FANUC βi Series Amplifier Overview
FANUC βi Series Amplifier Overview
2. Summary of Change
Group Name / Outline New, Add Applicable
Correct, Del Date
Basic Function
Optional
Function
Unit
Maintenance
Parts
Notice
Correction
DRAW.
No. B-65322EN/02-02
01 05.01.18 K.Inaba Add newly
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 1 / 17
β(HV)i series SVM DESCRIPTIONS
DRAW.
No. B-65322EN/02-02
βSVM1-40HVi βSVM1-10HVi
or
βSVM1-20HVi
(CAUTION)
FUSE FUSE
Stabilized power supply
NC Optical cable
COP10B COP10A COP10A
COP10B
3phase 400V to 480VAC
Optical cable
AC
Magnetic
Breaker CZ4 CZ4
Line
contactor
filter
5 A
Emergency Magnetic contactor CX29 CX29
Circuit
Stop switch Control signal JX5 JX5
breaker CX30 CX30
Emergency stop signal
Lighting
CZ5 CZ5
surge absorber CX5X CX5X
CZ6 CZ6
Step-down transformer
AC230~AC277V (CAUTION)
to AC200~AC240V Fan unit
CAUTION
supply.
amplifier. Common use with 24V power supply for motor brakes
cannot be performed.
details.
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
2 4 8 22
α4 α8 α12 α22
/4000HVi /3000HVi /3000HVi /3000HVi
αi (20A) (20A) (40A) (40A)
α2 α4 α8 α12
/5000HVi s /5000HVi s /4000HVi s /4000HVi s
αi s (10A) (10A) (40A) (40A)
MOTOR
β2 β4 β8 β12 β22
/4000HVi s /4000HVis /3000HVi s /3000HVi s /2000HVi s
βi s (10A) (10A) (10A) (20A) (20A)
SVM1- 10HVi ? ? ?
20HVi ? ? ? ?
40HVi ? ? ?
DRAW.
No. B-65322EN/02-02
4.1. Breaker
Name Specification Note
The breaker for A06B-6077-K101 Fuji Electric EA53B/30+ cover BZ-TB20B-3
main power supplies
(30A)
Please refer to the following table and select it. For details, please refer to B-65322/02JA.
Servo motor Continuous rating current Power supply capacity
[Arms] [kVA]
(Reference value) (Reference value)
β2/4000HVis 1.2 0.8
β 4/4000HVis 1.7 1.2
β 8/3000HVis 2.7 1.9
β12/3000HV is 4.0 2.8
β 22/2000HV is 5.6 3.9
α2/5000HVis 1.7 1.2
α4/5000HVis 2.3 1.6
α4/4000HV i 3.2 2.2
α8/3000HV i 3.6 2.5
α8/4000HVis 5.2 3.6
α12/4000HV is 5.6 3.9
α12/3000HVi 6.7 4.7
α22/3000HVi 9.0 6.2
DRAW.
No. B-65322EN/02-02
6. Derating
Consider derating as shown below, according to ambient temperature.
The solid line is a derating line for use when HRV2, while the dotted line is a derating line for
use when HRV3 is applied.
SVM1-20HVi
Motor current derating
Motor current (A)
5.6
3.4
30 55
SVM1 -40HVi
Motor current derating
Motor current (A)
9.2
8.3
0 50 55
DRAW.
No. B-65322EN/02-02
Switch Setup
Switch1 OFF
Switch2 OFF
Switch3 ON
Switch4 ON
ON
3
4 1
2
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
(R.A.V-801BXZ-4)
power lines
(R.A.V-152BYZ-2A)
Stabilized
power input
magnetic cabinet
CAUTIONS
(1) To increase the efficiency of lightning surge absorption, the wires indicated by bold
lines should be as short as possible.
Wire cross-sectional area : 2 mm2 or more
Wire length :
The total length of the cables used for line-to-line lightning surge protector (a) and
that used for line-to-ground lightning surge protector (b) must not exceed 2 m.
(2) When performing a dielectric strength test by applying an overvoltage to the power
line, line-to-ground lightning su rge protector must be removed to enable the applied
voltage to be maintained.
(3) The circuit breaker 2 (5A) works for line protection when the lightning surge absorber
is short-circuited because of a surge higher than its rating being applied.
(4) Because current does not flow through lightning surge protector in a normal state, the
circuit breaker 2 (5A) can be used together with the surge absorbers as well as with
other equipment.
DRAW.
No. B-65322EN/02-02
3 80
3 60
30
172 1 0 0 m a x.
60
External dimensions/ panel cut-out/ maintenance area is the same as SVM1-40i and
SVM1-80i. Please refer to B-65322/02EN for details.
DRAW.
No. B-65322EN/02-02
11.2.2 A81L-0001-0169
NOTE
The outer diagram and dimension may be
changed without announcement.
DRAW.
No. B-65322EN/02-02
Connection diagram
Connection diagram
Surge
Specification Rated voltage Clamp voltage withstand Surge withstand voltage
current
R⋅A⋅V-152BYZ-2A 460VAC 1470V ±10%(V1.0) 2500A(8/20µS) 20kV(1.2/50µS)
Surge
AC discharge start Maximum surge discharge
Specification Rated voltage withstand
voltage start voltage
current
line-to-line: 500VAC,
R⋅A⋅V-801BXZ -4 800VAC ±20%(Ua) 2500A(8/20µS) 2.32kV(1.2/50µS)
line-to-ground: 290VAC
DRAW.
No. B-65322EN/02-02
β SVM1-4 0 H Vi βSVM1-10HVi
or
βSVM1-20HV i
(CAUTION)
FUSE FUSE
Stabilized power supply
DC24V K11 K6
CXA19B CXA19A CXA19B CXA19A
NC
Optical
COP10B COP10A COP10A
COP10B
3phase 400V to 480VAC Optical cable
filter
5A
CX29 CX29
K7
Circuit Emergency
JX5 JX5
breaker stop switch CX30 CX30
K8
Lighting
CZ5 CZ5
surge absorber
CX5X CX5X
CZ6 CZ6
K10 K10
Step-down transformer K4 K4
AC230~AC277V
(CAUTION)
to AC200~AC240V
Fan unit
K3 K1
CAUTION K3 K1
K9
1. The input voltage specification of a fan unit is AC200~AC 240V.
5. The cabling of CX29 and CX30 of the second and subsequent amplifiers
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
2. Summary of Change
Group Name / Outline New, Add Applicable
Correct, Del Date
Basic Function
Optional
Function
Unit
Maintenance
Parts
Notice
Correction
DRAW.
No. B-65322EN/02-03
01 05.07.21 K.Inaba Add newly
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 1 / 22
i
β SV 20/20 DESCRIPTIONS
(Note)
This Servo amplifier β iSV 20/20 is available to use combining Series 0 i-MODEL C/
0i Mate-MODEL C.
DRAW.
No. B-65322EN/02-03
β i SV
20/20
TB
FUSE
Stabilized power supply Battery
Optical cable
NC COP10A
3 phase COP10B
200V to 240VAC
Magnetic AC line
Breaker CZ4
contactor filter
Magnetic contactor
CXA20 JF1
Separated regenerative
CZ5M
CAUTION
1 A circuit breakers, magnetic contactor, and AC line filter
are always required.
2 Use the stabilized 24VDC power supply for the amplifier.
24VDC power supply for the amplifier and 24VDC power
supply for the motor brake cannot be shared.
24V power supply
DRAW.
No. B-65322EN/02-03
Item βi SV 20/20
Interface FSSB
Unit Designation A06B-6136-H201
Power P.C.B. A16B-3200-0642
Control P.C.B. A20B-2101-0290
Input Voltage AC 200-240 V (+10%,-15%) 50 / 60 Hz
Main Power For
Current at 50Hz 7.6Arms
Three Phase Supply
Rated Capacity 2.7kVA
Control Input Voltage DC 24 V (+10%, -10%)
Power supply Input Current 0.8 Arms
L-Axis 6.5Arms
Rated Output Current
M-Axis 6.5Arms
L-Axis 20 Ap
Current Limit Value
M-Axis 20 Ap
Servo control HRV2, HRV3
Main Circuit Control Method Sine Wave PWM Control with Transistor Bridges
Servo output frequency range 0-667Hz
- High Current
- IPM Abnormal
- High Voltage of DC Link
- Low Voltage of DC Link
Warning and protectivefunctions - Overheat of Discharge Resistor
- Low Voltage of Control Power Supply
- FSSB Communication Error
- Locked Fan Motor
Ambient Temperature Range 0 to +55 degrees Celsius
Weight 3.9kg
Regererative resistor
(16ohm, 100W no-wind condition)
(16ohm, 200W no-wind condition)
Option
(16ohm, 400W wind velocity 2m/s condition)
Separated AC line filter
Separated battery
DRAW.
No. B-65322EN/02-03
0.4 0.5 1 2 4 8 12
αi F1 αi F2
/5000 /5000
αi F (20A) (20A)
αi S2
/5000 αi S4
/6000 /5000
αi S (20A) (20A)
MOTOR
βi S0.4 β i S0.5 βi S1 βi S2 βi S4 βi S8 βi S12
/5000 /6000 /6000 /4000 /4000 /3000 /2000
β i s (20A) (20A) (20A) (20A) (20A) (20A) (20A)
SV 20/20 L axis
M O O O O O O O
axis O O O O O O O
DRAW.
No. B-65322EN/02-03
Please refer to the following table and select it. For details, please refer to B-65322/02E N.
Servo motor Continuous rating current Power supply capacity
[Arms] [kVA]
(Reference value) (Reference value)
β iS 0.4/5000 0.6 0.2
β iS 0.5/6000 1.4 0.47
β iS 1/6000 2.3 0.77
β iS 2/4000 2.2 0.77
β iS 4/4000 3.3 1.2
5. Derating
Consider derating as shown below, according to ambient temperature.
The solid line is a derating line for use when HRV2, while the dotted line is a derating line for
use when HRV3 is applied.
6.5
5.2
4.6
35 45 55
DRAW.
No. B-65322EN/02-03
Refer to Section [I. SVM ] of B-65322EN/02 for details about calculation method of the
regeneration energy per regenerative cycle .
Cautions
l Please install into the cabinet, which fulfills the following conditions so that cutting fluid,
oil mist, cutting waste, etc. may not adhere to regeneration discharge resistor.
So, please install in the environment of the pollution degree 2 level specified to "IEC
60664-1."
In order to satisfy a pollution degree 2 under the severe environment of a machine tool,
it is necessary to install in a cabinet with which it is generally satisfied of IP54.
If the cabinet does not have a structure for preventing materials that adversely affect
regenerative discharge resistor from gettinng into the cabinet, normal operation and
safety may fail. So, special care should be taken.
DRAW.
No. B-65322EN/02-03
ON
3
4 1
2
DRAW.
No. B-65322EN/02-03
NOTE
The allowable voltage fluctuation is a change
observed for several minutes. It is not a continuous
change.
DRAW.
No. B-65322EN/02-03
380
60
172
DRAW.
No. B-65322EN/02-03
DRAW.
No. B-65322EN/02-03
β iSV 20/20
360
2-M5
DRAW.
No. B-65322EN/02-03
AIR FLOW
50mm
50mm
60mm
DRAW.
No. B-65322EN/02-03
In case of using this function, please add an uninterruptible power supply (UPS) etc. to be
able to maintain the control source (DC 24V) of CNC and amplifier after a power failure
occurs until mechanical brake operates.
Specification
2-axes amplifier β iSV output a power failure detect signal from a connector CX36, when
power failure is occurred.
The drop of three-phase circuit AC voltage inputted into the connector “CZ4” of 2-axes
amplifier β iSV is detected.
CZ4 input voltage range: 0 V-AC240V+10% 3φ 50Hz/60Hz±2Hz
CZ4 power failure detect voltage: AC165V±10V
Detection delay time is established so that it may not react sensitively to instantaneous
power failure.
Detection delay time: 8msec ~17msec
(Note)
The detect condition is simultaneous three-phase circuit AC voltage drop.
Therefore, it may be unable to detect a power failure correctly on following condition s.
1. Power failure (phase interruption) as only one phase drop.
2. Power failure occurred at the time of motor acceleration. (Please see below.)
Alarm occurred
DRAW.
No. B-65322EN/02-03
βiSV
20/20
TB
FUSE
Stabilized power supply K9 Battery
K11
DC24V CXA19B CXA19A case
Optical cable
NC COP10A
3 phase COP10B
200V to 240VAC
Magnetic AC line K2
Breaker CZ4
contactor filter
K7
5A circuit CX29
Emergency
breaker K8 JX5
stop switch CX30
K4 JF1
CXA20
Separated regenerative
K5
discharge resistor JF2
CX36
Lighting
Power failure signal K12
surge absorber CX5X
CZ5L
CZ5M
K3
K1
CAUTION
1 A circuit breakers, magnetic contactor, and AC line filter
K3 K1
are always required.
2 Use the stabilized 24VDC power supply for the amplifier.
24VDC power supply for the amplifier and 24VDC power
supply for the motor brake cannot be shared.
3 The cabling of CX29 and CX30 of the second and
subsequent amplifiers may be omitted. For details, see
"TOTAL CONNECTION DIAGRAM". 24V powersupply
DRAW.
No. B-65322EN/02-03
DRAW.
No. B-65322EN/02-03
DRAW.
No. B-65322EN/02-03
Regenerative
βiSV 20/20
discharge resistor
TB
DCP
DCP DCP
Resistor
CXA20
1 TH1
2 TH2
Thermostat
D-2000 series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire: 0.30 to 0.85mm2
Manufacture: Tyco Electronics AMP
WARNING
l Do not short between terminal “DCP” and terminal “DCC”.
l Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of
servo amplifier α i series.
Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-03
Cable specification:
JIS C 3312
DCC
DCC DCC
Resistor
Cable specification:
CXA20
1 TH1
2
TH2
Thermostat
D-2000series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire: 0.3mm2 to 0.85mm2
WARNING
l Do not short between terminal “DCP” and terminal “DCC”.
l Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of
servo amplifier α i series.
Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-03
β iSV 20/20
TB
DCP
Keep these pins unconnected.
(Do not install a jumper between pins.)
DCC
CXA20
Install jumper between pins.
1
D-2000 series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire 0.30 to 0.85mm2
Manufacture: Tyco Electronics AMP
WARNING
l Do not short between terminal “DCP” and terminal “DCC”.
l Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of
servo amplifier α i series.
Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-03
24V
CX36
βiSV 20/20 2
Power failure detect signal output
Normal: ON *ESP
Power failure detection: OFF 3
24V
PMC
DI DO
*ESP
Relay for mechanical brake coil
0V
DRAW.
No. B-65322EN/02-03
DRAW.
No. B-65322EN/02-03
2. Summary of Change
Group Name / Outline New, Add Applicable
Correct, Del Date
Basic Function
Optional
Function
Unit
Maintenance
Parts
Notice
Correction
This documents is described about the specification of 400V input model βiSV.
Please refer to FANUC SERVO AMPLIFIER βi series DESCRIPTIONS (B-65322EN/02) about
contents without in this.
DRAW.
No. B-65322EN/02-02
or
βiSV 20HV
(CAUTION)
FUSE FUSE
Stabilized power supply
NC Optical cable
COP10B COP10A COP10A
COP10B
3phase 400V to 480VAC
Optical cable
AC
Magnetic
Breaker CZ4 CZ4
Line
contactor
filter
5 A
Emergency Magnetic contactor CX29 CX29
Circuit
Stop switch Control signal JX5 JX5
breaker CX30 CX30
Emergency stop signal
Lighting
CZ5 CZ5
surge absorber CX5X CX5X
CZ6 CZ6
Step-down transformer
AC230~AC277V (CAUTION)
to AC200~AC240V Fan unit
CAUTION
supply.
amplifier. Common use with 24V power supply for motor brakes
cannot be performed.
details.
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
2 4 8 22
αi F4 αi F8 αi F12 αi F22
/4000HV /3000HV /3000HV /3000HV
αi (20A) (20A) (40A) (40A)
αi S2 αi S4 αi S8 αi S12
/5000HV /5000HV /4000HV /4000HV
αi s (10A) (10A) (40A) (40A)
MOTOR
βi S2 β i S4 β i S8 β i S12 β i S22
/4000HV /4000HV /3000HV /3000HV /2000HV
βi s (10A) (10A) (10A) (20A) (20A)
βi SV 10HV ? ? ?
20HV ? ? ? ?
40HV ? ? ?
DRAW.
No. B-65322EN/02-02
[Tab.: The amplifier input current at the time of continuous motor ouput power]
Servo motor Continuous rating current Power supply capacity
[Arms] [kVA]
(Reference value) (Reference value)
βiS2/4000HV 1.2 0.8
βiS4/4000HV 1.7 1.2
βiS8/3000HV 2.7 1.9
βiS12/3000HV 4.0 2.8
βiS22/2000HV 5.6 3.9
αiS2/5000HV 1.7 1.2
αiS4/5000HV 2.3 1.6
αiF4/4000HV 3.2 2.2
α iF8/3000HV 3.6 2.5
α iS8/4000HV 5.2 3.6
α iS12/4000HV 5.6 3.9
α iF12/3000HV 6.7 4.7
α iF22/3000HV 9.0 6.2
DRAW.
No. B-65322EN/02-02
02 06.06.07 INABA Addition of current va lue
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 6/
5. Cooling fan motor
The fan motor for amplifier cooling is needed for the following model.
Ordering number Amplifier Applied motor
6. Derating
Consider derating as shown below, according to ambient temperature.
The solid line is a derating line for use when HRV2, while the dotted line is a derating line for
use when HRV3 is applied.
βiSV 20HV
Motor current derating
Motor current (A)
5.6
3.4
30 55
βiSV 40HV
Motor current derating
Motor current (A)
9.2
8.3
0 50 55
DRAW.
No. B-65322EN/02-02
Switch Setup
Switch1 OFF
Switch2 OFF
Switch3 ON
Switch4 ON
ON
3
4 1
2
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
(R.A.V-801BXZ-4)
power lines
(R.A.V-152BYZ-2A)
Stabilized
power input
magnetic cabinet
CAUTIONS
(1) To increase the efficiency of lightning surge absorption, the wires indicated by bold
lines should be as short as possible.
Wire cross-sectional area: 2 mm2 or more
Wire length:
The total length of the cables used for line-to-line lightning surge protector (a) and
that used for line-to-ground lightning surge protector (b) must not exceed 2 m.
(2) When performing a dielectric strength test by applying an overvoltage to the power
line, line-to-ground lightning surge protector must be removed to enable the applied
voltage to be maintained.
(3) The circuit breaker 2 (5A) works for line protection when the lightning surge absorber
is short-circuited because of a surge higher than its rating being applied.
(4) Because current does not flow through lightning surge protector in a normal state, the
circuit breaker 2 (5A) can be used together with the surge absorbers as well as with
other equipment.
DRAW.
No. B-65322EN/02-02
3 80
3 60
30
172 1 0 0 m a x.
60
External dimensions/ panel cut-out/ maintenance area is the same as βiSV 40 and
βiSV 80. Please refer to B-65322/02EN for details.
DRAW.
No. B-65322EN/02-02
11.2.2 A81L-0001-0169
DRAW.
No. B-65322EN/02-02
Connection diagram
Connection diagram
Surge withstand
Specification Rated voltage Clamp voltage Surge withstand voltage
current
R⋅A⋅V-152BYZ-2A 460VAC 1470V ±10%(V1.0) 2500A(8/20µS) 20kV(1.2/50µS)
DRAW.
No. B-65322EN/02-02
β iSV 4 0 H V βi SV 1 0 H V
or
βi SV 2 0 H V
(CAUTION)
FUSE FUSE
Stabilized power supply
DC24V K11 K6
CXA19B CXA19A CXA19B CXA19A
NC
Optical
COP10B COP10A COP10A
COP10B
3phase 400V to 480VAC Optical cable
filter
5A
CX29 CX29
K7
Circuit Emergency
JX5 JX5
breaker stop switch CX30 CX30
K8
Lighting
CZ5 CZ5
surge absorber
CX5X CX5X
CZ6 CZ6
K10 K10
Step-down transformer K4
K12 K4
AC230~AC277V
(CAUTION)
to AC200~AC240V
Fan unit
K3 K1
CAUTION K3 K1
K9
1. The input voltage specification of a fan unit is AC200~AC 240V.
5. The cabling of CX29 and CX30 of the second and subsequent amplifiers
DRAW.
No. B-65322EN/02-02
DRAW.
No. B-65322EN/02-02
02
Cable specification:
Two-conductor polyvinyl heavy-duty power cable (JIS C 3312)
2
Conductor size: 3.5mm
Crimp terminal: 5.5-4
DRAW.
No. B-65322EN/02-02
02 06.06.07 INABA Addition of K12
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 16 /
13. Heat disspaton
The amount of heat dissipation depends on the SV model and the current that flows through
the servo motor. For the current that flows through a servo motor, reference the continuous
rated current of each servo motor. (For the continuous rated current of each servo motor,
refer to the servo motor descriptions.) As the current that flows through a servo motor, the
root-mean-square value of the current that flows through an actual servo motor on a machine
can be used. The amount of heat dissipation indicated below assumes the use of HRV2.
(1) Total amount of heat dissipation
The total amount of heat dissipation is calculated
according to the following expression:
Total amount of heat dissipation= a + Ka1 × b1
a: Amount of heat dissipation determined by the SV
model [W]
Ka1: Coefficient determined by the SV [W/Arms]
b1: Current flowing through the servo motor [Arms]
DRAW.
No. B-65322EN/02-02
Name i
FANUC SERVO AMPLIFIER β series DESCRIPTIONS
Spec.No./Version B-65322EN/02
2. Summary of change
Correction
Another
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 2/5
1.CONFIGURATION
This chapter shows an example of a 2-axis system configuration using the β iSV 40HV for the first axis (the
unit nearer the CNC) and the βi SV 10HV or βi SV 20HV for the second axis.
In this example, the servo check board adapter and servo check board in the configuration are provided for
the first axis.
βi SV 10HV
or
β iSV 40HV βi SV 20HV
FUSE FUSE
Battery
(CAUTION)
CXA19B CXA19A case
Stabilized power supply CXA19B CXA19A
Servo check board
DC24V
CNC
JD1B JD1A Servo check board JD1B JD1A
adapter
Breaker AC Magnetic
CZ4 Magnetic CZ4
line contactor
contactor
filter
5 A External
CX30 JA34 CX30 JA34 pulse
Circuit
breaker generator
CXA20 CXA20
JA72 JA72
Operator’s panel
Power magnetics
CZ5 CZ5
Lighting cabinet
surge CX5X CX5X Emergency
absorber CZ6 CZ6 stop switch
Step-down transformer
AC230V~ AC277V (Caution)
? AC200V~ AC240V Fan unit
24V power
CAUTION
supply for
1. The input voltage specification of a fan unit is AC200~AC240V. motor brake
2. Please confirm the input voltage specification of a stabilized power supply.
3. Please be sure to install a breaker, a magnetic contactor and AC line filter.
4. Please be sure to use a stabilized 24VDC power supply for βiSV HV. Common
use with 24V power supply for motor brakes cannot be performed.
5. The cabling of CX30 of the second and subsequent βiSV HV may be omitted.
See part I. of B-65322EN/02 for details.
6. A magnetic contactor may be shared. See “Total connection diagram” for details.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 3/5
2.SPECIFICATIONS
Model βi SV 10HV β iSV 20HV βi SV 40HV
No. of controlled axes 1 axis
Interface with CNC FANUC I/O Link
Unit drawing No. A06B-6133-H001 A06B-6133-H002 A06B-6133-H003
Power PCB drawing No. A16B-3200-0515 A16B-3200-0516 A16B-3200-0517
Control PCB drawing No. A20B-8101-0200
Main power for Input voltage AC 400-480 V (+10%, -15%) 50/60Hz
three-phase Input current (50Hz) 2.3 Arms 3.6 Arms 9.0 Arms
supply Power supply rating 1.6 kVA 2.5 kVA 6.2 kVA
Control powe r Input voltage DC 24 V (+10%, -10%)
supply Input current 0.9 A
Rated output current 3.1 Arms 5.6 Arms 9.2 Arms
Maximum output current 10 Ap 20 Ap 40 Ap
Servo HRV control HRV2
Control method Sine wave PWM control with transistor bridges
Dynamic brake circuit Built-in
Output frequency range 0-334 Hz
External pulse input Differential phase A/B, 1 ch
Internal DI 5 points (ESP, interlock, + overtravel, - overtravel, skip)
Setting display Performed by master CNC via I/O Link
LEDs for status display 8 LEDs
-High Current
-IPM Abnormal
-High/Low Voltage of DC link
-Overheat of Discharge Resistor
-Low Voltage of Control Power Supply
Protection function -I/O Link Communication Error
-Locked Fan Motor
-Disconnection of External Pulse Input
-Program or Setting Error
-Servo Motor Overheat
-Exceeding Stroke Limit
Ambient temperature range 0 ~ 55 ?
Weight 3.9 kg
Built-in regenerative resistor
(64ohm, 50W no-wind condition)
Remarks (64ohm, 130W wind velocity 2m/s condition)
Separated AC line filter
Separated battery
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 4/5
3.APPLICABLE MOTORS
See B-65322EN/02-02.
6.DERATING
See derating in case of applying HRV2 in B-65322EN/02-02.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 5/5
10.INSTALLING OF LIGHTING SURGE ABSORBER
See B-65322EN/02-02. In the figure of B-65322EN/02-02, change the positions of the magnetic contactor
and AC line filter in case that one magnetic contactor is connected per βiSV HV.
i
11.1. EXTERNAL DIMENSIONS OF β SV 10HV, β SV 20HV and β SV 40HVi i
External dimensions of these models are same.
See subsection 8.1.2 SVM1-40i, SVM1-80i in Part III. of B-65322EN/02.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 6/6
12.TOTAL CONNECTION DIAGRAM
This chapter shows a connection example of a 2-axis system using the β iSV 40HV for the first axis (the unit
nearer the CNC) and the βiSV 10HV or βi SV 20HV for the second axis.
There are two methods about connection of magnetic contactor. First one magnetic contactor is connected per
β iSV HV. Secondly a magnetic contactor is shared by some βi SV HVs. First case is recommended. In the
case of sharing a magnetic contactor, if an alarm that turns off the magnetic contactor is issued in the β iSV
HV, an alarm indicating DC link voltage shortage is issued in the other βi SV HVs. When emergency stop is
cancelled by different timing, an alarm indicating DC link voltage shortage may be issued in the βi SV HV.
FUSE FUSE
Battery
(CAUTION)
K11 CXA19B CXA19A K6 K9 case
Stabilized power supply CXA19B CXA19A
DC24V
CNC
K20 K20
JD1B JD1A JD1B JD1A
Breaker AC Magnetic K2 K2
CZ4 Magnetic CZ4
line contactor
contactor
filter
K7 K7
CX29 JF1 CX29 JF1
5 A External
K8
CX30 JA34 CX30 JA34 pulse
Circuit K22
breaker generator
K5
CXA20 K5 CXA20
JA72 K21 JA72 K21
Operator’s panel
Power magnetics
Lighting CZ5 CZ5
cabinet
surge
K4
CX5X CX5X Emergency
absorber CZ6 K4 CZ6
K10 K10 stop switch
Step-down transformer
AC230V~ AC277V (Caution)
? AC200V~ AC240V Fan unit
K3 K1 K3 K1
24V power
CAUTION
supply for
1. The input voltage specification of a fan unit is AC200~AC240V. motor brake
2. Please confirm the input voltage specification of a stabilized power supply.
3. Please be sure to install a breaker, a magnetic contactor and AC line filter.
4. Please be sure to use a stabilized 24VDC power supply for β iSV HV.
Common use with 24V power supply for motor brakes cannot be performed.
5. The cabling of CX30 of the second and subsequent βi SV HV may be omitted.
Refer to part I. of B-65322EN/02 for details.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 7/7
l Example for sharing a magnetic contactor (Reference)
βi SV 10HV
or
β iSV 40HV βi SV 20HV
FUSE FUSE
Battery
(CAUTION)
K11 CXA19B CXA19A K6 K9 case
Stabilized power supply CXA19B CXA19A
DC24V
CNC
K20 K20
JD1B JD1A JD1B JD1A
Breaker Magnetic AC K2 K2
contactor CZ4 CZ4
line
filter
K7 K7
CX29 JF1 CX29 JF1
5 A External
K8
CX30 JA34 CX30 JA34 pulse
Circuit K22
breaker generator
K5
CXA20 K5 CXA20
JA72 K21 JA72 K21
Operator’s panel
Power magnetics
Lighting CZ5 CZ5
cabinet
surge
K4
CX5X CX5X Emergency
absorber CZ6 K4 CZ6
K10 K10 stop switch
Step-down transformer
AC230V~ AC277V (Caution)
? AC200V~ AC240V Fan unit
K3 K1 K3 K1
24V power
CAUTION
supply for
1. The input voltage specification of a fan unit is AC200~AC240V. motor brake
2. Please confirm the input voltage specification of a stabilized power supply.
3. Please be sure to install a breaker, a magnetic contactor and AC line filter.
4. Please be sure to use a stabilized 24VDC power supply for βiSV HV. Common
use with 24V power supply for motor brakes cannot be performed.
5. The cabling of CX30 of the second and subsequent βiSV HV may be omitted.
Refer to part I. of B-65322EN/02 for details.
6. If an alarm that turns off the magnetic contactor is issued in the βiSV HV, an
alarm indicating DC link voltage shortage is issued in the other βiSV HVs. When
emergency stop is also cancelled by different timing, an alarm indicating DC link
voltage shortage may be issued in the β iSV HV.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 8/8
See part III. of B-65322EN/02 about details of cable.
See B-65322EN/02-02 about continuous rating current of servo motor to select cable of K2 and K3.
13.HEAT DISSIPATION
See B-65322EN/02-02.
TITL
DRAW. NO. CU
B-65322EN/02-04
SH
ED DATE DESIG DESCRIPTION F A N U C L T D 9/9
SERVO AMPLIFIER βiSVSP LEVEL-UP version
DESCRIPTIONS
2. Summary of Change
Maintenance
Parts
Notice
Correction
1. Overview ....................................................................................................................................... 4
..
3. Specification .................................................................................................................................... 6
..
3.1 Specification table ....................................................................................................................... 6
..
3.2 Weight ....................................................................................................................................... 8
..
3.3 Cooling fan motor ....................................................................................................................... 8
..
3.4 Applied motor .............................................................................................................................. 9
..
3.5 Breaker, Magnetic contactor, AC Line Filter ........................................................................... 9
.
3.6 Derating ...................................................................................................................................... 12
.
This model is the amplifier series for 0i/ 0i Mate like the current model.
This document describes only changed or added specifications from current model.
Therefore please refer the specifications which are not described in this document to FANUC SERVO
AMPLIFIER β i series DESCRIPTIONS B-65322EN.
1. Overview
[Level-up points]
· The level-up version servo amplifier, which is 2-axis or 3-axis servo and 1-axis spindle, is
added in the βiSVSP
· There is no sensor-less model
· 2nd FSSB connector is added
· Built-in of power failure detecting funtion
· Application of plastic case and terminal cover
· Addition of new model “40/40/80-15”
This model is the amplifier series for 0i/ 0i Mate like the current model.
[Compatibility]
· No applicable to spindle sensor-less type
· Plastic case and terminal cover are applied, however external dimensions and
maintenance area are same as current model.
Two-axis-type
ßiSVSP 20/20-7.5 ßiSVSP 20/20-11 ßiSVSP 40/40-15
Item (TypeD) (TypeD) (TypeD)
Unit designation A06B-6134-H201#D A06B-6134-H202#D A06B-6134-H203#D
Power PCB A20B-2101-0440 A20B-2101-0441 A20B-2101-0022
Control PCB A20B-2101-0450 A20B-2101-0450 A20B-2101-0450
Main power supply Input voltage AC200-240V (+10%,-15%) 50/60Hz
Rated current 36Arms 52Arms 68Arms
Rated capacity 13KVA 18KVA 24KVA
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
Model Weight
βiSVSP 20/20-7.5 10.2Kg
βiSVSP 20/20-11
βiSVSP 40/40-15
14.8Kg
βiSVSP 20/20/40-7.5
βiSVSP 20/20/40-11
βiSVSP 40/40/40-15
βiSVSP 40/40/80-15
CAUTION
** Combining with this motor requires changing the motor control parameter. An incorrect parameter setting may
damage the motor.
** Special motor number exists. So, please select it in combining with this motor.
SVSP CXA2A
COP10A
(FSSB I/F)
TB2 CZ2L CZ2M TB1 TB3
AC200V-240V
Breaker 1 MC AC Reacto r
JF2
G
Pulse Coder I/F
JYA2
Breaker 2 JF1
Lightning surgeabsorber Equipments
5A
Spindle Servo
Motor Motor
G
Cautions
The coil voltage of magnetic contactor is AC200V specification.
At short-time rating(min)
Available Operating Time
≈ ≈
continuous
30
20
10
0 10 20 30 40 50 60
Ambient temperature(C)
In case of using this function, please add an uninterruptible power supply (UPS) etc. to be able to maintain
the control source (DC 24V) of CNC and amplifier after a power failure occurs until mechanical brake
operates.
[Specification]
Connector “CX36” output power failure detect signal in case of power failure.
Detect the drop of three-phase AC input voltage of connector “CX38”.
CX38 input voltage range: 0 V-AC240V+10% 3F 50Hz/60Hz±2Hz
Detect delay time is set so that it may not react sensitively to instantaneous power failure.
Detection delay time: 8msec~17msec
(Note)
DC link voltage
Low voltage alarm
Of DC link
Alarm occurred
Power failure
Output of PMC
Close Open
a. Power failure detection delay time: The time from detecting the power failure till power failure
detection signal is output from βiSVSP (8msec ~ 17msec)
b. PMC delay time: The time from DI operating till DO operating of PMC (15msec)
c. Reset time of relay: The time from cutting off the rated voltage supplied to the coil of the relay
till the contact of the relay is turned off (“a contact ” is opened)
d. Response time of brake: The time from cutting off the rated voltage supplied to the coil of the
brake till the brake becomes effective
e. Operate time of brake: The time from occurring the power failure till the brake becomes
effective
Condition
(1) Power failure detection delay time --- 10msec
(2) PMC delay time---15msec
(3) Relay: G2R type made by OMRON --- Reset time of relay is 20msec
(4) Brake: Built-in brake for ? iS8 motor --- Response time of brake is 30msec
Result
10msec + 15msec + 20msec + 30msec = 75msec
Panel cuts when FANUC fan unit (A06B-6134-K001) is used and when not used are shown
below. A fan unit can be placed either on top of or below the servo amplifier.
NOTE
1 Attach the accompanying gasket around the panel cut-out to prevent oil
and dust from getting into it.
2 Reinforce the right and left sides of the panel cut-out in the power
magnetics cabinet by using fittings such as angles to maintain
satisfactory contact between the power magnetics cabinet and the
amplifier.
3 Placing a FANUC fan unit on top of the servo amplifier requires installing
a duct.
Refer to the “Example Duct Structure for Using a FANUC Fan Unit
(A06B-6134-K001)” for descriptions about the structure of the duct.
4 Placing a FANUC fan unit below the servo amplifier does not require
installing a duct.
If no FANUC fan unit is used, the user is requested to install a fan motor
that can generate an air flow of at least 2 m/s at the heat sink.
(1) When no FANUC fan unit (2) When one FANUC fan unit is used (3) When two FANUC fan units are used
is used (placed on top of the servo (placed on top of the servo amplifier)
amplifier)
7.5
131 131
20
20
60
75
60
75
2 2
10 10
11
11
11
4-M4 4-M4
338
360
338
360
338
360
24 6 246 246
11
11
338
360
338
360
246 246
7.5
10 10
20
6-M5
20
6-M5
16
60
75
60
75
2 2
4-M4 4-M4
131 131 131
7.5
12
(Note)
50 mm
26 0 mm 172 mm 92.5 mm
50 mm
380 mm
50 mm
(NOTE) When a right-angle type cable
connector is used (+30 mm when a
straight type cable connector is used)
(Note)
50 mm
130 mm 130 m m
380 mm 380 m m
50 mm 50 m m
50 mm 50 mm
380 mm 380 mm
130 mm 130 mm
(Note) 50 mm
Shown below is an example duct structure where a FANUC fan unit (A06B-6134-K001) is
used.
NOTE
1 Install a duct having the shape shown below between the fan unit and
heat sink to provide a ventilation flue.
2 Weld the duct to the cabinet.
3 If the fan unit is placed below the servo amplifier, no duct is needed.
102
64.5
102
230
70.5
64.5
AC200V IN
2
Applicable 1.25 ?
Applicable crimp terminal 1.25-4
K72
Fan unit Fan unit
CXA2 K74
SVSP
K76 CX38
JF3 K22 Servo Motor
K6 CX3 JX6
COP10A
K75 (FSSB I/F)
CZ2L CZ2M CZ2N TB1 TB3
TB2 Flange
K10 K21 K21 K21 K1
200-240VAC
K70 K70
JF3
Circuit breaker 1 Magnetic contactor AC reactor
NOTE
1 Always install the circuit breakers, magnetic contactor, and AC reactor.
2 To protect the equipment from lightning surge voltages, install a lightning
surge absorber across each pair of power lines and across each power
line and the grounding line at the power inlet of the power magnetics
cabinet.
3 Be sure to connect the grounding terminal (G) on TB2 to a substantial
ground.
WARNING
Do not touch any component in the module or any connected
cable when item24 ”DC LINK charge LED” is on, because it is
dangerous.
NOTE
The maximum current of contact for “K73, K74” is 4.0A.
24V
CX36
βiSVSP 2
Output signal of power failure detect
Normally ON *ESP
At power failure OFF 3
24V
PMC
DI DO
*ESP
Relay for drive brake
0V
Brake coil
The cable K22 is used to connect the SVPM and Pulsecoder of βiS servo motor.
(7) 6V (4)
See Subsection 5.4.1 for explanations about the SVPM-side connector that matches the recommended
cable.
Soldering or crimping
Connector
The total resistance (Round The total resistance (Round
trip) of 5 V and 0 V must be trip) of 5 V and 0 V must be
less than 2 Ω. less than 2Ω .
• Recommended cable
A66L-0001-0460 : Flexible cable 28m or less long
A66L-0001-0462 : Flexible cable 50m or less long
A66L-0001-0481 : Fixed cable 28m or less long
A66L-0001-0491 : Fixed cable 50m or less long
For separated
power supply 5V
connection 0V
i
β SV Shield Linear scale
(1) SD
(2) *SD
(5) REQ
(6) *REQ
(9, 20) 5V
(12, 14)0V
(7) 6V
Drain wire
(16) 0V
2.Power to CNC
(Note)
When the following power-on timing condition is satisfied, the power to βiSVSP and linear
scale is assumed to be turned on simultaneously when the power to CNC is turned on.
On
Power to CNC
Off
t1 t2
On
Power to BiSV and linear scale Off
t1: 200ms
Means that the power to βiSVSP and linear scale is turned on within 200 ms
before the power to CNC is turned on.
t2: 500ms
Means that the power to βiSVSP and linear scale is turned on within 500 ms
after the power to CNC is turned on.
(Note)
When the following power-off timing condition is satisfied, the power to BiSV and linear scale is
assumed to be turned off simultaneously when the power to CNC is turned off.
On
Power to CNC
Off
t1
On
Power to BiSV and linear scale Off
t1: 500ms
Means that the power to BiSV and linear scale is turned off within 500 ms
before the power to CNC is turned off.
The amount of heat generated in an SVSP series depending on its model, the current flowing
through the motor, and the motor output. (Refer to the respective motor description manuals
for the current and output of each motor.)
The total amount of heat dissipation by the SVSP is calculated according to the following
expression:
AC reactor
By placing the heat sink section of the SVSP outside the cabinet, the residual amount of heat
in the cabinet can be calculated according to the expression below.
Ka1 2.1
Ka2 0.9
βiSVSP 20/20-7.5 H201#D 22
Ka3 0.8
Ka4 0.8
Ka1 2.1
Ka2 0.8
βiSVSP 20/20-11 H202#D 22
Ka3 0.8
Ka4 0.8
Ka1 1.3
Ka2 0.6
βiSVSP 40/40-15 H203#D 22
Ka3 0.5
Ka4 0.5
Ka1 2.1
Ka2 0.9
βiSVSP 20/20/40-7.5 H301#D 24 Ka3 0.8
Ka4 0.8
Ka5 0.7
Ka1 2.1
Ka2 0.8
βiSVSP 20/20/40-11 H302#D 24 Ka3 0.8
Ka4 0.8
Ka5 0.7
Ka1 1.3
Ka2 0.6
βiSVSP 40/40/40-15 H303#D 24 Ka3 0.5
Ka4 0.5
Ka5 0.5
Ka1 1.3
Ka2 0.6
βiSVSP 40/40/80-15 H313#D 24 Ka3 0.5
Ka4 0.5
Ka5 0.5
2. Summary of Change
Maintenance
Parts
Notice
Correction
Another
A. Difference between β iSVSP for Series 0 i/0i Mate- MODEL D and current model ............... 3
2. Specification .................................................................................................................................... 5
..
2.1 Specification table ....................................................................................................................... 5
..
2.2 Weight ....................................................................................................................................... 9
..
2.3 Cooling fan motor ....................................................................................................................... 10
..
2.4 Applied motor .............................................................................................................................. 11
..
2.5 Breaker, Magnetic contactor, AC Line Filter ........................................................................... 12
.
2.6 Derating ...................................................................................................................................... 15
.
2.7 Sensor for spindle ........................................................................……………………… 16
….
NO. B-65322EN/02-07
NO. B-65322EN/02-07
Difference between β iSVSP for Series 0i/0 i Mate-MODEL D and current β iSVSP
(A06B-6134-H***#A or #C).
Difference between β iSVSP for Series 0i/0 i Mate-MODEL D and current β iSVSP
(A06B-6134-H***#D).
This document describes only changed or added specifications from current model.
Therefore please refer the specifications which are not described in this document to FANUC SERVO
AMPLIFIER β i series DESCRIPTIONS B-65322EN.
NO. B-65322EN/02-07
NO. B-65322EN/02-07
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
NO. B-65322EN/02-07
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
NO. B-65322EN/02-07
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
NO. B-65322EN/02-07
(Note)
This specification is described on the condition of intermitting motor operation and not continuous motor
operation.
NO. B-65322EN/02-07
βiSVSP20/20-11
Spindle motor βiΙ series
βiSVSP40/40-15
(α iM, α iMZ sensor model)
βiSVSP20/20/40-7.5
14.8Kg
βiSVSP20/20/40-11
βiSVSP40/40/40-15
βiSVSP40/40/80-15
βiSVSP20/20-7.5 10.2Kg
βiSVSP20/20-11
Spindle motor βiΙ series
βiSVSP40/40-15
βiSVSP20/20/40-7.5
(Sensor-less model) 14.8Kg
βiSVSP20/20/40-11
βiSVSP40/40/40-15
βiSVSP40/40/80-15
NO. B-65322EN/02-07
NO. B-65322EN/02-07
βi I 3 βi I 6 βi I 8 βi I 12 β i I P 8 β i I P 12 β i I P 15 βi IP 18 β i S 2 βi S 4 βi S 8 β i S 12 β i S 22 β i S 12 βi S 22 β i S 22
/10000 /10000 /10000 /8000 /6000 /6000 /6000 /6000 /4000 /4000 /3000 /2000 /1500 /3000 /2000 /3000
Spindle Ο Ο Ο
ß iSVSP 20/20-7.5
A06B-6164-H201#H580 Servo L axis Ο Ο Ο Ο Ο
A06B-6165-H201#H560
Servo M axis Ο Ο Ο Ο Ο
Spindle Ο Ο Ο ** ** Ο Ο
ß i SVSP 20/20-11
A06B-6164-H202#H580 Servo L axis Ο Ο Ο Ο Ο
A06B-6165-H202#H560
Servo M axis Ο Ο Ο Ο Ο
Spindle Ο Ο Ο Ο ** ** Ο Ο
ß i SVSP 40/40-15
A06B-6164-H223#H580 Servo L axis ** ** ** ** ** Ο Ο
A06B-6165-H223#H560
Servo M axis ** ** ** ** ** Ο Ο
Spindle Ο Ο Ο
ß i SVSP 20/20/40-7.5 Servo L axis Ο Ο Ο Ο Ο
A06B-6164-H311#H580
A06B-6165-H311#H560 Servo M axis Ο Ο Ο Ο Ο
Servo N axis ** ** ** ** ** Ο Ο
Spindle Ο Ο Ο ** ** Ο Ο
ß i SVSP 20/20/40-11 Servo L axis Ο Ο Ο Ο Ο
A06B-6164-H312#H580
A06B-6165-H312#H560 Servo M axis Ο Ο Ο Ο Ο
Servo N axis ** ** ** ** ** Ο Ο
Spindle Ο Ο Ο Ο ** ** Ο Ο
ß i SVSP 40/40/40-15 Servo L axis ** ** ** ** ** Ο Ο
A06B-6164-H333#H580
A06B-6165-H333#H560 Servo M axis ** ** ** ** ** Ο Ο
Servo N axis ** ** ** ** ** Ο Ο
Spindle Ο Ο Ο Ο ** ** Ο Ο
ß i SVSP 40/40/80-15 Servo L axis ** ** ** ** ** Ο Ο
A06B-6164-H343#H580
A06B-6165-H343#H560 Servo M axis ** ** ** ** ** Ο Ο
Servo N axis Ο
CAUTION
** Combining with this motor requires changing the motor control parameter. Special motor number exists. So,
please select it in combining with this motor.
Incorrect parameter setting may damage the motor.
NO. B-65322EN/02-07
SVSP CXA2A
AC200V-240V
Breaker 1 MC AC Reacto r
JF2
G
Pulse Coder I/F
JYA2
Breaker 2 JF1
Lightning surgeabsorber Equipments
5A
Spindle Servo
Motor Motor
G
(*) This is available in case of Spindle motor βiΙ series (α iM, α iMZ sensor model).
NO. B-65322EN/02-07
NO. B-65322EN/02-07
Cautions
The coil voltage of magnetic contactor is AC200V specification.
AC Reactor
Classification The suiting model Ordering number
For βiSVSP 20/20-7.5
A81L-0001-0155
For βiSVSP 20/20-11
For βiSVSP 40/40-15 A81L-0001-0156
Basic For βiSVSP 20/20/40-7.5
A81L-0001-0155
For βiSVSP 20/20/40-11
For βiSVSP 40/40/40-15 A81L-0001-0156
For βiSVSP 40/40/80-15
NO. B-65322EN/02-07
At short-time rating(min)
Available Operating Time
≈ ≈
continuous
30
20
10
0 10 20 30 40 50 60
Ambient temperature(C)
NO. B-65322EN/02-07
The following lists combinations of βi SVSP type, applicable sensors, and functions.
Type Remarks
Configuration 1 2 3 4 5 6 7
A06B-6164-H***#H580 O O O O O
βiSVSP
A06B-6165-H***#H560 O O
α iM sensor O O O O
Sensor on the motor α iMZ sensor O
Spindle system
Sensor–less O O
configuration
Sensor on the spindle α i position coder O O *3
External one-rotation
O *3
(Proximity switch)
α iBZ sensor O *3
O
O O O
Rigid tapping O *2 O
*1 *10
*9
O
Orientation by a position coder O O O
*6
Orientation by the external O
*5
one-rotation signal *2
O O O
Function Velocity synchronization O O O *4
Spindle synchronization *2 *2 *2
O
O
Phase synchronization O *2 O O *4
*6
*7
O
Threading O O O
*6
O O
Cs contour control O
*6 *8
*1 Connect spindle and motor directly or with timing belt or gear. Reference position return is
not be available to adjust the tapping start position.
*2 Connect spindle and motor directly or with timing belt or gear.
*3 Connect spindle and sensor with 1:1.
*4 Two pairs of motors and amplifiers are required.
*5 Note that the stop position may move by a backlash between spindle and motor.
*6 Connect spindle and motor with 1:1 by direct connection or timing belt or gear.
*7 Command orientation and detect one-rotation signal (PC1DT=1) before applying spindle
synchronization command
*8 The resolution of position detection is 4096 p/rev.
*9 In case of performing reference position return to adjust the tapping start position,
command orientation and detect one-rotation signal (PC1DT=1) before applying rigid
tapping.
NO. B-65322EN/02-07
Other functions
#H580 #H560 Remarks
Analog output of load meter
O Connector JY1
and speed meter
Analog output of either load
O Connector JY1
meter or speed meter
Analog override input O O Connector JY1
NO. B-65322EN/02-07
In case of using this function, please add an uninterruptible power supply (UPS) etc. to be able to maintain
the control source (DC 24V) of CNC and amplifier after a power failure occurs until mechanical brake
operates.
[Specification]
Connector “CX36” output power failure detect signal in case of power failure.
Detect the drop of three-phase AC input voltage of connector “CX38”.
CX38 input voltage range: 0 V-AC240V+10% 3F 50Hz/60Hz±2Hz
Detect delay time is set so that it may not react sensitively to instantaneous power failure.
Detection delay time: 8msec~17msec
(Note)
DC link voltage
Low voltage alarm
Of DC link
Alarm occurred
NO. B-65322EN/02-07
Power failure
Output of PMC
Close Open
a. Power failure detection delay time: The time from detecting the power failure till power failure
detection signal is output from βiSVSP (8msec ~ 17msec)
b. PMC delay time: The time from DI operating till DO operating of PMC (15msec)
c. Reset time of relay: The time from cutting off the rated voltage supplied to the coil of the relay
till the contact of the relay is turned off (“a contact ” is opened)
d. Response time of brake: The time from cutting off the rated voltage supplied to the coil of the
brake till the brake becomes effective
e. Operate time of brake: The time from occurring the power failure till the brake becomes
effective
NO. B-65322EN/02-07
Condition
(1) Power failure detection delay time --- 10msec
(2) PMC delay time---15msec
(3) Relay: G2R type made by OMRON --- Reset time of relay is 20msec
(4) Brake: Built-in brake for ? iS8 motor --- Response time of brake is 30msec
Result
10msec + 15msec + 20msec + 30msec = 75msec
NO. B-65322EN/02-07
NO. B-65322EN/02-07
Panel cuts when FANUC fan unit (A06B-6134-K001) is used and when not used are shown
below. A fan unit can be placed either on top of or below the servo amplifier.
NOTE
1. Attach the accompanying gasket around the panel cutout to
prevent oil and dust from getting into it.
2. Reinforce the right and left sides of the panel cutout in the
power magnetic cabinet by using fittings such as angles to
maintain satisfactory contact between the power magnetic
cabinet and the amplifier.
3. Placing a FANUC fan unit on top of the servo amplifier
requires installing a duct. Refer to the “Example Duct
Structure for Using a FANUC Fan Unit (A06B-6134-K001)”
for descriptions about the structure of the duct.
4. Placing a FANUC fan unit below the servo amplifier does not
require installing a duct. If no FANUC fan unit is used, the
user is requested to install a fan motor that can generate
airflow of at least 2 m/s at the heat sink.
(1) When no FANUC fan unit (2) When one FANUC fan unit is used (3) When two FANUC fan units are used
is used (placed on top of the servo (placed on top of the servo amplifier)
amplifier)
7.5
131 131
60
75
20
60
75
20
2 2
10 10
11
11
11
4-M4 4-M4
338
360
338
360
338
360
24 6 246 246
NO. B-65322EN/02-07
11
11
338
360
338
360
246 246
7.5
10 10
20
6-M5
20
6-M5
16
60
75
60
75
2 2
4-M4 4-M4
131 131 131
7.5
12
NO. B-65322EN/02-07
(Note)
50 mm
26 0 mm 172 mm 92.5 mm
50 mm
380 mm
50 mm
(NOTE) When a right-angle type cable
connector is used (+30 mm when a
straight type cable connector is used)
NO. B-65322EN/02-07
(Note)
50 mm
130 mm 130 m m
380 mm 380 m m
50 mm 50 m m
NO. B-65322EN/02-07
50 mm 50 mm
380 mm 380 mm
130 mm 130 mm
(Note) 50 mm
NO. B-65322EN/02-07
Shown below is an example duct structure where a FANUC fan unit (A06B-6134-K001) is
used.
NOTE
1 Install a duct having the shape shown below between the fan unit and
heat sink to provide a ventilation flue.
2 Weld the duct to the cabinet.
3 If the fan unit is placed below the servo amplifier, no duct is needed.
102
64.5
102
230
70.5
64.5
NO. B-65322EN/02-07
AC200V IN
Applicable wire 1.25mm2
2
Applicable crimp terminal 1.25-4
NO. B-65322EN/02-07
K72
Fan unit Fan unit
CXA2 K74
COP10B
CNC K27 (FSSB I/F) JYA4 K103 α iBZ sensor
COP10A
K75 (FSSB I/F)
CZ2L CZ2M CZ2N TB1 TB3
TB2 Flange
K10 K21 K21 K21 K1
200-240VAC
K70 K70
JF3
Circuit breaker 1 Magnetic contactor AC reactor
NOTE
1 Always install the circuit breakers, magnetic contactor, and AC reactor.
2 To protect the equipment from lightning surge voltages, install a lightning
surge absorber across each pair of power lines and across each power
line and the grounding line at the power inlet of the power magnetic
cabinet.
3 Be sure to connect the grounding terminal (G) on TB2 to a substantial
ground.
NO. B-65322EN/02-07
WARNING
Do not touch any component in the module or any connected
cable when item24 ”DC LINK charge LED” is on, because it is
dangerous.
NO. B-65322EN/02-07
The cable K22 is used to connect the SVPM and Pulse coder of βiS servo motor.
(7) 6V (4)
5V, 0V, 6V Wire construction 12/0.18 or 60/0.08 Wire construction 20/0.18 or 104/0.08
Insulation outer diameter φ0.8 to φ1.5 Insulation outer diameter φ0.8 to φ1.5
2
0.18mm or more 0.18mm2 or more
RD, *RD Twisted-pair wire Twisted-pair wire
Insulation outer diameter φ0.8 to φ1.5 Insulation outer diameter φ0.8 to φ1.5
Drain wire 0.15mm 2 or more 0.15mm2 or more
See Subsection 5.4.1 for explanations about the SVPM-side connector that matches the
recommended cable.
NO. B-65322EN/02-07
Soldering or crimping
Connector
The total resistance (Round The total resistance (Round
trip) of 5 V and 0 V must be trip) of 5 V and 0 V must be
less than 2 Ω. less than 2Ω .
• Recommended cable
A66L-0001-0460: Flexible cable 28m or less long
A66L-0001-0462: Flexible cable 50m or less long
A66L-0001-0481: Fixed cable 28m or less long
A66L-0001-0491: Fixed cable 50m or less long
NO. B-65322EN/02-07
For separated
power supply 5V
connection 0V
i
β SV Shield Linear scale
(1) SD
(2) *SD
(5) REQ
(6) *REQ
(9, 20) 5V
(12, 14)0V
(7) 6V
Drain wire
(16) 0V
NO. B-65322EN/02-07
2.Power to CNC
(Note)
When the following power-on timing condition is satisfied, the power to βiSVSP and linear
scale assume to be turned on simultaneously when the power to CNC is turned on.
On
Power to CNC
Off
t1 t2
On
Power to BiSV and linear scale Off
t1: 200ms
Means that the power to βiSVSP and linear scale is turned on within 200 ms
before the power to CNC is turned on.
t2: 500ms
Means that the power to βiSVSP and linear scale is turned on within 500 ms
after the power to CNC is turned on.
(Note)
When the following power-off timing condition is satisfied, the power to BiSV and linear scale is
assumed to be turned off simultaneously when the power to CNC is turned off.
On
Power to CNC
Off
t1
On
Power to BiSV and linear scale Off
t1: 500ms
Means that the power to BiSV and linear scale is turned off within 500 ms before the power to CNC
is turned off.
NO. B-65322EN/02-07
power supply
NOTE
The maximum current of contact for “K73, K74” is 4.0A.
NO. B-65322EN/02-07
NO. B-65322EN/02-07
NO. B-65322EN/02-07
24V
CX36
βiSVSP 2
Output signal of power failure detect
Normally ON *ESP
At power failure OFF 3
24V
PMC
DI DO
*ESP
Relay for drive brake
0V
Brake coil
NO. B-65322EN/02-07
(1) In case of α iBZ sensor (Current type A860-2120-T***) and α iBZ sensor (small type
A860-2155-T***)
JYA4
βi SVSP Shield
(5) MA VA (5) CN1
(6) *MA *VA (2)
(7) MB VB (6)
(8) *MB *VB (3)
(10) SS SS (5)
Cable specification:
Shielded cable with 4 pieces of 0.18mm2 twisted pairs and 4 pieces of 0.18mm2 wire
Recommended cable conductor: A66L-0001-0367
NOTE
If only one 5 V line and only one 0 V line are used, use pins 20 and
16 for them, so that, if the connector is attached the wrong way, the
sensor can be prevented from being damaged.
NO. B-65322EN/02-07
1 *VZ 4
2 *VA 5 VA
3 *VB 6 VB
Pin assignment of the connector CN2 (manufactured by Honda Tsushin Kogyo Co., Ltd.) on
the motor side
1 5V 4 5V
2 VZ 5 SS
3 0V 6 0V
(*) In case of aiBZ sensor (A860-2155-T***) pin numbers (1) and (3) are non-connection.
NO. B-65322EN/02-07
βi SVSP ( 5) ( 1)
PA VA αi BZ sensor
( 6) A860-2150-T***
*PA *VA ( 2)
JYA4
( 7) PB VB ( 5)
( 8) *PB *VB ( 6)
( 1) MZ VZ ( 8)
( 2) *MZ *VZ ( 9)
* (14), (16) 0V 0V ( 7)
(10) SS SS ( 3)
NO. B-65322EN/02-07
1 VA
2 *VA
3 SS
4 5V
5 VB
6 *VB
7 0V
8 VZ
9 *VZ
10
NO. B-65322EN/02-07
The amount of heat generated in an SVSP series depending on its model, the current flowing
through the motor, and the motor output. (Refer to the respective motor description manuals
for the current and output of each motor.)
The total amount of heat dissipation by the SVSP is calculated according to the following
expression:
NO. B-65322EN/02-07
AC reactor
NO. B-65322EN/02-07
By placing the heat sink section of the SVSP outside the cabinet, the residual amount of heat
in the cabinet can be calculated according to the expression below.
Ka1 2.1
A06B-6164-H201#H580 Ka2 0.9
βiSVSP20/20-7.5 48
A06B-6165-H201#H560 Ka3 0.8
Ka4 0.8
Ka1 2.1
Ka4 0.8
Ka1 1.3
Ka4 0.5
NO. B-65322EN/02-07
Ka1 2.1
A06B-6164-H311#H580 Ka2 0.9
βiSVSP 20/20/40-7.5 A06B-6165-H311#H560 48 Ka3 0.8
Ka4 0.8
Ka5 0.7
Ka1 2.1
Ka2 0.8
A06B-6164-H312#H580
βiSVSP 20/20/40-11 48 Ka3 0.8
A06B-6165-H312#H560
Ka4 0.8
Ka5 0.7
Ka1 1.3
Ka2 0.6
A06B-6164-H333#H580
βiSVSP 40/40/40-15 48 Ka3 0.5
A06B-6165-H333#H560
Ka4 0.5
Ka5 0.5
Ka1 1.3
Ka2 0.6
A06B-6164-H343#H580
βiSVSP 40/40/80-15 48 Ka3 0.5
A06B-6165-H343#H560
Ka4 0.5
Ka5 0.5
7. Detectors
NO. B-65322EN/02-07
2. Summary of Change
Group Name / Outline New, Add Applicable
Correct, Del Date
Basic Function Addition of βiSV 40/40 New 2009. 7
Optional
Function
Unit
Maintenance
Parts
Notice
Correction
Another
DRAW.
No. B-65322EN/02-10
01 09.07.29 K.Inaba Add newly
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 1 / 17
This is 2-axis βiSV for Series 0i/0i Mate.
This document describes only changed or added specifications from current model.
Therefore please refer the specifications which are not described in this document to FANUC SERVO
AMPLIFIER βi series DESCRIPTIONS B-65322EN.
A. Parameter setting
Setting for Series 0i/ 0i Mate-MODEL C mode is necessary. In case of combination with Series 0i/ 0i Mate-MODEL D,
please set following parameter.
14476#0=1 Series 0i / 0 i Mate-MODEL C mode
Power off/ on
(Note)
The maximum connectable number per 1 FSSB line is as follows.
- Up to 4 axes is connectable in case of servo control (HRV3).
- Up to 8 axes is connectable in case of servo control (HRV2).
B. DYNAMIC BRAKE
In case of using L axis and M axis of βiSV40/40, the distance of dynamic brake becomes long as compared with other
model (βiSV40). Please use the following coefficients for calculation of the distance of dynamic brake in the case of
using L axis and M axis of βiSV40/40. Please refer to FANUC AC SERVO MOTOR αi series DESCRIPTION
B-65262JA/05 about the details of calculation.
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 2 / 17
1. Ordering number
Model Orderin number
βiSV 40/40 A06B-6136-H203
2. Configuration
βiSV20/20
βiSV40/40
TB
FUSE
24V power supply for amplifier Battery
Optical cable
CNC
COP10B COP10A
3 phase
200V to 240VAC
Magnetic AC line
Breaker CZ4
contactor filter
Magnetic contactor
CXA20 JF1
Separated regenerative
CZ5M
CAUTION
1 A circuit breakers, magnetic contactor, and AC line filter
are always required.
2 Use the stabilized 24VDC power supply for the amplifier.
24VDC power supply for the amplifier and 24VDC power
supply for the motor brake cannot be shared.
24V power supply
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 3 / 17
3. Specification
Item βi SV 40/40
Interface FSSB
Unit Designation A06B-6136-H203
Power P.C.B. A16B-3200-0643
Control P.C.B. A20B-2101-0290
Input Voltage AC 200-240 V (+10%,-15%) 50 / 60 Hz
Main Power For
Current at 50Hz 13Arms
Three Phase Supply
Rated Capacity 4.8kVA
Control Input Voltage DC 24 V (+10%, -10%)
Power supply Input Current 0.8 A
L-Axis 13Arms
Rated Output Current
M-Axis 13Arms
L-Axis 40 Ap
Current Limit Value
M-Axis 40 Ap
Servo control HRV2, HRV3
Main Circuit Control Method Sine Wave PWM Control with Transistor Bridges
Servo output frequency range 400Hz
- High Current
- IPM Abnormal
- High Voltage of DC Link
- Low Voltage of DC Link
- Overheat of Discharge Resistor
Warning and protectivefunctions
- Low Voltage of Control Power Supply
- FSSB Communication Error
- Locked Fan Motor
- FSSB Communication Error
- Locked Fan Motor
Ambient Temperature Range 0 to +55 degrees Celsius
Weight 3.0kg
Regererative resistor
(16ohm, 100W no-wind condition)
(16ohm, 200W no-wind condition)
Option (16ohm, 400W wind velocity 2m/s condition)
Separated AC line filter
Separated battery
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 4 / 17
4. Applicable motors
Torque(Nm) 4 8 12 22
αi F4 αi F8
/4000 /3000 − −
Motor αi F (40A) (40A)
βi S12 βi S22
− − /3000 /2000
βi S (40A) (40A)
Please refer to the following table and select it. For details, please refer to B-65322/02EN.
6. Derating
Consider derating as shown below, according to ambient temperature.
The solid line is derating line for HRV2 and the dotted line is derating line for HRV3.
100%
80%
Percantage of
Rated Output Current
60%
40%
20%
0%
0 10 20 30 40 50 60 C
Ambient temperature
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 5 / 17
7. Regeneration discharge resistor
7.1. The condition of unnecessary of regenerative discharge resistor
When the regeneration energy per regenerative cycle is below the following amounts of energy [J], regeneration
discharge resistor is unnecessary.
Refer to Section [I. SVM ] of B-65322EN/02 for details about calculation method of the regeneration energy per
regenerative cycle.
Cautions
In case of “A06B-6130-H404”, please install into the cabinet, which fulfills IP54.
And in case of “A06B-6089-H500”, please install into duct area, which fulfills IP22 or IP23.
If the cabinet does not have a structure for preventing materials that adversely affect regenerative
discharge resistor from gettinng into the cabinet, normal operation and safety may fail. So, special care
should be taken.
Incorrect connection may cause to damage the amplifier.
ON
1
2
3
4
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 6 / 17
9. Power supply specification
9.1. Three-phase input power supply for motor power
- Nominal rating voltage: AC 200-240V
- Allowable voltage fluctuation: +10%, -15%
- Frequency: 50/60Hz
- Allowable frequency fluctuation: ±2Hz
- Power supply impedance : Voltage fluctuation by load (at maximum
output) not be exceed 7%.
- Power supply Unbalance: ±5% or less of rated voltage
NOTE
The allowable voltage fluctuation is not continuous
change but change for several minutes.
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 7 / 17
10. External dimention/ Panel cut-out drawing/ maintenance area
10.1. External dimension
βiSV 40/40
Without outerfin
90 172
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 8 / 17
External dimension regenerative discharge resistor (A06B-6130-H404)
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 9 / 17
10.2. Panel cut-out drawing
βiSV40/40,
360
2-M5
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 10 / 17
10.3. Maintenance area
βiSV 40/40
AIR FLOW
50mm
50mm
90mm
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 11 / 17
11. Total connection diagram
βiSV40/40
TB
FUSE
24V power supply for amplifier K9 Battery
K11
(Stabilized power supply) CXA19B CXA19A case
Optical cable
CNC
COP10B COP10A
3 phase
200V to 240VAC
Magnetic AC line K2
Breaker CZ4
contactor filter
K7
CX29
5A circuit
Emergency JX5
breaker K8 CX30
stop switch
K4 JF1
CXA20
Separated regenerative
K5
discharge resistor JF2
CX36
Lighting
Power failure signal K12
surge absorber CX5X
CZ5L
CZ5M
K3
K1
CAUTION
1 A circuit breakers, magnetic contactor, and AC line filter
K3 K1
are always required.
2 Use the stabilized 24VDC power supply for the amplifier.
24VDC power supply for the amplifier and 24VDC power
supply for the motor brake cannot be shared.
3 The cabling of CX29 and CX30 of the second and
subsequent amplifiers may be omitted. For details, see
"TOTAL CONNECTION DIAGRAM". 24V powersupply
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 12 / 17
11.1. Connection details
Please select specification of cables in consideration of following table. Refer to Section [ I .SVM ] of
B-65322EN/02 for details.
Please select specification of cables in consideration of following table. Refer to Section [ I.SVM ] of
B-65322EN/02 for details.
Servo motor Continuous rating current
[Arms]
(Reference value)
βis12/3000 10.2
βis22/2000 11.3
αiF4/4000 7.7
αiF8/3000 8.4
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 13 / 17
11.4. Details of cable K4 (Refer to B-65322/02EN)
In case of using regenerative discharge resistor
(a) A06B-6130-H404
β iSV 40/40
Regenerative
discharge resistor
TB
DCP
DCP DCP
Resistor
CXA20
1 TH1
2 TH2
Thermostat
D-2000 series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire: 0.30 to 0.85mm2
Manufacture: Tyco Electronics AMP
WARNING
Do not short between terminal “DCP” and terminal “DCC”.
Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of servo amplifier αi
series. Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 14 / 17
(b) A06B-6089-H500
Cable specification:
Two-conductor polyvinyl heavy-duty power cable
JIS C 3312
DCC
DCC DCC
Resistor
Cable specification:
CXA20
1 TH1
2
TH2
Thermostat
D-2000series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire: 0.3mm2 to 0.85mm2
WARNING
Do not short between terminal “DCP” and terminal “DCC”.
Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of servo amplifier αi
series. Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 15 / 17
(c) In case of not using regenerative discharge resistor
βiSV 40/40
TB
DCP
Keep these pins unconnected.
(Do not install a jumper between pins.)
DCC
CXA20
Install jumper between pins.
1
D-2000 series
Housing: 1-1318120-3
Contact: 1318107-1
Applicable wire 0.30 to 0.85mm2
Manufacture: Tyco Electronics AMP
WARNING
Do not short between terminal “DCP” and terminal “DCC”.
Do not connect this terminal “TB” to terminal “TB1(DCP/DCN)” of servo amplifier αi
series. Servo amplifier may be broken in case of above incorrect connection.
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 16 / 17
12. Heat disspaton
The amount of heat dissipation depends on the current that flows through servo motor. For the current that flows
through a servo motor, reference the continuous rated current of each servo motor. (For the continuous rated
current of each servo motor, refer to the servo motor descriptions.) As the current that flows through a servo
motor, the root-mean-square value of the current that flows through an actual servo motor on a machine can be
used. The amount of heat dissipation indicated below assumes the use of HRV2.
L Ka1: 5.8
βiSV40/40 H203 20
M Ka2: 5.8
L Kb1: 5.8
βiSV40/40 H203 20
M Kb2: 5.8
DRAW.
No. B-65322EN/02-10
EDIT DATE DESIGN DESCRIPTION FANUC LTD Page 17 / 17