0% found this document useful (0 votes)
43 views40 pages

Operating Instructions: Warning

This document provides operating instructions for a Vitodens 200-W series wall-mounted gas-fired condensing boiler. It includes warnings about fire and explosion risks from improper use and instructions to call the gas supplier if a gas leak is detected. The document outlines safety, installation, and warranty requirements and advises owners to have the system serviced annually.

Uploaded by

Red Squerrel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views40 pages

Operating Instructions: Warning

This document provides operating instructions for a Vitodens 200-W series wall-mounted gas-fired condensing boiler. It includes warnings about fire and explosion risks from improper use and instructions to call the gas supplier if a gas leak is detected. The document outlines safety, installation, and warranty requirements and advises owners to have the system serviced annually.

Uploaded by

Red Squerrel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Operating Instructions

Vitodens 200-W, B2HA Series and


Vitodens 222-F B2TA Series
Models 19 to 150
Wall-mounted, gas-fired condensing boiler

For operation with natural gas and liquid propane gas


Heating input 12 to 530 MBH
3.5 to 150 kW

VITODENS 200 Series


r
With Vitotronic 200 HO1B Controls

WARNING
If the information in this manual is not followed
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.

Do not store or use gasoline or other


flammable liquids in the vicinity of this
or any other appliance.
WHAT TO DO IF YOU SMELL GAS
 Do not try to light any appliances.
 Do not touch any electrical switches,
do not use any phone in your building.
 Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
 If you cannot reach your gas supplier,
call the fire department.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.

WARNING
Improper installation, adjustment, and/
or operation could cause carbon monoxide
poisoning resulting in injury or loss of life.

This product must be installed and serviced


by a professional service technician who is
experienced and qualified in hot water boiler
installation and gas combustion.

Product may not be exactly as shown

IMPORTANT
Read and save these instructions
H for future reference.
5683 712 - 01 03/2014 Please file in Service Binder
Safety Vitodens 200 Series 19 to 150 Operating
Safety, Installation and Warranty Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with
the instructions listed below and details printed in this manual can cause product/property damage, severe personal
injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information
found in manual subsections).
Product documentation Carbon monoxide
Read all applicable documentation before commencing Improper installation, adjustment, service and/or
installation. Store documentation near boiler in a maintenance can cause flue products to flow into
readily accessible location for reference in the future living space. Flue products contain poisonous carbon
by service personnel. monoxide gas.
 For a listing of applicable literature,  For information pertaining to the
please see section entitled “Important proper installation, adjustment, service
Regulatory and Safety Requirements”. and maintenance of this equipment to
avoid formation of carbon monoxide,
Warranty please see subsection entitled
Information contained in this and “Mechanical room” and “Venting
related product documentation must requirements” in the “Installation Instructions”.
be read and followed. Failure to do
so renders the warranty null and void. Fresh air
This equipment requires fresh air for
Licensed professional heating contractor safe operation and must be installed
The installation, adjustment, service and maintenance ensuring provisions for adequate
of this equipment must be performed by a licensed combustion and ventilation air exist.
professional heating contractor.
 For information pertaining to the
 Please see section entitled fresh air requirements of this product,
“Important Regulatory and Installation please see subsection entitled
Requirements”. “Mechanical room” in the “Installation
Instructions”.
Contaminated air
Air contaminated by chemicals can cause by-products Equipment venting
in the combustion process, which are poisonous to Never operate boiler without an installed venting
inhabitants and destructive to system. An improper venting system can cause
Viessmann equipment. carbon monoxide poisoning.
 For a listing of chemicals which  For information pertaining to
cannot be stored in or near the venting and chimney requirements,
boiler room, please see subsection please see section entitled “Venting
entitled “Mechanical room” in the Connection”. All products of
“Installation Instructions”. combustion must be safely vented
to the outdoors.
Advice to owner
Once the installation work is complete, the heating WARNING
contractor must familiarize the system operator/
ultimate owner with all equipment, as well as safety This boiler requires fresh air for safe operation and must
precautions/requirements, shutdown procedure, and be installed with provisions for adequate combustion
the need for professional service annually before the and ventilation air (in accordance with local codes and
heating season begins. regulations of authorities having jurisdiction).
Do not operate this boiler in areas with contaminated
WARNING combustion air. High levels of contaminants such as
dust, lint or chemicals can be found at construction
Installers must follow local regulations with respect to sites, home renovations, in garages, workshops, in dry
installation of carbon monoxide detectors. Follow the cleaning/laundry facilities, near swimming pools and in
Viessmann maintenance schedule of the boiler contained manufacturing facilities.
in this manual. Contaminated combustion air will damage the boiler
Operating and Service Documentation and may lead to substantial property damage, severe
personal injury and/or loss of life. Ensure boiler/burner
It is recommended that all product documentation such
is inspected and serviced by a qualified heating
as parts lists, operating and service instructions be handed
5683 712 - 01

contractor at least once a year in accordance with the


over to the system user for storage. Documentation is to
Service Instructions of the boiler.
be stored near boiler in a readily accessible location for
reference by service personnel.
2
Vitodens 200 Series 19 to 150 Operating Table of Contents

Page

Safety Safety, Installation and Warranty Instructions................2


About these Instructions.............................................5

For your Safety..........................................................5


Operation...............................................................5
Working on the equipment.......................................5
Maintenance and cleaning........................................5
Flue gas smell.........................................................5
Dangerous conditions..............................................5
Technical Information..............................................5
Carbon monoxide....................................................6
For safe operation...................................................6
Frozen water pipe hazard.........................................7
Replacement components, spare and wear parts.........7
Installation area conditions.......................................7

General Information Getting Started...........................................................8


Your Vitodens 200 Series Boiler...................................8
Your System is Preset at the Factory............................8
Central heating.......................................................8
Time and date.......................................................8
Power failure..........................................................8
DHW heating..........................................................8
Frost protection......................................................8
Wintertime/summertime changeover..........................8

Controls Overview of Controls.................................................9


Modular structure....................................................9
Programming unit (HO1B)........................................9

Menu......................................................................10
Programming unit.................................................10
“Help” menu........................................................10
Standard menu.....................................................10
Symbols on the display..........................................11
Extended menu....................................................11

How to Use the Controls...........................................12


Start-up/Shutdown
Starting the Heating System......................................14
Shutting Down the Heating System............................14
Heating
Required Settings (Central Heating)............................15
Selecting a Heating Circuit........................................15
Settings the Room Temperature................................16
Setting the Heating Program for Central Heating...........16
Setting the Time Program for Central Heating...............17
Changing the Heating Curve.......................................18
Stopping the Central Heating......................................18
Comfort and Energy Saving Functions.........................19
Required Settings (DHW heating)................................21
Setting the DHW Temperature....................................21
Setting the Heating Program for DHW Heating.............21
Setting the Time Program for DHW Heating.................22
5683 712 - 01

3
Table of Contents Vitodens 200 Series 19 to 150 Operating

Page

Additional Adjustments Setting the Display Contrast.....................................25


Setting the Display Brightness....................................25
Entering Names for the Heating Circuits.......................25
Setting the Language.................................................26
Changing the Time and Date......................................26
Changing the Standard Menu.....................................27
Setting the Temperature Unit °F (°C).........................27
Restoring Factory Settings.........................................27

Scanning Scanning Information.................................................28


Scanning Service Messages.......................................29
Scanning Fault Messages...........................................30

Emissions Emissions Test Mode................................................31

Troubleshooting Rooms are too Cold..................................................32


Rooms are too Hot...................................................32
There is no Hot Water...............................................33
The DHW is too Hot.................................................33
“” Flashes and “Fault” is Displayed..........................33
“ ” Flashes and “Service” is Displayed.......................34
“Controls Locked Out” is Displayed............................34
“External Hook-up” is Displayed..................................34
“External Program” is Displayed..................................34

Maintenance Inspection/Cleaning/Maintenance................................35

Additional Information Menu Overview........................................................36


Extended menu....................................................36
Scanning options in the extended menu...................37
Terminology............................................................38
Setback mode (reduced heating mode).....................38
Heating program...................................................38
Operating status...................................................38
Extension kit for heating circuit with mixing valve.....38
Mixing valve.........................................................38
Heating circuit pump.............................................38
Heating curve.......................................................38
Heating circuit......................................................38
Actual temperature...............................................39
Night setback.......................................................39
Standard heating mode..........................................39
Standard room temperature....................................39
Open flue operation...............................................39
Balanced flue operation..........................................39
Reduced heating mode..........................................39
Reduced room temperature.....................................39
Safety valve.........................................................39
Solar circuit pump.................................................39
Set temperature....................................................39
Summer mode......................................................39
Tank primary pump...............................................39
Drinking water filter...............................................39
Weather-compensated mode..................................39
DHW circulation pump...........................................39
Your contact.........................................................39
5683 712 - 01

4
Vitodens 200 Series 19 to 150 Operating Safety
About these Instructions

Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.

Warnings draw your attention to the presence of


WARNING potential hazards or important product information.

Indicates an imminently hazardous situation which,


if not avoided, could result in loss of life, serious injury
or substantial product/property damage.

Cautions draw your attention to the presence of


CAUTION potential hazards or important product information.
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or product/
property damage.

Helpful hints for installation, operation or maintenance


IMPORTANT which pertain to the product.

 This symbol indicates that additional, pertinent


information is to be found.

This symbol indicates that other instructions must


be referenced.

For your Safety

Operation
Flue gas smell
Before operating the boiler, make sure you fully
understand its method of operation. Your heating - Deactivate heating equipment.
contractor should always perform the initial start-up - Open windows and doors.
and explain the system. Any warranty is null and void - Inform your heating contractor.
if these instructions are not followed.
Dangerous conditions
Working on the equipment - Deactivate main power immediately.
All personnel working on the equipment or the heating - Close gas supply valve.
system must have the proper qualifications and hold all
necessary licenses. Technical information
Ensure main power to equipment, heating system, and Literature applicable to all aspects of the Vitodens 200
all external controls has been deactivated. Close main Series:
gas supply valve. Take precautions in all instances to - Technical Data Manual
avoid accidental activation of power during service work. - Installation Instructions
- Service Instructions
Maintenance and cleaning - Operating Instructions and User’s Information Manual
Regular inspection and service by a qualified heating Additional applicable literature:
contractor is important to the performance of the - Accessory manuals
Viessmann Vitodens 200 Series. Neglected maintenance
impacts on warranty; regular inspection ensures clean,
5683 712 - 01

environmentally friendly and efficient operation. We


recommend a maintenance contract with a qualified
heating contractor.

5
Safety Vitodens 200 Series 19 to 150 Operating
For your Safety (continued)

Carbon monoxide
The U.S. Consumer Product Safety Commission strongly
recommends the installation of carbon monoxide WARNING
detectors in buildings in which gas-burning equipment
is installed. Carbon monoxide (CO) is a colorless, As there are no user-serviceable parts on the boiler,
odorless gas, which may be produced during incomplete burner or control, the end-user must not perform
combustion of fuel and/or when the flame does not service activities or adjustments of any kind on system
receive an adequate supply of combustion air. components. Failure to heed this warning can cause
property damage, severe personal injury, or loss of life.
Carbon monoxide can cause severe personal injury or
loss of life.
Therefore, carbon monoxide detectors that are in
compliance with a nationally recognized standard (e.g. WARNING
ANSI/UL 2034-2002, CSA 6.19-01) should be installed
Improper installation, adjustment, service, or
and maintained in buildings that contain gas-burning
maintenance can cause flue products to flow into
equipment.
living space. Flue products contain poisonous carbon
monoxide gas which can cause nausea or asphyxiation
Note: Viessmann does not test any detectors and makes
resulting in severe personal injury or loss of life.
no representation regarding any brand or type of
detector.

For safe operation CAUTION


We recommend that you frequently:
- Check for debris which could obstruct the flow of Should overheating occur or the gas supply fail to
flue gases. The vent or chimney must not be blocked. shut off, do not disconnect the electrical supply to the
A blocked or partially blocked vent or chimney can pump. Instead, shut off the gas supply at a location
cause flue gases to leak into the structure. external to the appliance.
Flue gases leaking into the house can cause injury
or loss of life. Blocked or partially blocked chimneys
must have the blockage removed by a qualified
heating contractor. WARNING
- Check pressure gage for correct system (water)
The operator/ultimate owner is required to have the
pressure. Check for water on the floor from the
heating boiler, burners, and controls checked, as a
discharge pipe of the pressure relief valve or any
minimum once per year, by the original installer or
other pipe, pipe joint, valve or air vent.
by a competent heating contractor familiar with the
- Check for moisture, water, or appearance of rust
equipment. Defects must be corrected immediately.
on the flue gas pipes, their joints as well as vent
dampers, or side wall vent terminals (if so equipped).
- Ensure that nothing is obstructing the flow of
combustion and ventilation air and no chemicals, CAUTION
garbage, gasoline, combustible materials, flammable
vapors and liquids are stored (not even temporarily) Do not use this boiler if any part has been under water.
in the vicinity of the boiler. Immediately call a qualified heating contractor to
- Do not allow unsupervised children near the boiler. inspect the boiler and to replace any part of the control
system and any gas control which has been under
Service/inspection of the boiler and the system is water.
recommended once a year. Maintenance, service and
cleaning are specified in the Installation Instructions.
Before the heating season begins, it is recommended that
the boiler and burner be serviced by a qualified heating
contractor. Service contracts may be established through
gas suppliers or other licensed contractors in your area.
5683 712 - 01

6
Vitodens 200 Series 19 to 150 Operating Safety
For your Safety (continued)

Frozen water pipe hazard Installation area conditions


Your heating boiler is designed to provide a warm and
comfortable living environment. It is not designed to WARNING
ensure against freezing of water pipes.
The boiler is equipped with several safety devices that Incorrect ambient conditions can lead to damage to
are designed to shut down the boiler and to prevent it the heating system and put safe operation at risk.
from restarting in the event of various unsafe conditions.
Ensure ambient temperatures are higher than 32° F (0° C)
If your boiler remains off for an extended period of time and lower than 104° F (40° C).
during cold weather, water pipes may freeze and burst,
resulting in extensive water damage and conditions in Prevent the air from becoming contaminated by
which mold could grow. Certain molds are known to halogenated hydrocarbons (e.g. as contained in
cause respiratory problems, as well as to pose other paint solvents or cleaning fluids) and excessive dust
serious health risks. In case of water damage, immediate (e.g. through grinding or polishing work).
measures should be taken to dry out affected areas as Combustion air for the heating process, and
quickly as possible to prevent mold from developing. ventilation of the boiler room must be free of
corrosive contaminants. To that end, any boiler
If your home will be unattended for an extended period
must be installed in an area that has no chemical
of time during cold weather, you should...
exposure.
The list to the right indicates the main, currently
Shut off the water supply to the building, drain the
known sources.
water pipes and add an antifreeze for potable water
to drain traps and toilet tanks. Open faucets where Avoid continuously high levels of humidity
appropriate. (e.g. through frequent drying of laundry).
Never close existing ventilation openings.
Or..
Have someone check the building frequently during Sources of combustion and ventilation air contaminants
cold weather and call a qualified service agency if Areas likely to contain contaminants:
required. New building construction
Or... Swimming pools
Remodelling areas, hobby rooms
Install a reliable remote temperature sensor that will Garages with workshops
notify somebody of freezing conditions within the Furniture refinishing areas
home. Dry cleaning/laundry areas and establishments
Auto body shops
WARNING Refrigeration repair shops
Metal fabrication plants
Failure to protect against frozen pipes could result in Plastic manufacturing plants
burst water pipes, serious property damage and/or Photo processing plants
personal injury. Boiler may shut down. Do not leave Beauty salons
your home unattended for long periods of time during
Products containing contaminants:
freezing weather conditions without turning off the
water supply and draining water pipes or otherwise Chlorine-type bleaches, detergents and cleaning
protecting against the risk of frozen pipes. solvents found in household laundry rooms
Paint and varnish removers
Hydrochloric acid, muriatic acid
Chlorine-based swimming pool chemicals
Replacement components, spare and wear parts
Spray cans containing chlorofluorocarbons
Chlorinated waxes and cleaners
IMPORTANT Cements and glues
Refrigerant leaks
Components which are not tested with the heating
Calcium chloride used for thawing
system may damage the heating system or affect its
Sodium chloride used for water softening salt
functions. Installation or replacement may only be
Permanent wave solutions
performed by a qualified heating contractor.
Adhesives used to fasten building products and
other similar items
Antistatic fabric softeners used in clothes dryers
5683 712 - 01

7
General Information Vitodens 200 Series 19 to 150 Operating
Getting Started...

The timer of the control unit switches between “normal The timer of the control unit switches domestic hot water
room temperature” and “reduced room temperature” at production on and off at the required times.
the required times.
1. Domestic hot water heating can be set to take
1. Normal room temperature for the times you spend
place during the times you spend at home and
at home and require a comfortably warm room
require hot water for your daily DHW requirements
temperature [e.g. 68º F (20º C)].
(e.g. for showering).
Note: Times and duration of the two room
Note: Times and duration of the domestic hot
temperatures can be set on the programming
water production period can be set on the
unit of your control.
programming unit of your control. You may
The temperature settings for both the “normal
select a DHW temperature setting based on
room temperature” and “reduced room
your personal preference of up to 140º F (60º C).
temperature” can be set according to your
personal preference. The domestic hot water recirculation pump
(if installed) ensures that domestic hot water is
2. Reduced room temperature for the times you are readily available when domestic hot water is drawn.
away from home. To save energy, a lower
temperature is typically selected [e.g. 57º F (14º C)]. 2. Domestic hot water heating can be set not to take
place for the times you spend sleeping, for example.

Your System is Preset at the Factory


The control unit is factory-set to “Heating and DHW”.
Your heating system is therefore ready for use.

Central heating DHW heating


Between 6:00 and 22:00 h, the rooms are heated Between 5:30 and 22:00 h, the DHW is heated
to 68° F (20° C) “Set room temperature” (standard to 50° C “Set DHW temperature”. Any installed
heating mode). DHW circulation pump is on.
Between 22:00 and 6:00 h, the rooms are heated to Between 22:00 and 05:30 h, the DHW tank will
(3° C) “Set red. room temp” (reduced heating mode, not be reheated. Any installed DHW circulation
frost protection). pump is off.
Your heating contractor can make further settings Your heating contractor can make further settings
for you during commissioning. You can change any for you during commissioning. You can change
settings individually at any time to suit your any settings individually at any time to suit your
requirements (see chapter “Central heating”). requirements (see chapter “DHW heating”).

Time and date Frost protection


The day and time were set by your heating contractor Your boiler and DHW tank are protected against
during commissioning frost.

Power failure Wintertime/summertime changeover


All data is saved if there is a power failure. This changeover is automatic.
5683 712 - 01

8
Vitodens 200 Series 19 to 150 Operating Controls
Overview of Controls

On-Board Vitotronic 200, HO1B Control

Modular structure Programming unit (HO1B):


The control unit is integrated into the boiler. The control ■ Easy operation through:
unit comprises a standard unit, electronics modules and – Plain text display with graphic ability
a programming unit. – Large font and black & white depiction for good
contrast
Standard unit:
– Context-sensitive help text
■ ON/OFF switch
– Removable programming unit; can be mounted
■ Optolink laptop interface
on the wall with separate accessory
■ Operating and fault indicators
■ Reset button ■ With digital time switch
■ Fuses ■ Control keys for:
■ Boiler pressure gauge (psi) – Navigation
– Confirmation
– Help and additional information
– Menu
■ Setting the:
– Room temperature
– Reduced room temperature
– DHW temperature
– Heating program
– Time programs for central heating, DHW heating
and DHW circulation
– Economy mode
– Party mode
– Holiday program
– Heating curves
– Codes
– Actuator tests
– Test mode
■ Displaying the:
– Boiler water temperature
– DHW temperature
– Operating details
– Diagnostic details
– Fault messages
5683 712 - 01

9
Controls Vitodens 200 Series 19 to 150 Operating
Menu

You can change any settings on your heating system There are two control levels available, the “Standard
centrally at the programming unit of the control unit. menu” and the “Extended menu”.
If remote controls are installed in your rooms, you can
also adjust the settings at the remote controls.
Refer to the remote control
operating instructions

Standard menu

A Header (shows the heating program for displayed


heating circuit D)
B Current outside temperature
Note: The programming unit can be placed in a wall C Set room temperature
mounting base. This is available as an accessory. D Heating circuit which is selected for operation in the
Ask your heating contractor for more information. standard menu

Programming unit Note: If your heating system has 2 or 3 heating circuits:


Takes you to the previous step in the menu or You can select the heating circuit “HC1”, “HC2”
cancels a setting that has been started or “HC3” to be displayed in the standard menu
(see page 26).
Cursor keys To scroll through the menu or to set - If your heating system only has one heating circuit:
values No heating circuit name “HC...” is shown in the
OK Confirms your selection or saves the setting header.
? Calls up help texts for the selected menu option In the standard menu, you can adjust and scan the most
Calls up the extended menu frequently used settings for the heating circuit shown in
the header:
“Help” menu H Set room temperature
You can view a short guide giving an explanation of the Press the following keys:
controls and information about heating circuit selection
(see page 15). for the required value
OK to confirm
Call up the short guide as follows: H Heating program
H If the screen saver is active (see page 12): Press ?. Heating programs:
H If you are somewhere in the menu: Press until the 9 Standby mode with frost protection monitoring
standard menu is shown (see the following chapter). w Only DHW
Press ?. w Heating and DHW
5683 712 - 01

10
Vitodens 200 Series 19 to 150 Operating Controls
Menu

Standard menu (continued) Extended menu


Press the following keys:
for the required heating program
OK to confirm

Note: For any other connected heating circuits, use the


settings in the extended menu.

Call up the standard menu as follows:


H If the screen saver is active (see page 12): Press any
key except ?.
H If you are somewhere in the menu: Keep pressing
until the standard menu appears.
In the extended menu, you can adjust and scan the
Note: 2 minutes after any setting has been made, the
settings from the control unit’s range of functions used
display automatically reverts to the standard
less frequently, e.g. time programs and holiday programs.
menu.
The menu overview can be found on page 36.
Symbols on the display
Call up the extended menu as follows:
These symbols are not always displayed, but appear
H If the screen saver is active: Press any key except ?
subject to the system version and the operating state.
and then press .
Heating programs: H If you are somewhere in the menu: Press .
9 Standby mode with frost protection monitoring
w Only DHW
w Heating and DHW
s Central heating with standard temperature
m Central heating with reduced temperature
M Party mode enabled
N Economy mode enabled
In conjunction with a solar thermal system:
Solar circuit pump running
A Burner in operation

Displays
HC1 (2, 3) To display the heating circuit selected
in the standard menu. To change this,
(see page 26).
e Frost protection monitoring

Messages
Service message
Fault message
5683 712 - 01

11
Controls Vitodens 200 Series 19 to 150 Operating
How to Use the Controls

The screen saver will become active if you have not 1. Press OK. This takes you to the standard menu
adjusted any settings on the programming unit for a few (see page 11).
minutes. The display brightness is reduced. 2. Press This takes you to the extended menu (see
page 11). The selected menu option is highlighted in
white. The dialogue line E (see diagram on page 11)
then shows the necessary instructions.

The following diagram shows how to make settings with


different dialogue lines, using the set room temperature
setting as an example.

Legend
B Current outside temperature
C Set room temperature

5683 712 - 01

12
Vitodens 200 Series 19 to 150 Operating Controls
How to Use the Controls (continued)
5683 712 - 01

13
Start-up/Shutdown Vitodens 200 Series 19 to 150 Operating
Starting the Heating System

1. Check the heating system pressure at the pressure


gauge. The heating system pressure is too low if the
indicator points to the area below 1.0 bar. In this
case, top up with water or notify your local heating
contractor.
2. For open flue operation: Check that the ventilation
apertures of the installation room are open and
unrestricted.
Note: With open flue operation, the combustion air
is drawn from the installation room.

3. For Vitodens: Open the gas shut-off valve.


Note: Ask your heating contractor to explain the
positioning and handling of these components.
Legend 4. Switch ON the power supply, e.g. at a separate MCB/
A Fault indicator (red) fuse or a mains isolator.
B ON indicator (green) 5. Turn the ON/OFF switch “8“ ON. After a short time,
C Reset button (R) the standard menu is displayed (see page 10) and the
D ON/OFF switch “8“ green ON indicator illuminates. Your heating system
E Pressure gauge (psi) and, if installed, your remote controls are now ready
for operation.

Shutting Down the Heating System


With frost protection monitoring Without frost protection monitoring
For every heating circuit, select heating program “Standby 1. Switch the ON/OFF switch OFF.
mode”. 2. Close the shut-off valves.
H No central heating. 3. Isolate the heating system from its main power
H No DHW heating. supply, e.g. at a separate MCB/fuse or a mains
isolator.
H Frost protection for the boiler and the DHW tank
is enabled. 4. Where outside temperatures of below 37° F (3° C)
are anticipated, please take suitable measures to
For the heating circuit displayed in the header protect the heating system against frost. If necessary,
contact your heating contractor.
Standard menu
1. for the heating program “Standby mode” (frost Information on an extended shutdown
protection monitoring)
H Circulation pumps may seize up if they are not supplied
2. OK to confirm with power.

For the other heating circuits H After an extended shutdown, it may be necessary to
reset the date and time (see page 26).
Extended menu
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Heating program”
5. “Standby mode” (frost protection monitoring)
Note: The circulation pumps are briefly started every
24 hours to prevent them from seizing up.

Ending the heating program “Standby mode”


5683 712 - 01

Select another heating program.

14
Vitodens 200 Series 19 to 150 Operating Heating
Required Settings (Central Heating)

If you want central heating, check the following points:


H Have you selected the heating circuit?
For settings, see the page 15.
H Have you set the required room temperature?
For settings, see page 16.
H Have you set the correct heating program?
For settings, see page 16.
H Have you set the required time program?
For settings, see page 17.

Selecting a Heating Circuit

The heating of all rooms can, if necessary, be split over


several heating circuits.
H In the case of heating systems with several heating
circuits, for all central heating settings, first select the
heating circuit where you want to make a change.
H This selection is not possible in heating systems with
only one heating circuit.

Example:
H “Heating circuit 1” is the heating circuit for the rooms
occupied by you.
H “Heating circuit 2” is the heating circuit for the rooms
of a separate apartment.

The heating circuits are marked at the factory as “Heating


circuit 1” (HC1), “Heating circuit 2” (HC2) and “Heating
circuit 3” (HC3).

If you or your heating contractor have renamed the


heating circuits (e.g. as “Apartment”, etc.), the name is
displayed instead of “Heating circuit ...” (see page 25).

Extended menu
1.
2. “Heating”
3. for the required heating circuit

Note: If you return to the standard menu with , the


header will again display “HC1” (see page 10).
For changes to the heating circuit display in the
5683 712 - 01

standard menu, see page 27.

15
Heating Vitodens 200 Series 19 to 150 Operating
Setting the Room Temperature
Setting the room temperature for standard heating mode
Factory setting: 68° F (20° C).

For the heating circuit displayed in the header


Proceed as described on page 10.

For the other heating circuits


Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Set room temperature”
5. Set the required value

Setting the room temperature for reduced heating mode


(night setback)
Factory setting: 37° F (3° C).
Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Set reduced room temp”
5. Set the required value

The rooms are heated to this temperature:


H Between the time phases for standard heating mode
(see page 17).
H In the holiday program (see page 20).

Setting the Heating Program for Central Heating


Factory setting: “Heating and DHW”
For the heating circuit displayed in the header
Proceed as described on page 10.

For the other heating circuits


Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Heating program”
5. “Heating and DHW”
H The rooms of the selected heating circuit are heated
in accordance with the room temperature and time
program settings.
H DHW is reheated in accordance with the set DHW
temperature and time program (see chapter “DHW
heating”).
5683 712 - 01

16
Vitodens 200 Series 19 to 150 Operating Heating
Setting the Time Program for Central Heating

H The time program for central heating is made up of time


phases. One time phase from 6:00 to 22:00 h for every
day of the week is set at the factory.
H You can set the time program individually, to be the
same for every day of the week or different: You can
select up to 4 time phases per day for standard heating
mode. Set the start and end points for each time phase.
Between these time phases, the rooms are heated with
the reduced room temperature (see chapter “Setting the
room temperature for reduced heating mode”).
H When setting, bear in mind that your heating system
requires some time to heat the rooms to the required
temperature.
H In the extended menu, you can scan the current time
program under “Information” (see chapter “Scanning
information”, “Heating circuit ...” group).

Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary.
4. “Heating time program”
5. Select part of the week or a day.
6. Select the time phase !, ?, § or $.
7. Set the start and end points for the relevant time
phase.
8. Press to exit the menu.

Note: If you want to terminate a time phase setting


process prematurely, keep pressing until the
required display appears.

Example shown:
- Time program for Monday to Friday (“Mo-Fr”)
- Time phase !: From 05:00 to 08:30 h
- Time phase ?: From 16:30 to 23:00 h

Example:
You want to set the same time program for every day
except Monday:

Select the period “Monday–Sunday” and set the time


program.
Then select “Monday” and set the time program for this.

Deleting a time phase


Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase
5683 712 - 01

17
Heating Vitodens 200 Series 19 to 150 Operating
Changing the Heating Curve

Your system’s heating characteristics are affected by the


slope and the level of the selected heating curve. Further
information about the heating curve can be found under
“Terminology” on page 38.
Factory setting:
H Slope: 1.4
H Heating curve level: 0
H Standard room temperature (set value): 68° F (20 ºC)
H Reduced room temperature (set value): 37° F (3 ºC)

Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Heating curve”
5. “Slope” or “Level”
Note: Tips on when and how to change the heating
curve slope and level are displayed by pressing ?.
6. Set the required value
Example:
Change the heating curve slope to 1.5.
A graph clearly shows the change in the heating curve
as soon as you alter the value for the slope or level.
Depending on various outside temperatures (shown on
the horizontal axis), the assigned set flow temperatures
for the heating circuit are highlighted white.

Stopping the Central Heating


For the heating circuit displayed in the header
Standard menu:
1. for the heating program
“Only DHW” (summer mode, no central heating)
or
“Standby mode” (frost protection monitoring)
2. OK to confirm

For the other heating circuits


Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 38)
4. “Heating program”
5. “Only DHW” (summer mode, no central heating)
or
5683 712 - 01

“Standby mode” (frost protection monitoring)

18
Vitodens 200 Series 19 to 150 Operating Heating
Comfort and Energy Saving Functions

Selecting the comfort function “Party mode”


With this function, you can change the room temperature
for several hours, e.g. if guests unexpectedly stay longer
in the evening. You do not have to change any existing
control settings. The DHW is reheated in this function to
the selected set temperature.

Extended menu
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Party mode”
5. Set the required room temperature during party mode

Display in the standard menu


H The rooms are heated to the required temperature.
H DHW is reheated to the selected set temperature.

Ending the comfort function


H Automatically after 8 hours.
or
H Automatically when the system switches to standard
heating mode in accordance with the time program.
or
H In the extended menu, set “Party mode” to “OFF”.

Selecting the energy saving function “Economy mode”


To save energy, you can reduce the room temperature
in standard heating mode. For example, if you leave the
house for a few hours.
Extended menu
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Economy mode”
5683 712 - 01

19
Heating Vitodens 200 Series 19 to 150 Operating
Comfort and Energy Saving Functions (continued)

Display in the standard menu


Note: The display of the selected set room temperature
does not change.

Ending economy mode


H Automatically when the system switches to reduced
heating mode in accordance with the time program.
H In the extended menu, set “Economy mode” to “OFF”.

Selecting the energy saving function “Holiday program”


To save energy, for example over long holidays, you can
activate the “Holiday program”.

The control unit is set so that the holiday program applies


to all heating circuits. If you want to make changes,
contact your local heating contractor.

Depending on the heating program selected, the holiday


program can have various effects:
H Heating program “Heating and DHW”: The rooms are
heated to the selected reduced room temperature (see
page 16). DHW heating is switched OFF.
H Heating program “Only DHW”: For all heating circuits,
frost protection monitoring is only enabled for the boiler
and the DHW tank.
H The holiday program starts at 00:00 h the day following
your departure and ends at 00:00 h on the day of your
return. This means the selected time program is active
on the days of departure and return (see page 17).

Extended menu:
1.
2. “Heating”
3. “Holiday program”
4. Set the required departure and return dates
5.
Terminating or deleting a holiday program
Extended menu:
1.
2. “Heating”
3. “Holiday program”
4. “Delete program”
5683 712 - 01

20
Vitodens 200 Series 19 to 150 Operating Heating
Required Settings (DHW Heating)

If you want DHW heating, check the following points:


H Have you set the required DHW temperature?
For settings, see page 21.
H Have you set the correct heating program?
For settings, see page 21.
H Have you set the required time program?
For settings, see page 22.

Setting the DHW Temperature


Extended menu:
1.
2. “DHW”
3. “Set DHW temperature”
4. Set the required value

Setting the Heating Program for DHW Heating


Note: The control unit is set so that DHW heating applies
to all heating circuits. If you want to make changes,
contact your local heating contractor.

Extended menu:
1.
2. “Heating”
3. Select the heating circuit if necessary (see page 15)
4. “Heating program”
5683 712 - 01

5. “Heating and DHW” (with central heating)


or
“Only DHW” (summer mode, no central heating)

21
Heating Vitodens 200 Series 19 to 150 Operating
Setting the Time Program for DHW Heating

H The time program for DHW heating is made up of time


phases. One time phase from 5:30 to 22:00 h for every
day of the week is set at the factory.
H Automatic mode is set at the factory for DHW heating.
This means that, in standard heating mode, the DHW
is reheated to the set temperature. To ensure that hot
water is available at the start of standard heating mode,
the time phase for DHW heating begins automatically
half an hour earlier than the time phase for standard
heating mode.
H If you don’t want the automatic mode, you can select
up to 4 individual time phases per day for DHW heating,
which can be the same for every day of the week or
different. Set the start and end points for each time
phase.
H When setting, bear in mind that your heating system
requires some time to heat the DHW to the required
temperature.
H In the “Extended menu”, you can scan the current time
program under “Information” (see chapter “Scanning
information”, “DHW” group).

Extended menu:
1.
2. “DHW”
3. “DHW time prog”
4. “Individual”
5. Select part of the week or a day.
6. Select the time phase !, ?, § or $.
7. Set the start and end points for the relevant time
phase.
8. Press to exit the menu.

Note: If you want to terminate a time phase setting


process prematurely, keep pressing until the
required display appears.

Example shown:
H Time program for Monday to Friday (“Mo-Fr”)
H Time phase !: From 04:30 to 06:30 h
H Time phase ?: From 15:30 to 20:30 h

Example:
You want to set the same time program for every day
except Monday: Select the period “Monday–Sunday” and
set the time program. Then select “Monday” and set the
time program for this.
5683 712 - 01

22
Vitodens 200 Series 19 to 150 Operating Heating
Setting the Time Program for DHW Heating (continued)

Deleting a time phase


Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase “- - : - -”.

DHW heating once, no longer in the time program


Note: The heating program “Heating and DHW” or “Only
DHW” must be set for at least one system heating
circuit.

Extended menu:
1.
2. “Heating”
3. “Party mode”
4. Disable “Party mode” again with “OFF” to prevent
unintentional central heating with standard room
temperature.

Heating system with DHW circulation pump


Further information about the DHW circulation pump
can be found under “Terminology” on page 38.

H Automatic mode is set for the DHW circulation pump


time program. In other words, the DHW circulation
pump operates in parallel to the DHW heating time
program.
H If you don’t want the automatic mode, you can select
up to 4 individual time phases per day for the DHW
circulation pump, which can be the same for every day
of the week or different. Set the start and end points
for each time phase.
H In the “Information” menu, you can scan the current
time program (see chapter “Scanning information”,
“DHW” group).

Note: Activating the DHW circulation pump is only


advisable for those times when DHW is actually
drawn.

Extended menu:
1.
2. “DHW”
3. “DHW circ time prog”
4. “Individual”
5. Select part of the week or a day
6. Select the time phase !, ?, § or $.
7. Set the start and end points for the relevant time
phase

Note: If you want to terminate the setting process


prematurely, keep pressing until the required
display appears.
5683 712 - 01

23
Heating Vitodens 200 Series 19 to 150 Operating
Setting the Time Program for DHW Heating (continued)

Deleting a time phase for DHW circulation pump


Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase “- - : - -”.

Stopping DHW heating


You do not want to have DHW or heat the rooms.
For the heating circuit displayed in the header

Standard menu:
1. for the heating program “Standby mode”
(frost protection monitoring)
2. OK to confirm

For the other heating circuits


Extended menu:
1.
2. Select the heating circuit if necessary (see page 15)
3. “Heating”
4. “Heating program”
5. “Standby mode” (frost protection monitoring)

You do not want DHW, but do want to heat the rooms.


Extended menu:
1.
2. Select the heating circuit if necessary (see page 25)
3. “Heating”
4. “Heating program”
5. “Heating and DHW”
6. until the menu is displayed
7. “DHW”
8. “Set DHW temperature”
9. Select 50° F (10° C)

5683 712 - 01

24
Vitodens 200 Series 19 to 150 Operating Additional Adjustments
Setting the Display Contrast

Extended menu:
1.
2. “Settings”
3. “Contrast”
4. Set the required contrast.

Setting the Display Brightness


If you would like the texts in the menu to be more clearly
legible, change the brightness for “Control”.
You can also alter the screen saver brightness.

Extended menu:
1.
2. “Settings”
3. “Brightness”
4. “Control” or “Screen saver”
5. Set the required brightness.

Entering Names for the Heating Circuits


You can give heating circuits 1, 2 and 3 (“HC1”, “HC2”
and “HC3”) individual names. The abbreviations “HC1”,
“HC2” and “HC3” will be retained.

Extended menu:
1.
2. “Settings”
3. “Name for heating circ.”
4. “Heating circuit 1”, “Heating circuit 2” or “Heating
circuit 3”
5. “Change?”
6. You can select the required symbol with .
7. takes you to the next character.
8. Press OK to accept all entered characters at once
and simultaneously exit this menu.
5683 712 - 01

25
Additional Adjustments Vitodens 200 Series 19 to 150 Operating
Entering Names for the Heating Circuits (continued)

Note: The entered term is deleted with “Reset?”;


“Heating circuit 1” will then be shown again.

Example:
Name for “Heating circuit 2”: Apartment

The menu shows “Apartment” for “Heating circuit 2”

Setting the Language


At the commissioning stage, the display is in German.

1. “Sprache” (Language) Deutsch DE (German)


2. Select the required language with
3. Accept by pressing OK.

To change the language


Extended menu:
1.
2. “Settings”
3. “Language”
4. Select the required language with
5. Accept by pressing OK.

Setting the Time and Date


The time and date are factory-set. If your heating system
has been shut down for a long time, it may be necessary
to set the time and date.

Extended menu:
1.
2. “Settings”
5683 712 - 01

3. “Time/Date”
4. Set the time and date.

26
Vitodens 200 Series 19 to 150 Operating Additional Adjustments
Changing the Standard Menu

You want to have details about heating circuit 2 (HC2)


or heating circuit 3 (HC3) displayed in the header of the
standard menu (see page 10).

Extended menu:
1.
2. “Settings”
3. “Standard menu”
4. Select the heating circuit

Setting the Temperature Unit °F (°C)


Factory setting: °C
Extended menu:
1.
2. “Settings”
3. “Temperature unit”
4. Select the temperature unit “°C” or “°F”.

Restoring Factory Settings


You can reset the factory settings of all modified values
for each heating circuit separately.

Extended menu:
1.
2. “Settings”
3. “Standard setting”
4. “Heating circuit 1”, “Heating circuit 2” or
“Heating circuit 3”

The following settings and values are reset:


H Set room temperature for standard heating mode
(“Set room temperature”).
H Set room temperature for reduced heating mode
(“Set red. room temp”).
H Heating program (“Heating program”).
H Set DHW temperature (“Set DHW temperature”).
H Time program for central heating
(“Heating time program”).
H Time program for DHW heating (“DHW time prog”).
H Time program for DHW circulation pump
(“DHW circ time prog”).
H Heating curve slope (“Slope”) and level (“Level”).

Party mode, economy mode and holiday program are


deleted.
5683 712 - 01

27
Scanning Vitodens 200 Series 19 to 150 Operating
Scanning Information

Subject to the connected components and settings


made, you can scan current temperatures and operating
conditions.

The extended menu splits the information into groups:


H “General”
H “Heating circuit 1”
H “Heating circuit 2”
H “Heating circuit 3”
H “DHW”
H “Solar”
H “Reset data”

Note: If heating circuits have been given names, the name


is displayed (see chapter “Entering names for the
heating circuits”). For detailed scanning options
for the individual groups, see chapter “Scanning
options in the extended menu”.

Extended menu:
1.
2. “Information”
3. Select the category.
4. Select the required scan.

Scanning in conjunction with solar thermal systems


Extended menu:
1.
2. “Solar energy”

The solar energy yield for the past 7 days is displayed


on a graph.
The flashing line on the graph indicates that the current
day is not yet over.

Note: Further scanning options, e.g. for the solar circuit


pump hours run, can be found in the extended
menu under “Information” in the “Solar” group.

Resetting data
You can reset the following data:
H Burner hours run.
H Fuel consumption, if set by your heating contractor.
H In conjunction with a solar thermal system:
Solar energy yield, solar circuit pump hours run and
hours run output 22.
H All the above data simultaneously.

Extended menu:
1.
2. “Information”
5683 712 - 01

3. “Reset data”

28
Vitodens 200 Series 19 to 150 Operating Scanning
Scanning Service Messages

If your heating system is due for a service, the symbol


flashes in the display, and “Service” appears.

1. You can call up the reason for the service with OK.
2. Pressing ? calls up information on the service that
is due.
3. If you want to acknowledge the service message,
follow the instructions in the menu. Contact your
local heating contractor. The service message is
transferred to the menu.

Display in the standard menu

Display in the extended menu


Note: If the service can only be carried out at a later date,
the service message is displayed again the following
Monday.

Calling up an acknowledged service message


Extended menu:
1.
2. “Service”
5683 712 - 01

29
Scanning Vitodens 200 Series 19 to 150 Operating
Scanning Fault Messages

If any faults have occurred in your heating system, the


symbol flashes in the display, and “Fault” appears. The
red fault indicator also flashes (see chapter “Starting the
heating system”).

1. You can call up the cause of the fault with OK.


2. Pressing ? calls up information on the heating system
performance. Tips on which measures you can take
yourself before notifying your heating contractor are
also displayed.
3. Make a note of the cause of the fault and the
fault code next to it on the right. In this example:
“Outside temp sensor 18” and “Fault A2”.
This enables the heating contractor to be better
prepared for the service call and may save additional
travelling costs.
4. If you want to acknowledge the fault
message, follow the instructions in the menu.
The fault message is transferred to the menu.

Display in the standard menu


Note: - If you have connected up signalling equipment
(e.g. a buzzer) for fault messages, this is
deactivated when the fault message is
acknowledged.
- If the fault can only be rectified at a later date,
the fault message will be displayed again the next
day and the signalling equipment will be switched
on again.

Display in the extended menu

Calling up an acknowledged fault message


Extended menu:
5683 712 - 01

1.
2. “Fault”

30
Vitodens 200 Series 19 to 150 Operating Emissions
Emissions Test Mode

Emissions test mode should only be activated by your


flue gas inspector during the annual inspection.

Extended menu:
1.
2. “Test mode”
3. “Flue gas test ON”

If the burner is on, the symbol is shown.

Note: You can also enable emissions test mode if the


controls are locked out by your heating contractor.

Ending emissions test mode


H Automatically after 30 min.
H Press OK.
5683 712 - 01

31
Troubleshooting Vitodens 200 Series 19 to 150 Operating
Rooms are too Cold

Cause Remedy
The heating system is off. - Switch the ON/OFF switch ON (see diagrams page 9).
- Switch ON the mains isolator, if installed (outside the
boiler room).
- Reset the fuse/MCB in the power distribution board
(main domestic fuse/ MCB).
Control unit or remote control incorrectly adjusted. Check settings and correct if required:
- “Heating and DHW” must be selected (see page 16).
- Room temperature (see page 16).
- Time (see page 26).
- Time program (see page 17).
Only when operating with DHW heating: Wait until the DHW tank has been heated up.
DHW priority is enabled. In the case of operation with an instantaneous water
heater, stop DHW draw-off.
No fuel. With liquid propane gas:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with
your gas supply utility.
“Combustion controller” is shown on the display. Press R (reset button) see page 14.
Acknowledge the fault (see page 30).
Notify your heating contractor if this fault recurs.
The fault message is displayed until the cause is rectified.
“Fault” is displayed, and the red fault indicator flashes. Scan and acknowledge the type of fault (see page 30).
If necessary, notify your heating contractor.
Mixing valves motor faulty. Adjust the mixing valves manually.

Rooms are too Hot

Cause Remedy
Control unit or remote control is incorrectly adjusted. Check settings and correct if required:
- Room temperature (see page 16).
- Time (see page 26).
- Time program (see page 17).
“Fault” is displayed, and the red fault indicator flashes. Scan and acknowledge the type of fault (see page 30).
If necessary, notify your heating contractor.
Mixing valves motor faulty. Adjust the mixing valves manually.
5683 712 - 01

32
Vitodens 200 Series 19 to 150 Operating Troubleshooting
There is no Hot Water

Cause Remedy
The heating system is off. - Switch the ON/OFF switch ON (see diagrams page 14).
- Switch ON the mains isolator, if installed (outside the
boiler room).
- Reset the fuse/MCB in the power distribution board
(main domestic fuse/ MCB).
Control unit or remote control incorrectly adjusted. Check settings and correct if required:
- DHW heating must be enabled (see page 21).
- DHW temperature (see page 21).
- Time program (see page 17).
- Time (see page 26).
No fuel. With liquid propane gas:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with
your gas supply utility.
“Fault” is displayed, and the red fault indicator flashes. Scan and acknowledge the type of fault (see page 30).
If necessary, notify your heating contractor.

The DHW is too Hot

Cause Remedy
The control unit is incorrectly adjusted. Check and correct the DHW temperature if required
(see page 21).

“” Flashes and “Fault” is Displayed


Cause Remedy
Heating system fault. Proceed as described (see page 30).
5683 712 - 01

33
Troubleshooting Vitodens 200 Series 19 to 150 Operating
“ ” Flashes and “Service” is Displayed

Cause Remedy
The time for a service, as specified by your heating Proceed as described on page 29.
contractor, has arrived.

“Controls Locked Out” is Displayed

Cause Remedy
This function is blocked. Your heating contractor can lift this block.

“External Hook-up” is Displayed


Cause Remedy
The heating program set at the control unit was changed No remedy is required.
by an external device, e.g. extension EA1.

”External Program” is Displayed


Cause Remedy
The heating program set at the control unit was changed You can change the heating program.
by the Vitocom communication interface

5683 712 - 01

34
Vitodens 200 Series 19 to 150 Operating Maintenance
Inspection/Cleaning/Maintenance

Cleaning Safety valve (DHW tank)


You can clean the surface of the programming unit with The safety valve function should be checked every six
a microfiber cloth. All equipment can be cleaned with months by venting, either by the system user or the
a commercially available domestic cleaning agent (non- local heating contractor. The valve seat may become
scouring). contaminated (see the valve manufacturer’s instructions).

Inspection and maintenance Potable water filter (if installed)


Inspection and maintenance of your heating system is To maintain high hygienic standards, proceed as follows:
recommended. H Replace filter element on non-back flushing filters every
Regular maintenance ensures trouble free, energy six months (visual inspection every two months).
efficient, environmentally responsible and safe heating.
H On back flushing filters, back flush every two months.
Your heating system must be serviced by an authorised
contractor at least every 2 years. For this, we advise
you to arrange an inspection and maintenance contract
with your local heating contractor.

Boiler
Increasing boiler contamination raises the flue gas
temperature and thereby increases energy losses.
For that reason, all boilers should be cleaned annually.

DHW tank
Maintenance and cleaning should be carried out no later
than two years after commissioning and thereafter as
required.
Only a qualified heating contractor should clean the
inside of a DHW tank and the DHW connections.
Refill any water treatment equipment (e.g. water softener
or water filtration unit) on time, if such equipment is
installed in the cold water supply of the DHW tank.
Observe the manufacturer’s instructions.
5683 712 - 01

35
Additional Information Vitodens 200 Series 19 to 150 Operating
Menu Overview

Extended menu

Heating

DHW

Solar energy

Test mode

Information

Set DHW temperature


Settings
DHW time prog
DHW circ time prog

General Party mode


Detailed scan
Heating circuit 1 HC1 Economy mode
options
Heating circuit 2 HC2 see following Set room temperature
Heating circuit 3 HC3 page. Set red. room temp
DHW Heating program
Solar Heating time program
Reset data Holiday program
Heating curve

Time / Date
Language DE
Contrast
Brightness
Temperature unit Heating and DHW
Name for heating circ. Only DHW
Standard menu Standby mode
Standard setting
5683 712 - 01

36
Vitodens 200 Series 19 to 150 Operating Additional Information
Menu Overview (continued)

Scanning options in the extended menu Heating circuit 2, 3 (HC2, HC3)


“Heating program”
Note: Subject to the actual heating system equipment
level, not all of the scans listed here may be “Operating status:”
available. You can view more details on the “Time program”
information marked with .
“Set room temperature”
General “Room temperature”
“Outside temp” “Set reduced room temp”
“Boiler temperature” “Set ext. room temp”
“Common flow temp” (common flow temperature) “Set party temp”
“Burner” “Slope”
“Hours run” “Level”
“Burner stage 1” “Heating circ pump”
“Hours run” “Mixing valves”
“Burner stage 2” “Flow temperature”
“Hours run” “Return temp”
“Fuel consumption” “Holiday program”
“Feed pump”
“Central fault mess.”
DHW
“Participant no.”
“DHW time prog”
“Input ext. EA1”
“DHW circ time prog”
“Time”
“DHW temperature”
“Date”
“DHW tank prim pump”
“Radio clock signal”
“DHW circ pump”
“Flow switch”

Heating circuit 1 (HC1)


“Heating program”
Solar
“Operating status:”
“Collector temp”
“Time program”
“Solar DHW”
“Set room temperature” “Solar circuit pump”
“Room temperature” “Solar energy history”
“Set reduced room temp”
“Solar energy”
“Set ext. room temp”
“Solar circuit pump”
“Set party temp”
“Solar circ pump speed”
“Slope”
“Heating suppr. DHW”
“Level”
“SM1 output 22”
“Heating circ pump”
“SM1 output 22”
“Holiday program”
“Sensor 7”
“Sensor 10”
“Heat suppr. heating”
5683 712 - 01

37
Additional Information Vitodens 200 Series 19 to 150 Operating
Terminology

Setback mode (reduced heating mode) Heating curve


See “Reduced heating mode”. Heating curves illustrate the relationship between the
outside temperature, room temperature (set value) and
Heating program boiler water or (heating circuit) flow temperature.
The lower the outside temperature, the higher the
With the heating program you determine whether you
boiler water or (heating circuit) flow temperature.
heat your rooms and DHW, or only heat DHW or whether
In order to guarantee sufficient heat and minimum fuel
you shut down your heating system with frost protection
consumption at any outside temperature, the conditions
monitoring.
of your building and your heating system must be taken
into consideration. The heating curve is set by your
You can select the following heating programs:
heating contractor for this purpose.
H “Heating and DHW”
The rooms are heated and DHW is provided (winter Note: If your heating system includes heating circuits
mode). with mixing valves, then the flow temperature for the
H “Only DHW” heating circuit without mixing valves is higher by a
DHW is provided but there is no central heating selected differential than the flow temperature for the
(summer mode). heating circuits with mixing valves.
H “Standby mode”
Frost protection for the boiler and the DHW tank is The illustrated heating curves apply with the following
enabled, no central heating, no DHW heating. settings:
H Heating curve level = 0
Note: No heating program is available for central heating
H Standard room temperature (set value) = 68° F (20 ºC)
without DHW heating. When you want central
heating, hot water is generally also required (winter
mode). If you do want just central heating, select
the heating program “Heating and DHW” and set
Boiler water or supply

the DHW temperature to 50° F (10° C) (see page


18). This means that you will not heat DHW
unnecessarily but the DHW tank is protected
temperature

against frost.

Operating status
In the heating program “Heating and DHW”, the operating
status changes from “Standard heating mode” (see page
39) to the operating status “Reduced heating mode”
(see page 39) and vice versa. The times for the operating Room
set-point Outdoor temperature
status change are defined when the time program is set. temperature

Extension kit for heating circuit with mixing valve


Example:
Assembly (accessory) for controlling a heating circuit
with mixing valves. See “Mixing valves”. For outside temperature 7° F (-14° C):

Mixing Valve A Underfloor heating system, slope 0.2 to 0.8


A mixing valve mixes the water heated in the boiler B Low temperature heating system, slope 0.8 to 1.6
with the cooled water returning from the heating circuit. C Heating system with a boiler water temperature in
The water, heated to the right temperature in line with excess of 167° F (75° C), slope 1.6 to 2.0
demand, is delivered to the heating circuit by the heating
Heating circuit
circuit pump. The control unit adjusts the heating circuit
flow temperature via the mixing valve to the various A heating circuit is a sealed circuit between the boiler
conditions, e.g. different outside temperature. and radiators, in which the heating water circulates.
A heating system may comprise several heating circuits.
Heating circuit pump For example, one heating circuit for the rooms occupied
by you and one heating circuit for the rooms of a separate
Circulation pump for the circulation of the heating water
apartment.
in the heating circuit.
5683 712 - 01

38
Vitodens 200 Series 19 to 150 Operating Additional Information
Terminology (continued)

Reduced room temperature


When you are out or during the night, set the reduced
room temperature (see page 16). See also “Reduced
heating mode”.

Safety valve
A safety device that must be installed by your heating
contractor in the cold water pipe. The safety valve opens
automatically to prevent excess pressure in the DHW
tank.

Solar circuit pump


In conjunction with solar thermal systems. The solar
circuit pump delivers the cooled heat transfer medium
Factory settings: Slope = 1.4 and level = 0. from the DHW tank indirect coil to the collectors.

A Changing the slope: The steepness of the heating Set temperature


curve changes Default temperature that should be reached;
B Changing the level: The heating curves are shifted e.g. set DHW temperature.
in parallel in a vertical direction
Summer mode
Actual temperature Heating program “Only DHW”.
Current temperature at the time of the scan; e.g. actual At warmer times of the year, i.e. when rooms do not
DHW temperature. have to be heated, you can disable heating mode.
The boiler remains enabled for DHW heating.
Night setback
See “Reduced heating mode”. Tank primary pump
Circulation pump for heating the DHW in the DHW tank.
Standard heating mode
When you are in the house during the day, you can heat Drinking water filter
the rooms in standard heating mode. Set the periods
A device that removes solids from the water. The drinking
using the time program for central heating. During these
water filter is installed in the cold water pipe upstream of
periods, the rooms are heated to the standard room
the DHW tank or the instantaneous water heater.
temperature.
Weather-compensated mode
Standard room temperature
In weather-compensated mode, the heating flow
When you are in the house during the day, set the temperature is controlled according to the outside
standard room temperature (see page 16). temperature. This means that no unnecessary heat is
generated in order to heat the rooms to the set room
Open flue operation temperature you selected.
The combustion air is drawn from the room where the The outside temperature is captured and transmitted to
boiler is installed. the control unit by a sensor fitted outside the building.

Balanced flue operation DHW circulation pump


The combustion air is drawn from outside the building. The DHW circulation pump transports the hot water
around a circuit between the DHW tank and the draw-
Reduced heating mode off points (e.g. hot tap). This makes hot water available
When you are out or during the night, you can heat the quickly at the draw-off point.
rooms in reduced heating mode (setback mode). Set the
periods using the time program for central heating. During
these periods, the rooms are heated to a reduced room Your contact
temperature. Contact your local contractor if you have any questions
regarding the maintenance and repair of your system.
You may, for example, find local contractors on the
internet under www.viessmann.com.
5683 712 - 01

39
Vitodens 200 Series 19 to 150 Operating

5683 712 - 01 Technical information subject to change without notice. Printed on environmentally friendly
(recycled and recyclable) paper.

You might also like