Instruction Manual FS5
Instruction Manual FS5
TYPE 566M
Capacitor 2 µF
Fig. 1
1 – Air-damper
2 – Screws for fixing the air-damper
3 – 7 pole socket for electrical supply 7
and control 1
4 – 6 pole socket for gas train
5 – Grommet 6 2
5 4 3 D4064
NOTES
– The grommet (5) supplied with the burner, must be fitted to the same side of the gas train.
– After having installed the burner verify the access to the fixing screws of the cover.
If necessary replace them with the fixing screws (6) fig. 1 supplied as equipment.
2654
1
OVERALL DIMENSIONS
Flange Burner
ø 91
°
Rp 1/2
233
140
138
180
10
130 28 48
BURNER EQUIPMENT
Quantity Description
4 Screws with nuts
1 Insulating gasket
3 Screws for fixing the cover
1 Grommet
1 Hinge
1 7 pin plug
1 3 2
S7392
D5067
A B
2654
2
WORKING RANGE
Pressure in the combustion
1.0
chamber – mbar
0.8
0.6
0.4
0.2
0
20 30 40 50 60 kW
TEST BOILER
The working field has been defined according to DIN 4788 and EN 676 standards.
COMMERCIAL BOILERS
The burner-boiler matching is assured if the boiler is according to EN 303 and the combustion
chamber dimensions are similar to those shown in the diagram EN 676.
For applications where the boiler is not according to EN 303, or where the combustion chamber
dimensions differ from those shown in EN 676, please consult the manufacturers.
5
Gas pressure
4
mbar
1
20 30 40 50 60 kW
2654
3
LINE OF GAS-SUPPLY
1 2 3 M1 4 5 6 7 8 MBC 65 DLE
6 8 7
D5069 D7279
The gas train is supplied separately, for its adjustment see the enclosed instructions.
POSITIONING ELECTRODE-PROBE
Put the ceramic Ionization
near the diffuser disc probe Diffuser Ignition electrode
Probe
2 Electrode
D5033
IMPORTANT
Do not turn the starting electrode but leave it as shown in the drawing; if the starting electrode is
put near the ionization probe, the amplifier of the control box might be damaged.
2654
4
BURNER ELECTRICAL WIRING
(carried out in the factory)
Connector
CONTROL BOX
Brown
Capacitor
White
Blue
Motor
Black
Air pressure
switch
Suppressor
D4065
2654
5
ELECTRICAL WIRING
(to be carried-out by the installer)
B4 S3 T2 T1 N L1 3 2 1 N Ph
TS
h
6A
T
Black Grey
ADJUST.
1 2 3 1 2 3
N L PE P
VS V1
230V ~ 50Hz GAS
D5127
NOTES
– Do not exchange the neutral with the phase and connect exactly the above wiring.
– Wire of 1 mm2 section.
– Carry out a safe earth connection.
– Verify that the burner stops by operating the boiler control thermostats and that the burner goes
lock out by separating the red ionisation probe lead connector.
– The electric wiring carried out by the installer must be in compliance with the rules in force in
the Country.
2654
6
BURNER START-UP CYCLE
Normal Lock-out, due to light-failure
Thermostat
Motor
Ignition transformer
Valves
Flame
Lock-out
D5048
When flame-failure occurs during working, shut down takes place within one second; and the
cycle starts again; a lock-out follows if the flame do not start.
COMBUSTION-HEAD ADJUSTMENT
Loose the screw (A), move the elbow (B) so that the
rear plan of the coupling (C) coincides with the set
point. Tight the screw (A).
C
Example:
B S7015
The burner is installed on a 40 kW boiler with an effi-
ciency of 90%, the burner input is about 44 kW using
the diagram below, the combustion set point is 3.
kcal/h kW
60,000 70
50,000 60
50
40,000
44
40
30,000
30
20,000
20
10,000 10
0 1 2 3 4 5 Set point D5068
The diagram is to be used only for initial settings, to improve air pressure switch operation or
improve combustion, it may be necessary to reduce this setting (set point toward position 0).
2654
7
COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler,
adjustment and testing must be carried out observing the instruction manual of the boiler, includ-
ing verification of the CO and CO2 concentration in the flue gases, their temperatures and the
average temperature of the water in the boiler.
It is advisable to set the burner according to the type of gas used and following the indications of the
table:
IONIZATION CURRENT
The minimum current required by the control box is 5 µA.
The burner would normally have a higher current value than this, but if a check is required, open
the connector fitted in the red probe lead and insert a microammeter as shown.
Connector
D5049
2654
8
BURNER STARTING DIFFICULTIES AND THEIR CAUSES
DIFFICULTIES CAUSES
The valves are passing too little gas (low pressure in the gas pipe-
work).
The burner goes to lock- The valves are defective.
out, after the pre-purge
period, because the flame It is irregular or the ignition arc is not present; in this case remove
does not ignite. the control box and insert it again, taking care that the electrode
push-rod is in the proper seat.
The burner does not pass The air pressure switch does not change over: it has failed or the air
through the pre-purge pe- pressure is too low (combustion head bad set).
riod and the control box
goes to lock-out. Flame simulation exists (or the flame really lights).
The gas pressure switch does not close its contact due to incorrect
setting or a faulty switch.
The burner does not start
at the thermostat closing. The air pressure switch is changed over to the operational position.
Before to replace the control box, check that short-circuits are not
present on the power-line: of the motor, of the gas electrovalve/s
and on the external signaling devices.
OPERATING FAULTS
Re-cycle and lock-out may occur, because of : – Flame failure
– Ionization probe earthed
The burner goes to lock-out because of . . . . : – Opening of the air pressure switch
2654
9
WARNINGS TO AVOID BURNOUT OR BAD COMBUSTION OF
THE BURNER
1 – When the burner is stopped, the smoke pipe must be opened and effect a natural
draught in the combustion chamber. If the smoke pipe is closed, the burner must be
drawn back till the extraction of blast tube from the furnace. Before operating in this
way take the voltage off.
2 – The place, where the burner works, must have same openings suitable for the passage
of air necessary for combustion. To be sure about this, you have to control CO2 and
CO in the exhaust gases with all the windows and doors closed.
3 – If in the place, where the burner works, there are air-breathings, check the existence
of air-input openings with dimensions suitable for the necessary air-exchange. In any
case check that, when the burner is stopped, the air-breathings do not draw warm
smokes from pipes through the burner.
2654
10