Wide Area Monitoring System
Wide Area Monitoring System
Gopal R Gajjar
October 21, 2019
Indian Institute of Technology Bombay
1/13
Role of IIT Bombay in URTDSM
Development of analytics
• Line Parameter Estimation
• CT/CVT Calibration
Deployment
All analytics accept the control schemes for improving system security are installed in
five RLDCs and at several states SRLDCs.
2/13
Training Agenda
• Installation procedure.
• Database preperation.
3/13
Line Parameter Estimation
• State estimation software use line parameters for estimating the system states
• Distance relays use impedance information of the lines for proper zone settings
• Application of total least squares (TLS) method.
4/13
CT/CVT Calibration
• With one VT and CT as reference, PMUs can “soft calibrate” the remaining system.
5/13
Online Vulnerability Analysis of Distance Relays
6/13
Zone-3 Distance Protection
• With PMUs placed at both ends of the transmission lines, differential currents can be
computed.
• Once differential currents for all backed up lines are available, decision to block or
not block Zone-3 of the back up relay can be taken.
7/13
Field Testing of Secure Zone-3 Protection
8/13
Field Testing of Secure Zone-3 Protection
• Actual PMU data along with a simulated data to simulated fault condition were used.
9/13
Field Testing of Secure Zone-3 Protection
• Hardware setup to receive signal from analytics and forward it to protection relay for
blocking was setup.
• Modbus over Ethernet was used for communication within substation.
• Off the shelf IO that supports Modbus from Masibus was used for the purpose.
10/13
Linear State Estimation
• The control centre makes use of state estimation to take decisions on system
economy and security.
• Synchronized PMU measurements can be utilized to formulate a linear state
estimator.
• Estimation of bus voltage magnitude and angle i.e., system states from raw
measurements is defined as state estimation.
• The state estimator also includes the three important functions - network topology
processor (NTP), observability analysis and bad data detection.
• URTDSM also measures circuit breaker positions, hence topology processing is also
done through PMU data.
Bus-A
Bus-B
Disconnector
12/13
PMU Field Data
13/13
Thank You