Motor 1
13 201M242500080 Base 1
14 201M242500081 Clamp board 1
15 201M109990000 Panel 1
- 202M400100007 Stepper motor 2
- 203M342890005 Display control box ass'y 1
16 201M242800082 Wire clamp 1
17 201M102020216 Wire clip 1
18 201M242500083 Evaporator fixing hanger 3
19 201M242500084 Water pump board 1
20 202M400600200 Drain pump 1
21 201M242000003 Water Pump installation bracket ass'y 1
22 201M242500089 Board ass'y 1
23 201M242000013 Water pipe clamp 1
24 201M242000008 fan clip 1
25 201M242800092 Water cover ass'y 1
26 201M242500078 Board ass'y 1
- 201M242500085 Hook 2
27 201M142000002 water pipe 1
28 201M242800078 Sealed board ass'y 1
29 202M742000002 pump Rubber washer 3
30 203M3550A1500 Wireless remote,R91 HP,York brand,White 1
31 201M155090070 Remote holder,R91,York brand,White 1
32 202M301300303 Evaporator temp. sensor 1
33 202M401100353 202M401100354 Motor capacitor 1
- 148 -
4-Way Cassette
___________________________________________________________________________________
- 149 -
4-Way Cassette
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
9.0 kW 11.2 kW 14.0 kW
1 201M242800085 Electricity control box coping I 1
2 201M242800084 Electricity control box coping II 1
3 203M384090010 203M342990001 E-part box ass'y 1
- 201M242800091 201M242990001 E-part box 1
- 202M300900109 202M300900204 Transformer (TT2-B35+D90-1F) 1
- 202M301310009 room temp sensor ass'y 1
- 201M385000000 Main controller ass'y 1
- 202M301450046 Wire joint,4p 1
- 202M301450044 Wire joint, 3p 2
4 201M142800075 201M142990001 Ring ass'y 1
5 202M242800075 202M242990001 Foam ass'y 1
6 201M142000601 Fan ass'y 1
7 201M242800086 201M242990006 Evaporator fixing board 1
8 201M584500180 201M542990001 Evaporator ass'y 1
- 201M542800076 201M542990002 Evaporator 1
- 201M684090302 201M642990006 Evaporator Outlet pipe ass'y 1
- 201M684090300 201M642990001 Evaporator distributor ass'y 1
- 201M600200001 Sleeve 1
9 201M242800080 Board ass'y 1
- 201M242500085 Hook 2
10 202M242800076 202M242990002 Foam ass'y 1
11 201M242800093 201M242990007 Board ass'y 1
12 202M400420903 202M400400290 Motor 1
13 201M242800081 201M242990009 Base 1
14 201M242500081 Clamp board 1
15 201M109990000 Panel 1
- 202M400100007 Stepper motor 2
- 203M342890005 Display control box ass'y 1
16 201M242800082 Wire clamp 1
17 201M102020216 Wire clip 1
18 201M242800087 201M242990005 Evaporator fixing hanger 3
19 201M242800088 201M155060801 Water pump board 1
20 202M400600200 Drain pump 1
21 201M242000605 201M242990003 Water Pump installation bracket ass'y 1
22 201M242800094 Board ass'y 1
23 201M242000013 Water pipe clamp 1
24 201M242000008 fan clip 1
25 201M242800092 Water cover ass'y 1
26 201M242800079 201M284600001 Board ass'y 1
- 201M242500085 Hook 2
27 201M142000002 water pipe 1
28 201M242800078 201M242990008 Sealed board ass'y 1
29 202M742000002 pump Rubber washer 3
30 203M3550A1500 Wireless remote,R91 HP,York brand,White 1
31 201M155090070 Remote holder,R91,York brand,White 1
32 202M301300303 Evaporator temp. sensor 1
33 202M401100354 202M401100407 Motor capacitor 1
- 150 -
Wall mount
- 151 -
Wall mount
Contents
1. Features …………………………………………………………………………………………………..………………153
2. Specifications…………………………………………………………………………………………………………….154
3. Capacity table……………………………………………………………………………………………………………155
4. Dimensions……………………………………………………………………………………………………………….159
5. Piping diagram…………………………………………………………………………………………………………..159
6. Wiring diagrams…………………………………………………………………………………………………………160
7. Sound level………………………………………………………………………………………………………………..161
8. Velocity & temperature distribution……………………………………………………………………….…....162
9. Electrical characteristic…….…………………………………………………………………………………………162
10. Exploded view parts…………………………………………………………………………….……………………163
- 152 -
Wall mount
1. Features
1. LED display.
2. Big and small panels have different colors for choose: white and brown for big panel, blue
and brown for small panel, and the other colors can be customized according to the customers’
demands.
3. Built-in the electronic throttle kit.
4. Multi-refrigerant outlet pipe method: left\right\rear, satisfy the need of different rooms.
5. Adopt new type installation plate, easy for installation and stable.
6. Reserved the socket on main control board for water pump and PCB can be customized if
you need water pump function.
7. Three air flow speed: high, middle and low, double air guides.
8. Low noise, creates quite and comfortable environment.
9. Air cleaning equipment and the high efficiency filter, keep the air fresh.
- 153 -
Wall mount
2. Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
- 154 -
Wall mount
3. Capacity table
3.1) Cooling TC: total capacity SHC: sensible capacity
Indoor temperature (oWB)
Outdoor
Indoor Unit 14 16 18 19 20 22 24
temperature 0C
size (KW) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
Db
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.90 1.70
12 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.80 1.60
14 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.80 1.60
16 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.80 1.60
18 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.80 1.60
20 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.70 1.50
21 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.60 1.70 2.70 1.50
23 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.50 1.60 2.70 1.50
2.2
25 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.50 1.60 2.60 1.50
27 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.50 1.60 2.60 1.50
29 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.40 1.50 2.50 1.50
31 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.40 1.50 2.50 1.50
33 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.40 1.50 2.40 1.50
35 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.30 1.50 2.40 1.50
37 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.30 1.70 2.30 1.50 2.30 1.50
39 1.50 1.40 1.80 1.50 2.10 1.60 2.20 1.60 2.20 1.60 2.30 1.50 2.30 1.50
10 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.70 2.10
12 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.10
14 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.10
16 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.60 2.00
18 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.50 2.00
20 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.40 1.90
21 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.30 2.10 3.40 1.90
23 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.10 3.40 1.90
2.8
25 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.00 3.30 1.90
27 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.20 2.00 3.30 1.90
29 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.20 1.90
31 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.20 1.90
33 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.20 3.10 2.00 3.10 2.00
35 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.10 2.90 1.90 3.10 2.00
37 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.90 2.10 2.90 1.90 2.90 1.90
39 1.90 1.80 2.30 1.90 2.70 2.00 2.80 2.00 2.80 2.00 2.90 1.90 2.90 1.90
10 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.80 2.80
12 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.60 2.70
14 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.60 2.70
16 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.50 2.70
18 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.50 2.70
20 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
21 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
23 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.20 2.80 4.40 2.70
3.6
25 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.10 2.70 4.20 2.60
27 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.10 2.70 4.20 2.60
29 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.10 2.50
31 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.10 2.40
33 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.90 2.70 4.00 2.60 4.00 2.40
35 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.60 4.00 2.40
37 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.60 3.90 2.30
39 2.40 2.20 3.00 2.50 3.30 2.70 3.60 2.70 3.70 2.60 3.90 2.70 3.90 2.40
- 155 -
Wall mount
- 156 -
Wall mount
Indoor temperature 0C DB
Indoor Unit Outdoor temperature 14 16 18 20 22 24
size (KW) TC TC TC TC TC TC
0 CDB CWB
0 kW kW kW kW kW kW
-15 -14.7 1.64 1.64 1.64 1.64 1.64 1.64
-13 -12.6 1.74 1.74 1.74 1.74 1.74 1.74
-11 -10.5 1.82 1.82 1.82 1.82 1.82 1.82
-10 -9.5 1.90 1.90 1.90 1.90 1.90 1.90
-9.1 -8.5 1.95 1.95 1.95 1.95 1.95 1.95
-7.6 -7 1.98 1.98 1.98 1.98 1.98 1.98
-5.6 -5 2.05 2.05 2.05 2.05 2.05 2.05
-3.7 -3 2.16 2.16 2.16 2.16 2.16 2.16
2.2
-0.7 0 2.31 2.31 2.31 2.31 2.31 2.18
2.2 3 2.44 2.44 2.44 2.44 2.39 2.18
4.1 5 2.52 2.52 2.52 2.52 2.39 2.18
6 7 2.60 2.60 2.60 2.52 2.39 2.18
7.9 9 2.68 2.68 2.93 2.52 2.39 2.18
9.8 11 2.76 2.76 2.60 2.52 2.39 2.18
11.8 13 2.86 2.81 2.60 2.52 2.39 2.18
13.7 15 2.94 2.81 2.60 2.52 2.39 2.18
-15 -14.7 2.02 2.02 2.02 2.02 2.02 2.02
-13 -12.6 2.14 2.14 2.14 2.14 2.14 2.14
-11 -10.5 2.24 2.24 2.24 2.24 2.24 2.24
-10 -9.5 2.34 2.34 2.34 2.34 2.34 2.34
-9.1 -8.5 2.40 2.40 2.40 2.40 2.40 2.40
-7.6 -7 2.43 2.43 2.43 2.43 2.43 2.43
-5.6 -5 2.53 2.53 2.53 2.53 2.53 2.53
-3.7 -3 2.66 2.66 2.66 2.66 2.66 2.66
2.8
-0.7 0 2.85 2.85 2.85 2.85 2.85 2.69
2.2 3 3.01 3.01 3.01 3.01 2.94 2.69
4.1 5 3.10 3.10 3.10 3.10 2.94 2.69
6 7 3.20 3.20 3.20 3.10 2.94 2.69
7.9 9 3.30 3.30 2.93 3.10 2.94 2.69
9.8 11 3.39 3.39 3.20 3.10 2.94 2.69
11.8 13 3.52 3.46 3.20 3.10 2.94 2.69
13.7 15 3.62 3.46 3.20 3.10 2.94 2.69
-15 -14.7 2.52 2.52 2.52 2.52 2.52 2.52
-13 -12.6 2.68 2.68 2.68 2.68 2.68 2.68
-11 -10.5 2.80 2.80 2.80 2.80 2.80 2.80
-10 -9.5 2.92 2.92 2.92 2.92 2.92 2.92
-9.1 -8.5 3.00 3.00 3.00 3.00 3.00 3.00
-7.6 -7 3.04 3.04 3.04 3.04 3.04 3.04
-5.6 -5 3.16 3.16 3.16 3.16 3.16 3.16
-3.7 -3 3.32 3.32 3.32 3.32 3.32 3.32
3.6
-0.7 0 3.56 3.56 3.56 3.56 3.56 3.36
2.2 3 3.76 3.76 3.76 3.76 3.68 3.36
4.1 5 3.88 3.88 3.88 3.88 3.68 3.36
6 7 4.00 4.00 4.00 3.88 3.68 3.36
7.9 9 4.12 4.12 2.93 3.88 3.68 3.36
9.8 11 4.24 4.24 4.00 3.88 3.68 3.36
11.8 13 4.40 4.32 4.00 3.88 3.68 3.36
13.7 15 4.52 4.32 4.00 3.88 3.68 3.36
- 157 -
Wall mount
Indoor temperature 0C DB
Indoor Unit Outdoor temperature 14 16 18 20 22 24
size (KW) TC TC TC TC TC TC
0 CDB CWB
0 kW kW kW kW kW kW
-15 -14.7 3.15 3.15 3.15 3.15 3.15 3.15
-13 -12.6 3.35 3.35 3.35 3.35 3.35 3.35
-11 -10.5 3.50 3.50 3.50 3.50 3.50 3.50
-10 -9.5 3.65 3.65 3.65 3.65 3.65 3.65
-9.1 -8.5 3.75 3.75 3.75 3.75 3.75 3.75
-7.6 -7 3.80 3.80 3.80 3.80 3.80 3.80
-5.6 -5 3.95 3.95 3.95 3.95 3.95 3.95
-3.7 -3 4.15 4.15 4.15 4.15 4.15 4.15
4.5
-0.7 0 4.45 4.45 4.45 4.45 4.45 4.20
2.2 3 4.70 4.70 4.70 4.70 4.60 4.20
4.1 5 4.85 4.85 4.85 4.85 4.60 4.20
6 7 5.00 5.00 5.00 4.85 4.60 4.20
7.9 9 5.15 5.15 2.93 4.85 4.60 4.20
9.8 11 5.30 5.30 5.00 4.85 4.60 4.20
11.8 13 5.50 5.40 5.00 4.85 4.60 4.20
13.7 15 5.65 5.40 5.00 4.85 4.60 4.20
-15 -14.7 3.97 3.97 3.97 3.97 3.97 3.97
-13 -12.6 4.22 4.22 4.22 4.22 4.22 4.22
-11 -10.5 4.41 4.41 4.41 4.41 4.41 4.41
-10 -9.5 4.60 4.60 4.60 4.60 4.60 4.60
-9.1 -8.5 4.73 4.73 4.73 4.73 4.73 4.73
-7.6 -7 4.79 4.79 4.79 4.79 4.79 4.79
-5.6 -5 4.98 4.98 4.98 4.98 4.98 4.98
-3.7 -3 5.23 5.23 5.23 5.23 5.23 5.23
5.6
-0.7 0 5.61 5.61 5.61 5.61 5.61 5.29
2.2 3 5.92 5.92 5.92 5.92 5.80 5.29
4.1 5 6.11 6.11 6.11 6.11 5.80 5.29
6 7 6.30 6.30 6.30 6.11 5.80 5.29
7.9 9 6.49 6.49 2.93 6.11 5.80 5.29
9.8 11 6.68 6.68 6.30 6.11 5.80 5.29
11.8 13 6.93 6.80 6.30 6.11 5.80 5.29
13.7 15 7.12 6.80 6.30 6.11 5.80 5.29
- 158 -
Wall mount
4. Dimensions
YDS-22-56HC
5. Piping Diagrams
YDS-22-56HC
- 159 -
Wall mount
6. Wiring diagrams
YDS-22-56HC
- 160 -
Wall mount
7. Sound level
YDS-22-36HC YDS-45-56HC
- 161 -
Wall mount
Temperature
9. Electrical characteristic
- 162 -
Wall mount
PART NUMBER
ITEM NO PART NAME QTY REMARK
2.2 kW 2.8 kW 3.6 kW
1 201M187090020 Filter 2
2 202M486150220 Coil temp sensor 1
3 201M587090005 Evaporator 3
4 201M287090024 Evaporator right joint board 1
5 201M387090022 Display board ass'y 1
6 202M400400072 Motor 1
7 201M287090018 Motor plate 2
8 203M387090021 E-part box ass'y 1
- 201M187090027 Electric control box holder 1
- 201M287090021 Electric control box side board ass'y 1
- 201M287090020 Electric control box soleplate 1
- 201M287090019 E-Part box cover 1
- 201M387090027 dial code switch board ass'y 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 202M301450119 Wire joint, 5p 1
- 201M387090029 Main controller ass'y 1
- 202M401100006 Motor capacitor 1
- 202M301450134 Wire joint, 3p 1
- 163 -
Wall mount
- 202M432390005 room temp sensor ass'y 1
9 201M187090021 Air outlet ass'y 1
10 201M187090019 Top air deflector 1
11 201M187090018 Below air deflector 1
12 201M187090015 panel 1
13 201M187090016 Panel 1
14 202M400200028 Stepper motor 1
15 201M187090017 screw cover 3
16 201M687090057 Outlet pipe ass'y 1
- 202M441200200 Coil temperature sensor 1
17 201M287090017 Pipe clamp 1
18 201M187090022 Frame 1
19 201M187090036 Drainage pan 1
20 202M730100201 Bearing base 1
21 201M287090023 Evaporator connection board 1
22 201M687090063 Inlet pipe ass'y 1
23 201M187090023 Base ass'y 1
24 201M100200024 Cross fan 1
25 201M130490002 Sensor block 1
26 203M3550A1520 Remote controller 1
27 201M155090070 Remote holder,R91,York brand,White 1
- 164 -
Wall mount
PART NUMBER
ITEM NO PART NAME QTY REMARK
4.5 kW 5.6 kW
1 201M187090033 Filter 2
2 202M486150220 Coil temp sensor 1
3 201M587090012 Evaporator 2
4 201M287090027 Evaporator right joint board 1
5 201M387090022 Display board ass'y 1
6 202M400400062 Motor 1
7 201M287090025 Motor plate 2
8 203M387090021 E-part box ass'y 1
- 201M187090027 Electric control box holder 1
- 201M287090021 Electric control box side board ass'y 1
- 201M287090020 Electric control box soleplate 1
- 201M287090019 E-Part box cover 1
- 201M387090027 dial code switch board ass'y 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 202M301450119 Wire joint, 5p 1
- 201M387090029 Main controller ass'y 1
- 202M401100006 Motor capacitor 1
- 202M301450134 Wire joint, 3p 1
- 165 -
Wall mount
- 202M432390005 room temp sensor ass'y 1
9 201M187090028 Air outlet ass'y 1
10 201M187090032 Top air deflector 1
11 201M187090031 Below air deflector 1
12 201M187090029 panel 1
13 201M187090030 Panel ass'y 1
14 202M400200028 Stepper motor 1
15 201M187090017 screw cover 3
16 201M687090090 201M687090081 Outlet pipe ass'y 1
- 202M441200200 Coil temperature sensor 1
17 201M287090017 Pipe clamp 1
18 201M187090034 Frame 1
19 201M187090036 Drainage pan 1
20 202M730100201 Bearing base 1
21 201M287090026 Evaporator connection board 1
22 201M687090091 201M687090072 Inlet pipe ass'y 1
23 201M187090035 Base ass'y 1
24 201M100200025 Cross fan 1
25 201M130490002 Sensor block 1
26 201M587090027 Evaporator 1
27 203M3550A1520 Remote controller 1
28 201M131390022 Remote holder,R51,York brand,White 1
- 166 -
Floor ceiling
___________________________________________________________________________________
- 167 -
Floor ceiling
___________________________________________________________________________________
Contents
1. Features…………………………………………………………………………………………………………………….169
2. Specifications…………………………………………………………………………………………………………….171
3. Capacity table………………………………………………….…………………………………………………………173
4. Dimensions……………………………………………………………………………………………..………………..179
5. Wiring diagrams…………………………………………………………..…………………………………………….180
6. Refrigerant system diagrams …………………………………………………………………………..………….181
7. Noise level ………………………………………………………………………………..………………………………181
8. Velocity & temperature distribution…………………………………..……………………………..….………183
9. Functional part & safety device……………………………………………………………………………………185
10. Exploded view parts………………………………………………………………………………………………….186
- 168 -
Floor ceiling
___________________________________________________________________________________
1 Feature
- 169 -
Floor ceiling
___________________________________________________________________________________
- 170 -
Floor ceiling
___________________________________________________________________________________
2 Specifications
Floor Ceiling YDS-36-112FC16IA/IB R-410A 60Hz
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
- 171 -
Floor ceiling
___________________________________________________________________________________
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
- 172 -
Floor ceiling
___________________________________________________________________________________
3 Capacity table
3.1) Cooling TC: total capacity SHC: sensible capacity
- 173 -
Floor ceiling
___________________________________________________________________________________
- 174 -
Floor ceiling
___________________________________________________________________________________
- 175 -
Floor ceiling
___________________________________________________________________________________
Indoor temperature 0C DB
Indoor Unit Outdoor temperature 16 18 20 21 22 24
size (KW) TC TC TC TC TC TC
CDB
0 0CWB kW kW kW kW kW kW
-15 -14.7 2.52 2.52 2.52 2.52 2.52 2.52
-13 -12.6 2.68 2.68 2.68 2.68 2.68 2.68
-11 -10.5 2.80 2.80 2.80 2.80 2.80 2.80
-10 -9.5 2.92 2.92 2.92 2.92 2.92 2.92
-9.1 -8.5 3.00 3.00 3.00 3.00 3.00 3.00
-7.6 -7 3.04 3.04 3.04 3.04 3.04 3.04
-5.6 -5 3.16 3.16 3.16 3.16 3.16 3.16
-3.7 -3 3.32 3.32 3.32 3.32 3.32 3.32
3.6
-0.7 0 3.56 3.56 3.56 3.56 3.56 3.36
2.2 3 3.76 3.76 3.76 3.76 3.68 3.36
4.1 5 3.88 3.88 3.88 3.88 3.68 3.36
6 7 4.00 4.00 4.00 3.88 3.68 3.36
7.9 9 4.12 4.12 2.93 3.88 3.68 3.36
9.8 11 4.24 4.24 4.00 3.88 3.68 3.36
11.8 13 4.40 4.32 4.00 3.88 3.68 3.36
13.7 15 4.52 4.32 4.00 3.88 3.68 3.36
-15 -14.7 3.15 3.15 3.15 3.15 3.15 3.15
-13 -12.6 3.35 3.35 3.35 3.35 3.35 3.35
-11 -10.5 3.50 3.50 3.50 3.50 3.50 3.50
-10 -9.5 3.65 3.65 3.65 3.65 3.65 3.65
-9.1 -8.5 3.75 3.75 3.75 3.75 3.75 3.75
-7.6 -7 3.80 3.80 3.80 3.80 3.80 3.80
-5.6 -5 3.95 3.95 3.95 3.95 3.95 3.95
-3.7 -3 4.15 4.15 4.15 4.15 4.15 4.15
4.5
-0.7 0 4.45 4.45 4.45 4.45 4.45 4.20
2.2 3 4.70 4.70 4.70 4.70 4.60 4.20
4.1 5 4.85 4.85 4.85 4.85 4.60 4.20
6 7 5.00 5.00 5.00 4.85 4.60 4.20
7.9 9 5.15 5.15 2.93 4.85 4.60 4.20
9.8 11 5.30 5.30 5.00 4.85 4.60 4.20
11.8 13 5.50 5.40 5.00 4.85 4.60 4.20
13.7 15 5.65 5.40 5.00 4.85 4.60 4.20
-15 -14.7 3.97 3.97 3.97 3.97 3.97 3.97
-13 -12.6 4.22 4.22 4.22 4.22 4.22 4.22
-11 -10.5 4.41 4.41 4.41 4.41 4.41 4.41
-10 -9.5 4.60 4.60 4.60 4.60 4.60 4.60
-9.1 -8.5 4.73 4.73 4.73 4.73 4.73 4.73
-7.6 -7 4.79 4.79 4.79 4.79 4.79 4.79
-5.6 -5 4.98 4.98 4.98 4.98 4.98 4.98
-3.7 -3 5.23 5.23 5.23 5.23 5.23 5.23
5.6
-0.7 0 5.61 5.61 5.61 5.61 5.61 5.29
2.2 3 5.92 5.92 5.92 5.92 5.80 5.29
4.1 5 6.11 6.11 6.11 6.11 5.80 5.29
6 7 6.30 6.30 6.30 6.11 5.80 5.29
7.9 9 6.49 6.49 2.93 6.11 5.80 5.29
9.8 11 6.68 6.68 6.30 6.11 5.80 5.29
11.8 13 6.93 6.80 6.30 6.11 5.80 5.29
13.7 15 7.12 6.80 6.30 6.11 5.80 5.29
- 176 -
Floor ceiling
___________________________________________________________________________________
Indoor temperature 0C DB
Indoor Unit Outdoor temperature 16 18 20 21 22 24
size (KW) TC TC TC TC TC TC
CDB
0 0CWB kW kW kW kW kW kW
-15 -14.7 5.04 5.04 5.04 5.04 5.04 5.04
-13 -12.6 5.36 5.36 5.36 5.36 5.36 5.36
-11 -10.5 5.60 5.60 5.60 5.60 5.60 5.60
-10 -9.5 5.84 5.84 5.84 5.84 5.84 5.84
-9.1 -8.5 6.00 6.00 6.00 6.00 6.00 6.00
-7.6 -7 6.08 6.08 6.08 6.08 6.08 6.08
-5.6 -5 6.32 6.32 6.32 6.32 6.32 6.32
-3.7 -3 6.64 6.64 6.64 6.64 6.64 6.64
7.1
-0.7 0 7.12 7.12 7.12 7.12 7.12 6.72
2.2 3 7.52 7.52 7.52 7.52 7.36 6.72
4.1 5 7.76 7.76 7.76 7.76 7.36 6.72
6 7 8.00 8.00 8.00 7.76 7.36 6.72
7.9 9 8.24 8.24 2.93 7.76 7.36 6.72
9.8 11 8.48 8.48 8.00 7.76 7.36 6.72
11.8 13 8.80 8.64 8.00 7.76 7.36 6.72
13.7 15 9.04 8.64 8.00 7.76 7.36 6.72
-15 -14.7 5.67 5.67 5.67 5.67 5.67 5.67
-13 -12.6 6.03 6.03 6.03 6.03 6.03 6.03
-11 -10.5 6.30 6.30 6.30 6.30 6.30 6.30
-10 -9.5 6.57 6.57 6.57 6.57 6.57 6.57
-9.1 -8.5 6.75 6.75 6.75 6.75 6.75 6.75
-7.6 -7 6.84 6.84 6.84 6.84 6.84 6.84
-5.6 -5 7.11 7.11 7.11 7.11 7.11 7.11
-3.7 -3 7.47 7.47 7.47 7.47 7.47 7.47
8
-0.7 0 8.01 8.01 8.01 8.01 8.01 7.56
2.2 3 8.46 8.46 8.46 8.46 8.28 7.56
4.1 5 8.73 8.73 8.73 8.73 8.28 7.56
6 7 9.00 9.00 9.00 8.73 8.28 7.56
7.9 9 9.27 9.27 2.93 8.73 8.28 7.56
9.8 11 9.54 9.54 9.00 8.73 8.28 7.56
11.8 13 9.90 9.72 9.00 8.73 8.28 7.56
13.7 15 10.17 9.72 9.00 8.73 8.28 7.56
-15 -14.7 6.30 6.30 6.30 6.30 6.30 6.30
-13 -12.6 6.70 6.70 6.70 6.70 6.70 6.70
-11 -10.5 7.00 7.00 7.00 7.00 7.00 7.00
-10 -9.5 7.30 7.30 7.30 7.30 7.30 7.30
-9.1 -8.5 7.50 7.50 7.50 7.50 7.50 7.50
-7.6 -7 7.60 7.60 7.60 7.60 7.60 7.60
-5.6 -5 7.90 7.90 7.90 7.90 7.90 7.90
-3.7 -3 8.30 8.30 8.30 8.30 8.30 8.30
9
-0.7 0 8.90 8.90 8.90 8.90 8.90 8.40
2.2 3 9.40 9.40 9.40 9.40 9.20 8.40
4.1 5 9.70 9.70 9.70 9.70 9.20 8.40
6 7 10.00 10.00 10.00 9.70 9.20 8.40
7.9 9 10.30 10.30 2.93 9.70 9.20 8.40
9.8 11 10.60 10.60 10.00 9.70 9.20 8.40
11.8 13 11.00 10.80 10.00 9.70 9.20 8.40
13.7 15 11.30 10.80 10.00 9.70 9.20 8.40
- 177 -
Floor ceiling
___________________________________________________________________________________
Indoor temperature 0C DB
Indoor Unit Outdoor temperature 16 18 20 21 22 24
size (KW) TC TC TC TC TC TC
CDB
0 0CWB kW kW kW kW kW kW
-15 -14.7 7.88 7.88 7.88 7.88 7.88 7.88
-13 -12.6 8.38 8.38 8.38 8.38 8.38 8.38
-11 -10.5 8.75 8.75 8.75 8.75 8.75 8.75
-10 -9.5 9.13 9.13 9.13 9.13 9.13 9.13
-9.1 -8.5 9.38 9.38 9.38 9.38 9.38 9.38
-7.6 -7 9.50 9.50 9.50 9.50 9.50 9.50
-5.6 -5 9.88 9.88 9.88 9.88 9.88 9.88
-3.7 -3 10.38 10.38 10.38 10.38 10.38 10.38
11.2
-0.7 0 11.13 11.13 11.13 11.13 11.13 10.50
2.2 3 11.75 11.75 11.75 11.75 11.50 10.50
4.1 5 12.13 12.13 12.13 12.13 11.50 10.50
6 7 12.50 12.50 12.50 12.13 11.50 10.50
7.9 9 12.88 12.88 2.93 12.13 11.50 10.50
9.8 11 13.25 13.25 12.50 12.13 11.50 10.50
11.8 13 13.75 13.50 12.50 12.13 11.50 10.50
13.7 15 14.13 13.50 12.50 12.13 11.50 10.50
-15 -14.7 9.45 9.45 9.45 9.45 9.45 9.45
-13 -12.6 10.05 10.05 10.05 10.05 10.05 10.05
-11 -10.5 10.50 10.50 10.50 10.50 10.50 10.50
-10 -9.5 10.95 10.95 10.95 10.95 10.95 10.95
-9.1 -8.5 11.25 11.25 11.25 11.25 11.25 11.25
-7.6 -7 11.40 11.40 11.40 11.40 11.40 11.40
-5.6 -5 11.85 11.85 11.85 11.85 11.85 11.85
-3.7 -3 12.45 12.45 12.45 12.45 12.45 12.45
14
-0.7 0 13.35 13.35 13.35 13.35 13.35 12.60
2.2 3 14.10 14.10 14.10 14.10 13.80 12.60
4.1 5 14.55 14.55 14.55 14.55 13.80 12.60
6 7 15.00 15.00 15.00 14.55 13.80 12.60
7.9 9 15.45 15.45 15.00 14.55 13.80 12.60
9.8 11 15.90 15.90 15.00 14.55 13.80 12.60
11.8 13 16.50 16.20 15.00 14.55 13.80 12.60
13.7 15 16.95 16.20 15.00 14.55 13.80 12.60
- 178 -
Floor ceiling
___________________________________________________________________________________
4. Dimension
YDS-36-140FC
Ceiling installation
Capacity (KW) A B C D E F G
3.6~7.1 990 660 206 505 506 907 200
8.0-9.0 1280 660 206 795 506 1195 200
11.2- 14.0 1670 680 244 1070 450 1542 200
- 179 -
Floor ceiling
___________________________________________________________________________________
5. Wiring diagrams
YDS-36-140FC
- 180 -
Floor ceiling
___________________________________________________________________________________
YDS-36-140FC
7. Noise level
7.1) Test condition
- 181 -
Floor ceiling
___________________________________________________________________________________
7.2) Noise spectrums
YDS-36-56FC
Ceiling Floor
YDS-71-140FC
Ceiling Floor
- 182 -
Floor ceiling
___________________________________________________________________________________
7.3) Noise level
- 183 -
Floor ceiling
___________________________________________________________________________________
Floor Discharge angle 60°C
- 184 -
Floor ceiling
___________________________________________________________________________________
9. Electrical characteristic
Remark:
MCA: Min. Current Amps. (A)
MFA: Max. Fuse Amps. (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps. (A)
IFM: Indoor Fan Motor
- 185 -
Floor ceiling
___________________________________________________________________________________
- 186 -
Floor ceiling
___________________________________________________________________________________
12 202M244290003 foam ass'y 1
13 201M144290008 Right cover 1
14 201M244290013 installation board 1
15 201M144290005 Rear cover 1
16 201M244290024 Base ass'y 1
17 201M244290003 Evaporator right clapboard 1
18 201M244290014 installation board 1
19 201M144290009 Left cover 1
20 201M580590005 201M580590029 201M580590002 Evaporator ass'y 1
- 201M544090001 201M544290002 Evaporator 1
- 201M680590044 201M680590095 201M680590011 Evaporator intput pipe ass'y 1
- 201M600900040 Strainer 2
- 201M601300032 Electronic expansion valve 1
- 201M600320000 201M600320001 Copper nut, TLM-A01 1
- 201M644090000 201M680590091 201M644290000 Evaporator Outlet pipe ass'y 1
21 201M244290015 Installation clamp 2
22 201M244290004 Evaporator left clapboard 1
23 202M244290004 Foam ass'y 1
24 201M144290016 Display box 1
25 201M344290002 Display board ass'y 1
26 201M144290017 Manual button 1
27 201M244290017 Evaporator left clapboard 1
28 201M144290000 Air outlet ass'y 1
- 202M400200101 Stepper motor 1
- 202M400200100 Stepper motor(vertical) 1
29 201M144290041 Panel ass'y 1
30 201M144290012 Grille clamp 2
31 201M244290000 Grille strengthening rib 1
32 201M144290007 grille Clamp 1
33 201M144290003 grille 1
34 201M144290004 Filter 2
35 201M244290001 grille Clamp 2
36 201M280200006 motor clamp 1
37 201M144290015 Plastic fan 2
38 201M244290023 Drainage pan holder 2
39 201M601320018 EEV solenoid 1
40 203M3550A1510 Wireless remote,R92 HP, White 1
41 201M155090070 Remote holder,R91,York brand, White 1
42 202M440500003 Room temp sensor ass'y 1
43 202M301300133 Coil temp. sensor ass'y 1
44 202M440500002 Evaporator temp. sensorr Ass'y 1
- 187 -
Floor ceiling
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
8.0 kW 9.0 kW
1 201M144490004 Filter 3
2 201M244290001 grille Clamp 2
3 201M144490006 grille 1
4 201M144290012 Grille clamp 2
5 201M244490004 Grille strengthening rib 1
6 201M144290033 Volute shell 3
7 201M144290007 grille Clamp 2
8 201M144290015 Plastic fan 3
9 201M280200006 motor clamp 1
10 201M280200005 motor clamp 1
11 201M144290032 Volute shell 3
12 201M280200007 board 1
13 201M244490001 beam 1
14 201M244290010 E-part box cover 1
15 203M380590004 E-part box ass'y 1
- 201M244290016 E-Part box 1
- 188 -
Floor ceiling
___________________________________________________________________________________
- 202M401100354 Motor capacitor 1
- 201M380590000 Main controller ass'y 1
- 202M300900552 Transformer 1
- 202M301450125 Terminal block JX0-B6-D 1
- 202M301450042 Wire joint, 2p 1
16 201M144290009 Left cover 1
17 201M244290014 installation board 1
18 201M244490006 Base ass'y 1
19 201M144490001 Rear cover 1
20 201M580590003 Evaporator ass'y 1
- 201M601300032 Electronic expansion valve 1
- 201M601320018 EEV solenoid 1
21 201M244290013 installation board 1
22 202M244490003 foam ass'y 1
23 202M244290004 Foam ass'y 1
24 201M244290017 Evaporator left clapboard 1
25 202M244290005 foam ass'y 1
26 201M244290018 Evaporator right clapboard 1
27 201M244290003 Evaporator right clapboard 1
28 201M244290004 Evaporator left clapboard 1
29 201M144290008 Right cover 1
30 201M144290016 Display box 1
31 201M344290002 Display board ass'y 1
32 201M144290017 Manual button 1
33 201M144490002 Air outlet ass'y 1
- 202M400200101 Stepper motor 1
- 202M400200100 Stepper motor(vertical) 1
34 202M244290002 foam 1
35 201M244290023 Drainage pan holder 2
36 202M244490006 Drainage pan ass'y 1
37 201M144290018 Plastic cover 1
38 202M400420807 motor 1
39 201M144490021 Panel ass'y 1
40 203M3550A1510 Wireless remote,R92 HP,York brand,White 1
41 201M155090070 Remote holder,R91,York brand,White 1
42 202M440500003 Room temp sensor ass'y 1
43 202M301300133 Coil temp. sensor ass'y 1
44 202M440500002 Evaporator temp. sensorr Ass'y 1
- 189 -
Floor ceiling
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
11.2 kW 14.0 kW
1 201M144690004 Grille ass'y 2
2 201M280200006 motor clamp 2
3 201M280200005 motor clamp 2
4 201M244690003 Filter bracket 2
5 201M244290013 installation board 1
6 201M244290014 installation board 1
7 201M244690004 lfilter left holder 2
8 201M144690003 Sealed board 1
9 201M144690002 Left Sealed board 1
- 190 -
Floor ceiling
___________________________________________________________________________________
10 201M244690002 Pipe clamp 1
11 201M144690006 Right cover 1
12 201M144690005 Left cover 1
13 201M144690000 Display board ass'y 1
14 201M144690001 Display board box 1
15 201M144690008 Air outlet ass'y 1
- 202M400200101 Stepper motor 1
- 202M400200104 Stepper motor(horizontal) 1
- 202M400200103 Stepper motor(vertical) 1
16 201M244690006 Base ass'y 1
17 201M144690011 Plastic fan 4
18 201M144690033 Volute shell 4
19 202M400410844 motor 2
20 201M244290021 Motor bracket 2
21 201M144690032 Volute shell 4
22 201M244690009 Middle beam 1
23 201M244290022 E-part box cover 1
24 203M380590005 E-part box ass'y 1
- 201M244290016 E-Part box 1
- 202M401190019 Motor capacitor 2
- 201M380590000 Main controller ass'y 1
- 202M300900552 Transformer 1
- 202M301450125 Terminal block JX0-B6-D 1
- 202M301450042 Wire joint, 2p 1
25 202M244690000 foam 2
26 201M244690025 Top cover ass'y 1
27 201M244690016 Drainage pan ass'y 1
28 201M144290018 Plastic cover 1
29 202M244690000 Foam 2
30 201M144690007 Filter 4
31 201M580590004 Evaporator ass'y 1
- 201M601300033 Electronic expansion valve 1
32 201M601320018 EEV solenoid 1
33 203M3550A1510 Wireless remote,R92 HP,York brand,White 1
34 201M155090070 Remote holder,R91,York brand,White 1
35 202M440500003 Room temp sensor ass'y 1
36 202M301300133 Coil temp. sensor ass'y 1
37 202M440500002 Evaporator temp. sensorr Ass'y 1
- 191 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 192 -
High ESP Duct
___________________________________________________________________________________
Contents
1. Feature…………………………………………………………………………………………………………………..194
2. Specifications………………………………………………………………………….………………………………196
3. Capacity table…………………………………………………………………….…………………………………..198
4. Dimensions…………………………………………………………………….………………………………………204
5. Service space………………………………………………………………….………………………………………206
6. Wiring diagrams……………………………………………………………..………………………………………208
7. Refrigeration system diagram………………………………………….……………………………………….209
8. Noise level…………………………………………………………………………..…………………………………210
9. Electrical characteristic…………………………………………………………………………………………….211
10. Exploded view parts……………………………………………………………….………………………………212
___________________________________________________________________________________
- 193 -
High ESP Duct
___________________________________________________________________________________
1. Features
Panel
___________________________________________________________________________________
- 194 -
High ESP Duct
___________________________________________________________________________________
A long-life and high-efficiency filter
Filter
Way of air intake and inserting air filter
-Air intake can be positioned either at the back or below the unit. Similarly, the air filter
also can be inserted either from the back or from the bottom of the unit.
___________________________________________________________________________________
- 195 -
High ESP Duct
___________________________________________________________________________________
2. Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
___________________________________________________________________________________
- 196 -
High ESP Duct
___________________________________________________________________________________
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
___________________________________________________________________________________
- 197 -
High ESP Duct
___________________________________________________________________________________
3. Capacity table
3.1) Cooling TC: total capacity SHC: sensible capacity
Indoor temperature(°CWB)
Indoor Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
unit size temperature(°C
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(kW) DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
12 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
14 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.80 3.30
16 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
18 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
20 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.50 3.20
21 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.40 3.10
23 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.40 3.10
4.5
25 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.30 3.00
27 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.30 3.00
29 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.10 2.90
31 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 5.10 3.00
33 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.90 2.90
35 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.80 2.80
37 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
39 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
10 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
12 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
14 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.20 4.10
16 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
18 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
20 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
21 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.00 4.10
23 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
5.6
25 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.50 4.10 6.80 3.90
27 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.40 4.00 6.50 3.80
29 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.30 4.00 6.40 3.70
31 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.20 3.90 6.30 3.70
33 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.00 3.80 6.30 3.70
35 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.70 6.20 3.60
37 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.90 6.10 3.50
39 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 5.70 3.80 5.80 3.80 6.00 3.50
10 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.20 4.90
12 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.10 4.80
14 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.00 4.80
16 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.90 4.70
18 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.70 4.70
20 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.50 4.60
21 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.40 4.50
23 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.30 4.50
7.1
25 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.20 4.40
27 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.10 4.90 8.20 4.40
29 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.00 4.80 8.10 4.50
31 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.90 4.70 7.80 4.40
33 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.80 4.70 7.80 4.40
35 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.60 4.60 7.70 4.30
37 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.50 4.50 7.60 4.30
39 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.20 4.60 7.40 4.40 7.60 4.30
___________________________________________________________________________________
- 198 -
High ESP Duct
___________________________________________________________________________________
Indoor temperature(°CWB)
Indoor Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
unit size temperature(°C
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(kW) DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.40 5.60
12 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.20 5.50
14 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.20 5.50
16 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.00 5.40
18 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.80 5.30
20 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.60 5.20
21 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.40 5.10
23 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.40 5.10
8
25 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.30 5.00
27 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.10 5.30 9.20 5.10
29 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 9.00 5.30 9.10 5.00
31 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.90 5.20 8.80 4.80
33 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.80 5.20 8.80 4.80
35 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.60 5.10 8.60 4.80
37 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.30 5.40 8.40 5.00 8.60 4.90
39 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.10 5.30 8.30 5.00 8.60 4.90
10 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.70 6.60
12 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.50 6.50
14 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.40 6.40
16 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.30 6.30
18 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.00 6.30
20 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.80 6.20
21 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.60 6.10
23 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.50 6.00
9
25 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.40 6.00
27 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.30 6.40 10.40 5.90
29 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.10 6.20 10.30 5.80
31 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.00 6.20 9.90 5.70
33 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 9.90 6.10 9.90 5.70
35 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.50 6.50 9.60 6.00 9.70 5.70
37 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.30 6.30 9.50 5.90 9.60 5.80
39 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.20 6.20 9.40 5.80 9.60 5.80
10 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 15.50 9.00
12 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.40 8.40
14 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.20 8.20
16 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.10 8.20
18 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.00 8.10
20 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 13.90 8.10
21 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 13.80 8.00
23 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.10 8.10 13.70 7.90
11.2
25 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.00 8.10 13.60 7.90
27 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.90 8.00 13.40 7.80
29 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.80 7.90 13.30 7.90
31 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.70 7.80 12.80 7.50
33 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.50 7.80 12.50 7.40
35 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.80 8.00 12.40 7.70 12.30 7.30
37 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.60 7.90 12.30 7.60 12.10 7.10
39 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.40 7.80 12.20 7.60 11.90 7.10
___________________________________________________________________________________
- 199 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 200 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 201 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 202 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 203 -
High ESP Duct
___________________________________________________________________________________
4. Dimensions
4.1) YDS-45-140TC
___________________________________________________________________________________
- 204 -
High ESP Duct
___________________________________________________________________________________
4.2) YDS-280TC
___________________________________________________________________________________
- 205 -
High ESP Duct
___________________________________________________________________________________
5. Service space
5.1) YDS-45-140TC
___________________________________________________________________________________
- 206 -
High ESP Duct
___________________________________________________________________________________
5.2) YDS-280TC
___________________________________________________________________________________
- 207 -
High ESP Duct
___________________________________________________________________________________
6. Wiring diagrams
6.1) YDS-45-80TC
6.2) YDS-90-140TC16IA
___________________________________________________________________________________
- 208 -
High ESP Duct
___________________________________________________________________________________
6.3) YDS-280TC
7.1) YDS-45-140TC
___________________________________________________________________________________
- 209 -
High ESP Duct
___________________________________________________________________________________
7.2) YDS-280TC
8. Noise level
8.1) Test condition
DUCT TYPE
Duct
1.0m
Microphone
___________________________________________________________________________________
- 210 -
High ESP Duct
___________________________________________________________________________________
Model H M L
YDS-45TC 45.4 40.6 39.2
YDS-56TC 45.4 40.6 39.2
YDS-71TC 52.5 50.2 49
YDS-80TC 52.5 50.2 49
YDS-90TC 52.8 49.8 47.1
YDS-112TC 52.8 49.8 47.1
YDS-140TC 52.8 49.8 47.1
YDS-280TC 60 57 52
9. Electric characteristics
___________________________________________________________________________________
- 211 -
High ESP Duct
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
4.5 kW 5.6 kW 7.1 kW 8.0 kW
1 201M286090027 Base ass'y 1
2 201M280200007 Board 1
3 201M280200005 Motor clamp 1
4 201M280200006 Motor clamp 1
5 202M400400073 202M400410860 Fan motor 1
6 202M401100353 202M401190042 Motor capacitor 1
7 201M284400004 Motor bracket 1
8 201M286090056 Fan ass'y 3
9 201M286000011 E-Part box cover 1
10 202M301450125 Wire joint 1
11 202M300900109 Transformer 1
12 203M386090063 203M386090064 E-part box ass'y 1
- 201M285290000 E-part box 1
- 202M301450042 Wire joint, 2p 1
- 202M301450122 Wire joint 1
13 201M385020023 Main controller ass'y 1
14 201M286040414 Pipe clamp board 1
15 201M286090050 Sealed board ass'y 1
___________________________________________________________________________________
- 212 -
High ESP Duct
___________________________________________________________________________________
16 201M285490002 Left clapboard ass'y 1
17 203M342090023 Display board ass'y 1
18 203M3550A1520 Remote controller 1
19 201M131390022 Remote controller holder ass'y 1
20 201M185000303 Display box 1
21 201M686090143 201M686090132 Input pipe ass'y 1
22 201M586090040 201M586090041 Evaporator ass'y 1
- 202M440500003 Room temp sensor ass'y 1
- 202M440500002 Temp.sensor ass'y 1
- 202M301300303 Temperature sensor 1
23 201M686090127 201M686090125 Output pipe ass'y 1
24 201M285500001 Evaporator lining board 1
25 201M286090035 Evaporator left clapboard ass'y 1
26 201M286090038 Evaporator right clapboard ass'y 1
27 201M286000455 Drainage pan ass'y 1
28 201M286090033 Middle beam 1
29 201M285490001 Right cover ass'y 1
30 201M286000456 Rear cover ass'y 1
31 202M730500001 Bearing base 1
32 201M130000004 Bearing 1
33 201M284400003 Bearing supporting board 1
34 201M286090026 Rear beam 1
35 201M200200008 Connecting shaft 1
36 202M984400001 Coupling 1
37 201M609890035 Electric throttle ass'y 1
___________________________________________________________________________________
- 213 -
High ESP Duct
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
9.0 kW 11.2 kW 14.0 kW
1 201M286090063 Base ass'y 1
2 201M286090056 Fan ass'y 4
3 202M400400252 Motor 2
4 201M280200007 board 2
5 201M280200005 motor clamp 2
6 201M284400004 Motor bracket 2
7 201M280000024 Capacitor box 2
8 201M280200006 motor clamp 2
9 202M401100505 Motor capacitor 2
10 201M285490002 Left clapboard ass'y 1
11 202M301450125 Terminal block JX0-B6-D 1
12 203M386090062 E-part box ass'y 1
- 201M285290000 E-part box 1
- 202M301450042 Wire joint, 2p 1
- 202M301450122 Wire joint 1
13 202M300900109 Transformer (TT2-B35+D90-1F) 1
14 201M385020023 Main controller ass'y 1
15 201M286000011 E-Part box cover 1
16 201M286040414 Pipe clamp 1
17 201M286090050 Sealed board ass'y 1
18 203M342090023 Display board ass'y 1
19 203M3550A1520 Remote controller 1
___________________________________________________________________________________
- 214 -
High ESP Duct
___________________________________________________________________________________
20 201M131390022 Remote holder,R51,York brand,White 1
21 201M185000303 display box 1
22 201M686090141 Inlet pipe ass'y 1
23 201M686090131 Outlet pipe ass'y 1
24 201M586090035 Evaporator ass'y 1
- 202M440500003 Room temp sensor ass'y 1
- 202M440500002 Evaporator temp. sensorr Ass'y 1
- 202M301300303 Evaporator temp. sensor 1
25 201M286090035 Evaporator left clapboard ass'y 1
26 201M285700014 Evaporator lining board 1
27 201M286000062 Drain pan ass'y 1
28 201M286090038 Evaporator right clapboard ass'y 1
29 201M285490001 Right cover ass'y 1
30 201M286090067 Middle beam 1
31 201M286000068 Rear cover ass'y 1
32 201M286090062 Rear beam 1
33 201M609890040 Electric throttle ass'y 1
___________________________________________________________________________________
- 215 -
High ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 216 -
High ESP Duct
___________________________________________________________________________________
23 202M440500002 Temp.sensor ass'y 2
24 201M285890018 Base ass'y 1
25 201M585890001 Evaporator ass'y 1
26 202M450200314 Temp sensor ass'y 2
27 201M285890029 Rear board ass'y 1
28 201M285890024 Top cover ass'y 1
29 201M685890046 Connecting pipe ass'y 2
30 203M385890003 E-part box ass'y 1
- 202M301450042 Wire joint, 2p 1
- 202M301450044 Wire joint, 3p 2
- 202M301450122 Wire joint 3
31 201M131390022 Remote controller holder ass'y 1
___________________________________________________________________________________
- 217 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 218 -
Me ESP Slim Duct
___________________________________________________________________________________
Contents
1. Feature…………………………………………………………………………………………………………………..220
2. Specifications………………………………………………………………………….………………………………222
3. Capacity table…………………………………………………………………….…………………….……………..224
4. Dimensions…………………………………………………………………….………………………………………230
5. Service space………………………………………………………………….………………………………………231
6. Refrigeration system diagram………………………………………….………………………….…………….232
7. Wiring diagrams……………………………………………………………..……………………….………………233
8. Noise level…………………………………………………………………………..…………………………………234
9. Fan performance……………………………………………………………………………………………………..235
10. Electrical characteristic….……………………………………………………………………………………….236
11. Exploded view parts……………………………………………………………….………………………………237
___________________________________________________________________________________
- 219 -
Me ESP Slim Duct
___________________________________________________________________________________
1. Features.
1.1) Economic and convenient installation
-Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes
many rooms to be air-conditioned with only one indoor unit.
-All models feature thin design making them applicable to ceiling pocket that tends to be
shallow
Panel
1.3) A long-life and high-efficiency filter
Filter
___________________________________________________________________________________
- 220 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 221 -
Me ESP Slim Duct
___________________________________________________________________________________
2. Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
___________________________________________________________________________________
- 222 -
Me ESP Slim Duct
___________________________________________________________________________________
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
___________________________________________________________________________________
- 223 -
Me ESP Slim Duct
___________________________________________________________________________________
3 Capacity table
Indoor temperature(°CWB)
Combination, Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
%(Capacity temperature(°C
index) DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
12 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.90 3.40
14 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.80 3.30
16 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
18 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.60 3.20
20 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.50 3.20
21 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.40 3.20 5.40 3.10
23 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.40 3.10
4.5
25 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.20 3.20 5.30 3.00
27 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.30 3.00
29 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.00 3.00 5.10 2.90
31 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 5.10 3.00
33 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.90 2.90
35 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.80 3.30 5.30 3.50 4.80 2.80
37 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
39 3.10 2.60 3.60 2.90 4.20 3.10 4.50 3.20 4.60 3.20 4.80 3.10 4.80 2.90
10 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
12 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.30 4.10
14 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.20 4.10
16 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
18 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
20 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.10 4.10
21 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 7.00 4.10
23 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.60 4.60 6.90 4.00
5.6
25 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.50 4.10 6.80 3.90
27 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.40 4.00 6.50 3.80
29 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.30 4.00 6.40 3.70
31 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.20 3.90 6.30 3.70
33 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 6.00 3.80 6.30 3.70
35 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.70 6.20 3.60
37 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 6.00 4.00 5.90 3.90 6.10 3.50
39 3.90 3.20 4.60 3.50 5.20 3.90 5.60 4.00 5.70 3.80 5.80 3.80 6.00 3.50
10 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.20 4.90
12 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.10 4.80
14 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 9.00 4.80
16 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.90 4.70
18 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.70 4.70
20 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.50 4.60
21 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.40 4.50
23 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.30 4.50
7.1
25 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.40 4.90 8.20 4.40
27 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.10 4.90 8.20 4.40
29 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 8.00 4.80 8.10 4.50
31 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.90 4.70 7.80 4.40
33 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.80 4.70 7.80 4.40
35 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.60 4.60 7.70 4.30
37 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.50 4.80 7.50 4.50 7.60 4.30
39 5.00 3.80 5.80 4.20 6.70 4.60 7.10 4.70 7.20 4.60 7.40 4.40 7.60 4.30
___________________________________________________________________________________
- 224 -
Me ESP Slim Duct
___________________________________________________________________________________
Indoor temperature(°CWB)
Combination, Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
%(Capacity temperature(°C
index) DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.40 5.60
12 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.20 5.50
14 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.20 5.50
16 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 10.00 5.40
18 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.80 5.30
20 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.60 5.20
21 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.40 5.10
23 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.40 5.10
8
25 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.40 5.50 9.30 5.00
27 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.40 9.10 5.30 9.20 5.10
29 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 9.00 5.30 9.10 5.00
31 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.90 5.20 8.80 4.80
33 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.80 5.20 8.80 4.80
35 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.40 5.50 8.60 5.10 8.60 4.80
37 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.30 5.40 8.40 5.00 8.60 4.90
39 5.50 4.40 6.60 4.90 7.50 5.30 8.00 5.50 8.10 5.30 8.30 5.00 8.60 4.90
10 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.70 6.60
12 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.50 6.50
14 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.40 6.40
16 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.30 6.30
18 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 11.00 6.30
20 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.80 6.20
21 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.60 6.10
23 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.50 6.00
9
25 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.60 6.60 10.40 6.00
27 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.30 6.40 10.40 5.90
29 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.10 6.20 10.30 5.80
31 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 10.00 6.20 9.90 5.70
33 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.60 6.50 9.90 6.10 9.90 5.70
35 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.50 6.50 9.60 6.00 9.70 5.70
37 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.30 6.30 9.50 5.90 9.60 5.80
39 6.20 5.30 7.30 5.80 8.40 6.30 9.00 6.40 9.20 6.20 9.40 5.80 9.60 5.80
10 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 15.50 9.00
12 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.40 8.40
14 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.20 8.20
16 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.10 8.20
18 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 14.00 8.10
20 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 13.90 8.10
21 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.30 8.30 13.80 8.00
23 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.10 8.10 13.70 7.90
11.2
25 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 13.00 8.10 13.60 7.90
27 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.90 8.00 13.40 7.80
29 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.80 7.90 13.30 7.90
31 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.70 7.80 12.80 7.50
33 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.90 8.10 12.50 7.80 12.50 7.40
35 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.80 8.00 12.40 7.70 12.30 7.30
37 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.60 7.90 12.30 7.60 12.10 7.10
39 7.70 6.40 9.10 7.10 10.50 7.70 11.20 7.80 11.40 7.80 12.20 7.60 11.90 7.10
___________________________________________________________________________________
- 225 -
Me ESP Slim Duct
___________________________________________________________________________________
Indoor temperature(°CWB)
Combination, Outdoor
14/20 16/23 18/26 19/27 20/28 22/30 24/32
%(Capacity temperature(°C
index) DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 18.20 10.20
12 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.90 10.00
14 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.80 10.00
16 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.50 9.80
18 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 17.10 9.60
20 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 16.80 9.40
21 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.70 10.20 16.50 9.30
23 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.40 10.20 16.40 9.20
14
25 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.20 10.10 16.20 9.10
27 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.10 10.00 16.10 9.20
29 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 16.00 9.90 16.00 9.10
31 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 15.80 9.80 15.40 8.80
33 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.80 9.80 15.70 9.70 15.40 8.80
35 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.70 9.70 15.10 9.40 15.10 8.80
37 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.60 9.60 15.10 9.40 15.00 8.70
39 9.70 7.80 11.30 8.60 13.20 9.60 14.00 9.80 14.30 9.40 14.60 9.20 15.00 8.80
___________________________________________________________________________________
- 226 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 227 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 228 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 229 -
Me ESP Slim Duct
___________________________________________________________________________________
4. Dimensions
YDS-45-140YC
___________________________________________________________________________________
- 230 -
Me ESP Slim Duct
___________________________________________________________________________________
5. Service space
YDS-45-140YC
___________________________________________________________________________________
- 231 -
Me ESP Slim Duct
___________________________________________________________________________________
6. Piping diagram
m otor
fan
T2B flare nut
T1 gas side
T2
liquid side
EXV
___________________________________________________________________________________
- 232 -
Me ESP Slim Duct
___________________________________________________________________________________
7. Wiring diagrams
7.1) YDS-45-80YC
7.2) YDS-90-140YC
___________________________________________________________________________________
- 233 -
Me ESP Slim Duct
___________________________________________________________________________________
8. Noise level
Test condition
___________________________________________________________________________________
- 234 -
Me ESP Slim Duct
___________________________________________________________________________________
9. Fan performance
YDS-45-56YC YDS-71-80YC
YDS-90-140YC
___________________________________________________________________________________
- 235 -
Me ESP Slim Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 236 -
Me ESP Slim Duct
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
4.5 kW 5.6 kW 7.1 kW 8.0 kW
1 201M286090027 Base ass'y 1
2 201M280200007 board 1
3 201M280200005 motor clamp 1
4 201M280200006 motor clamp 1
5 202M400410649 202M400420620 motor 1
6 202M401100353 202M401190042 Motor capacitor 1
7 201M284400004 Motor bracket 1
8 201M286090056 Fan ass'y 3
9 201M286000011 E-Part box cover 1
10 202M301450125 Terminal block JX0-B6-D 1
11 202M300900109 Transformer (TT2-B35+D90-1F) 1
12 203M386090063 203M386090064 E-part box ass'y 1
- 201M285290000 E-part box 1
- 202M301450042 Wire joint, 2p 1
- 202M301450122 Wire joint 1
13 201M385020023 Main controller ass'y 1
14 201M286040414 Pipe clamp 1
15 201M286090050 Sealed board ass'y 1
16 201M285490002 Left clapboard ass'y 1
17 203M342090023 Display board ass'y 1
___________________________________________________________________________________
- 237 -
Me ESP Slim Duct
___________________________________________________________________________________
18 203M3550A1520 Remote controller 1
19 201M131390022 Remote holder,R51,York brand,White 1
20 201M185000303 display box 1
21 201M686090143 201M686090132 Inlet pipe ass'y 1
22 201M586090040 201M586090041 Evaporator ass'y 1
- 202M440500003 Room temp sensor ass'y 1
- 202M440500002 Evaporator temp. sensorr Ass'y 1
- 202M301300303 Evaporator temp. sensor 1
23 201M686090127 201M686090125 Outlet pipe ass'y 1
24 201M285500001 Evaporator lining board 1
25 201M286090035 Evaporator left clapboard ass'y 1
26 201M286090038 Evaporator right clapboard ass'y 1
27 201M286000455 Drain pan ass'y 1
28 201M286090033 Middle beam 1
29 201M285490001 Right cover ass'y 1
30 201M286000456 Rear cover ass'y 1
31 202M730500001 Bearing base 1
32 201M130000004 Bearing 1
33 201M284400003 Bearing base 1
34 201M286090026 Rear beam 1
35 201M200200008 Connecting shaft 1
36 202M984400001 Coupling 1
37 201M609890035 Electric throttle ass'y 1
___________________________________________________________________________________
- 238 -
Me ESP Slim Duct
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
9.0 kW 11.2 kW 14.0 kW
1 201M286090063 Base ass'y 1
2 201M286090056 Fan ass'y 4
3 202M400420621 motor 2
4 201M280200007 board 2
5 201M280200005 motor clamp 2
6 201M284400004 Motor bracket 2
7 201M280000024 Capacitor box 2
8 201M280200006 motor clamp 2
9 202M401100407 Motor capacitor 2
10 201M285490002 Left clapboard ass'y 1
11 202M301450125 Terminal block JX0-B6-D 1
12 203M386090062 E-part box ass'y 1
- 201M285290000 E-part box 1
- 202M301450042 Wire joint, 2p 1
- 202M301450122 Wire joint 1
13 202M300900109 Transformer (TT2-B35+D90-1F) 1
14 201M385020023 Main controller ass'y 1
15 201M286000011 E-Part box cover 1
16 201M286040414 Pipe clamp 1
17 201M286090050 Sealed board ass'y 1
18 203M342090023 Display board ass'y 1
___________________________________________________________________________________
- 239 -
Me ESP Slim Duct
___________________________________________________________________________________
19 203M3550A1520 Remote controller 1
20 201M131390022 Remote holder,R51,York brand,White 1
21 201M185000303 display box 1
22 201M686090141 Inlet pipe ass'y 1
23 201M686090131 Outlet pipe ass'y 1
24 201M586090035 Evaporator ass'y 1
- 202M440500003 Room temp sensor ass'y 1
- 202M440500002 Evaporator temp. sensorr Ass'y 1
- 202M301300303 Evaporator temp. sensor 1
25 201M286090035 Evaporator left clapboard ass'y 1
26 201M285700014 Evaporator lining board 1
27 201M286000062 Drain pan ass'y 1
28 201M286090038 Evaporator right clapboard ass'y 1
29 201M285490001 Right cover ass'y 1
30 201M286090067 Middle beam 1
31 201M286000068 Rear cover ass'y 1
32 201M286090062 Rear beam 1
33 201M609890040 Electric throttle ass'y 1
___________________________________________________________________________________
- 240 -
Me ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 241 -
Me ESP Duct
___________________________________________________________________________________
Contents
1. Feature…………………………………………………………………………………………………………………..243
2. Specifications………………………………………………………………………….………………………………245
3. Capacity table…………………………………………………………………….…………………….……………..246
4. Dimensions…………………………………………………………………….………………………………………250
5. Service space………………………………………………………………….………………………………………251
6. Refrigeration system diagram………………………………………….………………………….…………….252
7. Wiring diagrams……………………………………………………………..……………………….………………253
8. Noise level…………………………………………………………………………..…………………………………254
9. Fan performance……………………………………………………………………………………………………..255
10. Electrical characteristic…………………………………………………………………………………………..255
11. Exploded view parts……………………………………………………………….………………………………256
___________________________________________________________________________________
- 242 -
Me ESP Duct
___________________________________________________________________________________
1. Features
Normal body
Economic and convenient installation
-Several diffusers branch off from an indoor unit, adjusting the room temperature, which
makes many rooms to be air-conditioned with only one indoor unit.
-All models feature thin design making them applicable to ceiling pocket that tends to be
shallow
Panel
___________________________________________________________________________________
- 243 -
Me ESP Duct
___________________________________________________________________________________
Filter
Way of air intake and inserting air filter
-Air intake can be positioned either at the back or below the unit. Similarly, the air filter
also can be inserted either from the back or from the bottom of the unit.
___________________________________________________________________________________
- 244 -
Me ESP Duct
___________________________________________________________________________________
2. Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor
temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
___________________________________________________________________________________
- 245 -
Me ESP Duct
___________________________________________________________________________________
3. Capacity table
___________________________________________________________________________________
- 246 -
Me ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 247 -
Me ESP Duct
___________________________________________________________________________________
3.2) Heating TC: total capacity
___________________________________________________________________________________
- 248 -
Me ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 249 -
Me ESP Duct
___________________________________________________________________________________
4. Dimensions
YDS-22-36UC
___________________________________________________________________________________
- 250 -
Me ESP Duct
___________________________________________________________________________________
YDS-280UC
5. Service space
___________________________________________________________________________________
- 251 -
Me ESP Duct
___________________________________________________________________________________
6. Piping diagram
YDS-22-36UC
YDS-280UC
___________________________________________________________________________________
- 252 -
Me ESP Duct
___________________________________________________________________________________
7. Wiring diagrams
7.1) YDS-22-36UC
7.2) YDS-280UC
___________________________________________________________________________________
- 253 -
Me ESP Duct
___________________________________________________________________________________
8. Noise level
Test condition
___________________________________________________________________________________
- 254 -
Me ESP Duct
___________________________________________________________________________________
9. Fan performance
YDS-22-36UC YDS-280UC
___________________________________________________________________________________
- 255 -
Me ESP Duct
___________________________________________________________________________________
PART NUMBER
ITEM NO PART NAME QTY REMARK
2.2 kW 2.8 kW 3.6 kW
1 201M286100056 Drainage pan ass'y 1
2 201M186000005 water pipe 1
3 201M585020200 201M585100100 Evaporator ass'y 1
- 201M685020200 Input pipe ass'y 1
- 201M600500197 Distributor 1
- 201M600320000 201M600320001 Copper nut, TLM-A01 1
- 201M586100450 201M586100050 Evaporator 1
- 201M685020202 201M685100100 Output pipe ass'y 1
- 201M600320002 Copper nut, TLM-C03 1
- 202M301300133 202M301300303 Coil temp. sensor ass'y 1
- 202M440500002 Evaporator temp. sensorr Ass'y 1
4 201M286100001 partition plate ass'y 1
5 201M286000011 E-Part box cover 1
6 201M285700012 Cover plate ass'y 1
7 202M795000002 Rubber guard bush 4
8 201M285700000 Left clapboard ass'y 1
9 203M386190003 E-Part box ass'y 1
___________________________________________________________________________________
- 256 -
Me ESP Duct
___________________________________________________________________________________
- 201M286000078 E-part box 1
- 202M300900109 Transformer (TT2-B35+D90-1F) 1
- 201M385020023 Main controller ass'y 1
- 202M301450122 Wire joint 1
- 202M301450042 Wire joint, 2p 1
- 202M301450125 Terminal block JX0-B6-D 1
10 201M185000303 display box 1
11 203M3550A1520 Remote controller 1
12 201M186000201 E-part box cover 1
13 201M131390022 Remote holder,R51,York brand,White 1
14 203M342090023 Display board ass'y 1
15 201M280200005 motor clamp 1
16 201M284400004 Motor bracket 1
17 201M280200006 motor clamp 1
18 201M280200007 board 1
19 202M400410848 Fan motor 1
20 201M286100054 Rear clapboard ass'y 1
21 201M286100057 Volute shell 1
22 201M286000055 Wind ring ass'y 2
23 201M280000024 Capacitor box 2
24 202M401190019 Motor capacitor 1
25 201M186000050 fan ass'y 1
26 201M286000004 board 1
27 201M285700001 Right cover ass'y 1
28 201M286100051 Middle beam 1
29 201M286100052 beam Cover ass'y 1
30 201M609890034 Electric throttle ass'y 1
- 201M609800091 Electronic expansion valve ass'y 1
31 201M286100050 Base ass'y 1
32 201M286100002 Evaporator base board 1
33 202M440500003 Room temp sensor ass'y 1
___________________________________________________________________________________
- 257 -
Me ESP Duct
___________________________________________________________________________________
___________________________________________________________________________________
- 258 -
Me ESP Duct
___________________________________________________________________________________
16 203M385890003 E-part box ass'y 1
- 201M285890038 Electronic control box 1
- 201M385890000 Main controller ass'y 2
- 202M300900109 Transformer 2
- 202M300800071 Relay 3
- 202M301450042 Wire joint, 2p 1
- 202M301450044 Wire joint, 3p 2
- 202M301450122 Wire joint 3
17 201M285890109 Left clapboard ass'y 1
18 202M401000508 Compressor capacitor 1
19 201M226190015 Compressor capacitor box 1
20 201M286900313 Rear board ass'y 1
21 201M286900301 Pipe clamp board 1
22 201M286900302 Pipe clamp board 1
23 201M585890001 Evaporator ass'y 1
- 201M686900302 Input pipe ass'y 1
- 201M600320002 Copper nut 1
- 201M600910100 Strainer 1
- 201M686900303 Input pipe ass'y 1
- 201M600910100 Strainer 1
- 201M600320002 Copper nut 1
- 201M686900304 Output pipe ass'y 2
- 201M600320004 Copper nut 1
- 201M586900302 Evaporator 1
- 202M440500002 Temp.sensor ass'y 2
- 202M450200314 Temp sensor ass'y 2
24 201M286900318 Left Sealed board 1
25 201M286900314 Top cover ass'y 1
26 201M286000053 Motor below cover 1
27 201M286000052 Motor below cover 1
28 201M286000008 Motor up cover 1
29 201M286000007 Motor up cover 1
30 201M285000321 Board 1
31 201M286900317 Evaporator Sealed board 1
32 201M286900307 Waterproof board 1
33 201M286900316 Side board ass'y 1
34 201M685890011 Gas branch pipe ass'y 1
- 201M689590002 Liquid branch pipe ass'y 1
- 201M689590001 Gas branch pipe ass'y 1
35 201M286900020 Volute shell ass'y 1
36 201M609890075 Electric throttle ass'y 1
37 201M685890046 Connecting pipe ass'y 2
___________________________________________________________________________________
- 259 -
Installation
Part 5 Installation
____________________________________________________________________________________
260
Installation
Contents
____________________________________________________________________________________
261
Installation
1. Summarize of Installation
1.1) Installation Procedure
Note: The general procedure for refrigerant machine is subject to change according to the
situation.
____________________________________________________________________________________
262
Installation
Procedure:
Confirm installation position Label installation position Install hooks Install indoor units
Note: 1. The hook must strong enough to sustain the weight of indoor unit.
2. Check the models of indoor units before installation.
3. Pay attention to the main devices, such as the pipeline.
4. Hold enough places for maintenance.
Procedure:
Procedure:
Install indoor units Connect drainpipe Check water leakage
Note: It is no need to insulate the drainpipe if you choose the plastic pipe as drainpipe.
____________________________________________________________________________________
263
Installation
1.5.6 It is suggested to use 3-core shielded wire as signal wire between indoor and outdoor
units, multi-core wire is unavailable. Pay attention to the consistency. When signal wire parallel to
the power wire, please keep enough distance (about 300mm at least) to prevent interference.
1.5.7 The power wire and signal wire can’t be enlaced together.
Note: Collocate the air-outlet reasonably to prevent airflow short-circuit. Check the static
pressure whether in the allowable range. The air filters should be easy to unpick and wash. Do
pressure test on pipeline.
1.7) Heat-insulation
Procedure:
Refrigerant pipe work Check the heat-insulated part Pressure test Heat-insulation work
Note: For welding part, flare part and branch pipe, heat-insulation work must be done after
finished the pressure test.
Note: 1. Gutter must be set around the foundation to drain the condensation water.
2. When installing outdoor units at the roof, please check the strength of the roof and
pay attention not to destroy the waterproof of the roof.
Procedure:
Calculate the added volume according to liquid pipe length Recharge refrigerant
Note: Please calculate the additional amount of refrigerant according to the formula that we
supply to you, and the calculation result must be correct
____________________________________________________________________________________
264
Installation
1. Air-inlet and air-outlet temperature of indoor units: generally, the temperature difference
between them should be 10 degree according to and depended on the outdoor ambient
temperature, we think it is normal.
2. Fan speed of air-outlet of indoor units: Generally, for the duct type indoor units, the fan
speed of air-outlet should be 3m/s roughly.
Note: Do not make forced running, otherwise the protection device will not work, which is very
dangerous.
____________________________________________________________________________________
265
Installation
____________________________________________________________________________________
266
Installation
2.2.4 Distance between ground bolt is shown below: (Note: Outdoor units in the same system
should be located in the same level.
____________________________________________________________________________________
267
Installation
____________________________________________________________________________________
268
Installation
The top of any pile around the outdoor unit should be at least 800mm below the unit top,
unless there is mechanism for air discharging.
____________________________________________________________________________________
269
Installation
2.3) In snowy areas, facilities should be installed to prevent snow. Please lift the bracket higher
and install snow shed at the air inlet and air outlet.
____________________________________________________________________________________
270
Installation
Dimension A B C
Model
Four-way Cassette 1000mm above 2300mm above
____________________________________________________________________________________
271
Installation
Drain point
Capacity (KW) A B C D E F G H
2.2-7.1 KW 990 660 206 505 506 907 200 203
8.0-9.0 KW 1280 660 206 795 506 1195 200 203
11.2-14.0 KW 1670 680 224 1070 450 1542 200 240
____________________________________________________________________________________
272
Installation
♦ The refrigerant pipe adapter is located inside the outdoor unit. So remove the lower front
board first.
♦ The pipe can be connected from the front left lower side or the bottom notch of the outdoor
unit.
♦ In case the pipe is connected from the front side, lead out the pipe through the wiring panel of
the pipes, and then install the refrigerant manifold pipe leftward or rightward.
♦ In case the pipe is connected from the bottom notch, install the refrigerant manifold pipe
leftward, rightward or backward after connecting it out.
♦ In case of leading from the front side, remove the guard board at the corresponding notch
location on the panel in advance, and then lead the pipe out.
Caution: When welding the refrigerant pipe, in order to prevent internal oxidation of the pipe,
nitrogen must be filled in. Otherwise, the oxidized chips may block cooling circulatory system.
____________________________________________________________________________________
273
Installation
R-22 R-410A
A 250 350
B 300 500
C 130 150
D 150 175
E 50 70
F 30 40
♦ Conversion of the equivalent length: Convert into the direct pipe length according to branch part
0.5m/l.
____________________________________________________________________________________
274
Installation
4.3 How to choose the Branch joint and the refrigerant pipe?
4.3.1. The capacity of outdoor units to select the dimension of outdoor pipe (g1, g2, g3):
Model Capacity( kW) Liquid/gas side
25.2-33.5 Ф12.7/Ф28.6
Inverter
40.0-45.0 Ф15.9/Ф38
50 Hz
25.2-33.5 Ф12.7/Ф28.6
R-22 Digital scroll
40.0-45.0 Ф15.9/Ф35.0
25.2-33.5 Ф12.7/Ф28.6
60 Hz Inverter
40.0-45.0 Ф15.9/Ф38
25.2-33.5 Ф12.7/Ф25.4
Inverter
40.0-45.0 Ф15.9/Ф31.8
50 Hz
25.2-33.5 Ф12.7/Ф25.4
Digital scroll
40.0-45.0 Ф15.9/Ф31.8
R-410A
25.2-33.5 Ф12.7/Ф25.4
60 Hz 380 V Inverter
40.0-45.0 Ф15.9/Ф31.8
25.2-33.5 Ф12.7/Ф25.4
60 Hz 230 V Inverter
40.0-45.0 Ф15.9/Ф31.8
____________________________________________________________________________________
275
Installation
4.3.2. The total capacity of outdoor units to select the branch joint and dimension of outdoor
main pipe (g4, L):
Parallel pipe (g4) Main pipe (L)
Model Capacity( kW)
Gas side Liquid side Gas side Liquid side
25.2≤A≤33.5 Φ28.6 Φ12.7 Φ28.6 Φ12.7
40.0≤A≤45.0 Φ38.0 Φ15.9 Φ35.0 Φ15.9
53.2≤A≤61.5 Φ38.0 Φ19.0 Φ35.0 Φ19.0
Inverter A=68 Φ38.0 Φ19.0 Φ42.0 Φ19.0
73≤A≤96 Φ42.0 Φ22.0 Φ42.0 Φ22.0
101≤A≤135 Φ54.0 Φ25.0 Φ54.0 Φ22.0
140.5≤A≤180 Φ63.5 Φ25.0
R-22
25.2≤A≤33.5 Φ28.6 Φ12.7 Φ28.6 Φ12.7
40.0≤A≤45.0 Φ35.0 Φ15.9 Φ35.0 Φ15.9
53.2≤A≤61.5 Φ35.0 Φ19.0 Φ35.0 Φ19.0
Digital scroll A=68 Φ42.0 Φ19.0 Φ42.0 Φ19.0
73≤A≤96 Φ42.0 Φ22.0 Φ42.0 Φ22.0
101≤A≤135 Φ54.0 Φ22.0 Φ54.0 Φ22.0
140.5≤A≤180 Φ63.5 Φ25.0
Note: In case the joint size of outdoor unit is different from the main pipe, a diameter reducer
union should added transiting for it.
Branch part
Quantity of
R-22 R-410A
outdoor unit
Inverter Digital scroll Inverter Digital scroll
2 YDSA/FWT02 YDSA/FW02 YDSA/FN02 YDSA/FN02
3 YDSA/FWT03 YDSA/FW03 YDSA/FN03 YDSA/FN03
4 YDSA/FWT04 YDSA/FW04 YDSA/FN04 YDSA/FN04
____________________________________________________________________________________
276
Installation
4.3.4. The capacity of indoor unit select indoor main pipe (L1,-L7) and branch joint (A~H):
4.3.5 Selection the pipe connected to indoor units and connecting method
Connecting pipe
Refrigerant Type (A)
Liquid Gas
A≤4.5 kW Φ6.4 Φ12.7
R-22 5.6 kW ≤ A ≤ 9.0 kW Φ9.5 Φ15.9
10.0 kW ≤ A Φ9.5 Φ19.0
A≤4.5 kW Φ6.4 Φ12.7
R-410A
5.6 kW ≤ A Φ9.5 Φ15.9
R-22 R-410A
Model
Digital scroll Inverter Digital scroll Inverter
Gas balance pipe I Φ15.9 Φ15.9 Φ15.9 Φ6.4
Gas balance pipe II Φ19.1 Φ19.1 Φ19.1 Φ19.1
____________________________________________________________________________________
277
Installation
Example
The combination of 40+45+45+45=175 kW
____________________________________________________________________________________
278
Installation
(6) Selection the rest branch parts and main pipes of indoor side. Refer to table 4.3.4.
pipe/ below main A: Total capacity (kW) of indoor units below main pipe Range Branch part
(Gas/Liquid)
branch part pipe
(7) Selection the pipe connected to indoor units and connecting method. Refer to 4.3.5.
____________________________________________________________________________________
279
Converter pipe Converter pipe
Gas side joint Liquid side joint Gas balance joint 1 Gas balance joint 2
(Gas pipe use) (Liquid pipe use)
YDSA/FW01A
YDSA/FW01A
4.4 The dimension of branch part:
YDSA/FW02
280
YDSA/FW03
YDSA/FW04
Installation
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FW02
Flaring connection
W2 Flaring connection
W2 W1
W1
Liquid side pipes
W1
Field elbow bend
281
W2
Gas side pipes
Flaring connection
W1
W2 Welding
Flaring connection
Note: 1. It’s advised to use the max. HP unit as the main unit. See above figure W2 outdoor unit (main unit) Field pipe 19.1
Arranging the units with a sequence of Max. to Min. (i.e. W2>W1)
2. The above figure is only available for the models as belows when they are paraelled connected :
Field pipe 15.9 YDS-252WA35 to YDS-450WA35
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FW03
Field pipe, the caliber refer to
Table.3
If 8 W3 12, i.e. 28.6
If 14 W3 16, i.e. 34.9 Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to
Field pipe, the caliber refer to If 34 W1+W2+W3 48, i.e. 22.2 Table.3
Field pipe, the caliber refer to Table.3 If 8 W3 12, i.e. 12.7
Table.3 If 8 W2 12, i.e. 28.6 If 14 W3 16, i.e. 15.9
If W1+W2+W3=34, i.e. 41.3 If 14 W2 16, i.e. 34.9
If 36 W1+W2+W3 48, i.e. 54.1 Field pipe, the caliber refer to Field pipe, the caliber refer to
Table.3 Flaring connection Table.3
If 8 W1 12, i.e. 28.6 W3 If 8 W2 12, i.e. 12.7
If 14 W1 16, i.e. 34.9 If 14 W2 16, i.e. 15.9
W3
Flaring connection
W2
W2 Flaring connection
Gas side joint B W1 W1
Field pipe, the caliber refer to
Table.3 Converter pipe (gas pipe used) J
If 18 W1+W2 24, i.e. 34.9 Liquid side pipes
If 24 W1+W2 32, i.e. 41.3 Liquid side joint E
Converter pipe (liquid pipe used) I
Gas side joint A Field pipe, the caliber refer to
Converter pipe (gas pipe used) F W3(main unit) Table.3
If 18 W1+W2 24, i.e. 19.1 Converter pipe (liquid pipe used) I
If 26 W1+W2 32, i.e. 22.2 Liquid side joint D
W2 Converter pipe (liquid pipe used) H
282
Field pipe, the caliber refer to
Table.3
Field elbow bend W1 If 8 W1 12, i.e. 12.7
If 14 W1 16, i.e. 15.9
Flaring connection
Gas side pipes
W3
Flaring connection Field pipe 19.1
W2 W3
Flaring connection
Field pipe 19.1
W1
Gas balance pipes 1
W2
Gas balance pipes 2
Welding
Field pipe 15.9 W1
Installation
Note: 1. It’s advised to use the max. HP unit as the main unit. See above figure W3 outdoor unit (main unit)
Arranging the units with a sequence of Max. to Min. (i.e. W3>W2>W1) Field pipe 19.1
2. The above figure is only available for the models as belows when they are paraelled connected :
YDS-252WA35 to YDS-450WA35
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FW04 Field pipe, the caliber refer to Table.3
If 8 W4 12, i.e. 12.7
If 14 W4 16, i.e. 15.9
Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3
If 50 W1+W2+W3+W4 64, i.e. 63.5 If 8 W4 12, i.e. 28.6; If 8 W3 12, i.e. 12.7
If 14 W4 16, i.e. 34.9; Flaring connection If 14 W3 16, i.e. 15.9
Field pipe, the caliber refer to Table.3 W4
If 8 W3 12, i.e. 28.6 Flaring connection Field pipe, the caliber refer to Table.3
If 14 W3 16, i.e. 34.9 If 8 W2 12, i.e. 12.7
Field pipe, the caliber refer to Table.3
Field pipe, the caliber refer to Table.3 If 50 W1+W2+W3+W4 64, i.e. 25.4.
W3 If 14 W2 16, i.e. 15.9
If 8 W2 12, i.e. 28.6
If 14 W2 16, i.e. 34.9 Flaring connection
W4 Liquid side joint E Flaring connection
Field pipe, the caliber refer to Table.3 W2
If 8 W1 12, i.e. 28.6 Field pipe, the caliber refer to Table.3
W3 If 14 W1 16, i.e. 34.9 If 34 W1+W2+W3 48, i.e. 22.2
joint C
caliber
the side
Field pipe, Gas W1
refer to Table.3
If W1+W2+W3=34, i.e. 41.3 W2
If 36 W1+W2 48, i.e. 54.0 Liquid side joint E
Gas side joint B W1 Field pipe, the caliber refer to Table.3
Field pipe, the caliber refer to Table.3
If 18 W1+W2 24, i.e. 19.1
If 18 W1+W2 24, i.e. 34.9 Liquid side pipes
If 26 W1+W2 32, i.e. 22.2
If 24 W1+W2 32, i.e. 41.3
W2
W1
283
Flaring connection
W3
Flaring connection
W2 Flaring connection
W1 W4
Field pipe 15.9 Field pipe 19.1
W1
Field pipe 19.1 Welding
YDSA/FAY01
YDSA/FAY02
YDSA/FWT02
284
YDSA/FWT03
Installation
YDSA/FWT04
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FWT02
W2
W2
Liquid side pipes
W1
W1
W2(main unit)
W1 Liquid side
Field pipe, the caliber refer to Table.3 joint C
If 18 W1+W2 24, i.e. 38.1
If 26 W1+W2 32, i.e. 44.5.
Mounting H
Liquid side
joint C
Mounting I
Gas side pipes
285
W2
W2
W1
Oil balance pipes 1
Welding
Gas balance pipes 2 W1
Welding Welding
Welding
Note: 1. It’s advised to use the max. HP unit as the main unit. See above figure W2 outdoor unit (main unit)
Installation
W2 W1
Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3 Liquid side
Liquid side pipes If 34 W1+W2+W3 48, i.e. 25.4.
If 34 W1+W2+W3 48, i.e. 54.0. joint C
W1
286
Gas side pipes
W3 W3
Field pipe 19.1
Field pipe 6.4 Note: 1. It’s advised to use the max. HP unit as the main unit. See above figure W3 outdoor unit (main unit)
Arranging the units with a sequence of Max. to Min. (i.e. W3>W2>W1) Field pipe 19.1
2. The above figure is only available for the models as belows when they are paraelled connected :
YDV-252WA35 to YDV-450WA35
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FWT04
Field pipe, the caliber
refer to Table.3
If 8 W4 12, i.e. 12.7
If 14 W4 16, i.e. 15.9.
Field pipe, the caliber
refer to Table.3
Field pipe, the caliber If 8 W3 12, i.e. 12.7
refer to Table.3 Field pipe, the caliber refer to Table.4
W4
If 14 W3 16, i.e. 15.9.
If 8 W4 12, i.e. 28.6 If 50 W1+W2+W3+W4 64, i.e. 25.4.
Field pipe, the caliber
If 14 W4 16, i.e. 38.1.
Field pipe, the caliber refer to Table.3
Field pipe, the caliber refer to Table.3 W3 If 8 W2 12, i.e. 12.7
refer to Table.4 Field pipe, the caliber refer to If 14 W2 16, i.e. 15.9.
If 8 W3 12, i.e. 28.6
If 50 W1+W2+W3+W4 64, Table.3
If 14 W3 16, i.e. 38.1. Field pipe, the caliber
i.e. 63.5. If 8 W2 12, i.e. 28.6
W4 W2 refer to Table.3
If 14 W2 16, i.e. 38.1.
If 8 W1 12, i.e. 12.7
Field pipe, the caliber refer to If 14 W1 16, i.e. 15.9.
W3 Table.3 W1
If 8 W1 12, i.e. 28.6
If 14 W1 16, i.e. 38.1.
W2 Field pipe, the caliber refer to Table.3
If 50 W1+W2+W3+W4 64, i.e. 28.6
Field pipe, the caliber refer to Table.3
If 50 W1+W2+W3+W4 64, i.e. 66.7. W1 Liquid side pipes
Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3
If 50 W1+W2+W3+W4 64, i.e. 66.7. W4(main unit) If 50 W1+W2+W3+W4 64, i.e. 28.6
W1
287
Gas balance pipes 2
W4
YDSA/FN01A
YDSA/FN01B
YDSA/FN02
288
YDSA/FN03
YDSA/FN04
Installation
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FN02 Field pipe, the caliber refer to Table.3
If 8 W2 12, i.e. 12.7( 9.5)
Field pipe, the caliber refer to Table.3
If 14 W2 16, i.e. 15.9( 12.7).
Field pipe, the caliber refer to Table.3 If 8 W2 12, i.e. 25.4( 22.2)
If 18 W1+W2 22, i.e. 31.8( 28.6) If 14 W2 16, i e. 31.8( 28.6). Field pipe, the caliber refer to Table.3 Flaring connection
If 24 W1+W2 32, i.e. 34.9( 34.9). If 8 W1 12, i.e. 25.4( 22.2)
If 14 W1 16, i e. 31.8( 28.6).
W2
W2 Flaring connection
W1
Liquid side pipes
W1
Field pipe, the caliber refer to Table.3
W2(main unit) If 18 W1+W2 24, i.e. 19.1( 15.9)
If 26 W1+W2 32, i.e. 22.2( 19.1).
W1
Flaring connection Liquid side joint D
Field elbow bend Field pipe, the caliber refer to Table.3
If 8 W1 12, i.e. 12.7( 9.5)
W2 If 14 W1 16, i.e. 15.9( 12.7).
Flaring connection
W1
Gas side pipes
289
W2
Field pipe 15.9 Rejoining method for D series outdoor unit
W1
Welding Welding
Field pipe 6.4 Note: 1. If the equivalent length of all liquid pipes<90 m, the caliber is the number in bracket.
2. It’s advised to use the max. HP unit as the main unit. See above figure W2 outdoor unit (main unit)
Arranging the units with a sequence of Max. to Min. (i.e. W2>W1)
3. The above figure is only available for the models as belows when they are paraelled connected :
D series, Digital scroll , YDS-252WC35 to YDS-450WC35
V series, DC Inverter , YDV-252WC35/36/26 to YDV-450WC35/36/26
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FN03
W3
Flaring connection
W3
Converter pipe W2
(gas pipe used) G Flaring connection
Gas side joint B
W1 W2 Flaring connection
Converter pipe(liquid pipe used) I Liquid side pipes
Converter pipe (gas pipe used) J
Field pipe, the caliber refer to Gas side joint A Converter pipe (liquid pipe used) I W1
W3(main unit)
Table.3 Liquid side joint E
If 18 W1+W2 22, i.e. 31.8( 28.6)
If W1+W2=24, i.e. 34.9( 34.9) W2
If 26 W1+W2 32, i.e. 38.1( 34.9) Field elbow bend
Converter pipe (liquid pipe used) I
W1 Liquid side joint D
Converter pipe (liquid pipe used) H
Flaring connection
Gas side pipes
W3
Flaring connection
W2
Flaring connection
W1
290
Field pipe 15.9
Gas balance pipes 2 W3
Gas balance pipes 1 M Rejoining method for D series outdoor unit Gas balance pipes 1(D series)
Field pipe 19.1
Oil balance pipes 1 (V series)
Field pipe 15.9
W2
Field pipe 15.9
Welding
W1
W3
Welding
Rejoining method for V series outdoor unit
Note: 1. If the equivalent length of all liquid pipes<90 m, the caliber is the number in bracket.
Field pipe 6.4
1. It’s advised to use the max. HP unit as the main unit. See above figure W2 outdoor unit (main unit)
Arranging the units with a sequence of Max. to Min. (i.e. W2>W1)
2. The above figure is only available for the models as belows when they are paraelled connected :
D series, Digital scroll , YDS-252WC35 to YDS-450WC35
V series, DC Inverter , YDV-252WC35/36/26 to YDV-450WC35/36/26
___________________________________________________________________________________
APPEARANCE AND CONNECTION SKETCH OF YDSA/FN04
Field pipe, the caliber Field pipe, the caliber refer to Table.3
refer to Table.3 If 8 W4 12, i.e. 25.4( 22.2); Flaring connection
If 50 W1+W2+W3+W4 64, If 14 W4 16, i.e. 31.8( 28.6).
i.e. = 44.5( 44.5). W4
Field pipe, the caliber refer to Table.3 liquid side joint E
If 8 W3 12, i.e. 25.4( 22.2); Flaring connection
If 14 W3 16, i.e. 31.8( 28.6). W3
Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3
If 8 W2 12, i.e. 25.4( 22.2); If 50 W1+W2+W3+W4 60, i.e. 25.4( 22.2). Flaring connection
If 14 W2 16, i.e. 31.8( 28.6). W2
W4 Converter pipe (gas pipe used) K Flaring connection
Field pipe, the caliber refer to Table.3 Field pipe, the caliber refer to Table.3
Gas side joint C If 8 W1 12, i.e. 25.4( 22.2); If 34 W1+W2+W3 48, i.e. 22.2( 19.1).
W3 W1
If 14 W1 16, i.e. 31.8( 28.6).
liquid side joint E
Field pipe, the caliber refer to Table.3 Liquid side pipes
Converter pipe W2 Converter pipe (liduid pipe used) I
If W1+W2+W3+W4=34, i.e. 38.1( 34.9) (gas pipe used) G
If 36 W1+W2+W3 48, i.e. 41.3( 41.3). Gas side joint B W4(main unit)
Field pipe, the caliber refer to Table.3
W1
If 18 W1+W2 22, i.e. 31.8( 28.6)
If W1+W2=24, i.e. 34.9( 34.9)
W3 Converter pipe (liquid pipe used) I
If 26 W1+W2 32, i.e. 38.1( 34.9). liquid side joint D
Gas side joint A W2 Converter pipe (liquid pipe used) H
W4
Flaring connection
291
W2 Flaring connection
W1
Field pipe 15.9
Gas balance pipes 2
Gas balance pipes 1 M
Field pipe 15.9 Rejoining method for D series outdoor unit
Field pipe 15.9 Gas balance pipes 1 M
W3
W4
Field pipe 19.1
Rejoining method for V series outdoor unit Welding
W3 W2
Welding
W2 Welding
Installation
Welding W1
W1 Field pipe 19.1
Field pipe 6.4 Welding
Welding Gas balance pipes 2 N
Gas balance pipes 1 P
Field pipe 6.4 Field pipe 19.1
Welding
Gas balance pipes 1 P Welding
YDSA/FQ01
YDSA/FQ02
YDSA/FQ03
292
YDSA/FQ04
YDSA/FQ05
Installation
YDSA/FQ06
___________________________________________________________________________________
Installation
At the same system, the laying form of shunt-wound outdoor units: the outdoor units are on the
same level, the branch joints for the outdoor units are on the same level, the T-shaped pipes for
connecting the balance pipes are installed vertically.
The laying form of Y-shaped branch pipes for shunt-wound outdoor units: Laying horizontally.
The laying form of T-shaped branch pipes for shunt-wound outdoor units: Laying horizontally.
The laying form of Y-shaped branch pipes for indoor units:
____________________________________________________________________________________
293
Installation
4.7) Precautions:
4.7.1 Refrigerant pipe must use the pipe with specified diameter.
4.7.2 Branch Part should be installed in horizontal mode or vertical mode.
4.7.2 Y shape three-way pipe should be installed in horizontal mode with ground.
4.7.4 Horizontal installation of throttling unit (throttling unit is an external unit, so it need be
connected on site)
Caution:
a. Install the throttling part upright, and ensure that it does not incline or is reversed.
b. Use two spanners to connect the electronic throttling part with the pipes of the indoor and
outdoor units, so as to avoid the copper pipe from deforming or getting broken.
c. Use flaring opening to connect the electronic throttling part with the pipes of the indoor and
outdoor units. Do not use welding for the connection, because the heat caused during the welding
process will be transferred to the electronic expansion valve via the copper pipe, which may
damage the electronic expansion valve.
d. Pay attention to the connection direction (refer to the label on the electronic throttling part).
e. For the installation size of the electronic throttling part, see the above figure.
____________________________________________________________________________________
294
Installation
4.7.5 Refrigerant fastness, the Refrigerant fastness, the distance between the supports of the
cross direction tube (copper tube):
Liquid pipe
Φ6.35 Φ9.5 Φ12.7 Φ15.9 Φ19.0 Φ22.0 Φ25.0 Φ28.6 Φ38.0 Φ45.0 Φ54.0 Φ67
dimension
Junction(90°elbow) 0.1 0.15 0.2 0.25 0.3 0.4 0.45 0.5 0.55 0.6 0.65 0.7
2) All the open tips of the pipes need to be protected. The best feasible means is Enveloping End,
and you can select the easy means of Wrapping. Refer to the following table to select the means
used in different sites.
♦ Envelop End: Welding the leak while clamping the end of the pipe.
____________________________________________________________________________________
295
Installation
- When putting the pipe through the hole, filth can easily enter into the pipe.
- When the pipe is outside, rainwater can easily enter into the pip, especially when the
Pipe is placed vertically.
Precautions:
♦ Protect the open end of the pipe against moisture, dust and litter.
♦ Before finishing pipe connection, place a cap at the open end of the pipe.
♦ A cap must be placed on the end of the pipe when the pipe crosses the hole in the wall.
____________________________________________________________________________________
296
Installation
♦ Don’t place the pipe on the ground directly or scratch with the ground.
♦ Cut the pipe and remove burrs with the cut surface downward.
♦ Be sure to place a cap when raining.
4.8.2 Welding
1) Be sure to weld horizontally or downward, not upward.
2) Pay attention to the installation direction and angle to prevent oil-return or oil-accumulation.
3) Its necessary to charge nitrogen when welding.
♦ Be far away from fire and prepare fire extinguishers and water to prevent fire on field.
♦ Be careful not to injure people.
♦ Confirm the proper clearance between pipe and connector.
♦ Check if the supporting structural members are strong enough.
♦ The traverse distances between supporting structural members are as follows:
Diameter (mm) Below 20 25~40 50
Max. Distance (m) 1.0 1.5 2.9
____________________________________________________________________________________
297
Installation
0.050~0.27
16<D<25 10
D
25<D<35 12
0.050~0.35
35<D<45 14
Torque
Dimension
(kgf ·m) (N·cm)
1/4"(Φ6.4) 144―176 1440―1720
3/8"(Φ9.5) 133―407 3270―3990
1/2"(Φ12.7) 504―616 4950―6030
5/8"(Φ15.9) 630―770 6180―7540
3/4"(Φ19.0) 990―1210 9270―11860
____________________________________________________________________________________
298
Installation
4.8.4 Laying
♦ Centralized laying, lying along the wall, and trying to make full of use of corridor.
♦ After finishing lying, binding up the refrigerant pipes with white binding-strap. After
finishing winding-up every pipe separately, please try to binding up all pipes together according to
the diameters and the degree of tightness should be based on no feeling of flexible.
♦ When installing the connection pipes and electric wires (power wire, control wire), they
should be laid along the wall, turn the corner logically, flat and straight, parallel with each other
and packed together. And try to avoid striding over and blocking the traffic.
♦ Try to bind up all pipes and no bareness is allowed at the connecting part.
4) Precautions about laying refrigerant pipes
♦ Pulling pipe: mark the system No. in the pipes to prevent wrong connection.
____________________________________________________________________________________
299
Installation
♦ When the end of the pipe can’t seal well, flushing can eliminate filter and humidity.
3) Jam well all the connection part in liquid side except indoor unit A.
4) Open the valve of nitrogen cylinder to 5kgf/cm2.
5) Check if there is nitrogen in liquid pipe of indoor unit A.
6) Flushing
♦Use the insulating material in hand to resist the nozzle of gas main pipe of the indoor unit.
♦When the pressure can’t be resisted, release the insulating material quickly (flushing for
the first time), then use the insulating material to resist the nozzle again (flushing for the second
time).
____________________________________________________________________________________
300
Installation
♦The dunghill can be checked by putting a piece of cloth in the nozzle loosely. Occasionally,
some dampness can be found, please dry the pipe thoroughly. Do as follows:
♦ Scouring the inner part of the pipes with nitrogen until no dampness.
♦Do the vacuum drying procedure (see the YDS refrigerant pipes vacuum drying in detail)
7) Close the nitrogen main valve.
8) Repeat the above operations.
9) After finishing flushing the liquid pipes, then flushing the gas pipes.
____________________________________________________________________________________
301
Installation
♦ Add and keep pressure 28.0kgf/cm2G for more than 24 hours, pass if there’s no
pressure drop. If the pressure falls, it should be corrected. After that, if the pressure is still lower
than that when adding pressure, the leakage should be checked out and corrected.
♦ Correcting method
♦
Correcting formula: actual value = pressure in the stage of adding pressure
+(temperature in the stage of adding pressure – observed temperature) x 0.1 kgf/cm2
____________________________________________________________________________________
302
Installation
♦ Compare the correcting value and adding pressure value to see whether the pressure
falls.
♦ Look up the leakage point in three phases when the pressure falls.
♦ Check the leakage by hands---put the hands in the pipe connection to check the
leakage.
♦ Check the leakage by suds---the leakage point will emit air bubble.
♦ Use halogen detector when finding the tiny leakage point or pressure falls but no
leakage point can be found during the adding pressure test.
♦ Add fluorine to the point 5.0 kgf/cm2 (mixed state of fluorine and nitrogen).
♦ If no leakage can be found, continue to add pressure to 28.0 kgf/cm2 , then check
again.
____________________________________________________________________________________
303
Installation
4) Precautions
- The maximum pressure in gas proof test should not exceed 28.0 kgf/cm2.
- If the pipe is too long, check by sections.
- Indoor side
- Indoor side + Vertical pipe
- Indoor side+ Vertical pipe +Outdoor side
____________________________________________________________________________________
304
Installation
♦ If the pump can’t achieve below -755mmHg after pumping 2 hours, moisture or leakage
point will still exist in the pipe. At this time, it should be pumped 1 hour more.
♦ If the pump can’t achieve -755mmHg after pumping 3 hours, please check if there’s
some leakage points.
♦ Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum
watch shows no rising. If it rises, it shows there’s moisture or leakage point.
♦ Vacuuming from liquid pipe and gas pipe at the same time.
____________________________________________________________________________________
305
Installation
____________________________________________________________________________________
306
Installation
____________________________________________________________________________________
307
Installation
Calculation
Equivalent Refrigerant for Pipe Length of 1m (kg/m)
Diameter of Liquid Pipe
R-22 R-410A
Φ6. 4 0.030 0. 022
Φ9. 5 0.065 0. 060
Φ12. 7 0.115 0. 110
Φ15. 9 0.190 0. 170
Φ19. 1 0.290 0. 250
Φ22. 2 0.380 0. 350
Φ25. 4 0.580 0. 520
Φ28. 6 0.760 0. 680
Note: Conversion of the equivalent length: Convert into the direct pipe length According to branch
Junction 0.5m/l.
Remark:
L1—Actual total length of Φ6.4 liquid pipe (m) L2—Actual total length of Φ9.5 liquid pipe (m)
L3—Actual total length of Φ12.7 liquid pipe (m) L4—Actual total length of Φ15.9 liquid pipe (m)
L5—Actual total length of Φ19.1 liquid pipe (m) L6—Actual total length of Φ22.2 liquid pipe (m)
L7—Actual total length of Φ25.4 liquid pipe (m) L8—Actual total length of Φ28.6 liquid pipe (m)
____________________________________________________________________________________
308
Installation
Caution:
For different series of air conditioning system, the calculating formula of refrigerant to be
supplemented might be different, so it is necessary to checkup the “formula in installation
information” attached with outdoor unit. Formula in installation information is superior to prevent
error.
♦ Write the added volume in the outdoor nameplate.
♦ The added volume must be measured with electron scale.
♦ The total real length includes two parts: one is total pipe length; the other is the equivalent
length of curves or elbows.
____________________________________________________________________________________
309
Installation
3) Precautions
♦ The diameter of drainpipe should meet the drainage requirement at least.
♦ The drainpipe should be heat-insulated to prevent atomization.
♦ Drainpipe should be installed before installing indoor unit. After powering on, there is some
water in water-receiver plate. Please check if the drain pump can act correctly.
♦ All connection should be firm.
♦ Wipe color on PVC pipe to note connection.
♦ Climbing, horizontal and bending conditions are prohibited.
♦The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
♦ Heat-insulation should be done well to prevent condensation.
♦Indoor units with different drainage type can’t share one convergent drainpipe.
5.2) Drainpipe Trap
1) If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe
trap.
2) Every indoor unit needs one drainpipe trap.
3) A plug should be designed to do cleaning.
50cm 50cm
Pl ug
To ensure the gradient 1/100, the drainpipe can be lifted to 340mm. After upwards, place downwards,
or it will cause malfunction to drain pump.
____________________________________________________________________________________
310
Installation
1) The number of indoor units should be as small as possible to prevent the traverse main pipe
overlong.
2) Indoor unit with drain pump and indoor unit without drain pump should be in different
drainage system.
____________________________________________________________________________________
311
Installation
♦ Turn on the power to cooling operation. Check the pump’s operation and switch on the Water
Level Switch. Check the pump’s sound and look into the transparent hard pipe in the outlet at the
same time to check if the water can discharge normally.
♦ Stop the air conditioner running, turn off the power, and put back the cover.
♦ Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drain
pipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even
circumfluence from the water plate.
♦ Keep on pouring water until it gives an alarm signal for high water level, check if the pump
drains water at once. If the water level can’t fall below the alarmed water level after 3 minutes, the
air conditioner will stop (means this indoor unit stops, stand-by, but the outdoor unit still work if
there is capacity requirement). Turn off the power and drain the remained water, and then turn on
the air conditioner.
Note: the drain stopper in the main water plate is for maintenance. Stuff up the drain stopper
to prevent water leakage.
____________________________________________________________________________________
312
Installation
no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side (For the
cooling type machine, no requirements at the low-pressure side.)
____________________________________________________________________________________
313
Installation
Wrong Right
Gas pipe and liquid pipe Insulate the gas pipe Insulate the gas pipe and
should (Cooling only) the liquid pipe
For construction convenience, before laying pipes, use insulation material to insulate the
pipes to be deal with, at the same time, at two tips of the pipe, remain some length not to be
insulated, in order to be welded and check the leakage after laying the pipes.
(3) Insulate for the jointing area, expanding area and the flange area
♦ Insulate for the jointing area, expanding area and the flange area should be done after
checking leakage of the pipes
♦ Make sure there’s no clearance in the joining part of the accessorial insulation material and
local preparative insulation material.
____________________________________________________________________________________
314
Installation
- The connection part should be insulated, or else water will be condensing at the
non-insulation part.
6.4) Note
(1)The jointing area, expanding area and the flange area should be heat insulated after passing
the pressure test
(2) The gas and liquid pipe should be heat insulated individually, the connecting part should be
heat insulated individually.
(3) Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie in,
expand nut ) of the indoor unit.
____________________________________________________________________________________
315
Installation
7. Pipeline Installation
7.1) Pipeline facture
(1) The material of the pipeline
Standard: lubricity inside; small friction resistance; not absorbing moisture; incombustibility;
erosion resistance; longevity; lightness; good sealing; no accumulation; easily cleaning. Normally,
we can select galvanization steel, aluminum, and plastic. For short pipeline, we can also select
aluminum foil board.
(2) The process of the piping
The process of the piping should meet the requirements of the design. The process can be
done in subsection. And every subsection’s length is about between 1.8m and 4m. In order to
improve the pipeline’s rigid, a rib often be added at the outer surface. The pipeline usually adopts
the flange to connect and add the asbestos washer with thickness 3mm to prevent air leakage. At
present, the sealant and adhesive tape are also used to seal.
(3) The shape of the pipeline
Pipeline diameter
Accessorial Accessorial Accessorial
Basic series Basic series Basic series
series series series
100 80/90/100 300 300/320 900 850/900
120 110/120 360 340/360 1000 950/1000
140 130/140 400 380/400 1120 1060/1120
160 150/160 450 420/450 1250 1180/1250
180 170/180 500 480/500 1400 1320/1400
200 190/200 560 530/560 1600 1500/1600
220 210/220 630 600/630 1800 1700/1800
250 240/250 700 670/700 2000 1900/2000
280 260/280 800 750/800
____________________________________________________________________________________
316
Installation
(5) The hanger of insulated pipeline should set outside the insulation layer and can’t injure the
insulation layer.
(6) The distance between hangers:
Diameter (long border) Diameter (long border)
dimension< 400mm dimension≥ 400mm
Horizontal distance ≤4mm ≤3mm
≤4mm,the part for fixing of every vertical pipeline
Vertical distance
should not less than 2
____________________________________________________________________________________
317
Installation
(1) Type
Familiar outlet type: Louver outlet, disperser and linear outlet.
Linear outlet
(2) Specification
The specification of the air-outlet should be based on outer-diameter and outer-line.
♦Allowed tolerance of round air-outlet (mm)
Air-outlet: In the design and construction, no matter cooling and heating, cooling and heating are
sent to places through air-outlet, so it’s important to select the right air-outlet.
____________________________________________________________________________________
318
Installation
♦ Indoor fitment
♦ Try to assure the equality of the indoor parameters (especially the temperature)
♦ The air-inlet shouldn’t be set at places where people stays long to prevent short-circuit
and open-circuit. If adopting side-sending, it is suitable to set at the same side of the air-outlet.
♦ For side air-inlet, normally, it is set under the same side. If adopting parallel air-sending,
the air-inlet also is set underside mostly. In order to avoid dust and filter, the height from the
underline of the air-inlet to the ground should at least keep 0.15m. For high big workshops, it is
suitable to add air-inlet or discharge air-let to discharge surplus-heat.
♦ The distance from the air-inlet of the scatter setting to the wall should not less than
half of the space between scatter settings.
Fresh air-let:
♦ Fresh air-let should be set at clean places and far away from discharge air-let.
♦ Fresh air-let should be set in the shade and avoid roof and west-wall. The distance
from the ground is at least 2m and 1m in case of green ground. And shutter is needed under the
air-let.
____________________________________________________________________________________
319
Installation
♦ Pay attention to the insulation of pipeline and the condensing water in the outlet.
♦ The appearance of the air-outlet hasn’t obvious impress, nick and spot. The color should
be consistent and welding points should be lubricous.
♦ The match between inner sphere and outer sphere of spherical air-outlet should rotate
freely and isn’t flexible after orientation.
♦ The diffusing loop and modulation loop of the scatter setting should be at the same axis
and space distributing in radial direction should be even.
____________________________________________________________________________________
320
Installation
8. Electric Installation
-Electric installation must be carried out according to National Standard.
-This chapter is just for reference.
8.1) Brief Introduction
♦ Please select power supply for indoor unit and outdoor unit separately.
♦ The power supply should have specified branch circuit with leakage protector and manual
switch.
♦ The power supply, leakage protector and manual of all the indoor units connecting to the
same outdoor unit should be universal. (Please set all the indoor unit power supply of one system
into the same circuit.)
♦ It is suggested to use 3-core shielded wire as signal wire between indoor and outdoor
units, multi-core wire is unavailable.
♦ Please put the connective wiring system between indoor unit and outdoor unit with
refrigerant piping system together.
381-415V 50/60 Hz 3 ph
220V 60Hz Hz 3 ph
____________________________________________________________________________________
321
Installation
4×16(L≤29m)
100 mA
25.2-28.0 kW 380-415V,3N~60Hz 4×25(L≤46m) 16 60 50
under
4×35(L≤78m)
0.1sec
33.5-45.0 kW 380-415V,3N~60Hz 35(L≤78m) 16 80 70
4×16(L≤20m)
25.2-28.0 kW 220V,3N~60Hz 16 60 50
4×25(L≤50m)
4×25(L≤20m)
33.5-45.0 kW 220V,3N~60Hz 16 80 70
4×35(L≤50m)
Note: The wiring diameter and the length in the table indicate the condition that the voltage
dropping range is within 2%. If the length exceeds the above figure, please select the wire
diameter according to relevant standard.
____________________________________________________________________________________
322
Installation
____________________________________________________________________________________
323
Installation
Note: the data in the above table is under the condition that the voltage decreases no more than
2%. If the length of wiring is more than the data in the diagram, please select wires according
to certain standards.
Note: The length in the table equals the value of power cord connecting parallel indoor units,
indicating the condition that the voltage dropping range is within 2%. If the length exceeds the
above figure, please select the wire diameter according to relevant standard.
____________________________________________________________________________________
324
Installation
Note:
1. Set refrigerant piping system, signal wires between indoor-indoor unit, and that between
outdoor-outdoor unit into one system.
2. Please do not put the signal wire and power wire in the same wire tube; keep distance between
the two tubes. (Current capacity of power supply: less than 10A--300mm, less than
50A--500mm.)
3. Make sure to set address of outdoor unit in case of parallel multi-outdoor units.
____________________________________________________________________________________
325
Installation
____________________________________________________________________________________
326
Installation
____________________________________________________________________________________
327
Installation
____________________________________________________________________________________
328
Installation
1) Communication wire should be 3-core shield wire; there should be metal-shield layer twist.
Otherwise it will be easily interfered and bring wrong action.
2) And the size should be above 0.75mm2 (Diameter.)
3) The material is RVVP (copper core PVC-insulated PVC-sheathed metal shielded flexible cable)
or RVVP1(copper core PVC-insulated PVC-sheathed metal twisted shielded flexible cable) series
4) It has three cores (X, Y, E) inside, and E is a 5V layer.
5) The metal layer should be grounded well indoor control box in order to prevent interference.
____________________________________________________________________________________
329
Installation
220V
50/60
Hz
Note:
1. The signal connecting line between outdoor units, indoor and outdoor units and indoor units
has polarity. When connecting, be careful to prevent error connection.
2. Signal line shall adopt three-core shielded wire with an area above 0.75 mm2.
3. Do not bind signal line and copper pipe together with belting.
____________________________________________________________________________________
330
Installation
RS232
connector: connect
with compuer COM correct communication cable treatment
plug
120Ω
DCM
RS485 to RS232 NO.1Indoor unit NO.2Indoor unit NO.3Indoor unit
Other
central
controller
All in group
Online units ON OFF
Mode Auto
off
on
1#Indoor Unit
In Group
E rro r Code
P rotecti on Code Curren t Function
Conflict
Central controller
120Ω
120Ω
network communication
Power220V ~
A/C communicaton
Conection Connection
A ll in group
No2
Room Temp.
K1 K2 E K1 K2 E K1 K2 E K1 K2 E
Set Temp.
Communication Communication
No1 No2 Communication L N K1 K2 E F2 F1
off
No1 slave
16#indoor unit
on
Communication In G roup
auxiliary unit
Master auxiliary unit auxiliary unit auxiliary unit
Unit Operation state set failure
controller
ABCN ABCN ABCN ABCN
Notice:
1.Four communications:PQE(beween indoor unit and
outdoor unit);XYE(between indoor unit and indoor unit
central controller);K1K2E(between outdoor unit and
outdoor unit central controller) ;F1F2E(bewteen PC and
Note: indoor/outdoor unit central controller).communication line
must use shield three-core line ,and should add resisitance
1.Power supply of outdoor unit must be connected with ammeter first, Outdoor Unit
according parameters of outdoor unit to choose the wire dia. of 120 ohm for head and end of each communication, pay
2.The wire controller can max. connect with 32 sets of outdoor units. attention to the polarity;the longest distance of each
communication line is 1000m;
120Ω 2.There is a shield three-core communication line between
120Ω
ammeter and outdoor unit according to the distance
E-part
between outdoor unit and ammeter, one outdoor unit
E-part E-part E-part
box
K1 K2 E
box
K1 K2 E
box
K1 K2 E
box
K1 K2 E matchs a ammeter;
16#outdoor unit
L N K1 K2 E F2 F1
No X NoX
No10 Power220V ~
central controller
wiring terminal
communication communication unit communication communication Unit
unit
No10 No10 No X No X
Master unit Slave unit Master unit Slave unit
Ammeter Ammeter Ammeter Ammeter
Note: The 120 ohm resistance can be cancelled because we have strengthened the anti- interfere
capacity in the program.
____________________________________________________________________________________
331
Controller
___________________________________________________________________________________
- 332 -
Controller
___________________________________________________________________________________
Contents
- 333 -
Controller
___________________________________________________________________________________
1. Control system
1.1) Brief introduction about controlling system
The control system adopts modular design, that is, all indoor units communicate with
outdoor units, refer to the following figures for the control structure between indoor units and
outdoor units. In the structure, the indoor control board receives the information from users (for
exam. set temp., fan speed etc.) and environment (ex, indoor coil temp., indoor temp. etc.) ,and
organize it to control the action of relevant parts such as EXV, four-way valve etc , then
transmits the signals to outdoor control board through the following communication circuit.
Outdoor main control board can deal with the information from indoor unit and figure out the
best running mode, and then transfer the instruction to the outdoor Slave units and indoor units
to carry out it.
- 334 -
Controller
___________________________________________________________________________________
Remark:
- 335 -
Controller
___________________________________________________________________________________
1.2) Outdoor electric control board
- 336 -
Controller
___________________________________________________________________________________
No. Contents
1 No.1 fixed compressor discharge temperature detect port
2 Digital compressor outlay discharge temperature detect port
3 Digital compressor inlay discharge temperature detect port
4 Phase sequence detection
5 Phase C power
6 Power input for transformer
7 Load output
8 Load output
9 Load output
10 Load output
11 Power output for transformer
12 Load output
13 Electric expansion valve drive port
14 Electric expansion valve drive port
15 Communication between indoor/outdoor units
16 No.2 Fixed compressor current detect mutual-inductor
17 No.1 Fixed compressor current detect mutual-inductor
18 Digital compressor current detect mutual-inductor
19 Ambient temperature detect port
20 Outdoor unit condenser coil pipe temperature detect port
21 Low pressure detect switch signal input port
22 High pressure detect switch signal input port
23 Communication between outdoor units
24 Reserved
25 Reserved
26 Reserved
27 Reserved
28 No.2 fixed compressor discharge temperature detect port
- 337 -
Controller
___________________________________________________________________________________
Sw4 query instructions:
Remarks: When the check is end (step 23), if you press the check button again, LED will
normally display the capacity demand. If you press the check button over again, the whole check
process will be cycled display.
When stand by, LED displaying the amount of indoor units which communicate with
Normally display: outdoor units; When operation, LED displayed open degree of running frequency of
inverter compressor when there is capability demand.
Running mode: 0---Turn off; 1---fan only; 2---Cooling; 3---Heating; 4---Forced cooling
Outdoor fan speed: 0---Turn off; 1---Low speed; 2---High speed
- 338 -
Controller
___________________________________________________________________________________
Address dial switch Main or auxiliary units Power dial switch Capacity
0 Master unit 0 8HP
1 Slave unit 1 1 10HP
2 Slave unit 2 2 12HP
3 Slave unit 3 3 14HP
>=4 Error 4 16HP
------------------- >=5 Error
- 339 -
Controller
___________________________________________________________________________________
E2 Communication malfunction between indoor/master outdoor unit All the outdoor units display
- 340 -
Controller
___________________________________________________________________________________
- 341 -
Controller
___________________________________________________________________________________
3. ENC2 (NUM_S) ― Number Setting (for outdoor)
The present address setting has been put outside the electric control board for convenient
setting. The range is 0-F. Before indoor units are power on, the address setting must be finished
and the address setting of indoor units that match with the same outdoor unit can’t be repeated,
or it may cause compressor jumping-down, indoor EXV can’t open, indoor fan motor jumping-
down, and so on. After finishing address setting, indoor units must be power on again and
address setting must be checked again to ensure no repeated setting. The checking method is
as follows: press the button on the display board for 5 seconds, the display board will display
address setting, continue to press for 5 seconds, the display board will display power setting.
The setting is as follows:
Operation Timer lamp Defrosting lamp Alarm lamp Communication Address Indoor kW
lamp
0
OFF OFF OFF ON 1 2.8 kW
OFF OFF ON OFF 2 3.6 kW
OFF OFF ON ON 3 4.5 kW
OFF ON OFF OFF 4 5.6 kW
OFF ON OFF ON 5 7.1 kW
OFF ON ON OFF 6 7.2 kW
OFF ON ON ON 7 9.0 kW
ON OFF OFF OFF 8 11.2 kW
ON OFF OFF ON 9 14.0 kW
ON OFF ON OFF 10
ON OFF ON ON 11
ON ON OFF OFF 12
ON ON OFF ON 13
ON ON ON OFF 14
ON ON ON ON 15
16
OFF OFF OFF Flash 17 2.8 kW
OFF OFF Flash OFF 18 3.6 kW
OFF OFF Flash Flash 19 4.5 kW
OFF Flash OFF OFF 20 5.6 kW
OFF Flash OFF Flash 21 7.1 kW
OFF Flash Flash OFF 22 7.2 kW
OFF Flash Flash Flash 23 9.0 kW
- 342 -
Controller
___________________________________________________________________________________
Flash OFF OFF OFF 24 11.2 kW
Flash OFF OFF Flash 25 14.0 kW
Flash OFF Flash OFF 26
Flash OFF Flash Flash 27
Flash Flash OFF OFF 28
Flash Flash OFF Flash 29
Flash Flash Flash OFF 30
Flash Flash Flash Flash 31
The indoor and outdoor units adopt RS-485 communication standard. P and Q are for
communication and have polarity. E is shield layer and is connected to +5V on the display board
to strengthen the anti-jamming ability of the communication wire. When the indoor and outdoor
units can’t communicate for 1 minute, it will display communication malfunction.
- 343 -
Controller
___________________________________________________________________________________
8. CN14―SWING
13. CN13―SWING
Output 220 V. Use 220V synchronization swing-motor. The action is as same as CN14 step-
motor.
- 344 -
Controller
___________________________________________________________________________________
14. CN3―PUMP
220 V output. When indoor unit starts to cooling operation, the pump starts at once and
running continue until stopping this mode. At any time, if the water-level in the water receiver
raises to the position point of the water-level switch, that is, the water-level switch signal is cut
down, the pump will start at once and forced running. If the water level falls to below the alarm
water-level (the drain pump delay 1 minute to be off), operation recovers according to former
setting mode. On the otherwise, after 3 minutes, indoor unit stops (Including pump) and display
water-level alarm signal, and indoor unit takes part in the whole system operation according to
standing-by mode. When again checking the water-level alarm signal is off, the protection will
be released and recover operation according to former setting.
20. CN6―T1, T2
- 345 -
Controller
___________________________________________________________________________________
1 2
00 ~ 15
~
ON
16 ~ 31
1 2
~
ON
32 ~ 47
1 2
~
ON
48 ~ 63
1 2
~
- 346 -
Controller
___________________________________________________________________________________
♦ System will not carry out the AUTORESTART function for the first time power on.
♦ During operating or stand-by, if power failure occurs, previous settings will restore after
supplying power again.
♦ The following settings can be restored after power failure occurs: ON/OFF, MODE, FAN
SPEED, and TEMP. LOCK by CCM and so on. And the following can’t be remembered:
ECONOMIC, TIMER ON, TIMER OFF, SLAVE Function and so on.
- 347 -
Controller
___________________________________________________________________________________
♦ AUTORESTART is only valid to the remote control signal receiving through NIM or information
set by distance-control. It doesn’t remember the operation by manual button and forced button.
If power failure occurs and the air-conditioners are in operation by manual button or forced
button, after supplying power again, no AUTORESTART signal will be sent to air-conditioners
and the air-conditioners will be in stand-by.
♦ AUTORESTART has time-delay start function, which can avoid all air-conditioners start at the
same time when power on. The delay time is decided according to the address code in LAN.
And the calculation formula is 180s+n*2s, where, n means the address code and the effective
range is 0-63, and “s” means time unit Second. When the set delay time is arrived, send
AUTORESTART signal to PCB.
♦ During AUTORESTART time-delay, if the air-conditioners receive the Mode set operation by
users, including distance-control and local-control, the air-conditioners will cancel
AUTORESTART and run according to the present operation by users.
- 348 -
Controller
___________________________________________________________________________________
00 ~ 15
1 2 ~
ON
16 ~ 31
1 2
~
ON
32 ~ 47
1 2
~
ON
48 ~ 63
1 2
~
- 349 -
Controller
___________________________________________________________________________________
- 350 -
Controller
___________________________________________________________________________________
f. Lock Symbol means the CCM is in Lock state or the buttons are in Lock state. ON means
the buttons are in Lock state or both CCM and Buttons are in Lock state, and 0.5 second flash
means the CCM is in Lock state.
g. When setting page layout, if the selected air-conditioner is in Remote Controller Lock state
(in case that several air-conditioners are in operation, if only one is in Remote Controller Lock
state, then that means in Lock state.), symbol will display steadily. If in Mode Lock state,
Mode Lock state exist at the same time, symbol will display steadily.
Data Display area adopts 7-segment code, and there are 5 groups of 2-digital 7-segment
display.
a. TEMP. Display
TEMP. Display is applicable to the following: Set Temp. Ts(17-30℃), Indoor Return Air
Temp. T1, Evaporator Pipe Temp. T2A, Evaporator Middle Pipe Temp. T2B, Condenser Pipe
Temp. T3. And the allowable data display range is 0℃--99℃. If higher than 99℃, then display
99℃. If lower than 0℃, then display 0℃. What’s more, the real display range also has
relationship with the PCB temperature checking range. If no effective data, then display “-“and
Unit symbol ℃ will be ON.
b. CURRENT Display
CURRENT display is applicable to Compressor Current. The allowable range is 0A-99A. If
no effective data, then display “-“and Unit symbol mp will be ON.
- 351 -
Controller
___________________________________________________________________________________
c. TIMER Display
TIMER is used to display the time of TIMER ON and TIMER OFF. The unit symbol Hr will
be ON at the same time.
d. ERROR code display
ERROR is used to display malfunction warning data of the air-conditioner or the CCM.
The display range of ERROR code is E0-EF, where, E means ERROR; 0-F means ERROR code, or
Network ERROR display 00-0F#. If no EEROR, then display “E-“and ﹟ will be ON.
e. PROTECT. Code display
PROTECT. Is used to display malfunction warning data of the air-conditioner or the CCM.
The display range of PROTECT. Code is P0-PF, where, P means PROTECT, 0-F means PROTECT.
Code. If no PROTECT, then display “P-“and will be ON.
f. ADDRESS display
ADDRESS is used to display the ADDRESS code of the present selected air-conditioner.
The display range is 0-63, and at the same time will be ON.
g. Number Display of Online air-conditioners and ON/OFF air-conditioners
It is used to display the number of online air-conditioners in LAN and ON/OFF air-
conditioners at present. The display range is 0-64.
h. Auxiliary function display
Stand-by page data consist of several pages and the page number is not fixed.
Stand-by page can display the total number of air-conditioners in network, under ON state
and under OFF state. If one or more air-conditioners in network have malfunction, or the CCM
checks other malfunctions, the Stand-by page will display the first ERROR Code from small to
big according to the number. Other malfunctions can be queried by buttons “+” and “-“. If no
malfunction and one or more online air-conditioners in network are in ON state, the Stand-by
page will display present main Running Mode, Set Temp. And Indoor Fan Speed. If no
malfunction and all air-conditioners in network are in OFF state, ERROR Code nor Running mode
will not be displayed.
Query Page data consist of several pages and the page number is not fixed.
a. When first entering into Query Page Display, the address of the first online air-conditioner
will be selected in default and the data of the first page will be displayed.
b. The data of other pages can be displayed in circulation by pressing buttons “+” or “-”.
- 352 -
Controller
___________________________________________________________________________________
c. The running state data of different air-conditioners can be queried by pressing “Previous” or
“Next” to select the address.
5) Running Mode Setting Page Display
Running Mode Setting Display only has one page. And display the selected mode, auxiliary
function and the selected operation state.
6) Installation
NOTE
z Never turn screws too tightly, otherwise the cover would be dented, or the Liquid Crystal
would be broken.
z Do not cut wires when installing the cover of Central Control Monitor.
2. Installation
Terminals P, Q, E at the back of CCM are connected to the terminal P, Q, E of PC.
The CCM power connects 220V~ 50Hz power directly to the terminal L, N, At the
back of wire controller.
1) The communication cable of CCM and power cable should not be placed in the same
electrical wire tube and the two tubes should have 300-500mm distance.
2) The length of CCM communication cable should not exceed 1200m.
- 353 -
Controller
___________________________________________________________________________________
3) The shield cable should try to avoid middle transfer connector. If have connectors, it had
better to connect by terminal block.
4) After finishing connection, do not use Megger to have the insulation check to the signal wire.
The communication port between CCM and NIM has polarity, and terminal X, Y, E must
connect to the responding X, Y, E. It is the same for the port between CCM and module of
Rs485 to Rs232.
- 354 -
Controller
___________________________________________________________________________________
2.2.2 AMR03Y Indoor central controller
- 355 -
Controller
___________________________________________________________________________________
1. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two
blocks of different sizes (as shown in the above figure).
2. The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates
00+, 16+, 32+ and 48+ on the left side, which indicate the address of the indoor unit. The sum
of the horizontal coordinate and the vertical coordinate of the grid is the address of the grid.
Each grid corresponds to an indoor unit of this address.
3. One grid is composed of two blocks of different sizes. The status
- 356 -
Controller
___________________________________________________________________________________
1) The LCD displays the standby page, 60 air conditioners are in service, of which 28 are
powered on and 32 off.
2) In the matrix, the big dots of (00, 16+) and (15, 32+) are luminous, and the small dots are not
luminous. It indicates the 32 air conditioners with the addresses from 16 to 47 are powered off.
3) In the matrix, the big and small dots of (09, 48+) and (12, 48+) are not luminous. It indicates
the four air conditioners with the addresses from 57 to 60 are outside the network.
4) All other big and small dots in the matrix are luminous. It indicates all other air conditioners
are in the network and powered on.
5) The address of the air conditioner is sum of the coordinates. For example, the address of
(09, 48+) is 09+48=57.
6) The centralized controller keypad is locked, and the centralized controller communicates
with the computer normally.
1) The LCD displays the query page, and the air conditioner with the address of 08 is being
queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor
temperature 22°C, set temperature 20°C, cooling mode “lock”.
2) In the matrix, only the big and small black dots at (00, 00+) and (01, 00+) are luminous. It
indicates the in-service and power-on status of the air conditioners with the addresses of 00
and 01.
3) The centralized controller communicates with the computer normally.
- 357 -
Controller
___________________________________________________________________________________
- 358 -
Controller
___________________________________________________________________________________
2.2.3 AMR09Y Indoor central controller
Designed base on the CCM03, max. 64 indoor units control, weekly schedule timer
function.
Note: It can’t be connected to the network control system.
Dimensions
- 359 -
Controller
___________________________________________________________________________________
Installation Method:
Connecting diagram of network-based air conditioning system (There are two types of
indoor units, namely indoor unit with external network interface module on the main control
board or built-in network interface module in the main control board.)
General drawing of the liquid crystal display of the weekly-timer central controller:
- 360 -
Controller
___________________________________________________________________________________
- 361 -
Controller
___________________________________________________________________________________
Key instructions of the weekly-timer central controller:
Key Name Usage
Press the ON/OFF button. All air conditioners will be shut down if they are running; on the contrary,
they will be started up. If you press the button for less than 5 seconds, the startup mode is the last
running mode of the air conditioner. If you press the button for more than 5 seconds, the startup mode
is cooling, high Speed, 24 degrees.
Press the “SET” button, and then select “set single” or “set all”. “Set single” indicates to set the
parameter (such as mode/ temperature/Fan speed/ weekly timer) of an selected air conditioner. “Set all”
indicates to set the parameter of all air conditioners controlled by the central controller.
Press the “query” button to query the running condition of the air conditioner, such as on/off,
temperature setting, indoor temperature, running mode and Fan speed. Press “up”, “down”, “Left” and
“right” to select the air conditioner that you want to query.
When querying or setting the indoor unit, press the “up” to select the indoor unit to be set or queried.
When querying or setting the indoor unit, press “down” to select the indoor unit that you want to set or
query.
When querying or setting the indoor unit, press “Left” to select the indoor unit to be set or queried. In
setting the weekly timer, it is used for selecting the day of the week and the time of startup and
shutdown.
When querying or setting the indoor unit, press “right” to select the indoor unit to be set or queried. In
setting the weekly timer, it is used for selecting the day of the week and the time of startup and
shutdown.
When querying the indoor unit, press the “Add” button to query more parameter of the indoor unit. In
setting the indoor unit, it is for modifying the setting temperature. In setting the weekly timer, it is for
modifying the time of startup and shutdown.
When querying the indoor unit, press the “Reduce” button to query more parameter of the indoor unit.
In setting the indoor unit, it is for modifying the setting temperature. In setting the weekly timer, it is for
modifying the time of startup and shutdown.
In setting the indoor unit, it is used for setting the running mode of the indoor unit which includes
Automation, Cool, Heat, Fan Only, Dry and Off. You can select among them.
In setting the indoor unit, it is for setting the wind speed of the indoor unit which includes high speed,
middle speed, low speed and automatic speed. You can select among them.
In setting the indoor unit, it is for setting the swing-function of the indoor unit. The running mode is
selected between “swing-on” and“swing-off”.
When setting, press the “Lock” button to lock the remote controller of all or single indoor unit. Press
the “Query” button and hold under the main page, then repress the“Lock” button again to lock the
keyboard of the central controller; press the “Mode” button and then repress the “Lock” button to lock
the running mode.
The central controller re-scans the indoor unit in the network as recharging after power off.
Under the main page, press the “Program” button to set the weekly timer of “single indoor unit” or “all
indoor units”. Press the “Query” button and hold, and then press the “Program” button to query the
weekly timer parameters of the indoor unit.
Under the main page, press the “Weekly” button to start up or shut down the weekly timer function. .
Under the main page, press the “Time” button for 5 seconds to enter the time-modifying status, and
then press “Add” or “Reduce” button to modify the time. Press “Left” or “Right” to select minute/ hour/
day/ month/ year. Finally, press the “Confirm” button to save the modification.
Save data and send the command required to the indoor unit, such as setting the mode of the air
conditioner.
Cancel the last operation and return to the last interface.
- 362 -
Controller
___________________________________________________________________________________
- 363 -
Controller
___________________________________________________________________________________
- 364 -
Controller
___________________________________________________________________________________
- 365 -
Controller
___________________________________________________________________________________
3.3) Operation
Indicator Display:
Indicator lamp will be on when the CCM is power on.
CCM Locked:
All the other button will not be on controlled anytime when pushing the CCM is locked.
And unlock happens when receiving the lock.
- 366 -
Controller
___________________________________________________________________________________
2) Figure and function
- 367 -
Controller
___________________________________________________________________________________
3) Data
♦ Mode display:
means cool,
means heat,
means shut off,
- 368 -
Controller
___________________________________________________________________________________
means locked heat.
NOTE: The page will increase or decrease by 1 every time you press “PAGE UP” or “PAGE
DOWN”. Select the online outdoor unit by push the “previous” or “next” freely.
- 369 -
Controller
___________________________________________________________________________________
ERROR Code ERROR Contents Description ERROR Code ERROR Contents Description
Outdoor adding
H3 malfunction (valid for PA Defrost Protection
host unit)
Outdoor decreasing
Compressor Current
H2 malfunction (valid for P8
3rd Protection
host unit)
Discharge Low-
E2 Sensor malfunction P2
pressure Protection
Discharge High-
Communication
pressure Protection
E1 E0 malfunction Phase P1 P0
Compressor High
sequence or lack of phase
Temp. Protection
PF Other Protection
PE Oil Balance
PD Oil Return
- 370 -
Controller
___________________________________________________________________________________
4. 3rd Intelligent Network Control & Monitor System
2) Applications
This network system is ideal for applications in small and medium-sized buildings and can
manage up to 1024 indoor units and 512 outdoor units. It is mainly used for centralized
monitoring and controlling of air conditioning system of small and medium-sized buildings.
3) Characteristics
3.1 The system adopts constructive concepts, where the system assigns some properties
to the air conditioners so that the air conditioners can contact with outdoor units and sets and
meanwhile have billing features during use.
3.2 The system adopts the concept of hierarchical users to ensure the all the operations
of users will not influence correctness of system data
3.3 The system pays attention to the operation data of indoor and outdoor units and this
provides basis for future maintenance of air conditioners.
3.4 The YDS LON gateway offered by the system can facilitate control of system air
conditioners by outside LON.
3.5 The system can select electricity allotment by changing the property of indoor unit.
3.6 The system can rapidly prompt the faults and troubleshooting method of a certain air
conditioner within the system.
3.7 The system can fulfill on-line diagnosis service through INTERNET to ensure safe use
of your air conditioning system.
- 371 -
Controller
___________________________________________________________________________________
4.2 Requirement of network system
1) Hardware Requirement
Watt hour Function:Dynamically change the address of Zhengtai DTS634 Conform to DL/T
meter(WHM) WHM as per the standard and display the 645-1997 standard
reading of WHM as per the dynamic address of
main board input
Softdog Yingdu
2.1.1 The functions of indoor centralized controller include transmission of status information of
indoor unit to the computer and of the control and query commands from the computer, and
meanwhile it can query for the status of indoor unit and send control commands.
2.1.2 Overview of indoor centralized controller
♦ An indoor centralized controller and 64 YDS indoor units of air conditioner form an air
conditioner LAN and thus centrally control all the air conditioners within the LAN, where various
control commands can be sent to the indoor units and status can be set up to satisfy various
control requirements. The control signal of centralized controller can be sent up to 1200m.
♦ A centralized controller enables interface with computer or gateway to realize centralized
computer control over and parameter setting and status query of all the air conditioners in the
network. Furthermore, it enables connection with WAN through the computer or gateway and
thus computerized remote control.
- 372 -
Controller
___________________________________________________________________________________
2.2.1 The controller enables centralized control over and data query of the outdoor units. Each
controller can form a monitoring and controlling network with up to 32 outdoor units through a
network interface module. Wired connection is used for communication and to enable
centralized control over outdoor units in the network.
2.2.2 The controller can communicate the computer via RS485/RS232 transformation interface.
Each computer can connect with 16 outdoor centralized controllers and 16 indoor centralized
controllers. The computer enables central control over, management, status query, etc of the
outdoor centralized controllers, indoor centralized controllers, indoor units and outdoor units
within the monitoring and controlling system.
2.2.3 For communications between controllers and outdoor units, as well as between computers
and controllers, the primary machine queries and the secondary machine replies. In the
monitoring and controlling network consisting of controller and outdoor units, the controller is
the primary machine, while the outdoor unit is the secondary machine.
- 373 -
Controller
___________________________________________________________________________________
4) Uninterrupted power supply (UPS APC SU700 option)
Requirement Performance
Capacity 200~250w/20minutes
Voltage 220~240V
Control signal Power failure signal( from UPS)UPS off signal(to UPS)
4.1.1 As per the use instructions supplied with APC SU700, connect the power supply line and
signal line with the power supply and computer respectively.
♦ The signal line connecting UPS and computer may be connected with any serial port of the
computer
♦ UPS power output port
♦ UPS power input port
- 374 -
Controller
___________________________________________________________________________________
network package purchased into any USB port and it is ready.
- 375 -
Controller
___________________________________________________________________________________
(1) Install Database SQL Server2000
The system adopts Microsoft SQL server 2000 simplified version with the installation
process as follows:
♦ Double click AUTORUN.EXE to enter the following window:
- 376 -
Controller
___________________________________________________________________________________
♦ In case of first time installation of SQL server2000, select “Create a new SQL Server case or
install customer tool”. Then press “Next”
- 377 -
Controller
___________________________________________________________________________________
♦ Select ID verification “mixed mode” and input the logon password “sa” (As the password for
connection between system and database is SA, the logon password must be SA). Then press
“Next” to automatically complete installation.
- 378 -
Controller
___________________________________________________________________________________
♦ Run SetupEx.exe in the installation package and then the window below will be displayed:
♦ System initiation
- 379 -
Controller
___________________________________________________________________________________
Before installation of system, it is essential to firstly install Microsoft SQL SERVER2000 (refer
Third Generation Network monitoring and control system operation manual for installation
process).Then begin system installation and after that run C:\Program
Files\SCUT\YDSNetControl\YDSIniting.exe
♦ Press “Test Database” and then a password box is prompted. The password is in the
installation guide file of the installation CD.
♦ Execute the buttons in the window from up to bottom to complete system initiation.
♦ After completion of the above process, all the indoor units, outdoor units, indoor centralized
controllers and outdoor centralized controllers will be stored in the database according to their
addresses.
- 380 -
Controller
___________________________________________________________________________________
Double click the shortcut icon of new system to display the following window:
3.1.1 User can be created in the database of system and selected through the drop down box of
account in this window.
3.1.2 If you select remembering password, you can logon to the system only by press OK each
time.
3.1.3 If you select auto logon, you can enter the system by pressing the user name and password
each time.
3.1.4 User authorities the users may be divided into super administrator, administrator and user.
Super administrator has the authority to operate all the pages, including all the authorities such
as communication diagnosis, communication status browse, system construction, query and
control of air conditioners and centralized controllers, query of outdoor units and group schedule
management.
Administrator has all the authorities of super administrator except communication diagnosis and
communication status browse, and mainly has the function of site construction of system and
system management.
User mainly has the function of main window, uniform setting window, indoor centralized
controller window, air conditioner window, group operation, schedule management, report
query, etc.
- 381 -
Controller
___________________________________________________________________________________
After the user name and password are entered, you can enter the billing base reading
selection window, shown as follows:
3.2.1 The system default electricity billing base is the last reading of the database.
3.2.2 If the latest meter reading is selected as the calculation base, the system checks the watt-
hour meter in the first cycle during system operation without any calculation. Normally, the last
reading of the database shall be used as the calculation base of electricity billing, except watt-
hour meter replacement.
3.3.1 The port of network air conditioning system may be selected according to the actual
condition of computer in use.
3.3.2 Building system interface is the port interfacing with LON gateway and shall be selected as
per the actual condition.
3.3.3 Electricity rate is an important parameter and will be used in the report and actual
- 382 -
Controller
___________________________________________________________________________________
calculation process.
3.3.4 Currency unit is the unit of money involved in our report.
♦ Select Outdoor, press “New” and the left list will display a blank line. Select the row and then
input the name for centralized controller to be created under the centralized controller name.
Select the icon used in the system. Finally, press “Update” to create the centralized controller in
the system.
♦ After creation, you can select and modify it from the list and then press “Update” button for
updating.
♦ It can be deleted from the list.
- 383 -
Controller
___________________________________________________________________________________
After the outdoor centralized controller is created, a set can be created under the
outdoor centralized controller.
♦ Select outdoor centralized controller, and then all the sets under the centralized controller
will be displayed in the list.
♦ Press “New” and the list will display a blank item. Select it and input the name of set and after
that press “Update” button.
♦ The set can be deleted if it consists of no outdoor unit. Select the set to be deleted and then
press “Delete” to delete the set.
- 384 -
Controller
___________________________________________________________________________________
♦ To create an outdoor unit, you can select an address from the outdoor centralized controller
address drop down box. Then all the outdoor units under the centralized controller are in the
list.
♦ Press “New” and then the list will display a blank line. Click the blank to input the address,
name and model of the outdoor unit and its icon in the system. In the meanwhile select the set.
Then press “Update” complete input of outdoor unit.
♦ After selecting the address of centralized controller, click the outdoor unit to be modified in
the left list. Then you may modify the outdoor unit parameters from the options on the right.
♦ If an outdoor unit does not exist, select the outdoor unit and then press “Delete” to delete
the outdoor unit.
- 385 -
Controller
___________________________________________________________________________________
♦ Selects the centralized controller option from the menu to enter the centralized controller
setting window. Then select indoor option and the left list will display the created indoor
centralized controllers.
♦ Press “New” and the list will display a blank. Click the blank and input the name of centralized
controller to be created. Select the address of centralized controller and its icon to be used in
the system. Then press “Update” and the centralized controller are ready.
♦ The centralized controller to be modified may be selected from the left. Then modify the
name of centralized controller and its icon in the system from the right options. After
modification, press “Update” to update the changes into the database.
♦ If an indoor centralized controller has no air conditioner and will not be used, the centralized
controller can be deleted. During deletion, select the centralized controller to be deleted from
the left list and then press “Delete” button. When the centralized controller still has air
conditioners, a prompt box will be displayed that the centralized controller cannot be deleted. A
centralized controller can be deleted if it has no air conditioner under control.
- 386 -
Controller
___________________________________________________________________________________
♦ If you want to view the indoor units of a centralized controller, you may select the address of
centralized controller through the centralized controller address option. So the left air
conditioner list will display all the air conditioners under the centralized controller.
♦ If an air conditioner needs to be created under the centralized controller, press “New” to
display a blank at the bottom of the left list. Click the blank and then input at the right options
the name of indoor unit, centralized controller address, air conditioner address, the set
connected in the system, capacity of indoor unit, capacity of Slave electric heater for the indoor
unit, type of indoor unit, indoor unit model and its icon displayed in the system.
♦ When the electricity bill with cost limit is calculated in the system, the electricity limit option
may be selected. Then fill in the specific electricity quantity. If electricity balance of a month can
be carried over to the next month, the electricity balance carrying over option shall be selected.
♦ Air conditioners in public area indicate that they serve the common area, and their electricity
costs shall be shared if they are ticked as common air conditioners.
♦ After all the options are filled in, directly press “Update” to create the air conditioner.
♦ If the basic parameters of an air conditioner shall be changed, select the address of
centralized controller of the indoor unit and select the air conditioner from the left list. Then all
the information about the air conditioner will be displayed on the right. Modify the parameters
and after that directly press “Update” and the modification is complete.
♦ When an air conditioner does not actually exist; delete it as per the following steps. Select the
- 387 -
Controller
___________________________________________________________________________________
centralized controller for the air conditioner to be deleted; select the air conditioner to be
deleted from the left list and then press “Delete” directly to delete the air conditioner from the
system.
♦ Create. When entering the group parameter setting window, all the groups of the system will
be in the list. To create a new group, press “New” and the list will display a blank. Click the blank
and input the name of the new group in the group name box. Then press “Update Group” button
and the new group are created.
♦ Change of group name. To change the group name, enter the group parameter setting
window directly and click the group to be changed. Then input a new name in the group name
box and press “Update Group” button. Then the group name is changed.
♦ Delete a group. When there is no air conditioner in a group, you can delete the group by
selecting it from the list and press “Delete Group” to delete the group.
- 388 -
Controller
___________________________________________________________________________________
♦ Select the group to be maintained in a and all the indoor units of the group will be displayed
in list b.
♦ Select the indoor unit to be added into the group from tree c and then press “ ”. If the
indoor unit is already in the group, it prompts that the indoor unit is already in the group. If the
indoor unit is in another group, it will prompt that the indoor unit is in another group and
whether to change its group property to add it into this group. If No is chosen, its group
properties will not be changed. The indoor unit can join the group directly if it is not in any
group.
♦ To delete the air conditioners in the group, select the indoor unit in list b and press “ ”.
Then the selected air conditioner is deleted from the group.
- 389 -
Controller
___________________________________________________________________________________
3.5.1 Main window
- 390 -
Controller
___________________________________________________________________________________
♦ In this window, the system automatically builds a tree structure as per the relations between
indoor units and centralized controllers, as shown in a. Direct click the icon of centralized
controller and the connected indoor units will be displayed. Light green indicates on line and
normal operation, but grey indicates off line and reddish brown indicates on line and faults.
♦ The centralized controller status display can be referred to b, displaying the centralized
controller No. and the number of on-line air conditioners under the centralized controller.
♦ c is the centralized controller selection box. The selection box at d on the right is linked with
centralized controller selection box and lists all the air conditioner names under the centralized
controller selected in the centralized controller selection box.
♦ The indoor unit selection box d is linked with c.
♦ The centralized controller setting box e can lock and unlock the centralized controller. The
centralized controller will be locked upon a locking command being successfully sent. Then the
locked icon of centralized controller will be displayed and the air conditioners under it cannot be
operated from the centralized controller level. The locked icon of centralized controller will
disappear after the unlocking command is successfully sent to the locked controller and then the
air conditioners can be operated through the centralized controller.
♦ The air conditioner setting boxes can be divided into remote control settings, On/Off settings,
swing setting, mode setting, fan speed setting, temperature setting and timing setting.
- If “All air conditioners” under f is not ticked, the air conditioner setting box is to set up the air
conditioner selected from the air conditioner selection box d.
- 391 -
Controller
___________________________________________________________________________________
- If “All air conditioners” under f is ticked, the settings are valid for all the air conditioners under
the centralized controller selected in c.
- The centralized controller settings include two options: remote controller locking and
unlocking. The default is unlocking. When locking is selected, the selected air conditioner will
not receive remote controller setting signals after successful locking, but the upper level settings
are still valid. When the remote controller of air conditioner is locked, the remote controller can
be unlocked and then the indoor unit can receive remote controller signals.
- On/Off setting is used to set up the air conditioner switching On/Off. When timing on or off is
selected, On/Off setting is shielded and cannot be operated.
- Mode setting is used to set up the operation mode of air conditioner, including Cooling,
Heating, Auto, Dehumidifying and Fan. The fan speed options include high, low and auto. The
temperature setting can vary between 17~30°C.
- Timing On/Off option, if not ticked and selected, the timing on/off time is not available. When
either option is selected, all the setting information cannot be sent to the indoor unit
immediately through “Send”. Instead, such information will be saved in the database as per the
selected timing on /off status. If timing on is selected only, all the setting information except air
conditioner On/Off will be saved, including set timing on time. When the set timing on time is
up, the setting information, including switching on will be sent to the indoor unit. If timing off is
selected, only the timing off is saved and switching off command will be sent upon the timing off
time.
- 392 -
Controller
___________________________________________________________________________________
♦ a is made of the tree consisting of outdoor centralized controllers, sets and outdoor units. The
set refers to the outdoor units under the same refrigeration system.
♦ b is the centralized controller selection box. After the centralized controller is selected, the
outdoor units in c will change with the centralized controller. Press “Query” to display the
information of centralized controller. Press “Previous” to query for the information of the
previous outdoor centralized controller and “Next” for the information of the next outdoor
centralized controller.
♦ c refers to the outdoor unit selection box and selection of an outdoor unit under the selected
outdoor centralized controller.
♦ d refers to the type of outdoor units. f displays the specific information about a specific
model, including digital, frequency variable and water type outdoor units. If no specific
information about the outdoor unit is available, the default is frequency variable.
♦ e displays the common information of all the outdoor units.
♦ The outdoor centralized controller and outdoor units can only be queried and cannot be
controlled.
- 393 -
Controller
___________________________________________________________________________________
♦ Uniform setting is specific to all the indoor units within the system and includes mode setting,
locking, unlocking and mode locking and unlocking for indoor units.
♦ a is the air conditioner setting column, where the remote controller locking setting is to send
the locking commands to all the indoor units so that they cannot receive remote controller
signals. The default is unlocking. On/Off option refers to sending commands to switch on or off
the air conditioner. In case of Off, the swing, mode, fan speed or temperature setting is
disabled. Such settings are enabled if On is selected. Swing function includes swing On /Off with
Off as the default. Mode option includes cooling, heating, fan, dehumidifying and auto. The fan
speed of indoor unit fan may be high, medium, low and auto. The temperature can be set within
17~30°C. After “Send Command” is pressed, the system sends commands to each indoor unit
for setting.
♦ b is the timing On/Off setting option. When either option is selected, On/Off option will be
shielded. If timing On is selected, press “Send Command” to save all the settings and switching
on information into the database. If timing Off is selected, press “Send Command” to save the
switching off information into the database. All the timing information of each indoor unit can be
displayed at the query system when the timing time is not up. When timing time is up, all the
setting information will be sent to the indoor units and the timing information will then be
removed if you query any air conditioner in the system.
♦ c is the locking option of centralized controller, including locking and unlocking. In case of
locking, all the controller key operations will be disabled after all the indoor centralized
- 394 -
Controller
___________________________________________________________________________________
controllers receive a locking command. Select centralized controller unlocking, and then press
“Send uniform centralized controller locking command” to unlock all the indoor centralized
controllers after successfully sending the commands.
♦ e is the mode locking selection box. When only one mode is allowed for the whole system,
select cooling or heating from the option, and then press “Uniform mode locking command”.
After it is successfully sent, the operation mode of indoor unit cannot be changed through a
remote controller or centralized controller. But the indoor unit can be unlocked or other
operation mode may be used from the upper level. When the mode locking is applied to all the
indoor units, select unlocking and press “Uniform mode locking command” to unlock the indoor
units and the mode of all the indoor units can be changed after the command is successfully
sent.
♦ a consists of the group name drop down box and selected indoor unit of group. After a group
is selected, all the indoor units under the group will be in the list.
♦ b is the group setting box and includes remote controller setting, On/Off setting and operation
mode setting, fan speed of indoor unit and temperature setting. As for the previous indoor unit
settings, direct press “Send Command” after proper settings to send such settings to all the
indoor units of the group.
- 395 -
Controller
___________________________________________________________________________________
♦ After a group is selected in a, the schedule management information related to the group will
be displayed in the schedule management box c. The schedule management information
consists of a number of tasks, which are all switching on tasks - starting from switching on and
ending at switching off. The schedule management box consists of many arrow lines. When we
need to know the setting of a specific task, select the arrow line of the task (it will turn red after
selection). Double click to enter the schedule management page. So we can view the specific
setting of the task.
♦ a is used to display the status of selected indoor unit. After Query is pressed, the icons in box
a display the status of the current indoor unit. In the display box, there is icon of indoor unit
operation mode, icon of timing setting, icon of indoor fan speed and locking icon. For the mode
- 396 -
Controller
___________________________________________________________________________________
prompted in the dropdown box. Then press Query and the relevant information of the indoor
unit will be in the display box in d.
♦ c is used to set indoor units. It is almost the same as the indoor unit setting in indoor
centralized controller window. But there is no air conditioner selection box here. So it can only
set up the air conditioner selected in b.
♦ d is used to display the indoor unit operation status. If no operation information is available
for an indoor unit, a blank is used. Timing information may be expresses as “ ”, or
“0:0:00” in case of none. After a timing task is fulfilled, the air conditioner returns to non-
timing status. In case of mode conflict, the word “conflict” will be displayed behind the mode
and at the mode conflict column. The information displayed at the status information display
column and the information of database is simultaneously updated.
- 397 -
Controller
___________________________________________________________________________________
♦ Only query function is available for outdoor units and so it has only one outdoor unit selection
column, outdoor unit status display column and outdoor unit status marking. The displays at
outdoor unit status display column are updated simultaneously with database updating. The
latest current status will be reflected only if Query button is used.
♦ a is the selection column of outdoor unit. Press outdoor unit drop down box “ ”, and the
tree consisting of outdoor centralized controllers, sets and outdoor units will be prompted, as
shown in below figure. After an outdoor unit is selected, press “OK” and the name of selected
outdoor unit will be displayed in the most front.
♦ b is the outdoor unit status display column to display the latest status of selected outdoor unit
in the specific items in the column. A blank is used if no status information is available for an
- 398 -
Controller
___________________________________________________________________________________
outdoor unit. It is updated simultaneously with the database updating.
♦ c is the status marking column of outdoor unit to mark the operation mode of outdoor unit
and outdoor fan status. In the operation mode, “ ”indicates Cooling mode, and “ ”
indicates Heating mode. For the outdoor fan,“ ” indicates High and “ ” indicates Low.
♦ The group selection column a, can select a specific group and display the information related
to the group. When a group is selected from the group selection box a, c will display all the set
tasks for the group. b is the task setting column.
♦ All the tasks of the group are switching on tasks, namely starting from switching on and
ending at switching off.
♦ After a group is selected, you may delete, modify and create tasks.
♦ To add a new command, firstly press “New” and then select the items in setting column b one
by one. The task setting is basically the same as the setting of indoor unit, but On/Off option
cannot be operated. The system default is that all the tasks are switching on tasks. After all the
settings are selected, the task can be set as a weekly task. If it is set as a weekly task on every
Tuesday, task will be executed every Tuesday. If it is not set as a weekly task, the task will be
executed when it is time and will be deleted after execution. After the above operations, press
- 399 -
Controller
___________________________________________________________________________________
“Save” and a new task is created. You can view the task from c.
♦ To modify a task, you may select the task from c and then the setting of the task is displayed
in b. Then the setting can be modified in b and after that press “Save” and the task modification
is OK.
♦ To delete a task, you only need to select the task in c and then press “Delete” to delete the
task.
♦ Refrigeration system TOP diagram is used to connect the outdoor units with indoor units
within the same refrigeration system. So you can view the distribution status of system visually.
♦ a lists all the refrigeration systems within the system and the refrigeration systems has the
name of outdoor sets.
♦ Click any refrigeration system in a and b and c will display all the indoor units and outdoor
units of the refrigeration system. The indoor unit is represented with the icon of indoor unit in
the system. Likewise, the outdoor units are represented with their icons in the system.
♦ In b, when we move the cursor to any icon, the complete name of the indoor unit will be
displayed through a small mark. When we press any icon, we will enter the indoor unit page and
meanwhile the latest status of the indoor unit will be displayed.
♦ The outdoor unit operations in c are the same as the indoor unit operations in b. The
- 400 -
Controller
___________________________________________________________________________________
difference is that to press outdoor unit icon will skip to the outdoor unit window and the latest
information of outdoor unit will be displayed.
♦ The system sends commands in two forms – to send commands manually, and the system
sets timing and group task commands. If the commands are manually sent successfully, the
sending box will be automatically closed after sending. Unsuccessfully sending commands shall
be manually closed. The auto commands triggered by the system will be closed automatically
upon completion of sending.
♦ The type of command sent and successful or unsuccessful sending will be listed in the sending
box.
- 401 -
Controller
___________________________________________________________________________________
♦ The system allotment adopts peroration and the electricity for peroration is mainly the
electricity consumption of outdoor units and of indoor unit fan and Slave electric heater.
♦ The indoor units of the same refrigeration system share the electricity consumption of the
outdoor sets of the refrigeration system. The indoor units outside the system do not share the
electricity of the outdoor sets of the refrigeration system.
♦ The electric bill of an indoor unit in certain time period can be divided into two parts: basic
electricity and shared electricity.
♦ The basic electricity includes the electricity consumption of the indoor unit due to operations
in Cooling, heating or fan mode. 4-7-1-3-2The shared electricity includes electricity consumed
by outdoor units when all the indoor units are in standby status, as well as the electricity
consumed by outdoor set (an administrator may log onto the system to select to incorporate
this portion of electricity or not) when the whole refrigeration system runs normally but the
billing system has some faults.
- Calculation of basic electricity: Fa = FA*e Where FA is the total shared electricity
consumed by the refrigeration system during a certain time period, and e is the ratio based on
the capacities of indoor units.
- Calculation of shared electricity Fa = FA*e Where FA is the total shared electricity
consumed by the electricity consumers of a system during a certain time period, and e is the
ratio based on the capacities of indoor units.
♦ Electricity fee allotment of a refrigeration system under different circumstances
- When all the indoor units of system are in standby status (not in cooling, heating or fan
mode), each indoor unit shall be allotted with the electricity consumed by the outdoor set during
the time period (shared electricity) in proportion to their capacities.
- Cooling mode (basic electricity)
Indoor unit in Cooling mode:Shared electricity consumed by outdoor set plus electricity
consumed by indoor unit’s own fan and Slave electric heater.
Indoor unit in Fan mode: Only the electricity consumed by indoor unit’s own fan
Indoor unit in Stand-by:No electricity is incorporated.
- When the system runs in heating mode and there is no indoor unit in conflict status
(basic electricity)
Indoor unit in Heating mode:Shared electricity consumed by outdoor set plus the electricity
consumed by indoor unit’s own fan and Slave electric heater.
Indoor unit in Stand-by:No electricity is incorporated.
- When the system runs in heating mode and there is indoor unit in conflict status (basic
electricity)
Indoor unit in Heating mode:Shared electricity consumed by outdoor set plus the electricity
consumed by indoor unit’s own fan and Slave electric heater.
- 402 -
Controller
___________________________________________________________________________________
Indoor unit in Cooling mode(conflict): Only the electricity consumed by indoor unit’s own
fan
Indoor unit in Fan mode(conflict): Only the electricity consumed by indoor unit’s own fan
Indoor unit in Stand-by:No electricity is incorporated
3.6.2 Report
♦ Air conditioner billing statistics sheet
- The billing statistics is based on groups and the billing data of all or individual air conditioners
of the group can be printed out.
- The electricity fees for any time period can be queried for and printed.
- The electricity bill consists of two parts: basic electricity fee and shared electricity fee. The fee
of each indoor unit for the time period is displayed in the total electricity fee item in the report.
- 403 -
Controller
___________________________________________________________________________________
♦ The detailed bill is the list for a certain time period as per the On/Off information of indoor
units. It is similar to a telephone bill. The detailed bill of the group of air conditioners or an
individual air conditioner can be output.
- The bill for any time period can be output.
- All the output bills only include basic electricity fees without shared electricity fees.
- 404 -
Controller
___________________________________________________________________________________
- The indoor unit operation data report is the list of operation data of indoor units under query
for a certain time period.
- Only the data of one indoor unit can be outputted and the maximum time period is 7 days.
- The report is used to analyze data during maintenance and it can facilitate identification of
causes for faults.
- 405 -
Controller
___________________________________________________________________________________
- As the operation data of indoor units, the outdoor unit operation data report is the list of
operation data of outdoor units under query for a certain time period.
- Only the data of one outdoor unit can be outputted and the time period is 7 days.
- The report is used to analyze data during maintenance and it can facilitate identification of
causes for faults.
- 406 -
Controller
___________________________________________________________________________________
- As the indoor unit operation data report, it is used to query for the report of all indoor unit
faults and protection information for a certain time period.
- The maximum query time period of report is 7 days.
- It is mainly used to query for the faults and protection of indoor units of system during a time
period.
- 407 -
Controller
___________________________________________________________________________________
- As the outdoor unit operation data report, it is used to query for the report of all outdoor unit
faults and protection information for a certain time period.
- The maximum query time period of report is 7 days.
- It is mainly used to query for the faults and protection of outdoor units of system during a time
period.
- 408 -
Controller
___________________________________________________________________________________
- If the report needs to be printed, direct press “ ” button to output the report to the
default printer.
- If the report shall be saved as an EXCEL worksheet, you need to operate as follows: click
select all button“ ”, press copy button “ ”,and then click EXCEL output button to
output the report to an EXCEL worksheet. Finally you only need to save it.
- If the report shall be saved as a WORD table, repeat the process for EXCEL worksheet but
5. Remote controller
- 409 -
Controller
___________________________________________________________________________________
5.1 Wireless remote R-51/E
Model R51/E
Rated Voltage 3.0V
Lowest Voltage of CPU Emitting Signal 2.0V
Reaching Distance 8m (when using 3.0 voltage, it can get 11m)
Environment Temperature Range -5 O C~60 O C
TEMP DOWN Button: Push the TEMP DOWN button to decrease the indoor temperature setting
or to adjust the timer in a counter-clockwise direction.
MODE SELECT Button: Each time you push the button, a mode is selected in a sequence that
goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates:
SWING Button: Push this switch button to change the louver angle.
- 410 -
Controller
___________________________________________________________________________________
RESET Button: When the RESET button is pushed, all of the current settings are cancelled and
the control will return to the initial settings.
ECONOMIC RUNNING Button: Push this button to go into the Energy-Saving operation mode.
LOCK Button: Push this button to lock in all the current settings. To release settings, push again.
TIMER Button: This button is used to preset the time ON (start to operate) and the time OFF
(turn off the operation)
ON/OFF Button: Push this button to start the unit operation. Push the button again to stop the
unit operation.
FAN SPEED Button: This button is used for setting fan speed in the sequence that goes from
AUTO, LOW, MED to HIGH, and then back to Auto.
TEMP UP Button: Push this button to increase the indoor temperature setting or to adjust the
timer in a counter-clockwise direction.
VENT Button: Push this button to set the ventilating mode. The ventilating mode will operate in
the following sequence:
- 411 -
Controller
___________________________________________________________________________________
Remote Controller Specifications
MODE Select Button: Each time you push the button, a mode is selected in a sequence that
goes from AUTO, COOL, DRY, HEAT, and FAN, as the following figure indicates:
- 412 -
Controller
___________________________________________________________________________________
FAN SPEED Button: This button is used for setting Fan Speed in the sequence that goes from
AUTO, LOW, MED to HIGH, then back to AUTO.
AIR HORIZONTAL Button: When press the button once and quickly, the air flow direction
setting feature of the louver is activated. The moving angle of the louver is 6° for each press.
Keep pressing the button to move the louver to the desired position. If keep pressing the button
without releasing for 2 more seconds, the auto swing feature of the louver is activated. The
horizontal louver would swing up/down automatically. Press it again to stop.
TIMER ON Button: Press this button to preset the time ON (start to operate). Each press will
increase the TIMER ON setting in 30 minutes increments. When the setting time displays 10:00,
each press will increase the TIMER ON setting in 60 minutes increments. To cancel the time ON
program, simply adjust the TIMER ON to 0:00.
VENT Button: Push this button to set the ventilating mode. The ventilating mode will operate in
the following sequence: AUTO Continuous Off
RESET Button: When the RESET button is pushed, all of the current settings are cancelled and
the control will return to the initial settings. (Use a 1mm little round stick to push the button)
TURBO Button: Push this button on COOL/HEAT mode and the air conditioner will go into
powerful cooling or heating operation. Push again to cancel the TURBO function. (Available for
Master Gold and Everest only)
ECONOMIC Button: Press this button to activate the Energy-Saving mode. Press again to stop
the function. This function is available on COOL, HEAT or AUTO mode only and maintains the
most comfortable temperature for you.
ON/OFF Button: Push this button to start the unit operation. Push the button again to stop the
unit operation.
AIR VERTICAL Button: When press the button once and quickly, the air flow direction setting
feature of the louver is activated. The moving angle of the louver is 6° for each press. Keep
pressing the button to move the louver to the desired position. If keep pressing the button
without releasing for 2 more seconds, the auto swing feature of the louver is activated. The
vertical louver would swing up/down automatically. Press it again to stop.
NOTE: If the auto swing up/down feature has been set by unit control panel, press the AIR
VERTICAL button on remote controller will cancel the feature.
- 413 -
Controller
___________________________________________________________________________________
TIMER OFF Button: Press this button to preset the time OFF (turn off the operation). Each press
will increase the TIMER OFF setting in 30 minutes increments. When the setting time displays
10:00, each press will increase the time OFF setting in 60 minutes increments. To cancel the
TIMER OFF program, simply adjust the TIMER OFF to 0:00
TEMP Button: Press the button to increase the indoor temperature setting.
TEMP Button: Press the button to decrease the indoor temperature setting.
LOCK Button: Push this button to lock all the current settings, push again to cancel the LOCK
function.
- 414 -
Controller
___________________________________________________________________________________
- 415 -
Controller
___________________________________________________________________________________
Wire controller and their functions
Installation
Installation into the wall
The diameter of Wire Controller wire must be suitable for its length.
Wiring Tube must be suitable for the wires.
Turn a screwdriver at the concave on bottom panel of the Wire Controller to remove the Cover.
- 416 -
Controller
___________________________________________________________________________________
NOTE
z Never turn screws too tightly, or else the cover would be dented, or the Liquid Crystal
breaks.
z Do not cut wires when installing Wire Controller cover.
Refer to Electrical Switch Box Installation above for other installation information you need.
Use Clue around the Screen Cables and the Hole for sealing after installation completed.
NOTE
z Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal
breaks.
z Do not cut wires when installing Wire Controller Cover.
z Please leave enough long cable for maintenance of the Wire Controller Board.
- 417 -
Controller
___________________________________________________________________________________
1. Operation mode indication: When press” MODE” button, the following mode can be selected
in circle. Auto Cool Dry Heat Fan only Auto.
- 418 -
Controller
___________________________________________________________________________________
Auto→ Cool→ Dry →Heat→ Fan only →Auto
For cooling only model, heat mode is skipped.
2. Timer: When adjust setting on time or only on time is set, the “ON” is lighted. When adjust
setting off time or only off time is set, the” OFF" is lighted. If on and off timer are both set, the
“ON” and “OFF” are both lighted.
3. Follow me function: There is a temperature sensor inside the wire controller, after setting
temperature, it will compare the two temperatures, and the space of wire controller will be the
same as setting temperature. It is available under cooling, heating, auto mode.
4. ON/OFF indication: When it is on, the icon display, otherwise it is extinguished.
5. Fan speed indication: There are four fan modes: low, middle, high, and auto. For some
models, no middle fan then the middle fan is seen as high speed.
6. Lock: When the"LOCK"button is pressed, the icon appears and other buttons is unable, press
again, the icon disappears.
7. Temperature display zone: Generally it displays setting temperature; it can be adjusted by
press temperature button▲and▼ .But in fan mode, no display here.
- 419 -
Controller
___________________________________________________________________________________
Mode button: When press this button, the operation mode change as the following sequence:
Remark: For the cooling only model, the heating mode is skipped.
Timer on button: Press this button, timer on function is active. Then every press, the time
increase 0.5h, after 10h, 1h incensement after each press. If cancel this Function, just set it to
"0.0"
Timer off button: Press this button, timer off function is active. Then every press, the time
increase 0.5h, after 10h, 1h increase after each press. If cancel this function, just set it to "0.0" .
Follow me button: When under cool, heat and auto mode, press this button, follow me function
is active. Press again, this function is ineffective.
Electrical heater button: If press this button in heat mode, electrical heater function become
ineffective.
Reset button (hidden): Use a 1mm stick to press in the little hole, then the current setting is
canceled. The wire controllers enter into original state.
ON/OFF button: When in off state, press this button, the indicator is on, the wire controller
enter into on state, and send setting information to in door Pcb . When in on state, press this
button, the indicator is off, and send instruction. If timer on or timer off has been set, it cancel
this setting then send instruction to stop the machine.
Adjust button: Set indoor temperature up. If press and hold on, it will increase at 1degree per
0.5 second.
Adjust button: Set indoor temperature down. If press and hold on, it will decrease at 1degree
per 0.5 second.
Swing button: First press, start swing function; second press, stop swing. (Match to some
model with swing function).
Economy operation button: press this button, the indoor unit operates in economy mode, press
again, exit this mode (it may be ineffective for some models)
Fan speed button: press this button consecutively; the fan speed will circle as follow:
- 420 -
Controller
___________________________________________________________________________________
Lock button (hidden): When you push the LOCK button, all current settings are locked in and
the wire controller does not accept any operation except that of the LOCK button. Use the lock
mode when you want to prevent setting from being changed accidentally or play fully. Push the
LOCK button again when you want to cancel the LOCK mode.
Installation
- 421 -
Controller
___________________________________________________________________________________
NOTE
z The connecting wire should be a little longer as to take away the switch board easily for
maintenance.
z The connecting wire should be a little longer as to take away the controller easily for
maintenance.
- 422 -
Controller
___________________________________________________________________________________
5.5 Weekly schedule timer AMR02M
- 423 -
Controller
___________________________________________________________________________________
1. Operation mode indication: When press "MODE” and "ADD" or "REDUCE" button, the
following mode can be selected
In circle: Cool→ Heat→ Off.
For cooling only model, heat mode should be skipped.
2. Fan speed indication: There are four fan modes: low, middle, high, and auto. For some
models, no middle fan then the middle fan is seen as high speed.
3. Fault indication.
4. Temperature indication.
5. Weekly Schedule Controller switch indication.
6. Date indication.
7. Time indication.
8. Period indication.
9. Lock indication.
10. Week indication.
Fan speed button: press this button and ADD or REDUCE Button to select of High or Middle or
Low or Auto, press Confirm to save and back.
- 424 -
Controller
___________________________________________________________________________________
Edit button: When press this button, can setup Week and Date and Period.
Day button: press this button and ADD or REDUCE button to select of High or Middle or Low or
Auto, press Confirm to save and back.
Timer on/off button: Press this button, can turn off the weekly timer function.
Reset button: When press this button, all of the display part of LCD will be light last 2 second
when weekly timer has been electrified or reset. Following the lamp will be closed and last 1
second. So the system will come into normal display state and need to carry out initial setting.
Lock button: press this button, weekly timer come into lock mode, Press LOCK again, lock mode
is unchained at once. Weekly timer lock mode state can not be canceled when weekly timer has
come back to supply power after interruption of power supply.
Cancel button: It is for not saving and retreating, or to cancel the lock.
Query button: Press “Query” “Select” “query ”“present” temperature value press “Cancel ”to
back, press “Confirm” time section parameters' setting :press “Add” or “reduce” to select
several days from “Sun” to “Sat” 7 days, press” Confirm “”1 “~”8 “time section selection
beginning from No.1 time section , setting mode, fan's velocity, starting time and end time, till 8
time sections are finished press “Confirm” to save press “Cancel” to retreat.
Reduce button: It is for reducing to numbers and moving left or up to the other.
Add button: It is for adding to numbers, and moving right or down to the other.
Time button: When press button, and press “Add” or “Reduce” to adjust the hours value , press
“Confirm” adjust minutes: press “Add “or “Reduce” to adjust the minutes value, press “Confirm”
to save and back.
- 425 -
Controller
___________________________________________________________________________________
Installation
Instruction for installing: When a weekly schedule controller is needed, a small 2-cores wire and
3-cores wire should be added. Connect with the same color.
Note:
• The connecting wire should be a little longer as to take away the switch board easily for
maintenance.
• The connecting wire should be a little longer as to take away the controller easily for
maintenance.
- 426 -
Controller
___________________________________________________________________________________
- 427 -
Controller
___________________________________________________________________________________
6.3) Concealed duct type
- 428 -
Controller
___________________________________________________________________________________
6.4) Floor & Ceiling type
6.5) Hi wall
- 429 -
2009 Johnson Controls, Inc. www.johnsoncontrols.com Form No. 035M00464-000
Johnson Controls reserve the right to change product features without prior notice.