Trouble Shooting Sheet
Trouble Shooting Sheet
Check that the lines of Excitation equipment Excitation equipment materiel are damaged.
are loosely connected or opened.
*. The cause and trouble shooting for each fault of the machine including excitation equipment.
Several different causes can produce same abnormal result during setting of excitation equipment
So, it is recommended that the trouble shooting should be started to check one by one from
The most possible cause.
page : 6/1
Procedure for the trouble shooting of 'Lower output Voltage' of the generator.
Check that the lines of Excitation equipment are Excitation equipment materiel are damaged.
loosely connected or opened.
page : 6/2
Procedure for the trouble shootiing of 'Hunting output Voltage' of the generator.
Check that the lines of Excitation equipment Check whether the engine speed of prime
are loosely connected or opened. mover has the hunting or not.
Check that the Series resistor (R48) terminals A.V.R is damaged : change it to normal operating
are loosely connected. A,V,R.
Check the connecting status on the taps with Check whether there would be any coloring point by
secondary winding of Current transformers excessive heating with all the transformers
(T1,T2,T3). (T1,T2,T3, L1, T6, T4).
Check the boltings on the Auxiliary terminals in Power thyrister are internally discontinuity.
the terminal box.
page : 6/3
Procedure for the trouble shootiing of Different P.F' of the generator.
Check that the lines of Excitation equipment are High variation of active power due to instability
loosely connected or opened. of Engine speed.
Different no load voltage setting by Incorrect active load(KW) sharing due to different
Reference setter(90R). speed variation ratio of each Engine.
Voltage droop values by Droop potentiometer A.V.R is damaged : change it to normal operating
("S" on A1) are different from each other. A,V,R.
The accurate load sharing is impossible if the Check whether there would be any coloring point by
voltage droop values by droop potentiometer excessive heating with all the transformers
("S" on A1) are too low. (T1,T2,T3, L1, T6, T4).
page : 6/4
Trouble Shooting for electric trouble of generators.
The voltage decreases with light load and then increases with higher load
during on-load maximum voltage setting.
page : 6/5
Trouble Shooting for electric trouble of generators.
Insulation failure between turns on the secondary Opened circuit with one or several cables or pins
winding of Rectifier transformer(T6). between the secondary winding terminals(2.2) of
Current transformers(T1,T2,T3) and the input
terminals(2U,2V,2W) of Rectifier transformer(T6).
*. To investigate the exact causes of it, inform the actial phenomenon to makers
(Generator and Engine maker resepctively).
page : 6/6