Fermator Door Operator VF7 Relay User Manual SW V7.01.04 - 05 - 2018

This document is a user manual for an automatic horizontal sliding car door. It provides information on the VF7 Relay Electronic Module component, including its inputs, outputs, and functions like opening, closing, and responding to sensors. Safety warnings are also given to not open the cover of the module.

Uploaded by

alfrelia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
83% found this document useful (6 votes)
12K views28 pages

Fermator Door Operator VF7 Relay User Manual SW V7.01.04 - 05 - 2018

This document is a user manual for an automatic horizontal sliding car door. It provides information on the VF7 Relay Electronic Module component, including its inputs, outputs, and functions like opening, closing, and responding to sensors. Safety warnings are also given to not open the cover of the module.

Uploaded by

alfrelia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

User manual.

ENG Automatic horizontal sliding car door.


Component: VF7 Relay Electronic Module. V7.01.04.

MAN-MU00000V7ENGHP-05.2018
2
230 V

ENTRADAS / INPUTS
12...60 V DC 100...230 V AC N 5
8 CERRAR
SALIDAS / OUTPUTS CLOSE ATENCIÓN / CAUTION
NO ABRIR LA TAPA
32 31 11 0V
ABIERTA DO NOT OPEN THE COVER
OPEN PE 6
30 33 10 COM
CERRADA
34 35 CLOSED 9 OUT +12 V EN 12016: 2013 INMUNIDAD NIVEL INDUSTRIAL
12...60 V DC 100...230 V AC EN 12016: 2013 IMMUNITY INDUSTRIAL LEVEL OFF ON
ABRIR L 7
38 37 FOTOCÉLULA 12
OPEN
PHOTOCELL
36 39 ALIM. SUPPLY
100...230 VAC
OBSTRUCCIÓN
OBSTRUCTION ENTRADAS PRIORITARIAS / PRIORITY INPUTS
40 41

44 43 BARRERA MOTOR
FOTOELÉCTRICA REABRIR SEÑAL DE PISO
LIGHT CURTAIN RE-OPEN 21 26 FLOOR LEVEL QCI-VF.7A.C.I.0.EE
42 45 U 56
TEMPERATURA OUT +12 V 23 25 CERRAR LENTO
46 47 TEMPERATURE SLOW CLOSE V 57
BARRERA 22 24
FOTOELÉCTRICA CONTACTO DE BYPASS
LIGHT CURTAIN BYPASS CONTACT M W 58
PUERTO COM
COM PORT
PE 59
13 OK ESTADO
OK STATUS

ENCODER

55

Optional

VF4+ OUTPUT 230 V. AC


SALIDA VF4+ SUPPLY
DO NOT OPEN
THE COVER
ALIMENTACIÓN
5 L1’
230 V
NO ABRIR LA TAPA
L2 1
6 GND
GND 2
7 L2’
L1 3

LANDING FLOOR
ALIMENTADOR DE RELLANO PISO

EMERGENCIA 66
CONTROL VF4+
EMERGENCY 67
26 FLOOR / PISO
SUPPLIER
23 12 V COM

BATTERY
ON 1 BAT BATERIA
OFF 2 ON

INPUTS STANDBY
29
ENTRADAS ESTADO
(yellow / amarillo)

28
FUSE 20A

1 2

ON OFF
12 V 2 Ah

VF7
CONNECTION
INPUTS / OUTPUTS

4 - 7 POWER SUPPLY.
The circuit has been designed to operate with a main supply of 230 V AC (+10%,-15%, 50
or 60 Hz).
The VF7 Relay incorporates a soft-start system to control the bulk capacitors charge and
prevent short circuits.

Note: It is important that the Door Operator Module has a good earth connection.

INPUTS
The circuit can work with external voltage inputs or internal voltage input (voltage free contact).

8 CLOSE SIGNAL.

This signal is used for ordering to close the door. With an external voltage input the tension
to apply could be from 12 V DC to 60 V DC or 100 V AC to 230 V AC between this input and
common (10). With an internal voltage input the tension applied is 12 V DC between this input
and Out +12 V (9).

9 12 VOLT.
Isolated 12 Volts output available to control the door through a voltage free contact.
Features are:
a) This supply must only be used for this purpose.
b) This contact must be isolated from any other power supply.

10 COMMON.
Is the reference used for the opening and closing signal.

11 0 VOLTS.
Is the opposite pole to 12 V, in the case of using internal voltage it should be connected
to common input.

VF7 3
INPUTS / OUTPUTS

12 OPEN SIGNAL.
Is a signal that orders the door to open. With an external voltage input the tension to
apply could be from 12 V DC to 60 V DC or 100 V AC to 230 V AC between this input and
common (10). With an internal voltage input the tension applied is 12 V DC between this
input and Out +12 V (9).

13 COM PORT. PUERTO COM


COM PORT
The serial port is used to connect with external devices, interfaces and
13
future expansion devices. Operating speed 1.200 Baud per second,
current loop.

21 - 26 PRIORITY INPUTS.

21 REOPEN.
This signal is used for installing the cabin door switch, an external barrier or other devices.
In order to active this signal, connect the re-open input (21) with the +12 V (23). Use voltage
free contacts. The reopening signal has priority over the closing signal.

22 LIGHT CURTAIN.
This input is used to detect a failure from the light curtain installed.

23 OUT +12 V.
Isolated 12 Volts output available to activate the priority inputs via a voltage free contact.
Features are:
a) This supply must only be used for this purpose.
b) This contact must be isolated from any other power supply.

24 BYPASS CONTACT.
This signal is used to connect an external security switch to detect door closed position.

25 SLOW CLOSING.
This signal is used for ordering to close the door slowly. The slow signal has priority over
the control signals and the photocell. It's created for working with fire fighting systems.

26 FLOOR LEVEL.
This input is used to connect the external emergency supplier that allows the opening
manoeuvre in the case of power failure. Fermator emergency supplier uses a battery of
12 V, able to give power during 15 seconds for a passengers rescue.

4 VF7
INPUTS / OUTPUTS

30 - 47 OUTPUT RELAYS AND LED INDICATORS.


Output relays have been provided to give continuous information to the main lift controller
concerning the status of the doors.

• Open.
LED indicator and relay activated when the
doors are fully open.

• Closed.
LED indicator and relay activated when the
doors are fully closed and locked.

• Photocell.
LED indicator and relay activated when
the photocell or the reopening input is
operated.

• Obstruction.
LED indicator and relay activated when an
obstacle is detected that stops the doors
from closing. The signal will reset when
the doors reach the opened or closed
position.

• Light curtain.
LED indicator and relay activated when a failure occurs on the light curtain.

• Temperature.
LED indicator and relay activated when the VF temperature or motor temperature exceeds
the safety limit. When this output is activated the manoeuvre must give the order to the
cabin to go to the next floor, open the door to let out the passengers and stop applying
tension to the motor.

• Status.
Blinking green LED indicating proper working conditions. If an
alarm occurs the LED lights red.
OK STATUS

VF7 5
INPUTS / OUTPUTS

55 ENCODER. ENCODER
An integral quadrature pulse encoder is connected to this input. The
purpose of the encoder, which is situated inside the motor, is to inform
the control of the exact position and speed of doors.
55

The software V7.00.02 is not compatibility with Fermator asynchronous


motor.

56 - 59 MOTOR. MOTOR

Output to the 3 phase motor varying the voltage and frequency to U 56

control speed and torque. V 57

VF7 Relay power supply switch has to be turned off before disconnecting M W 58
the motor power connector.
PE 59

60 ON / OFF SWITCH.
Disconnects the unit from the 230 V AC mains supply.

GRAPHIC INTERFACE

Three main objectives can be achieved with the VF7 Relay graphic interface:
1. To detect possible alarms or errors in the unit (Alarms Menu).
2. To see the parameters value and active signals (Monitor Menu).
3. To modify the internal program parameters and options (Programming Menu).

Once the unit is connected it will show the software version Fermator V7.01.04 .

Push the button to a access to the VF7 Relay menus.

There are four main menus with different submenus: Alarms Menu, Monitor Menu, Programming
Menu and Settings Menu.

Push the or button to select the menu.

Push the button to enter into the VF7 Relay menus.

Push the button to return to the software version screen.

6 VF7
GRAPHIC INTERFACE
ALARMS MENU.
The Alarms Menu shows the last five alarms activated in the unit.

Push the or button to see the different alarms.

While an Alarm is activate the VF7 Relay graphic interface shows the alarm activated in that moment.
After an alarm has been disabled the VF7 Relay performs a start-up.

Alarm Description Possible problem Actions VF7 recovery

Short-C The power module has been -- The motor could be short- -- Check the motor wire. Push the OK button.
short-circuited. circuited. -- Check the motor.
If 3 short-circuits take place -- VF7 malfunction
in one minute, the alarm will
be permanent activated.

Current High current consumption. -- Hard obstacle in clearance. -- Check the mechanical Push the OK button.
part.

Memory The memory is failing. -- The VF could have some -- Return to Factory Push the OK button.
internal problems. settings.

Friction The door has a high friction. -- The mechanical part could -- Check the mechanical Push the OK button.
not be correct installed. part.
Belt The belt is broken. -- The belt could be -- Check the mechanical Push the OK button.
damaged. part.
-- The pullet could be
damaged.
Encoder The unit does not receive a -- The encoder wire could be -- Check the encoder wire. Push the OK button.
signal from the encoder. damaged. -- Check the motor.
-- The encoder could be
damaged.
Manoeuvre An obstruction has been -- The lift controller could has -- Check the lift controller. Push the OK button.
Failure performed in salve mode some problems. -- Check the signal wires. The alarm is disabled after
and the lift controller does 15 seconds.
not reopened.

VF7 7
GRAPHIC INTERFACE

Alarm Description Possible problem Actions VF7 recovery

Open Obstruction A blockage has been -- The mechanical part could -- Check the mechanical - Push the OK button.
happened in the opening not be correct installed. part. -- The alarm is disabled
movement. after 5 seconds.

Calib. The VF7 Relay can not -- The motor encoder signals -- Check the encoder wire. -- Push the OK button.
complete the Motor are not arriving correctly to
Calibration process. the VF7 Relay.

Motor Temper. The motor coil has reached -- The door could have a high -- Check the mechanical -- The alarm is disabled
125ºC . friction. part. when the motor reach
The VF7 Relay remains in -- The door could be blocked -- Check the motor. 105ºC or after 3 minutes
normal operation. during the opening/closing without measurements.
movement.
-- The motor could be
damaged.

VF7 Temper. The VF7 Relay has reached -- The door could have a high -- Check the mechanical -- The alarm is disabled
90ºC. friction. part. when the VF7 Relay
The VF7 Relay remains in -- The VF7 Relay metal cover -- Tighten the screws of the reach 70ºC.
normal operation. could not be making good metal cover.
contact.
-- Check that the VF is
installed on a metal
surface.

Motor Temp. Crit The motor coil has reached -- The door could have a high -- Check the mechanical -- The alarm is disabled
140ºC. friction. part. when the temperature of
The VF7 Relay stops the -- The door could be blocked -- Check the motor. the motor down enough
normal operation. during the opening/closing after 5 minutes.
movement.
-- The motor could be
damaged.

VF7 Temper. Crit The VF7 Relay has -- The door could have a high -- Check the mechanical -- The alarm is disabled
reached 105ºC. friction. part. when the VF7 Relay
The VF7 Relay stops the -- The VF7 Relay metal cover -- Tighten the screws of the reach 70ºC.
normal operation. could not be making good metal cover.
contact. -- Check that the VF is
installed on a metal
surface.

Referencing The VF7 Relay can not -- The learning is not done. -- Do a learning -- Push the OK button
recognize the clear opening.

Motor The unit does not receive a -- The Motor wire could be -- Check the motor wire. -- Push the OK button.
signal from the Motor. damaged. -- Check the motor. -- The alarm is disabled
-- The Motor could be after 5 seconds.
damaged.

Disconnected The unit does not receive a -- The motor is disconnected. -- The motor must to be -- Push the OK button.
motor signal from the Motor. connected.

Bypass The bypass contact -- The bypass contact could -- Check the bypass -- Push the OK button.
remained in close but the have a short-circuited. contact.
door is open.
The VF7 Relay remains in
normal operation.

Remark: If the incidence is not solved with the previous tips please, contact Fermator aftersales.

8 VF7
MONITOR MENU

The Monitor Menu displays the VF7 Relay parameters in real time.

Push the or button to select the submenu.

Push the button to return to the VF7 Relay menus.

Push the or button to see the different parameters.

Monitor Parameters

Parameter Description Units

Supply Voltage Voltage supply in AC (V). V (RMS)

VF7 Temperature Temperature in the power module area (ºC). ºC

Supply Type AC or DC supply. -

VF7 9
MONITOR MENU

Monitor Door

Parameter Description Units

Position Position of the door in m, indicating the zero point with the door closed and the clear m
opening + Clutch length with the door open.

Status Status of the door (Door closed, Door opened, Closing door, ...). -

CDL Door with Car Door Lock (automatic detection during autoadjustment). -

Friction Friction value detected during the autoadjustment. Frictionless door when this Scaled from 0 to 150
parameter is 0.

Bypass Length The distance from closed door position to open bypass contact detected during the m
learning process.

Monitor Motor

Parameter Description Units

Speed Motor speed (m/s). m/s

Voltage Tension that the circuit applies to the motor (V). V (RMS)

RMS Current Output current (A). A

Motor Type Motor connected to the circuit. -

Temperature Temperature in the PM motor (Temperature measurement option has to be ºC


enabled).

Speed limited by kinetic This is the maximum speed in closing limited by the kinetic energy. m/s
energy

Monitor Inputs

Parameter Description Units

Open Status of the open signal. -

Close Status of the close signal. -

Re-open Status of the re-open signal. -

Floor Status of the floor level signal. -

Slow Close Status of the slow close signal. -

Bypass Status of the Close Position signal. -

Curtain error Status of the curtain error. -

Monitor Outputs

Parameter Description Units

Open Door Status of the door open signal. -

Closed Door Status of the door closed signal. -

Re-open Status of the Re-open signal. -

Obstruction Status of the obstruction signal. -

Curtain Error Status of the light curtain signal. -

Temperature Error Status of the temperature signal. -

10 VF7
MONITOR MENU

Monitor Counters

Parameter Description Units

Hours Number of working hours. -

Total Cycles Number of cycles done by the door. -

Powerups Number of connections to the mains supply or blackouts suffered. -

Learning Cycles Number of learning cycles made. -

Reopenings Number of re-open cycles. Only by external signal inputs of reopening. -

Short-Circuits Number of times that the short-Circuits alarm has been activated. -

OverCurrents Number of times that the Over Currents alarm has been activated. -

Security Device Faults Number of times the light curtain has fault or blocked more than 2 minutes -

VF7 Overtemperature Number of times that the VF7 Relay overtemperature alarm has been activated. -

Motor Overtemperature Number of times that the Motor overtemperature alarm has been activated. -

VF7 Crit. Overtemp. Number of times that the VF7 Relay critical overtemperature alarm has been activated. -

Motor Crit. Overtemp. Number of times that the Motor critical overtemperature alarm has been activated. -

Op. Obstructions Number of obstructions in the opening movement. -

Cl. Obstructions Number of blockages in the closing movement. -

Manoeuvre Failures Number of times that the Manoeuvre Failures has been activated. -

Motor disconnections Number of times that the motor has been disconnected. -

Monitor Information

Parameter Description Units

Software Version Circuit software version. -

Software subversion Circuit software subversion. -

Hardware Version Circuit hardware version. -

Hardware Subversion Circuit hardware subversion. -

Serial Number Identification serial number for each unit. -

Supplier Supplier identification code. -

Test Date Date of manufacture. -

PROGRAMMING MENU

The Programming Menu displays the VF7 Relay internal parameters an options.

Push the or button to select the sub-menu.

VF7 11
PROGRAMMING MENU

Push the or button to see the different parameters of each submenu.

To modify a parameter or an option to do the following steps:

1. Select de parameter / option to be modify and push the button to enter in modify
mode.

2. The parameter value or option status will appear blinking, push the or

button to increase / decrease the parameter value or enable/disable the option.


3. Push the button to save the modification.

12 VF7
PROGRAMMING MENU

Program Options

Options basic

Door Model T1 Automatic horizontal sliding door 1 panel side opening.

T2 Automatic horizontal sliding door 2 panel side opening.

T3 Automatic horizontal sliding door 3 panel side opening.

T4 Automatic horizontal sliding door 4 panel side opening.

C2 Automatic horizontal sliding door 2 panel centre opening.

C4 Automatic horizontal sliding door 4 panel centre opening.

C6 Automatic horizontal sliding door 6 panel centre opening.

C8 Automatic horizontal sliding door 8 panel centre opening.

Control Master The unit will execute the instructions directly. Example: Curtain activation will cause the doors to
re-open immediately without control of the lift controller.

Slave There is no automatic reopen movements. The doors will only react to instruction given by the main
lift controller. Example: When the light curtain detects an obstacle instead of reopen automatically
the VF7 Relay module will send a signal to the lift controller with the Light Curtain output (42, 43,
44). Then, the main lift controller must remove the close signal and active the open signal.

Landing Door Automatic Operators with Clutch (automatic landing door). In this case a special movement is made for
locking and unlocking the Clutch.

Semiautomatic Operators without Clutch (Semiautomatic landing door).

Rotation Clockwise (CW) During the opening movement the motor will rotate clockwise.
Sense

Counterclockwise During the opening movement the motor will rotate counterclockwise.
(CCW)

Inputs 1 Input

The unit will be controlled by a single input. Any voltage between 12 V DC to 60 V DC or 100 V AC to 230 V AC applied
between terminals 8 & 10 will close the doors. Without input active the door remains opened. Open input is not used.

2 Inputs

The unit will be controlled by two independent inputs. Any voltage between 12 V DC to 60 V DC or 100 V AC to 230 V AC
applied between terminals 8 & 10 will cause the doors to close. And between terminals 10 & 12 will cause the doors to
open. In the absence of a signal, the doors will remain static. If both inputs are applied then the open signal has priority.

VF7 13
PROGRAMMING MENU

Program Options

Options interact

Priority Input Open In case that open signal and close signal are activated at the same time the door must open.

Close In case that open signal and close signal are activated at the same time the door must close.

Stop In case that open signal and close signal are activated at the same time the door must stop.

Slow Close In case that open signal and close signal are activated at the same time the door must close
in slow speed.

No Test priority If enabled, the Test manoeuvre does not have priority over the input signals.

Keyboard shortcuts If enabled, keyboard shortcuts are allowed in the home screen:

• Autoadjustment: Push the button during 2 seconds.

• Test: Push the button during 2 seconds.

• Rotates the screen display: Push the and button during 2 seconds.

• Move the door to open: Push button during 2 seconds.

• Move the door to close: Push button during 2 seconds.

HK Firefight If enabled, the first opening operation after a power up it is totally slave.

Slow close signal Action Slow close is performed when the Slow close input is activated.

Command Slow close / open is performed when the Slow close input and Close / Open input are
activated.

Unlock on standby If enabled, with the clutch / CDL fully closed, the VF7 Relay opens only the clutch / CDL if the closing signal is
removed or after a delay time (Eco Delay). Once the clutch is open, the VF7 Relay remains in standby. (This
option is not compatible with Eco Mode No).

Close Anticipated The Closed output is activated when the door is closed but doesn't need the Clutch close. This signal is
activated when the door arrives to the distance of the “Clutch Length”.

Open Anticipated The Opened output is activated when the door is in the open proximity. This signal is activated when the door
arrives to the distance of the “Open Proximity Length”.

Signal Close by Bypass When it is active, the closed signal output takes the value of the bypass input.

IMPORTANT: With this option enable is possible to have an output signal open and close enable at the same time.

Function Bypass When it is active, after a power blackout the VF7 Relay will only need to reach closed door position once
(detection of Bypass contact transition closed to open) to apply the normal speed profile.

IMPORTANT: The bypass contact must be installed before doing the door learning process. If the bypass
contact is removed or changes its position, a door learning process has to be repeated.

Curtain error only When it is active, the curtain error output will be only activated when the door is closing.
closed

DPM System If enabled, the obstruction output frame is sent to indicate when the door is in the first third of the Open Length.
If an obstruction happens, the photocell output frame will be sent.

14 VF7
PROGRAMMING MENU

Program Options

Options inputs logics

NC Open If enabled, Open signal is activated without voltage (Normally closed contact).

NC Close If enabled, Close signal is activated without voltage (Normally closed contact).

NC Slow Close If enabled, Slow close signal is activated without voltage (Normally closed contact).

NC Floor level If enabled, Floor level is activated without voltage (Normally closed contact).

NC Reopen If enabled, Reopen signal is activated without voltage (Normally closed contact).

NC Curtain Error If enabled, Light Curtain is activated without voltage (Normally closed contact).

NC Bypass If enabled, Close position is activated without voltage (Normally closed contact).

Program Options

Options functions

Eco Mode No The VF always applies the Close Maintenance Torque.

Control The VF stops applying the Close Maintenance Torque if the closing signal is removed.

Close delay The VF stops applying the Close Maintenance Torque after a programmable time delay
(Eco delay) since the door is closed.

Control delay The VF stops applying the Close Maintenance Torque if the closing signal is removed
and the programmable time delay has finished (Eco delay).

CDL Electronic
If enabled, After a power failure the VF Relay opens the Car Door Lock if the cabin is on the floor level.

Security Device None None security device installed.

Curtain Light Curtain installed. The blocked signal must be connected to Re-open input and the
failure signal must be connected to Light Curtain input.

Barrier timer If enabled, an intelligent timer is used in case of photocell or curtain permanent obstruction. The protection
is disabled after 2 minutes permanently blocked. If a physical obstruction happens during the next closing
movement, the VF reopens and wait 4 minutes before closing again. If another physical obstruction happens
during the next closing, the VF reopens and wait 10 minutes before closing again. Finally, if another physical
obstruction happens during the next closing, the VF reopens and remains always open. The photocell or
curtain is enabled again when there is not any physical obstruction during the closing movement.

Temperature If enabled, the VF7 Relay measure the motor temperature.


measurement

Temperature Drive When the overheating alarm is active the circuit does not allow the door closing.
Protection
Lift When the overheating alarm is active the lift does not allow the door closing

Energy limit The circuit limits the maximum velocity in order not to exceed a kinetic energy of 10 joules.

Obstruction Backstep If enabled and an obstruction occurs in the opening or closing movement, the VF7 Relay makes a backward
movement and wait a delay time (Backstep delay).

E.P.S. Slave If enabled, the Emergency Power Supplier will not open the door if the closing signal is activated.

E.P.S. Open Clutch If enabled, the Emergency Power Supplier will only open the car door clutch.

Static Torque If enabled, a constant torque will be applied when door is completely open or completely close. Closing
constant torque will be applied according to the Eco Mode selected option.

VF7 15
PROGRAMMING MENU

Programming Parameters (Speed Profiles)

Open profile

Close profile

Program Parameters

Parameters generals

Parameter Description Units Min Max

Door mass Mass of the door. (kg) 1 500

Clutch mass Mass of the Clutch. (Kg) 0.0 50

Gear ratio Gear ratio when a reduction pulley is used. - 1.00 10.00

Program Parameters

Parameters speeds

Parameter Description Units Min Max

Open Initial Speed The initial speed at opening. (m/s) 0.025 0.100

Close Initial Speed The initial speed at closing. (m/s) 0.025 0.100

Open Proximity Speed The approximation speed at opening. (m/s) 0.025 0.100

Close Proximity Speed The approximation speed at closing. (m/s) 0.025 0.100

Open Clutch Speed Clutch speed at opening. (m/s) 0.025 0.100

Close Clutch Speed Clutch speed at closing. (m/s) 0.025 0.100

Open Limit Speed Speed limit at opening. (m/s) 0.100 1.000

Close Limit Speed Speed limit at closing. (m/s) 0.100 0.600

Open Acceleration The opening acceleration. (m/s2) 0.050 0.700

Close Acceleration The closing acceleration. (m/s2) 0.050 0.700

Open Deceleration The opening deceleration. (m/s2) 0.050 0.700

Close Deceleration The closing deceleration. (m/s2) 0.050 0.500

Program Calibration

Motor calibration The motor calibration process has to be done to detect the electrical characteristics of the motor installed.

The calibration only has to be done once when the motor or the VF7 module are replaced.

Before doing the motor calibration place the door in a middle position.

To perform an optimal calibration of the motor installed the process has to be done without charge. Never
perform calibration with the car door and landing door.

16 VF7
PROGRAMMING MENU

Program Parameters

Parameters lengths

Parameter Description Units Min Max

Open Length Door clear opening + Clutch length. (m) 0.100 5.000

Open Initial Length The space at the initial opening movement. (m) 0.001 0.100

Close Initial Length The space at the initial closing movement. (m) 0.001 0.100

Open Proximity Length The space at the final opening movement. (m) 0.001 0.040

Close Proximity Length The space at the final closing movement. (m) 0.001 0.040

Clutch Length The required space to open / close the Clutch. (m) 0.000 0.100

Additional Clutch Additional clutch movement to personalize the opening distance in (m) 0 0.2
Movement emergency mode.

Pinion Perimeter Perimeter of the motor pinion. (m) 0.001 1.000

Backstep length Length of the backwards movement (Obstruction Backstep option). (m) 0.010 0.150

Program Parameters

Parameters torques

Parameter Description Units Min Max

Max open torque Maximum torque in the opening movement. (Value 0 is disabled the limit (N·m) 1 4.0
torque).

Max close torque Maximum torque in the closing movement. (Value 0 is disabled the limit (N·m) 0.5 3.0
torque).

Hold torque Torque applied to maintain the door stopped in any position of the clear (N·m) 0.5 1.5
opening.

Final Constant Torque Static torque applied to maintain the door stopped in open and closed (N·m) 0.010 1.100
positions.

Program Parameters

Parameters times

Parameter Description Units Min Max

Eco Delay Programmable time delay (Eco mode option). (s) 1 300

Backstep delay Programmable time delay (Obstruction Backstep option). (s) 0 5

Time standby Hold Programmable time during the hold voltage is applied. (s) 0 1.800

Program Control

Test Makes a door open or close cycle to verify proper operation.

Door Learning Makes a Door Learning process to set up the door.


Before doing a Door Learning a Motor Calibrations has to be done.
The door will do a close movement and then will do two complete movements to detect the clear opening. From
the information obtained the microprocessor will calculate the acceleration and deceleration ramps to give the
optimum control of the doors. Once the autoadjustment has been completed the parameters are stored in non
volatile EEPROM. The autoadjustment process sets all parameters to the factory value if these are not protected.

Autoadjustment process:

1. The door will close completely in slow speed until the end to detect the 0 position.
2. The door will open slowly counting the clear opening until it reach the open mechanical stop.
3. The door will close after a short delay. From the information obtained the microprocessor will calculate the
acceleration and deceleration ramps and to give the optimum control of the doors.

VF7 17
SETTINGS MENU

Program Calibration

Calibration The motor calibration process has to be done to detect the electrical characteristics of the motor installed.

The calibration only has to be done once when the motor or the VF7 Relay module are replaced.
Before doing the motor calibration place the door in a middle position.

To perform an optimal calibration of the motor installed the process has to be done without charge. Never
perform calibration with the car door and landing door.

Settings Menu

The Settings Menu is used to change the VF configuration.


Push the or button to see the different options.

To modify an option to do the following steps:

1. Select de option to be modify and push the button to enter


in modify mode.

2. The option status will appear blinking, pus the or button to enable / disable it.

3. Push the button to save the modification.

Settings Menu

Language The unit can be programmed in the following languages:


• English.
• Spanish.
• German.
• French.
• Italian.

Display Rotates the screen display (Straight / Invert).

Guide Starting guide to configure main parameters and options in VF7 Relay. The following steps have to be followed
in order to configure VF7 Relay according to the Guide:
1. Motor Calibration: it detects the electrical characteristics of the motor installed, place the door in middle
position. To perform an optimal calibration of the motor installed the process has to be done without load.
Never perform calibration with the car door and landing door.
2. Door model: select door opening according to the door where VF7 Relay has been installed (T1, T2, T3,
T4, C2, C4, C6 or C8).
3. Control: select if the VF7 Relay will operate in Master mode or Slave mode.
4. Landing: select if landing door is Automatic or Semi-automatic.
5. Rotation sense: select whether the rotation sense of the motor is Clockwise(CW) or Counter-
clockwise(CCW).
6. Inputs: select if the VF7 Relay will operate with 1 Input or 2 Inputs.
7. Door mass: adjust the mass of the door where the VF7 Relay has been installed.
8. Clutch mass: introduce mass of clutch of the door where the VF7 Relay has been installed.
9. Gear ratio: introduce the gear ratio when the motor has reduction.
10. Clutch length: introduce the length of the pulling rod.
11. Pinion perimeter: introduce the perimeter of the pinion.
12. Learning: with the load connected to the motor belt, initiate the learning process.
When making the first start-up in a VF7 Relay replacement, the menu will be automatically opened so as to
configure the parameters related to the door where the VF7 Relay will be replaced.

Factory Settings Sets all parameters to the factory value.

Password Entering the correct password the advanced menu will be unlocked.

18 VF7
INSTALLATION PROCESS

The whole installation process has to been done when a new circuit is installed on a door.
If the circuit is already installed only do steps 7 and 11.

1. Connections.
• Connect the motor wire and encoder wire (#55, #56, #57, #58, #59).
• If it has been installed, connect the Fermator photocell (#17, #18, #19, #20).
• Disconnect all other inputs and outputs.
• Connect the 230 V AC mains supply to the controller (#5, #6, #7).

2. Switch on the VF door controller button I / O in the front of the box.

3. Follow the Guide for configuration of VF7 Relay main parameters if the circuit is a replacement.

4. Program in ”2 INPUTS” and “MASTER”, this options are located in the Programming Options
menu in the VF7 Relay Graphic Interface.

5. Active the Motor Calibration, to detect the electrical characteristics of the motor installed, place
the door in a middle position.To perform an optimal calibration of the motor installed the process
has to be done without charge. Never perform calibration with the car door and landing door.

6. Program the door type, this options are located in the Programming Options menu in the VF7
Relay Graphic Interface.
• Door model (T1, T2, T3, T4, C2, C4, C6 or C8).
• Landing door type (Semiautomatic or Automatic).
• Rotation sense (Clockwise or Counterclockwise).

7. Place the door in a middle position in order to see the starting movement.

8. Active the Door Learning option to start the learning cycle.


This option is located in the Programming Options menu in the VF7 Relay Graphic Interface.
The correct steps that the door has to make are:
• The door will close completely in slow speed until the end to detect the 0 position.
• The door will open slowly counting the pulses from the encoder built into drive motor until it
reach the open mechanical stop. Will detect the final position.
• The door will close after a short delay. From the information obtained the microprocessor will
calculate the acceleration and deceleration ramps and the braking torque required to give the
optimum control of the doors.

9. Door Test.
• Active the Test option to open the door and verify the proper operation. Active again the test
option to close the door.

10. Program the VF7 Relay control behaviour, this options are located in the Programming Op-
tions menu in the VF7 Graphic Interface.
• 1 Input or 2 Inputs.
• Master or Slave.

11. Connect the cables coming from the lift controller.


• Connect the inputs cables (Pins 8 to 12).
• Connect the priority inputs cables (Pins 21 to 26).
• Connect the relays outputs cables that inform the lift controller (Pins 30 to 47).

VF7 19
POWER FAILURES

The VF7 Relay incorporates two new security systems related to power failures:

• Anti-banging system.
When a power failure occurs while the door is opening, closing or fully open, the new anti-banging system
brakes the PM motor to perform a slow closing and avoid the door hits at closing.

• Electronic Car Door Lock.


When a power failure occurs while the door is fully closed, the VF7 Relay detects the voltage drop and
opens the Car Door Lock if the cabin is on the floor level.
The Electronic Car Door Lock system could be enable or disabled by software.

Note: After the power supply has been restored and the open signal is activated, the doors will open slowly
for the first operation in order to recognize the clear opening.

In this section the modifications are listed for customer knowledge in order to comply with the new lift standard
EN 81-20/50.

LIFT STANDARD EN 81-20/50

KINETIC ENERGY.

The average closing speed has to be limited to 10 J. To limit it is necessary to know the moving mass, the
door opening and the panels number. This parameters are programmed by default except for the spare
part. In this case the parameters have to be introduced by the VF7 Relay programming menu. In order to
comply the standard is necessary to configure some options and parameters:

Menu Option Configuration to comply EN81-20/50

Door model. Select door model.

Photoc. / Curtain timer. Enable.

Eco Mode. Select modes Control, Close delay or Control delay.

Security Device. Curtain.


Programming options
Close Anticipated (recommended). Enable.

Unlock on standby. Enable.

Temperature measurement. Enable.

Energy limit. Enable.

Menu Option Configuration to comply EN81-20/50

Max. open torque. Limit only in case of a glass door. If glass door the value must to be
up to 1,2.

Programming parameters Max. close torque. Up to 1,2.

Door mass. Masses of the door and landing door. To know check Annex 1 and
Annex 2.

20 VF7
LIFT STANDARD EN 81-20/50
LIGHT CURTAIN.

• The light curtain is mandatory and it can be ENTRADAS PRIORITARIAS / PRIORITY INPUTS

connected to the lift controller or to the VF7


Relay in the pin 22. REABRIR
RE-OPEN 21 26
SEÑAL DE PISO
FLOOR LEVEL
• In case of failure or deactivation of the light OUT +12 V 23 25 CERRAR LENTO
SLOW CLOSE
curtain, the kinetic energy of the doors must BARRERA 22 24 CONTACTO DE BYPASS
be limited to 4J. To limit it the lift controller FOTOELÉCTRICA
LIGHT CURTAIN BYPASS CONTACT

has to activate the slow close input, pin 25,


of VF7 Relay.

OVERHEATING PROTECTION.

• The internal temperature of the PM motor is measured by the VF7 Relay when the option of
“Temperature measurement” inside the “Programming options” menu is enabled.

DOOR CONTACT.

• A separate monitoring signal is necessary to check that the car door(s) is/are in the closed position.
To comply this point an additional door contact is added, and the signal should be connected to the
lift controller. The maximum contact rating is 2 A 230 V AC.

REFERENCE DATA

Power supply

AC voltage range 230 V AC + 10%, -15%

Frequency supply 50 ~ 60 Hz

Standby power 0,05 A 4W

Nominal power 0,21 A 20 W

Inverter

Carrier frequency 16 KHz

Frequency range 0,5 ~ 100 Hz

Voltage range 40 ~ 200 V AC III

Maximum output current 4A

Positional control Quadrature encoder

Inputs

Synchronous permanent 10 pole


magnet

Voltage supply 106 V

Power 94 W

Nominal torque 1,5 N·m

Nominal speed 600 rpm

Thermal class F-155ºC

Inputs

Impedance 20 kΩ

Voltage 12 V DC to 60 V DC

VF7 21
REFERENCE DATA

Outputs

Contacts Switched

R. contact 50 mW

Switch time 5 ms

Output current Maximum 0,15 A

Voltage 230 V AC

Performance

Open speed 0 ~ 1.000 mm/s

Close speed 0 ~ 1.000 mm/s

ANNEX 1

COMPACT PRODUCT LINE.

# Model Opening Number of PL HL [mm] Panel type Fire homologation Moving mass [Kg]
panels [mm]

0 Compact Side 2 800 2.000 Metal sheet F.R. E120 29,46

# Concept Multiplier factor

1 Difference from T2 to C2. 0,02

2 Difference of 100 mm in PL. 0,03

3 Difference of 100 mm in HL. 0,01

4 Difference from F.R. E120 to F.R. EI60. 0,16

5 Difference from F.R. E120 to F.R. EI120. 0,20

6 Difference from F.R. E120 to F.R. EW60. 0,12

7 Difference from F.R. E120 to F.R. E30 Russia. 0,00

8 Difference from F.R. E120 to F.R. EI60 Russia. 0,16

9 Difference from F.R. E120 to F.R. EI60 Ukraine. 0,16

10 Difference from Metal sheet panels to Wien type vision panels. 0,28

11 Difference from Metal sheet panels to Flush big vision panels. 0,23

12 Difference from Metal sheet panels to Full glass in skirting panels. 0,07

13 Difference from Compact to Compact PM model. 0,01

14 Difference from Compact to Compact+ PM 150 model. 0,05

22 VF7
ANNEX 1

40/10 PRODUCT LINE.


# Model Opening Number of PL HL [mm] Panel type Fire homologation Moving mass [Kg]
panels [mm]

0 40/10 Side 2 800 2.000 Metal sheet F.R. E120 31,93


PM

# Concept Multiplier factor

1 Difference from T2 to T3. 0,08

2 Difference from T2 to C2. 0,00

3 Difference from T2 to C4. 0,26

4 Difference of 100 mm in PL. 0,07

5 Difference of 100 mm in HL. 0,03

6 Difference from F.R. E120 to F.R. EI30. 0,19

7 Difference from F.R. E120 to F.R. EI60. 0,19

8 Difference from F.R. E120 to F.R. EI120. 0,25

9 Difference from Metal sheet panels to Double skin panels. 0,32

10 Difference from Metal sheet panels to Flush big vision panels. 1,02

11 Difference from Metal sheet panels to Full glass in skirting panels. 0,95

12 Difference from Metal sheet panels to Wien type vision panels. 0,32

13 Difference from Metal sheet panels to Vision panels. 0,61

PREMIUM PRODUCT LINE.

# Model Opening Number of PL HL [mm] Panel type Fire homologation Moving mass [Kg]
panels [mm]

0 Premium Side 2 800 2.000 Metal sheet F.R. E120 36,61


PM

# Concept Multiplier factor

1 Difference from T2 to T3. 0,07

2 Difference from T2 to T1. -0,17

3 Difference from T2 to C2. -0,03

4 Difference from T2 to C4. 0,30

5 Difference from T2 to C6. 1,15

6 Difference of 100 mm in PL. 0,07

7 Difference of 100 mm in HL. 0,11

8 Difference from F.R. E120 to F.R. EI30. 0,18

9 Difference from F.R. E120 to F.R. EI60. 0,18

10 Difference from F.R. E120 to F.R. EI120. 0,24

11 Difference from Metal sheet panels to Double skin panels. 0,12

12 Difference from Metal sheet panels to Flush big vision panels. 0,60

13 Difference from Metal sheet panels to Full glass in skirting panels. 0,60

14 Difference from Metal sheet panels to Foam filled panels. -0,17

VF7 23
ANNEX 1

PLATINUM PRODUCT LINE.

# Model Opening Number of PL HL [mm] Panel type Fire homologation Moving mass [Kg]
panels [mm]

0 Platinum Side 2 800 2.000 Double skin F.R. E120 56,85


PM

# Concept Multiplier factor

1 Difference from T2 to C2. 0,06

2 Difference of 100 mm in PL. 0,08

3 Difference of 100 mm in HL. 0,07

ANNEX 2
EXAMPLE 1: INCREMENT OF PL AND HL.

Door to be calculated:

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire protection

40/10 PM Side 2 900 2.100 Metal sheet F.R. E120

Taking as basis(1):

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire Moving mass [Kg]
homologation

40/10 PM Side 2 800 2.000 Metal sheet F.R. E120 31,93

Calculations:

Difference per Difference Difference per PL Difference Difference Difference per SUM Moving mass
opening per (each 100 mm) per HL per panel fire homologation
number of (each 100 type
panels mm)

There are There are 31,93 x 0,07(2) = 31,93 x There are There are 2,23 + 0,95 31,93 + 3,18 =
equals equals 2,23 Kg 0,03(3) = equals equals = 3,18 35,11 Kg
0,95 Kg

1. These specifications are in the Annex 1.

2. This factor is the increment of 100 mm in PL. There is the number 4 of the second table of 40/10
PM in the Annex 1.

3. This factor is the increment of 100 mm in HL. There is the number 5 of the second table of 40/10
PM in the Annex 1.

24 VF7
ANNEX 2

Example 2: Difference of opening and number of panels + increment of PL and HL.

Door to be calculated:

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire protection

Premium PM Side 1 800 2.000 Double skin F.R. E120

Taking as basis(1):

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire Moving mass [Kg]
homologation

Premium PM Side 2 800 2.000 Metal Sheet F.R. E120 36,61

Calculations:

Difference per Difference Difference per PL Difference Difference Difference per SUM Moving mass
opening per (each 100 mm) per HL per panel fire homologation
number of (each 100 type
panels mm)

36,61 x (-0,17) = -6,13 Kg There are There are 36,61 x There are 4,39 – 6,13 = 36,61 – 1,74 =
equals equals 0,12 = 4,39 equals -1,74 Kg 34,87 Kg
Kg

1. These specifications are in the Annex 1.

2. This factor is the difference between T2 (side 2 panels) to T1 (side 1 panel). There is the number 2
of the second table of Premium PM in the Annex 1.

3. This factor is the difference between metal sheet panel and double skin panel. There is the number
11 of the second table of Premium PM in the Annex 1.

ANNEX 3
Reduction, Clutch length and Pinion Perimeter.

Gear Ratio
1:3.21

Clutch Length
0.052 m

Pinion Perimeter
131 mm

Premium PM with manufacture date ≤ 12/2016

VF7 25
ANNEX 3

Gear Ratio
1:2,67

Clutch Length
0,052 m

Pinion Perimeter
106 mm

Premium PM with manufacture date ≥ 01/2017

Gear Ratio
1:2,67

Clutch Length
0,052 m

Pinion Perimeter
106 mm

Premium PM with manufacture date ≥ 01/2017

Gear Ratio
1:1

Clutch Length
50/11 PM SLIM = 0,030 m
Other doors = 0,052 m

Pinion Perimeter
80 mm

26 VF7
DECLARATION CE OF CONFORMITY

Ets. Henri Peignen S.A.S.


3 Rue de la Borne Blanche
77380 Combs la Ville (France)

We hereby declare that the products described in this document conform


with the following E.U. council directive:

Norm EN 81-1/2. DIRECTIVE 2006/42/EC (Machinery directive),


DIRECTIVE 2014/30/EU (Electromagnetic compatibility),
of the European Parliament and of the Council.
VF7 Electronic Module
(15/31709299)

Combs la Ville, 07-05-18

Olivier Guillard
General Manager

VF7 27
ATTENTION: Any proposed modification not shown in this manual, should be clarified with our
Technical Department before actioning.
TECNOLAMA accepts no responsability for any damage produced in the equipment described in
this manual and associated installation if the instructions given have not been followed.
TECNOLAMA reserves the right to modify the product or specifications in this technical brochure
without prior notification.