102 80 - DE - 4322 4372 - Withpermanent Magnet - IO PDF
102 80 - DE - 4322 4372 - Withpermanent Magnet - IO PDF
Installation and
operating instructions
File No: 102.80
Date: february 14, 2020
Supersedes: 102.80
Date: janaury 10, 2020
contents
1.0 mechanical setup 4
1.1 precautions 4
1.1.1 instructions for safe use 4
1.1.2 ambient temperature 4
1.1.3 enclosure rating 4
1.1.4 storage 4
1.1.5 warranty 4
1.1.6 uncrating 4
1.1.7 handling design envelope
4322 & 4372 units 5
1.2 mechanical installation 5
1.2.1 location 5
1.2.2 installation 5
1.2.3 pump piping-general 9
1.2.4 alignment 9
2.0 electrical setup 10
2.1 precautions 10
2.1.1 ground leakage current 10
2.1.2 start/stop of pump 10
2.1.3 additional motor protection 10
2.1.4 motor thermal protection
and derating 10
2.2 electrical specification 12
2.3 electrical installation 13
2.3.1 power wiring 13
2.3.2 tools you will need 13
2.3.3 the main cover disassembly 13
2.3.4 control terminal wiring 14
2.3.5 analog / digital inputs 15
2.3.6 digital output 17
2.3.7 relay output 17
2.3.8 supply voltage 17
2.3.9 supply fusing 17
2.4 design envelope pump controller
wiring 18
2.4.1 battery 18
2.4.2 ethernet and wifi connectivity 18
2.4.3 can bus wiring 18
2.4.4 rs 485 wiring 18
2.4.5 networking options 18
3.0 networking controls 19 5.7 quadratic curve control with minimum
3.1 modbus register map – version 1 - & maximum flow protection 42
for firmware v1.16 and older 20 5.8 parallel sensorless pump
3.2 BACnet objects – version 1 - control (pspc) 42
for firmware v1.16 and older 22 5.8.1 embedded parallel sensorless pump
3.3 modbus register map – version 2 - control for multiple pumps 42
for firmware v1.17 and newer 23 5.8.2 modifying motor ramp up and
3.4 BACnet objects – version 2 - down time 43
for firmware v1.17 and newer 25 5.8.3 three different control modes can
4.0 operation 27 be accessed 44
4.1 start-up checklist 27 5.8.4 fallback percentage of maximum speed 4 4
4.2 starting pump 27 5.8.5 standby pumps 44
4.2.1 auto flow balancing 27 5.9 2*100% capacity split units 44
4.3 touch screen 28 5.10 alternation 44
4.3.1 login 28 5.11 constant pressure control 45
4.3.2 logout 28 5.12 dual season setup 45
4.3.3 about 29 5.13 sensored control 45
4.3.4 general settings 30 5.13.1 adding dp sensors through lcd screen 45
4.3.5 manual/auto mode 31 5.13.2 adding dp sensors from webserver 45
4.3.6 pump control 32 5.15 bypass valve control 46
4.3.7 alarms & warnings 34 6.0 maintenance 48
4.3.8 trend-graph 35 6.1 general care 48
4.3.9 brightness adjustment 35 6.2 lubrication 48
4.3.10 touch screen calibration 36 6.3 mechanical seal 48
4.3.11 data logging 37 6.3.1 mechanical seal replacement
4.4 web interface 38 instructions for rigid split- coupled
4.4.1 connecting via ethernet 38 pumping units (series 4300 & 4322) 49
4.4.2 connecting via wifi 38 6.3.2 mechanical seal replacement
4.5 design envelope flow readout instructions for close-coupled
tolerance 40 pumping units (series 4380 & 4372) 50
4.6 noise levels 40 6.4 system cleanliness 52
This manual contains specific information regarding the safe The standard enclosure rating for Design Envelope 432 2 and
installation, operation and maintenance of Armstrong Design Design Envelope 4372 integrated controls is ul Type 12 / ipp55 .
Envelope pumps. Read this manual carefully before installing or If the pump is to be installed in a wet or dusty environment,
using the product. If clarification is needed on any point please then a higher enclosure rating may be required (contact
contact Armstrong quoting the equipment serial number. Armstrong).
1.1.1 instructions for safe use Pumps not immediately placed into service, or removed from
service and stored, must be properly prepared to prevent exces-
No installation of this equipment should take place un-
sive rusting. Pump port protection plates must not be removed
less this document has been studied and understood.
until the pump is ready to connect to the piping.
Handling, transportation and installation of this equipment
Rotate the shaft periodically (at least monthly) to keep rotating
should only undertaken by trained personnel with proper use of
element free and bearings fully functional.
lifting equipment. See later diagrams for lifting advice. Refer to
the pump nameplate for pump speed, pressure and temperature For long term storage (longer than three months), the pump
limitations. The limits stated must not be exceeded without must be placed in a vertical position in a dry environment.
written permission from Armstrong. Internal rusting can be prevented by removing the plugs at the
top and bottom of the casing and drain or air blow out all water
1.1. 2 ambient temper ature to prevent rust buildup or the possibility of freezing. Be sure to
reinstall the plugs when the unit is made operational. Rustproof-
Install the Design Envelope unit with adequate ac- ing or packing the casing with moisture absorbing material and
cess for routine maintenance. A minimum of 2" (50 covering the flanges is acceptable. When returning to service be
mm) clearance is required at the fan inlet to facilitate sure to remove the drying agent from the pump.
airflow. Where several Design Envelope units are installed in
close proximity, care must be taken to ensure that there is no
1.1.5 warr ant y
re-circulation of exhausted warm air.
To avoid the inverter unit getting overheated, the Armstrong’s warranty period for Design Envelope pumps is
ambient temperature is not to exceed 45°c /113°f [ 18] months from date of shipment, or [ 12] months from date
average daily temperature. Operating in higher of installation, whichever comes first. Please refer to File 9 .10us
ambient temperatures will require derating of the inverter. / 9 .10c for full terms and conditions. To receive an additional
[6] months of standard coverage, owner may register the pump
Under normal operating conditions the pump surface tempera-
unit at
ture may reach 68°c/ 155°f (Restricted Zone) to 80°c/176°f
www.armstrongfluidtechnology.com/warrantyregistration
(Unrestricted Zone). Steps should be taken to minimize contact
or warn operators/users that normal operating conditions will
be exceeded. In certain cases, where the temperature of the 1.1.6 uncr ating
pumped liquid exceeds the above stated temperature levels, Armstrong Design Envelope 432 2 & 4372 Vertical In-Line
pump casing temperatures may exceed 10 0°c /2 12°f and not pumps are thoroughly inspected before shipment to assure
withstanding pump insulation techniques appropriate measures they meet with your order requirements. After removing the
must be taken to minimize risk for operating personnel. The pump from the packaging, make sure the equipment is in good
ambient temperature for standard motors must be no greater order and that all components are received as called for on the
than 45°c /113°f. packing list. Any shortages or damage should be reported im-
mediately. Use extreme care in handling the unit, placing slings
and hooks carefully so that stress will not be imposed on the
integrated controls, pump or motor. Never place cable slings
around the pump shaft or integrated controls. The hoist rings
should be used to lift the complete pump assembly.
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
1.1.7 handling design envelope 4322 & 4372 adequate space is left above and around the unit for operation,
units maintenance, service and inspection of parts.
To handle Design Envelope 432 2 & 4372 units when received In closed systems, where possible, the pumps should be in-
on site, secure the pallet following uncovering the unit, then stalled immediately downstream of the expansion tank /make-
hook straps as detailed below, and carefully lift the pumping up connection. This is the point of zero pressure change and
unit to stand the pump vertically upright. Lift only sufficiently to is necessary for effective pump operation. Do not install more
remove the pallet, then lower onto a flat surface. than one expansion tank connection into any closed hydronic
The pump and motor unit will free-stand on the casing ribs. system.
Extra care is required to ensure the integrated controls do not Electric motor driven pumps should not be located in damp or
get damaged during lifting and installation. Simply connect the dusty location without special protection.
lifting straps to the lifting rings on each side of the unit.
Airflow into the motor and/or motor fan should not be obstructed.
As the lifting device is engaged (Using a spacer bar if neces-
It is good practice to leave sufficient space around equipment
sary) and the straps tighten ensure no part of the strapping
for operation, maintenance, and service needs.
is touching any part of the control or motor fan cover. Lift the
pumping unit carefully from the pallet in this manner and allow
the unit to stand upright on a flat surface and re-position the 1. 2 . 2 installation
straps, if necessary, to ensure safe and damage-free transporta- When installing vertical in-line pumps, an important consid-
tion into the pipe installation.
eration to accrue full added-value from the pump design is to
fig . 1.1.1 ensure that the pump is pipe-mounted and free to float with any
movement, expansion and contraction of the piping. Should any
vertical in-line pump use support to the structure it is impera-
tive that no pipe strain is imposed on the pump flanges. Tell-tale
pieces of equipment such as springs or waffle style neoprene
isolation pads that distort with pressure to indicate added pip-
ing weight, should be used under pump supports should the
pump not be truly pipe mounted.
Do not run the pump for any length of time under very
low flow conditions at the maximum speed or with the
discharge valve closed.
To do so could cause the water in the casing to reach super
heated steam conditions and will cause premature failure and
could cause serious and dramatic damage to the pump and
surrounding area.
2' or 3'
1. 2 mechanical installation height
above
finished
floor
1. 2 .1 location
In open systems, locate the unit as close as practical to the
liquid being pumped, with a short, direct suction pipe. Ensure
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
Recommended
field pressure
gauge piping
Split arrangement
Recommended coupler Flush line Flo-trex valve
field pressure
gauge piping Suction Pet cock
arrangement Flush line Guide (typ.)
Flo-trex valve
Suction
Pet cock
guide (typ.)
Pipe support 2' or 3'
Split height
coupler above
Neoprene
isolation finished
Drain connection floor
2' or 3' pad
height above
Drain connection finished floor
c discharge elbow for minimum footprint Floor mounted saddle supports (fig. 1.2.5) are typical for
condenser water pumps where cooling tower base is at the
Should additional space saving be required the discharge spool
mechanical room elevation.
piece may be replaced by a long-radius elbow.
fig . 1. 2 .5
fig . 1. 2 .3
Split coupler
Flush line
Flo-trex valve
Recommended field
pressure gauge
piping arrangement
Suction
Guide
Drain
Connection
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
Recommended field
pressure gauge Flush
Stanchion Plates line Flo-Trex valve
piping arrangement
Pet cock
(typ.)
Isolation Pads Suction guide
Stanchion plates
10
2.0 electrical setup stop digital input must be used (mains voltage directly con-
nected). This is the preferred method of starting and stopping
2 .1 precautions Design Envelope Pumps.
Safety, risk of death The three phase mains must be isolated before performing
All electrical connections should be carried out by maintenance of the pump.
a qualified and authorised electrician in accordance
with local site regulations and the latest issue of the iee 2 .1.3 additional motor protection
regulations.
With the exception of supply fuses / MCB’s to protect
Before removing the main cover, the system must be
the installation (for over-current and short-circuit
disconnected from the mains supply. After switching
protection), no additional overload or over-tempera-
off, wait for at least 4 minutes for the capacitors to
ture protection is required (i.e. thermal overloads).
discharge before opening the cover.
Protection features include:
caution
• Mains phase loss
High voltage testing (Megging) of the motor/inverter
• Over voltage
may cause damage to the electronic components and
• Under voltage
therefore should not be carried out.
• Electronic thermal motor protection
• Short circuit on motor terminals
2 .1.1 ground leak age current
• Ground fault on motor terminals
Ground leakage current is primarily caused by the • Over temperature
capacitance between motor phases and the motor 2 .1. 4 motor thermal protection and der ating
frame. The Radio Frequency Interference (rfi) filter
contributes additional leakage current, as the filter circuit is The Design Envelope motors are thermally protected in case
connected to ground through capacitors. limits are exceeded (140°c), another protection is provided
thought the drive.
The size of the leakage current to the ground depends on the
following factors, in order of priority:
a der ating for ambient temper ature
1 Switching frequency
The ambient temperature (tama x) is the maximum tempera-
2 Motor grounded on site or not
ture allowed.
The leakage current is of importance to safety during handling/
operation of the Design Envelope pump if (by mistake) the on- derating for ambient temperature
11
derating for air pressure
M
100
rated torque [%]
80
60 1 3 2 4
40
20
0
0 500 1000 1500 2000 2500 3000 3500 d earth leak age current
altitude [m]
Earth leakage current is primarily caused by the capacitance
between motor phases and the motor frame. The rfi filter
c der ating for running at low speed contributes additional leakage current, as the filter circuit is
connected to earth through capacitors (Cy).
When a centrifugal pump or a fan is controlled by a 432 2 &
4372 type A Motor, it is not necessary to reduce the output The size of the leakage current to the ground depends on the
at low speed because the load characteristic of the centrifugal following factors, in order of priority:
pumps/ fans, automatically ensures the necessary reduction. 1 Switching pwm frequency
The 432 2 & 4372 Permanent Magnet motors running con- 2 Motor grounded on site or not
stant load torque applications continuously at low speed must
The leakage current is of importance to safety during handling/
be de-rated (see diagram) or an independent fan must be used.
operation of the drive if (by mistake) the drive has not been
In the Permanent Magnet motor all control terminals are sup-
earthed.
plied from or in connection with extra low voltage (pelv).
80
1 The load generates energy.
60
2 During deceleration (ramp-down) if the moment of inertia is
40
high, the load is low and the ramp-down time is too short for
20 the energy to be dissipated as a loss in the motor frequency
0
converter, the motor and the installation.
0 1000 2000 3000 4000 The drive turns off to protect the igbt transistors and the
rated speed [rpm] intermediate circuit capacitors when a certain voltage level is
reached on DCbus.
The components that make up the electrical isolation, as de-
scribed below, also comply with the requirements concerning f mains supply interference/harmonics
higher isolation and the relevant test as described in en 50178. A motor integral drive takes up a non-sinusoidal current from
The galvanic isolation can be shown in three locations (see mains. A non-sinusoidal current can be transformed by means
drawing below),namely: of a Fourier analysis and split up into sine wave currents with
1 Power supply (smps) including signal isolation of VDCbus, different frequencies, i.e. different harmonic currents in with 50
indicating the intermediate voltage. Hz as the basic frequency.
2 Gate drive that runs the IGBTs (opto couplers) Some of the harmonic currents might disturb communication
3 DCbus Voltage transducer (opto couplers) equipment connected to the same transformer or cause reso-
nance in connection with power-factor correction batteries.
4 Current transducers (Hall Effect-Based Current Sensor).
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
12
To ensure low, harmonic currents, for the residential and com- Max relatively 95% (iec 60068-2-3)
mercial environments, an optional harmonic filter is necessary. humidity
Operating ambient 0:40°c
2 . 2 electrical specification temperature
Storage ambient Temperature - 25°c:60°c
Main supply (l1 l2 l3)
Min. ambient 0°c
Supply frequency 48 - 62Hz
temperature at full
Supply voltage 1 × 200-230v ± 10%, operation
3 × 200-230v ± 10%, Altitude 0 - 3000m, de-rate 1% per 100m
3 × 380-480v ± 10%, above 1000m
3 × 575-600v ± 10%
Max. imbalance of ± 2% of rated supply Compliance with Standards
supply voltage en 61800-3:2004 Adjustable speed electrical power drive
Switching on Once every 2 minutes systems. emc requirements
supply voltage
iec 61800-5-1 Adjustable speed electrical drive sys-
tems - part 5-1: safety requirements
Output ratings - electrical, thermal and energy
Output Current 100% Drive Rated Power continuously en 60204-1 Safety of machinery - electrical emc
Overload Capacity 150% for 60 secs equipment of machines-part 1: gen-
Digital inputs eral rules
Programmable 2
digital inputs
Voltage level 0-24Vdc (user selectable npn or pnp)
Analog input
Programmable 1
analog voltage input
Voltage level 0:10Vdc
Input resistance Rin 10KΩ
Resolution 12bit
Programmable 1
analog current inputs
Current range 0:20mA
Input resistance Rin 500Ω
Relay Output
Programmable relay 2 (n.o. n.c. com)
output
Max terminal load 250Vac 2A 500VA
Externals
Enclosure ip55
Vibration test ec 60068-2-6
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
13
fig 2 .3 .1 Upper right corner of the motor. Use Access port #1 Before removing the main cover, the system must be
for power wiring and ground. disconnected from the mains supply. After switching
pin1 l1 l1 power supply
off, wait for at least 4 minutes for the capacitors to
pin2 l2 l2 power supply
discharge before opening the cover.
pin3 l3 l3 power supply 1 a
b
Ground
Access1
Access2
Access1
2.5 mm
l3
l2 Access2 2 a
l1
3 mm
2.5 &
3 mm
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
14
caution
5
power
from mcc
ethernet
cable
router
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
15
Analog
b set ting the analog / digital inputs from
Input
web interface
Wiring
i set ting the digital inputs from the web
interface
Login to the web interface (Check Web Interface in section
4.4) From Setting Pump
Under Digital Input 1/ Digital Input 2, Select On/Off and hit
Digital
Update
Input
Wiring
16
b setting speed control through voltage signal d setting speed control through differential
0-10v pressure (dp) sensor 0-10v
17
500 Ohm
2 .3 .9 supply fusing
Branch circuit protection
V
In order to protect the installation against electrical and fire
Vdig_out1
hazard, all branch circuits in an installation, switch gear, ma-
2 .3 .7 relay output chines etc., must be short-circuit and over-current protected
according to the national/international regulations. Please refer
J5 & J8 for Relay output
to section 8 .0 (Fuse and wire recommendation).
n.o. 2 Relay n.o.
j8
n.c . 2 Relay n.c. Short circuit protection
Run
com2 Relay 2A 250Vac The inverter must be protected against short-circuit to avoid elec-
trical or fire hazard. The frequency converter provides full short
n.o. 1 Relay n.o.
j5 circuit protection in case of a short-circuit on the motor output.
n.c . 1 Relay n.c.
Alarm
com 1 Relay 2A 250Vac
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
18
2 . 4 . 4 rs 485 wiring
For Modbus rtu or BACNet ms/ tp connection to building automation sys-
CAN bus
tem, connect r s485 cable to this port per fig. 2 . 4 . If the depc is connected
to the ba s, ensure that the terminating resistor switch is set to Enabled
(towards the en label for the ba s ports).
Modbus If multiple pumps are connected in parallel to the ba s, the ba s wiring (sup-
plied by others) should be daisy chained together. Ensure that only the first
and last terminating resistor switches are set to Enabled. See example below
in fig 2.4.1
fig 2 . 4 .1
fig 2 . 4 a ba b a ba ba
g g g g
2 . 4 .5 networking options
A = + Positive
B = - Negative bms
G = Ground
rs-485
2 . 4 .1 bat tery
The battery is used to power the real-time clock
whenever the pump is disconnected from mains
power. It is recommended the battery be changed
periodically every 2 to 3 years.
bms
2 . 4 . 2 ethernet and wifi connectivit y
For BACNet tcp/ip connection to building
automation system, connect connect r j-45 cable
to this port per fig. 2 . 4
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
19
3 .0 networking controls
For connection to the building automation system (ba s), the
pump needs to be properly configured to the network. Ensure
the r s485 cable is connected to the controller board (fig.2 . 4).
Or if connecting to the bas via router, ensure that the r j-45
cable is connected to the controller board (fig. 2 . 4).
20
21
function
code
change
start modbus # of data
read write address register description register s
during
t ype
unit notes
oper ation
0×03 0×0 6
Control Settings
1 = Parallel; 2 = Inputs; 3 = Remote;
4 = Constant Flow; 5 = Constant Pressure;
6 = Linear Pressure; 7 = Quadratic Pressure;
x 300 3 01 Control Mode 1 Yes uint16 -
8 = Quad Pressure Maximum;
9 = Quad Pressure Minimum;
10 = Quadratic Pressure Max/Min
x x 3 01 302 HOA State 1 Yes uint16 - 0 = Off; 1 = Hand; 2 = Auto
1 = standard; 2 = mode 1 (heating mode);
x x 302 303 Active Parameters 1 Yes uint16 -
3 = mode 2 (cooling mode)
x x 303 304 Minimum Speed Limit 1 Yes uint16 0.1 In rpm
x x 304 305 Maximum Speed Limit 1 Yes uint16 1 In rpm.
x x 305 306 Hand Mode Speed 1 Yes uint16 0.1 Units as configured on Pump Control Module.
x x 306 3 07 BMS Set Speed 1 Yes uint16 0.1 Units as configured on Pump Control Module.
Alarms and Warnings
x 400 4 01 Alarms 2 n/a uint32 - Refer to Alarms Table for Bit Positions
x 402 403 Warnings 2 n/a uint32 - Refer to warnings table for Bit Positions
x 404 405 Acknowledge Warnings 2 Yes uint32 - 32-bit field corresponding to the warning field
Parameters
Standard Mode – Zero Value for standard active mode. Units as
x 500 5 01 2 Yes uint32 0.01
Flow Head configured on Pump Control Module.
Standard Mode – Design Value for standard active mode. Units as
x 502 503 2 Yes uint32 0.01
Head configured on Pump Control Module.
Standard Mode – Design Value for standard active mode. Units as
x 504 505 2 Yes uint32 0.01
Flow configured on Pump Control Module.
Standard Mode – Minimum Value for standard active mode. Units as
x 506 5 07 2 Yes uint32 0.01
Flow configured on Pump Control Module.
Value for active mode 1. Units as configured
x 508 509 Mode 1 – Zero Flow Head 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 1. Units as configured
x 510 511 Mode 1 – Design Head 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 1. Units as configured
x 512 513 Mode 1 – Design Flow 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 1. Units as configured
x 514 515 Mode 1 – Minimum Flow 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 2. Units as configured
x 516 517 Mode 2 – Zero Flow Head 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 2. Units as configured
x 518 519 Mode 2 – Design Head 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 2. Units as configured
x 52 0 521 Mode 2 – Design Flow 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 2. Units as configured
x 522 52 3 Mode 2 – Minimum Flow 2 Yes uint32 0.01
on Pump Control Module.
Information
The pump name as a series of ascii
x 900 9 01 Pump Name / Tag name 8 n/a ascii -
characters.
Serial No. of the Pump represented by ascii
x 908 909 Serial Number 7 n/a ascii -
characters
Divide the number by 100 to get the major.
x 915 916 Firmware Version 1 n/a uint16 00.00
minor version of the dep c .
x 916 917 Hardware Version 1 n/a uint16 - The Pump Control Module hardware version.
x 917 918 Modbus Version 1 n/a uint16 - Version of the Armstrong Modbus version
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
22
23
24
function
code
change
start modbus # of data
read write address register description register s
during
t ype
unit notes
oper ation
0×03 0×0 6
Units
x 250 2 51 Flow Units 1 n/a uint16 - 1 = l/s; 2 = m 3 /h; 3 = g/m
x 2 51 2 52 Pressure Units 1 n/a uint16 - 1 = bar; 2 = kPa; 3 = psi; 4 = ft; 5 = m
x 2 52 253 Power Units 1 n/a uint16 - 1 = kw; 2 = hp
x 253 254 Speed Units 1 n/a uint16 - 1 = rpm; 2 = %
1 = Degrees Celsius;
x 254 255 Temperature Units 1 n/a uint16 -
2 = Degrees Fahrenheit
Counters
Total Pump Running
x 275 276 2 n/a uint32 1 h
Hours
Trip Pump Running
x x 277 278 2 n/a uint32 1 h Writing 0 to this register resets the counter.
Hours
Total Controller
x 279 280 2 n/a uint32 1 h
Running Hours
Present Controller The running hours since the controller was
x 2 81 282 2 n/a uint32 1 h
Running Hours powered on.
Total Pump Running
x 283 284 2 n/a uint32 1 kWh
kWh Counter
Trip Pump Running kWh
x x 285 286 2 n/a uint32 1 kWh Writing 0 to this register rests the counter.
Counter
Control Settings
1 = Parallel; 2 = Inputs; 3 = Remote;
4 = Constant Flow; 5 = Constant Pressure;
6 = Linear Pressure; 7 = Quadratic Pressure;
x 300 3 01 Control Mode 1 Yes uint16 -
8 = Quad Pressure Maximum;
9 = Quad Pressure Minimum;
10 = Quadratic Pressure Max/Min
x x 3 01 302 HOA State 1 Yes uint16 - 0 = Off; 1 = Hand; 2 = Auto
1 = standard; 2 = mode 1 (heating mode);
x x 302 303 Active Parameters 1 Yes uint16 -
3 = mode 2 (cooling mode)
x x 303 304 Minimum Speed Limit 1 Yes uint16 1 In rpm
x x 304 305 Maximum Speed Limit 1 Yes uint16 1 In rpm.
x x 305 306 Hand Mode Speed 1 Yes uint16 0.1 Units as configured on Pump Control Module.
x x 306 3 07 BMS Set Speed 1 Yes uint16 0.1 Units as configured on Pump Control Module.
x x 308 309 Start/Stop 1 Yes uint16 - 0 = stop pump; 1 = start pump
Alarms and Warnings
x 400 4 01 Alarms 2 n/a uint32 - Refer to alarms table for bit positions.
x 402 403 Warnings 2 n/a uint32 - Refer to warnings table for bit positions.
x x 404 405 Acknowledge Warnings 2 Yes uint32 - 32-bit field corresponding to the warning field.
Parameters
Standard Mode – Zero Value for standard active mode. Units as
x 500 5 01 2 Yes uint32 0.01
Flow Head configured on Pump Control Module.
Standard Mode – Value for standard active mode. Units as
x 502 503 2 Yes uint32 0.01
Design Head configured on Pump Control Module.
Standard Mode – Value for standard active mode. Units as
x 504 505 2 Yes uint32 0.01
Design Flow configured on Pump Control Module.
Standard Mode – Value for standard active mode. Units as
x 506 5 07 2 Yes uint32 0.01
Minimum Flow configured on Pump Control Module.
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
25
function
code
change
start modbus # of data
read write address register description register s
during
t ype
unit notes
oper ation
0×03 0×0 6
Mode 1 – Zero Flow Value for active mode 1. Units as configured on
x 508 509 2 Yes uint32 0.01
Head Pump Control Module.
Value for active mode 1. Units as configured on
x 510 511 Mode 1 – Design Head 2 Yes uint32 0.01
Pump Control Module.
Value for active mode 1. Units as configured on
x 512 513 Mode 1 – Design Flow 2 Yes uint32 0.01
Pump Control Module.
Value for active mode 1. Units as configured on
x 514 515 Mode 1 – Minimum Flow 2 Yes uint32 0.01
Pump Control Module.
Mode 2 – Zero Flow Value for active mode 2. Units as configured
x 516 517 2 Yes uint32 0.01
Head on Pump Control Module.
Value for active mode 2. Units as configured
x 518 519 Mode 2 – Design Head 2 Yes uint32 0.01
on Pump Control Module.
Value for active mode 2. Units as configured
x 52 0 521 Mode 2 – Design Flow 2 Yes uint32 0.01
on Pump Control Module.
Mode 2 – Minimum Value for active mode 2. Units as configured
x 522 52 3 2 Yes uint32 0.01
Flow on Pump Control Module.
Information
The pump name as a series of ascii
x 900 9 01 Pump Name / Tag name 8 n/a ascii -
characters.
Serial No. of the Pump represented by ascii
x 908 909 Serial Number 7 n/a ascii -
characters
Divide the number by 100 to get the major.
x 915 916 Firmware Version 1 n/a uint16 00.00
minor version of the depc.
x 916 917 Hardware Version 1 n/a uint16 - The Pump Control Module hardware version.
Version of the Armstrong Modbus registers
x 917 918 bms Modbus Version 1 n/a uint16 -
used.
Patch version of the depc. To be appended to
x 918 919 Firmware Patch Version 1 n /a uint16 00
firmware version register.
26
27
Warranty
Does not cover any damages to the equipment resulting from
failure to observe the above precautions. Refer to Armstrong
General Terms and Warranty sheet. Contact your local Arm-
strong representative for full information.
4 . 2 starting pump
Ensure that the pump turns freely by hand, or with 4 . 2 .1 auto flow balancing
some gentle mechanical help such as a strap or Allen
key in coupling bolt. Auto-Flow Balancing automatically determines the control
curve between the design flow at the on-site system head,
Ensure that all protective guarding is securely fixed in position.
and the minimum (zero-flow) head that will typically be
The pump must be fully primed on start up. Fill the pump cas- lowered (reset).
ing with liquid and rotate the shaft by hand to remove any air
Often the actual system head is less than expected, and the
trapped in the impeller. On split-coupled Design Envelope units
pump will operate further to the right of the curve at a higher
any air trapped in the casing as the system is filled must be
flow rate than it was designed for due to less system resistance.
removed by the manual air vent in the seal flush line. Ensure
The Auto Flow Balancing function performs a scan of the
entrained air is removed from Design Envelope pumps, prior to
sensorless map against the actual system to establish the actual
starting, through the air vent on the seal flush line. Open vent
head for the design flow. The minimum (zero-flow) head will
until clear of air.
be reset according to the actual head at the design flow – the
Design Envelope close-coupled units are fitted with seal flush/ factory default is 40% of the design head, but can be lowered
vent lines piped to the pump suction area. When these units oper- further for more energy savings if all zones are still satisfied.
ate, residual air is drawn out of the pump towards the suction pip-
ing. Energize each motor momentarily and check that the rotation
corresponds with the directional arrow on the pump casing.
Start the pump with the discharge valve closed and the suction
valve open, then gradually open the discharge valve when the
motor is at operating speed. The discharge valve may be cracked
or open slightly at start up to help eliminate trapped air.
When stopping the pump: Close the discharge valve and
de-energize the motor.
Do not run the pump against a closed discharge valve at full
speed for an extended period of time (a few minutes maximum.)
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
28
1234
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
29
4 .3 .3 about
Click on Reset to
reset Trip counters
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
30
save
save
a
save
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
31
32
4 .3 .6 pump control
Activate Energy
Performance Bundle
b
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
33
Single
c d
d
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
34
35
4 .3 .8 trend - gr aph
There are 3 parameters that can be trended on the touch
screen interface:
• Power
• Flow
• Head
Which allows users to see a quick history of key performance data.
To see a more comprehensive view of the trends, the pump data can
be exported in CSV format for review and analysis on a separate
computing device.
4 .3 .9 brightness adjustment
To adjust the brightness of the touch screen interface, go to Settings -> Brightness.
10 = highest brightness, 1 = lowest brightness
save
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
36
37
Connect the depc to the Webserver, in the Data -> Trends ->
Export Log File section.
Select the start date, the end date, and then click Export History
to download the data log file in CSV format.
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
38
bms
Connect your device to the router via wifi or by Ethernet cable. Press settings General, select desired units and click Update
39
To modify Date/Time: click Settings General and modify date To modify out settings: Settings Pump,
and time To modify digital outputs: enable in Outputs and select desire,
To modify analog outputs: click enable and speed.
To modify relay settings: enable Relay functions and select
desired settings
Settings Pump,
To set the BACnet max info from, Settings Communication,
To change motor ramp up and down settings, input in Motor
enable BACnet Serial and input in Max Info. Frame
Ramp up Time and Motor Ramp Down Time
To change Pump high and Low Speed, input rpm in High Speed
Limit and Low Speed Limit
To change pump tag, input new tag in Pump Tag
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
40
Region of
5% flow & head
0205H-001.5 1.5 62.6
accuracy
40 0205-002.0 2 62.6
0205H-002.0 2 62.6
30
54% Nominal
pump speed
0205-003.0 3 62.6
20 Sensorless Limit 0205H-003.0 3 62.6
40% Nominal
pump speed
10
0205-005.0 5 69.2
End of Envelope
0205-007.5 7.5 69.2
0
0 100 200 300 400 500 600 700 800 900 0205-010.0 10 80.3
Flow (USgpm) 2505-001.5 1.5 62.6
2505-002.0 2 62.6
The tolerance is applicable when the flow is between 30% and 2505-003.0 3 62.6
110% of bep flow at Nominal Pump Speed; and the operating 2505-005.0 5 69.2
point is at 5 4% of Nominal Pump Speed, or greater; and the 2505-007.5 7.5 69.2
motor power is 2hp, or greater. 0305-003.0 3 62.6
Flow readouts outside the above limits will be less accurate. 0305-005.0 5 62.6
Nominal Pump Speed is displayed as the top speed on any 0305-007.5 7.5 69.2
Design Envelope pump curve. 0305-010.0 10 77.0
Sound pressure level measurements made in accordance with iso
3744,± 3dB tolerance (measuring level A-Weighted)
Data based on motor frames at 380-480V. Audible noise is mainly
from the motor fan and will be reduced when operating at part load
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
41
600
curve
5.2 constant pressure 400 ta r g e t
200
Design Envelope pumps can be configured to maintain a con-
0
stant pump head in a system as the demand varies. This effec- 0 20 40 60 80 100 120 140 160 180 flow
0
crease speed to maintain a minimum flow setting as the system
180 flow
0 20 40 60 80 100 120 140 160
load is shutting down.
Pump controls can only control the flow to the maximum speed
5.3 linear pressure or motor limit;
head
Linear Pressure Control is where the controller is set to control 1200
the speed according to a control ‘curve’ between max and min 1000
flow. This type of control will change the pump speed to ensure 800
target curve
the pump operates on the projected linear control curve, where 600
Minimum Flow Setting
the pump head varies directly with the flow. This type of control
400
is well known globally and is effective as far as the straight lin-
200
ear line will allow. For more realistic hvac control with superior 0
energy savings, consider the following control recommendation 0 20 40 60 80 100 120 140 160 180 flow
flow protection
1000
800
Linear Pressure Control Curve
600 This configuration is ideal for hvac hydronic systems where
pumps are generally oversized and a flow limit is required for
400
ve
cur
200 ta r
get system equipment stability and resulting energy savings. This
0 control will take advantage of the 5.4 Quadratic Curve Con-
0 20 40 60 80 100 120 140 160 180 flow
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
42
trol mode, where the pump will decrease speed to maintain a 1p eff 2p eff 3p eff 4p eff
efficiency
head
pumps are typically oversized for the application. Pump controls pspc control curve
2- pu m
1-pu mp
head
1200
1000 flow
600 Both individual pumps and total parallel flow can be monitored
400
by accessing Settings -> Pump -> Control Mode -> Parallel
target curve
200
Sensorless
0
0 20 40 60 80 100 120 140 160 180 flow
1000
target curve
800 Minimum & Maximum
Flow Settings
600
43
For 2 pump parallel operation: From the Webserver, choose Settings -> Pump, set control
Ensure that both terminating resistor switches are set to En- mode to Parallel with the following parameter values:
abled (towards the en label for the canbus port).
lh l h
g g
A = + Positive A = + Positive
B = - Negative B = - Negative
G = Ground G = Ground
A = + Positive
B = - Negative
G = Ground
A = + Positive
B = - Negative
G = Ground
A = + Positive
B = - Negative
G = Ground
5 .8. 2 modifying motor r amp up and down time
pump controller 1 pump controller 2 pump controller 3 Modify the time in the respective fields after clicking on Pump
l h lh
g
lh lh
g
under Settings
g g
44
45
Head 66.55 FT
Power 2.54 kW
Pump Auto Flow Parallel Single
Control Balancing
Voltage 333.6 V
Current 5.16 A iO
i Frequency
Adjust
IO Remote
Optional:
Current Terminal +10V or +24EXT can be used
for external power to sensor(s).
46
> 10% of
20 mA maximum pump
4 mA
setpoint 1 setpoint 2
flow
Pump
Optional 499±1% Ω resistor for
AO voltage control on each pump.
GND
+24V GND
External
+24V
+24V
GND
Control
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
47
Additional Pump
Optional 499±1% Ω resistor for
AO AO voltage control on each pump.
GND GND
Relay 2 Relay
+24V GND
NO NO
External
NC NC +24V
+24V
COM COM
GND
Control
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
48
Vertical In-Line pumps are built to operate without periodic Lubrication is not required. There are no bearings in the pump
maintenance, other than motor lubrication on larger units. A that need external lubrication service.
systematic inspection made at regular intervals, will ensure Large Design Envelope 432 2 units are installed with a shaft
years of trouble-free operation, giving special attention to the bushing located beneath the impeller that is lubricated from the
following: pump discharge.
• Keep unit clean
• Provide the motor with correctly sized overload protection. Motor
Keep moisture, refuse, dust or other loose particles away Follow the lubrication procedures recommended by the mo-
from the pump and ventilating openings of the motor. tor manufacturer. Many small and medium sized motors are
• Avoid operating the unit in overheated surroundings (Above permanently lubricated and need no added lubrication. Gener-
100°f/40°c). ally, if there are grease fittings evident the motor needs periodic
lubrication. None if not.
If one pump requires service, install the blanking plate to allow
the other pump head to continue operating Check the lubrication instructions supplied with the motor for
the particular frame size indicated on the motor nameplate.
warning
Whenever any service work is to be performed on
6.3 mechanical seal
a pumping unit, disconnect the power source to Mechanical seals require no special attention. The mechanical
the driver, lock it off and tag with the reason. Any seal is fitted with a flush line. The seal is flushed from discharge
possibility of the unit starting while being serviced must be of the pump casing on Design Envelope 432 2 pumps and from
eliminated. If mechanical seal environmental accessories are the suction on Design Envelope 4372 pumps.
installed, ensure water is flowing through the sight flow
The Design Envelope 432 2 pump is flushed from the pump dis-
indicator and that filter cartridges are replaced as recommend-
charge because the mechanical seal chamber is isolated from
ed. (See Armstrong files 43 . 85 and 43 . 86 for seal environmen-
the liquid in the pump by a throttle bushing. Because the seal
tal instructions).
chamber is isolated, seal environmental controls such as filters
and separators, when installed in the Design Envelope 432 2
flush line are very effective, as only the seal chamber needs
cleansing, and will prolong seal life in hvac systems.
Do not run the pump unless properly filled with water as the
mechanical seals need a film of liquid between the faces for
proper operation.
v-clamp ring
Mechanical seals may weep slightly at start-up. Allow the pump
to continue operating for several hours and the mechanical seal
to seat properly prior to calling for service personnel.
blanking plate
warning
Hydronic system components may be pressurized
which, if suddenly released, can cause serious injury or
death. When performing any kind of service to the
pump, the pressure must be released in the system and
the unit should be properly drained before starting any
service work.
Design Envelope 4322 & 4372 insta lla t io n &
Tango Pumping Unit oper ating in struct io n s
49
6.3 .1 mechanical seal replacement instruc- c Remove the mechanical seal rotating assembly (62) through
tions for rigid split- coupled pumping the gap between the pump and motor shafts.
units (series 4300 & 4322) d Disconnect the seal flush piping (59) from pump discharge.
Mark seal gland plate (5 4) position. Remove the seal gland
plate bolts and washer (lock washer) (5 2,163) and seal
10 05 gland plate (5 4). Remove the stationary seat (61) and seat
3 1
156
144 145 155
gaskets (55).
140
149
148
Seal replacement
21A 2 4 62 Handle mechanical seal carefully to protect seal faces from
62A 62C damage. Do not contaminate seal faces with finger prints
52163 62B e Replace the stationary seat (61) and gaskets (55) from
9 mechanical seal package, aligning the seat flush hole with
55
59 the seal gland plate flush line connection. Ensure the large
55
54 diameter gasket is on the bottom. Replace seal gland plate
61 21 (5 4) and tighten the seal gland plate bolts (5 2,163) evenly
and diagonally to 5 (ft. lbs) for 0.75" seal size.
f When installing the mechanical seal (62), ensure parts are
perfectly clean.
g Apply a small amount of temporary rubber lubricant emul-
sion to the O-ring (62b). Carefully slide the mechanical seal
rotating assembly (62) down the shaft onto the stationary
warning seat (61). Do not tighten the set screws (62 a ) on the side of
When reinstalling the clamp, tighten the clamp nut to the mechanical seal yet. Do not remove holding clips (62c).
90-100 in-lb torque.
If motor is replaced: Loosen set screws (56) on motor shaft
collar ( 155) and remove from old motor shaft. To position the
caution collar ( 155) correctly on the new motor shaft, temporarily fit
motor shaft collar ( 155) into groove of the keyed coupling half.
Do not use oil, Vaseline or other petroleum or silicon Slide collar, with coupling half onto new motor shaft until end of
based products for seal elastomer lubrication. Other- shaft lines up with line scored into coupling. Tighten the visible
wise elastomer swelling may occur, causing seal failure. set screws ( 156) in the collar ( 155) enough to hold the collar
Recommended: International Products Corp p-80 Rubber in place on the shaft and remove the coupling half. Tighten all
Lubricant Emulsion in USA & UK www.ipcol.com collar set screws ( 156) evenly and diagonally.
h Fit the motor shaft key (05) and the pump shaft key ( 149)
Seal Removal
then install the keyed coupling half ( 140) first.
An important feature of the rigid split-coupled pump is that the
note:
design permits removal of the mechanical seal without disturb-
ing the pump, motor or electrical wiring. For easier coupling installation, motor and pump shaft keys (05
& 149) should be 18 0 degrees from the working area. To auto-
a Disconnect the power supply at the main switch and close
matically locate the impeller in the pump, insert the coupling
the isolating valves on the suction and discharge. Empty
screw Allan wrench into positioning hole (2 1a ) and lift pump
casing by removing drain plug(s) located at the bottom.
shaft until the pump shaft collar is positioned in the coupling
b Loosen off the seal collar set screws (62 A ) Remove the groove, then rotate shaft to locate the pump shaft key ( 149)
coupling screws and lock washer ( 14 4,145) and separate into blind keyway in coupling.
the coupling halves ( 140). Remove the motor shaft key (05)
i Place the second coupling half into position and tighten the
and the pump shaft key ( 149).
coupling screws ( 14 4,145) following the tightening pattern
Do not remove motor collar ( 155) for seal replacement. shown on the illustration ( 1-2-3 -4).
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
50
b Isolation valves
6.3 . 2 mechanical seal replacement instruc- If the system is not drained: Ensure that the suction and dis-
tions for close- coupled pumping units charge piping isolation valves are closed. Remove drain plug
(series 4380 & 4372) ( 35) from the bottom of the casing and drain the pump.
51
be loosened by heating the impeller hub with a torch during the face first, until the carbon face is pressed firmly against the
pulling process to remove the impeller from the motor shaft. stationary seat (61). Firmly press on the rotating seal [seal
head] metal parts with a screw driver all the way around
h Remove mechanical seal from motor shaft the seal which will ensure that the faces are mated properly.
The mechanical seal spring usually comes free with the impeller. Remove the spring retainer from the seal spring and place
The mechanical seal rotating element [seal head] (62) must the seal spring over the rotating seal.
be pried loose with pry bars or screwdrivers, placed under
each side of the seal drive band. Leverage is applied against l Replace pump impeller
the adapter. Once loosened, the seal may be pulled free of • Install the impeller key on the shaft and place the seal spring
the shaft. retainer onto the impeller hub register. Slide the impeller in
Do not damage the carbon face when removing the rotating place on the stub shaft.
element [seal head]. It may be needed for analysis if seal failure • Take care and ensure that the seal spring is kept in place on
investigation is required. the seal rotating assembly and fits well into the retainer on
the impeller hub.
i Remove seal seat from adapter
The stationary seat (61) typically O-ring or L-cup mounted m Tighten impeller cap screw
Silicon Carbide material, is pried loose from the recess in the It is good practice to replace self locking screws, once removed.
adapter. If the seat cannot be removed in this manner, remove Install the impeller cap screw and washer (83 & 86). Hold the
the motor cap screws and washers [lock washers] (43 , 4 4) impeller the same way as when the cap screw was successfully
and separate the adapter (40) from the motor ( 10). A screw- loosened (pry bar or screw driver placed carefully between the
impeller blades) and tighten the cap screw with a socket wrench.
driver may then be used to push the seat out of the adapter
from the rear.
p Install new adapter O-ring
j Remove old casing gasket Insert new adapter O-ring into the O-ring groove of the adapter
and apply silicon or glycerine lubricant around the O-ring.
The former adapter O-ring should be scraped from the adapter,
leaving clean surfaces [groove] for the new O-ring. [A standard q Clamp Ring
putty knife and wire brush are useful for this purpose]. Insert Clamp Ring thru the impeller and adapter flange. Tighten
the nut on the clamp ring to 9 0 -10 0 lbs-in.
k Assembly Procedures:
Replace mechanical seal r Lower rotating assembly into place
• Clean the shaft stub (2 1) surface, ensuring all the former seal The rotating assembly motor, adapter and impeller combination
elastomer pieces have been removed. Inspect for damage. may now be lowered into the casing.
Replace if necessary.
s Casing and adapter clamp-ring
• Install a new stationary seat (61) in the adapter cavity, being
The casing and adapter clamp-ring is now installed and tight-
sure the lapped (polished) side of the insert is facing up.
ened with a wrench.
Ensure that the cavity has been thoroughly cleaned. Lubri-
Reconnect the flush/vent flex hose assembly [check for damage
cate the stationary seat O-ring or L-cup with a small amount
and replace if necessary].
silicon or glycerine lubricant and firmly press down straight
and even into the adapter cavity. Do not press the seat in
t Isolation valves
with bare fingers or hammer it down, use a clean cloth or the
Replace the casing drain plug and open the suction and dis-
cardboard disc typically supplied with the seal packaging.
charge isolation valves.
Contamination of the polished and lapped stationary seat
face could cause leakage. If the adapter was removed from Motor wiring
the motor, taking care that the stationary seat is carefully • The motor conduit and its wiring are now replaced. If the
guided over the stub shaft when assemble the adapter back motor is new, double check that the voltage and rpm are
onto the motor. identical to the original motor.
• Lubricate the inside of the rotating seal [seal head] (62) • Be sure to check rotation of the motor after rewiring if the
with a small amount of silicon or glycerine lubricant and motor is three phase and correct if necessary, by switching
slide onto the stub shaft (2 1) with a twisting motion, carbon any two lead wires.
i nstall a ti o n & Design Envelope 4322 & 4372
o perat i ng i nstr uct i on s Tango Pumping Unit
52
• Ensure that the pump is filled with water before operating to 6. 4 system cleanliness
check rotation.
Before starting the pump, the system must be thoroughly
u Conduit Box Cover cleaned, flushed and drained and replenished with clean liquid.
The conduit box cover is replaced after checking the motor rota-
Welding slag and other foreign materials, Stop Leak and clean-
tion. The pump may now be placed in operation.
ing compounds and improper or excessive water treatment are
all detrimental to the pump internals and sealing arrangement.
Proper operation cannot be guaranteed if the above conditions
are not adhered to.
53
54
Armstrong disconnect switch and fuse rating - 380-480v input power for use Design
Envelope Permanent Magnet Motors
Armstrong disconnect switch and fuse rating - 575v-660v input power for use Design
Envelope Permanent Magnet Motors
55
Features
Connect pump to
Secure IoT Connectivity network wirelessly
via Wifi
Plug 'n play setup, no l an connection required. Pump con-
nected to the ibm Watson analytics platform cloud via a 4g
pumps
lte router with built-in cellular modem. Authentication key and
1-way push notifications only with no inbound communication
to pumps make for safe connection
Real Time Alerts 10.0 connectivity kit
Know of problems before they occur. Pump Manager will alert
you when something is wrong Pump Manger integration procedure
Performance Reports This procedure describes the steps to connect an Armstrong Pump
Manger router to a Design Envelope Pump with a depc controller.
You can now view operation trends and make data informed
decisions Each site will be required to have a factory programmed router for
data transfer (included with each Design Envelope Pump order).
Predictive Maintenance
The pump will advise which parts it needs! And tell you where Refer to File No: 100.8154 on Armstrong Corporate Website for
to buy them as well full details.
Benefits
Lower Operating Costs
• Optimal operation for maximum energy efficiency
• Lower OpEx costs
Increase Availability & Reliability
• Reduce unexpected failures
• Early problem detection
• Faster return to service
Improve Comfort and Productivity
• Keep flows in the desired range, reducing temperature
swings
Improve Building Resilience and Future Decisions
• Make informed capital investment decisions
buffalo
93 east avenue
north tonawanda, new york
u.s.a., 14120 -6594
+1 716 693 8813
birmingham
heywood wharf, mucklow hill
halesowen, west midlands
united kingdom, b62 8dj
+44 (0) 8444 145 145
manchester
wolverton street
manchester
united kingdom, m11 2et
+44 (0) 8444 145 145
bangalore
#59, first floor, 3rd main
margosa road, malleswaram
bangalore, india, 560 003
+91 (0) 80 4906 3555
shanghai
unit 903, 888 north sichuan rd.
hongkou district, shanghai
china, 200085
+86 (0) 21 5237 0909
são paulo
rua josé semião rodrigues agostinho,
1370 galpão 6 embu das artes
sao paulo, brazil
+55 11 4785 1330
ly o n
93 rue de la villette
lyon, 69003 france
+33 (0) 420 102 625
dubai
jafza view 19, office 402
p.o.box 18226 jafza,
dubai - united arab emirates
+971 4 887 6775
mannheim
dynamostraße 13
68165 mannheim
germany
+49 (0) 621 3999 9858
a r m s t r o n g f lu i d t e c h n o lo g y
established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m