Wind Load Calculation Sheet

The document provides details for calculating wind load on an enclosed building structure with dimensions of 80m length, 51.7m width, and 12m height. It includes the basic wind speed, terrain category, roof slope, and external pressure coefficients for the windward and leeward sides of the roof and frames to determine the design wind pressure and load on each surface.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views6 pages

Wind Load Calculation Sheet

The document provides details for calculating wind load on an enclosed building structure with dimensions of 80m length, 51.7m width, and 12m height. It includes the basic wind speed, terrain category, roof slope, and external pressure coefficients for the windward and leeward sides of the roof and frames to determine the design wind pressure and load on each surface.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

WIND LOAD CALCULATION SHEET-(ENCLOSED)

LENGTH (L) = 80 m Basic Wind speed,Vb= 44 m/s


WIDTH(W) = 51.7 m Terrian Category = 2
HEIGHT(H) = 12 m Bay Spacing(sidewall) = 7.938 End = 6.514
SLOPE = 1 10 Enclosed Condition 0.2 -0.2

Calculation for wind pressure :


k1 = 1.00 General building, As per Table-1 of IS-875-Part-3
k2 = 1.020 For Terrian category 2 as per Table 2, Clause: 6.3.2.1-b
k3 = 1.00 Upwind slope is less than 3 degree
k4 = 1.15 for Cyclonic Region
Vz = k1xk2xK3xK4XVb = 51.612 m/s
wind pressure Pz = 0.6Vz^2 = 1598.28 N/m2 = 1.60 kN/m2
Kd = 0.9 (Directionality factor)
Ka = 0.8 (Area Averaging factor)
Kc = 0.9 (Combination factor for pressure & Suction)
Design wind pressure Pd
KdxKaxKcxPz = 1.04 kN/m2

H/W = 0.23 h/w≤0.5


L/W = 1.55 1.5<l/w≤4

Wind load on frame


CASE-1- WIND ACROSS THE RIDGE(ZERO DEGREE) Positive Cpi
SURFACE Cpe Cpi Cpe-Cpi Wind load on frame
A 0.70 0.2 0.50 0.5x1.04x7.938= 4.13
EF -0.95 0.2 -1.15 -1.15x1.04x7.938= -9.49
GH -0.40 0.2 -0.60 -0.6x1.04x7.938= -4.95
B -0.25 0.2 -0.45 -0.45x1.04x7.938= -3.71
C -0.60 0.2 -0.80 -0.8x-0.2x6.514= -5.42
D -0.60 0.2 -0.80 -0.8x-0.2x6.514= -5.42
CASE-2- WIND ACROSS THE RIDGE(ZERO DEGREE) Negative Cpi
SURFACE Cpe Cpi Cpe-Cpi Wind load on frame
A 0.70 -0.2 0.9 0.9x1.04x7.938= 7.43
EF -0.95 -0.2 -0.75 -0.75x1.04x7.938= -6.19
GH -0.40 -0.2 -0.2 -0.2x1.04x7.938= -1.65
B -0.25 -0.2 -0.05 -0.05x1.04x7.938= -0.41
C -0.60 -0.2 -0.4 -0.4x-0.2x6.514= -2.71
D -0.60 -0.2 -0.4 -0.4x-0.2x6.514= -2.71

CASE-3- WIND PARALLEL TO RIDGE(90 DEGREE) WITH Posative Cpi


SURFACE Cpe Cpi Cpe-Cpi Wind load on frame
A -0.50 0.2 -0.7 -0.7x1.04x7.938= -5.78
EF -0.80 0.2 -1 -1x1.04x7.938= -8.26
GH -0.80 0.2 -1 -1x1.04x7.938= -8.26
B -0.50 0.2 -0.7 -0.7x1.04x7.938= -5.78
C 0.70 0.2 0.5 0.5x-0.2x6.514= 3.39
D -0.10 0.2 -0.3 -0.3x-0.2x6.514= -2.03
CASE-4- WIND PARALLEL TO RIDGE(90 DEGREE) WITH Negative Cpi
SURFACE Cpe Cpi Cpe-Cpi Wind load on frame
A -0.50 -0.2 -0.3 -0.3x1.04x7.938= -2.48
EF -0.80 -0.2 -0.6 -0.6x1.04x7.938= -4.95
GH -0.80 -0.2 -0.6 -0.6x1.04x7.938= -4.95
B -0.50 -0.2 -0.3 -0.3x1.04x7.938= -2.48
C 0.70 -0.2 0.9 0.9x-0.2x6.514= 6.10
D -0.10 -0.2 0.1 0.1x-0.2x6.514= 0.68
CALCULATION OF EXTERNAL PRESSURE COEEFFICIENT ON PITCH
(AS PER IS-875 1987:PART 3 ;REAFFIRMED 2003)

α= 5.71

w (in meters) = 51.7

h/w = 0.2
ROOF ANGLE WIND ANGLE = 0 deg.
α E F G H
5.71 -0.943 -0.943 -0.400 -0.400

EXTERNAL PRESSURE COEEFFICIENT ON PITCHED R


NOTE:
when wind acts in lateral direction of frame ( i.e 0 deg wind angle)
*E & F falls on windward side & has same co-efficients
*G & H falls on leeward side & has same co-efficients

when wind acts in longitudinal direction of frame ( i.e 90 deg wind angle)
*E & G has same coefficients
*F & H has same co-efficients

the coefficients are assumed to act outwards i.e suction pressure


(as mentioned in clause 6.2.2.2 of IS 875)

co-efficients for the local effects are not used for calculating

force on structural elements(as mentioned in clause 6.2 of IS 875)

LINEAR INTERPOLATION USING EXCEL

=FORECAST(NewX,OFFSET(KnownY,MATCH(NewX,KnownX,1)-1,0,2),
OFFSET(KnownX,MATCH(NewX,KnownX,1)-1,0,2))
SURE COEEFFICIENT ON PITCHED ROOFS
987:PART 3 ;REAFFIRMED 2003)

h (in meters) = 12

WIND ANGLE = 90 deg.


E F G H
-0.800 -0.429 -0.800 -0.429

COEEFFICIENT ON PITCHED ROOFS (AS PER TABLE 65 OF IS-875:PART 3)

ROOF WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


ANGLE(α) E F G H E F G H
0 -0.8 -0.8 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
5 -0.9 -0.9 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
10 -1.2 -1.2 -0.4 -0.4 -0.8 -0.6 -0.8 -0.6 FOR H/W <= 1/2
20 -0.4 -0.4 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
30 0 0 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
45 0.3 0.3 -0.5 -0.5 -0.7 -0.6 -0.7 -0.6
60 0.7 0.7 -0.6 -0.6 -0.7 -0.6 -0.7 -0.6
5.71 -0.943 -0.943 -0.400 -0.400 -0.800 -0.429 -0.800 -0.429

ROOF ANGL WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


α E F G H E F G H
0 -0.8 -0.8 -0.6 -0.6 -1.0 -0.6 -1.0 -0.6
5 -0.9 -0.9 -0.6 -0.6 -0.9 -0.6 -0.9 -0.6
10 -1.1 -1.1 -0.6 -0.6 -0.8 -0.6 -0.8 -0.6
20 -0.7 -0.7 -0.5 -0.5 -0.8 -0.6 -0.8 -0.6 1/2 < H/W <= 3/2
30 -0.2 -0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
45 0.2 0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
60 0.6 0.6 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
5.71 -0.929 -0.929 -0.600 -0.600 -0.886 -0.600 -0.886 -0.600

ROOF ANGL WIND ANGLE = 0 deg. WIND ANGLE = 90 deg


α E F G H E F G H
0 -0.7 -0.7 -0.6 -0.6 -0.9 -0.7 -0.9 -0.7
5 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
10 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
20 -0.8 -0.8 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8 3/2 < H/W < 6
30 -1.0 -1.0 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
40 -0.2 -0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
50 0.2 0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
60 0.5 0.5 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
5.71 -0.700 -0.700 -0.600 -0.600 -0.800 -0.800 -0.800 -0.800