FA142C Program Manual
FA142C Program Manual
– 2–
FA142C PROGRAMMING FORM
Local programming requires the use of a 2-line Alpha keypad (e.g., FA550KP) .
To set all program fields to First Alert default values: Key ✱97.
Field Function Programmed Values [ ] = Default Value
SYSTEM SETUP (✱ 20- ✱27)
✱20 INSTALLER CODE Enter 4 digits, 0-9...[4] [1] [1] [1]
✱21 QUICK ARM ENABLE [0 = no]; 1 = yes
✱22 RF SYSTEM TYPE [0 = none]; 1 = 5700 (4281); 2 = 5800 (5881)
✱23 FORCED BYPASS FUNCTION [0 = none]; 1 = bypass open zones
2 = bypass open zones + (if in system) zones 17, 30, 31, 46, 47.
✱24 RF HOUSE ID CODE [0][0] MUST enter (01-31) for 5700 System. Enter also for 5827 or
5827BD Keypad.
✱25 WIRED EXPANSION/RELAY USED Ê [0 = none]; 1 = 4219; 2 = 4229; 3 = 4204
✱26 VOICE MODULE ACCESS CODE 1st digit: Enter 1Ð9; 2nd digit: Enter only #+11 for '✴', #+12 for '#'.
[0] in either position = disabled.
✱27 OUTPUT TO LONG RANGE RADIO ÊÊ ÊÊ[0 = no]; 1 = yes If yes selected, dialer reports to PRIMARY No. (field
ÊÊÊ ✴47) will also be sent via LRR. All dialer and LRR reports will be in Contact
ÊÊÊID format (overriding field ✴46 selection).
ZONE SOUNDS AND TIMING (✱ 28- ✱39)
✱28 SINGLE ALARM SOUNDING/ZONEÊ ÊÊ [0 = no]; 1 = yes
✱29 FIRE SOUNDER TIMEOUT [0 = fire sounder timeout]; 1 = no fire sounder timeout
✱30 ALARM BELL TIMEOUT 0 = none; [1= 4 min]; 2 = 8 min; 3 = 12 min; 4 = 16 min.
✱38 ENTRY DELAY 0 = 0 sec ; 1= 20 sec; [2 = 30 sec]; 3 = 45 sec; 4 = 60 sec; 5 = 90 sec
EXIT Delay = ENTRY Delay + 15 sec
✱39 AUDIBLE EXIT WARNING 0 = no; [1 = yes]
DIALER PROGRAMMING ( ✱40- ✱50) In fields ✴40, ✴ 41, ✴42, enter up to the number of digits shown. Do not fill unused spaces.
Enter 0-9; #+11 for ' ✴'; #+12 for '#'; #+13 for a pause.
✱40 PABX ACCESS CODE Enter up to 4 digits.
If fewer than 4 digits entered, exit by pressing ✴ (and press 41, if entering next field). To clear entries from field, press ✴ 40 ✴.
✱41 PRIMARY PHONE No. Enter up to 12 digits.
If fewer than 12 digits entered, exit by pressing ✴ (and press 42, if entering next field). To clear entries from field, press ✴41 ✴.
✱42 SECONDARY PHONE No. Enter up to 12 digits.
If fewer than 12 digits entered, exit by pressing ✴ (and press 43, if entering next field). To clear entries from field, press ✴42 ✴.
✱43 SUBSCRIBER ACCT No. Enter 0-9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; [#+15 for F]. Enter ✴ as 4th digit, if 3+1 dialer reporting is to be used.
If only 3 digits used, exit by pressing ✴(and press next field). To clear entries from field, press ✴43 ✴.
Examples: For Acct No. 1234 , enter: 1 2 3 4
For Acct No. B234, enter: #+11 2 3 4
For Acct No. 123, enter: 1 2 3 ✴
✱45 PHONE SYSTEM SELECT If Cent. Sta. IS NOT on a WATS line:[0 = Pulse Dial]; 1 = Tone Dial
If Cent. Sta. IS on a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
✱46 REPORT FORMAT Also see field ✴ 27.
Ê Entry of a number other than one [0 = 3+1, 4+1 ADEMCO L/S STANDARD] 6 or undefined = 4+2 ADEMCO EXPRESS
ÊÊÊspecified will give unpredictable 1 = 3+1, 4+1 RADIONICS STANDARD 7 = ADEMCO CONTACT ID REPORTING
ÊÊÊresults. 2 = 4+2 ADEMCO L/S STANDARD 8 = 3+1, 4+1 ADEMCO L/S EXPANDED
3 = 4+2 RADIONICS STANDARD 9 = 3+1, 4+1 RADIONICS EXPANDED
Duress 0 8 Ñ Ñ Ñ Ñ
Tamper 0 9 0 5 Ñ Ñ
–4–
I N TH E P R E V I O U S P A G E ' S Z O N E A S S I G N M E N T T A B L E :
Zn = ZONE NUMBER Zone Nos. are from 01 to 63, 95, 96. Some are pre-assigned.
With Field ✴25 set for auxiliary wired loops (4219 or 4229), use Zone Nos. 10Ð17 for loops A-H.
With Field ✴22 set for RF (5700 or 5800), use Zone Nos. 18-63 if 4219/4229 is ALSO used,
or 10-63 if 4219/4229 is NOT used.
ZT = ZONE TYPE 00 = Zone Not Used 05 = Trouble Day/Alarm 10 = Interior w/Delay DEFAULT VALUES
01 = Entry/Exit ÊÊÊÊÊÊÊÊÊNight 20 = ArmÐStay* Zn: 01 02 03 04 05
02 = Do not use 06 = 24 Hr Silent 21 = ArmÐAway* ZT: [01] [04] [03] [03] [09]
03 = Perimeter 07 = 24 Hr Audible 22 = Disarm* Zn: 06 07 95 96
04 = Interior Follower 08 = 24 Hr Aux 23 = No Alarm ZT: [07] [06] [00] [00]
09 = Fire ÊÊÊÊÊÊÊÊResponse
* Used for 5800 RF systems only
RC = ALARM REPORT CODE Two Hex Digits. For each Hex Digit, enter: 00Ð09 for 0Ð9,
10 for A, 11 for B, 12 for C, 13 for D, 14 for E, 15 for F.
If "00" is entered in the first pair of boxes, there will be no report for that zone.
For contact ID reporting, this is an enabling code only. Make any hex digit entry (other than "00") in the first
pair of boxes. The second pair of boxes will be ignored.
In = LOOP INPUT DEVICE HW: Hard Wire Enter 3 for RF: Supervised RF These are automatically
AW: Aux Wire (4219 or 4229) Enter 4 for UR: Unsupervised RF assigned, except "UR"
Enter 5 for BR: Button Type RF and "BR" for 5800 RF.
L = RF INPUT LOOP Used with 5800 RF Loop Input Devices.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT ✱74 LOW BAT RESTORE RPRT CODE
CODES (✴ 60-✴ 75):
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: ✱75
1-9, 0, B, C, D, E, or F. Enter "#+10" for 0, "#+11" for B, "#+12" for RF XMTR LO BAT RST RPRT CODEÊ
C, "#+13" for D, "#+14" for E, "#+15" for F. OUTPUT AND SYSTEM SETUP (✱ 80-✱ 92)
A "0" ( not "#+10") in the first box will disable a report.
✱80 OUTPUT RELAYS
A "0" ( not "#+10") in the second box will result in automatic Program only if Relays are to
advance to the next field when programming. ✱81 ZONE LISTS FOR be used. See next page.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st OUTPUT RELAYS
and 2nd digits) for 1-9, 0, or B-F, as described above. ✱82 CUSTOM ALPHA EDITING: (Also entered from field
A "0" ( not "#+10") in the second box will eliminate the expanded ✴56): See procedure in instructions.
message for that report.
✱83 SEQUENTIAL MODE (Used for enrolling transmitters in
A "0" ( not "#+10") in both boxes will disable the report.
a 5800 RF system after all other zone information has
With Ademco Contact ID Reporting: Enter any digit (other than been programmed.)
"0") in the first box, to enable zone to report (entries in the second
boxes will be ignored). ✱91 CUSTOM OPTION SELECTION (See field ✴ 98)
A "0" ( not "#+10") in the first box will disable the report. ÊÊ[0 = None selected] 4 = AAV (Audio 6 = Sounder Delay
Examples: For Code 3 (Single Digit), enter: 3 0 1 = Local Lockout Alarm Veri- + AAV
2 = Sounder Delay fication) 7 = Local Lockout
For Code 32 (Two Digits), enter: 3 2 3 = Local Lockout 5 = Local Lockout + Sounder Delay
+ Sounder Delay + AAV + AAV
For Code B2 (Hexadecimal) enter:
#+11 2
✱92 REPORTS PER ARMED PERIOD
SYSTEM STATUS REPORT CODES ( 60-✱ 68)
✱
[0 = 10 max total alarm + alarm restore], 1 = unlimited
✱60 TROUBLE REPORT CODE
DOWNLOAD INFO (✱ 94, ✱ 95)
✱61 BYPASS REPORT CODE ✱94 DOWNLOAD PHONE No.
✱62 AC LOSS REPORT CODE
✱63 LOW BATTERY REPORT CODE Enter up to 12 digits: 0-9; #+11 for ' ✴'; #+12 for '#'; #+13
for a pause. Do not fill unused spaces. If fewer than 12
✱64 TEST REPORT CODE digits entered, exit field by pressing ✴ (and press 95, if
entering next field).
✱65 OPEN/EXIT ALARM RPRT CODE / To clear entries from field, press ✴ 94 ✴.
2nd digit of OPEN REPORT is automatically sent as the user ✱95 RING DET COUNT FOR DOWNLOADING
number if expanded or 4+2 reporting is selected. [0=Disable Station Initiated Download]; 1Ð14 = number of
2nd digit of EXIT ALARM REPORT is automatically sent as rings (1-9, #+10=10, #+11=11, #+12=12, #+13 =13,
the 2nd digit of the zone alarm report code programmed in #+14=14); 15=answering machine defeat (#+15 =15)
✴56, if expanded or 4+2 reporting is selected. ✱96 INITIALIZES DOWNLOAD ID , SUBSCRIBER
✱66 AWAY/STAY CLOSE RPRT CODE / ACCOUNT No. FOR INITIAL DOWNLOAD:
2nd digit of any CLOSE REPORT is automatically sent as the No entry required.
user number, if expanded or 4+2 reporting is selected. ✱97 SETS ALL PROGRAM FIELDS TO DEFAULT
✱67 RF XMTR LOW BAT RPRT CODE VALUES: No entry required.
✱68 CANCEL REPORT CODE TO EXIT PROGRAM MODE (✱ 98 or ✱ 99)
RESTORE REPORT CODES (✱ 70-✱ 75) Press ✴98 or ✴ 99 if exiting programming, or next field
number if continuing.
✱70 ALARM RESTORE RPRT CODE
✱98 EXITS PROGRAMMING MODE and prevents
2nd digit is automatically sent as the 2nd digit of the
zone alarm report code programmed in ✴56, if re-entry by (or, if Local Lockout has been chosen
expanded or 4+2 re porting is selected. in field ✴91, allows re-entry only by):
✱71 TROUBLE RESTORE RPRT CODE Master Code + Code + 0.
✱99 EXITS PROGRAMMING MODE and allows
✱72 BYPASS RESTORE RPRT CODE
re-entry by: Master Code + Code + 0
✱73 AC RESTORE RPRT CODE or by: Power-up + ✴ + #.
–5–
OUTPUT RELAYS WORKSHEET FOR FIELDS ✱80, and ✱81.
Applicable only if relays are to be used.
Fill in required data and follow detailed programming procedure described for Output Relays in the
Installation Instructions.
✱80 OUTPUT RELAYS
Notes: 1. Field ✴25 must be programmed for a 4229 (Relays 01 and 02) or a 4204 (Relays 01 to 04).
2. If an AAV (Audio Alarm Verification) option is selected in field ✴91,
Relay 01 should not be programmed here.
3. Tampers of contacts or expansion units cannot be used to operate relays.
S T A R T S T O P
=either or both - =either or both -
RELAY ZONE ZONE TYPE "RESTORE of" ZONE TYPE
OUTPUT ACTION EVENT LIST /SYST OP'N ZONE LIST /SYST OP'N
RELAY (A) (EV) (ZL) (ZT) (ZL) (ZT)
01
SEE NOTE 2 ABOVE
02
03
04
Where: A = RELAY ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off
EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble
ZL = ZONE LIST 1, 2, or 3 (from Field ✴ 81) or 0 = Not Used.
START ZONE LIST : Upon alarm, fault, or trouble of ANY zone on this list, relay action will START.
STOP "RESTORE of" ZONE LIST: Upon restore of ALL zones on this list, relay action will STOP.
ÊÊÊÊÊIt need not be same list as used for START.
ZT = ZONE TYPE/SYSTEM OPERATION
Choices for Zone Types are:
00 = Not Used 06 = 24 Hr Silent
Note : Any zone in "ZT" going into alarm,
01 = Entry/Exit 07 = 24 Hr Audible fault, or trouble will actuate relay.
03 = Perimeter 08 = 24 Hr Aux
04 = Interior Follower 09 = Fire Trouble Any zone of that type that restores
will stop relay action.
05 = Trouble Day/Alarm Night 10 = Interior w/Delay
Choices for System Operation are:
20 = ArmingÐStay 33 = Any Burglary Alarm 39 = Any Fire Alarm
21 = ArmingÐAway 34 = Code + # + 7 Key Entry 40 = Bypassing
22 = Disarming (Code + OFF) 35 = Code + # + 8 Key Entry 41 = AC Power Failure
31 = End of Exit Time 36 = At Bell Timeout** 42 = System Battery Low
32 = Start of Entry Time 38 = Chime 58 = Duress
**Or at Disarming, whichever occurs earlier.
✱81 ZONE LISTS FOR OUTPUT RELAYS Record desired zone numbers. More or fewer boxes than shown may be
needed, since any list may include any or all of system's zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 00 to end entries).
, , , , , , , , , ...etc.
–6–
MECHANICS OF PROGRAMMING
The following program fields must be programmed (as required) before doing
any programming.
✱ 22. RF SYSTEM
✱ 25. OUTPUT RELAY MODULE
See Programming System Setup Fields on next page.
–7–
3. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for ex ample, the phone number field), enter the
desired data, then press ✱ and the next data field number to be programmed.
4. If you try to enter a non-existent field, an Alpha keypad will display NOT
USED and EE (Entry Error). Simply key [✱ ] again plus a valid field number.
Typical prompt displayed Press [ ✱] plus menu mode No. (for example, ✱ 56). The Alpha keypad will
during interactive menu display the first of a series of prompts requesting entries.
mode programming
A detailed procedure (with displays of prompts) is provided in those sections in
Enter Zn Num. the Installation Instructions where programming in the menu mode is to be
performed.
(00 = Quit) 01
Menu Mode Used To Program
ÊZone Number ↑
✱56 Zone Programming Zone characteristics, report codes, alpha descrip -
tors and serial numbers for 5800 transmitters
✱80 Relay Programming 4204 Relay modules
✱81 Zone List Programming Zone Lists for 4204 relay activation
✱82 Alpha Programming Zone alpha descriptors
✱83 Sequential Mode 5800 series transmitter serial numbers
✱96 resets the Subscriber Account number and CSID in preparation for an
initial download.
Programming System Setup Fields
–8–
5800 Series Transmitter Input Loop Identification
¥ All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
Each of the inputs requires its own programming zone (e.g., a 5804's four inputs require four programming
zones).
¥ Transmitter inputs entered as:
"RF" (Supervised RF) Type send periodic check-in signals, as well as fault, restore and low battery
signals. The transmitter must remain within the receiver's range.
ÒUR" (Unsupervised RF) Type send all the signals that the "RF" Type does, but the control does
not supervise the check-in signals. The transmitter may, therefore, be carried off-premises.
"BR" (Unsupervised Button RF) Type only send fault signals. Restore or check-in signals are not
sent, but low battery signals are sent when a button is pressed. The transmitter may be car ried off-
premises. The transmitter may be carried off-premises.
INPUT
(LOOP)
3
INPUT INPUT
2 (LOOP) (LOOP)
1 2
1 (PRIMARY) (REED)
INPUT
(LOOP) 2 LOOP 1
1 (AUX. CENTER) (TERMINALS)
4
3
(ALWAYS USE) (AUX. RIGHT)
5802MN
LEARN AS "UR" OR "RF" LOOP 3
5801 5817 (TERMINALS) 5819
LEARN AS "UR" OR "RF" LEARN AS "RF" LEARN AS "RF"
5827
SET HOUSE ID
YOU MUST LOOP 3 INPUT
(LOOP) (DIP SWITCHES) 5827
LEARN THIS
BUTTON 2 SET HOUSE CODE
LOOP 2 (REED)
LOOP 4
INPUT
LOOP 1 LOOP 1
(LOOP)
1 (INTERNAL
SHOCK 5827BD
5827BD
SENSOR)
5808 SET HOUSE CODE
LEARN AS "RF" SET HOUSE ID
5804
LOOP 3(KEYPAD PROGRAMMABLE)
LEARN
(TERMINALS)
AS "BR"
5819S (WHS & BRS)
LEARN AS "RF"
INPUT INPUT
(LOOP) (LOOP)
2 2
(REED) (REED)
INPUT
LOOP 1 LOOP 1 (LOOP)
(TERMINALS) (TERMINALS) 1
(Green) (MOTION)
(Red)
(Yellow)
–9–
ALPHA VOCABULARY LIST
(For Entering Zone Descriptors)
NOTE : Some rarely-used words appearing in previously published lists have been deleted from the list
below. Use only this list for selecting zone descriptors.
000 (Word Space) ¥ 057 DOOR L R V
A ¥ 059 DOWN ¥ 106 LAUNDRY 155 RADIO 209 VALVE
¥ 001 AIR ¥ 060 DOWNSTAIRS ¥ 107 LEFT ¥ 156 REAR 210 VAULT
¥ 002 ALARM 061 DRAWER 108 LEVEL 157 RECREATION 212 VOLTAGE
004 ALLEY ¥ 062 DRIVEWAY ¥ 109 LIBRARY 159 REFRIGERATION W
005 AMBUSH ¥ 064 DUCT ¥ 110 LIGHT 160 RF 213 WALL
¥ 006 AREA E 111 LINE ¥ 161 RIGHT 214 WAREHOUSE
¥ 007 APARTMENT ¥ 065 EAST ¥ 113 LIVING ¥ 162 ROOM ¥ 216 WEST
¥ 009 ATTIC 066 ELECTRIC ¥ 114 LOADING 163 ROOF ¥ 217 WINDOW
010 AUDIO 067 EMERGENCY 115 LOCK S ¥ 219 WING
068 ENTRY 116 LOOP 164 SAFE 220 WIRELESS
B
¥ 069 EQUIPMENT 117 LOW 165 SCREEN
¥ 012 BABY X
¥ 071 EXIT ¥ 118 LOWER 166 SENSOR
¥ 013 BACK 222 XMITTER
¥ 014 BAR 072 EXTERIOR M ¥ 167 SERVICE Y
¥ 016 BASEMENT F ¥ 119 MACHINE ¥ 168 SHED 223 YARD
¥ 017 BATHROOM ¥ 073 FACTORY 121 MAIDS 169 SHOCK
122 MAIN Z
¥ 018 BED 075 FAMILY ¥ 170 SHOP
¥ 123 MASTER 224 ZONE (No.)
¥ 019 BEDROOM ¥ 076 FATHERS 171 SHORT
¥ 125 MEDICAL ¥ 225 ZONE
020 BELL ¥ 077 FENCE ¥ 173 SIDE
126 MEDICINE ¥ 226 0
¥ 021 BLOWER ¥ 079 FIRE 174 SKYLIGHT
128 MONEY ¥ 227 1
¥ 022 BOILER ¥ 080 FLOOR 175 SLIDING
129 MONITOR ¥ 228 1ST
023 BOTTOM 081 FLOW ¥ 176 SMOKE
¥ 130 MOTHERS ¥ 229 2
025 BREAK 082 FOIL ¥ 178 SONS
¥ 131 MOTION ¥ 230 2ND
¥ 026 BUILDING ¥ 083 FOYER ¥ 179 SOUTH
132 MOTOR ¥ 231 3
C 084 FREEZER 180 SPRINKLER
¥ 232 3RD
028 CABINET ¥ 085 FRONT N ¥ 182 STATION
¥ 233 4
¥ 029 CALL ¥ 134 NORTH 184 STORE
G ¥ 234 4TH
030 CAMERA 135 NURSERY ¥ 185 STORAGE
¥ 089 GARAGE ¥ 235 5
031 CAR O 186 STORY
¥ 090 GAS ¥ 236 5TH
033 CASH ¥ 136 OFFICE 190 SUPERVISED
091 GATE ¥ 237 6
034 CCTV ¥ 138 OPEN 191 SUPERVISION
¥ 092 GLASS ¥ 238 6TH
035 CEILING 139 OPENING 192 SWIMMING
093 GUEST ¥ 239 7
036 CELLAR ¥ 140 OUTSIDE 193 SWITCH
094 GUN ¥ 240 7TH
¥ 037 CENTRAL 142 OVERHEAD T ¥ 241 8
H
038 CIRCUIT P 194 TAMPER ¥ 242 8TH
¥ 095 HALL
¥ 040 CLOSED 143 PAINTING 196 TELCO ¥ 243 9
¥ 096 HEAT
¥ 046 COMPUTER ¥ 144 PANIC 197 TELEPHONE ¥ 244 9TH
098 HOLDUP
047 CONTACT 145 PASSIVE ¥ 199 TEMPERATURE
099 HOUSE
D ¥ 146 PATIO 200 THERMOSTAT
100 INFRARED
¥ 048 DAUGHTERS 147 PERIMETER ¥ 201 TOOL
¥ 101 INSIDE 250 Custom Word #1
049 DELAYED ¥ 148 PHONE 202 TRANSMITTER
102 INTERIOR
¥ 050 DEN 103 INTRUSION 150 POINT U 251 Custom Word #2
051 DESK 151 POLICE ¥ 205 UP
J
¥ 052 DETECTOR 152 POOL ¥ 206 UPPER 252 Custom Word #3
104 JEWELRY
¥ 053 DINING ¥ 153 POWER ¥ 207 UPSTAIRS
K ¥ 208 UTILITY 253 Custom Word #4
054 DISCRIMINATOR R
¥ 105 KITCHEN
055 DISPLAY 155 RADIO 254 Custom Word #5
¥ 156 REAR
Note: Bulleted (¥) words in boldface type are those that are also available for use by the 4285 Phone Module. If using a
Phone module, and words other than these are selected for Alpha descriptors, the module will not provide annunciation
of those words.
CHARACTER (ASCII) CHART
(For Adding Custom Words)
32 (space) 42 ✴ 52 4 62 > 72 H 82 R
33 ! 43 + 53 5 63 ? 73 I 83 S
34 " 44 , 54 6 64 @ 74 J 84 T
35 # 45 Ð 55 7 65 A 75 K 85 U
36 $ 46 . 56 8 66 B 76 L 86 V
37 % 47 / 57 9 67 C 77 M 87 W
38 & 48 0 58 : 68 D 78 N 88
39 ' 49 1 59 ; 69 E 79 O 89 Y
40 ( 50 2 60 < 70 F 80 P 90 Z
41 ) 51 3 61 = 71 G 81 Q
ÊÊ
– 10 –
ZONE RESPONSE TYPE DEFINITIONS
Type 00 Program a zone with this zone type if the zone is not used.
Zone Not Used
Type 01 This zone type provides entry delay whenever the zone is faulted if the control
Entry/Exit Burglary is armed in the AWAY or STAY modes. When the panel is armed in the
Instant or Maximum modes, no entry delay is provided. Exit delay begins
whenever the control is armed, regardless of the arming mode selected. These
delays are programmable. This zone type is usually assigned to sensors or
contacts on doors through which primary entry and exit will take place.
Type 02 Not used in this system
Type 03 This zone type gives an instant alarm if the zone is faulted when the panel is
Perimeter Burglary armed in the AWAY, STAY, INSTANT or MAXIMUM modes. This zone type
is usually assigned to all sensors or contacts on exterior doors and windows.
Type 04 This zone type is active when the panel is armed in the AWAY or MAXIMUM
Interior, Follower modes. Entry delay (using the programmed entry time) results if the panel is
armed in the AWAY mode and the entry/exit zone is faulted first. Otherwise
this zone type gives an instant alarm. Exit delay is present for any arming
mode. This zone type is usually assigned to a zone covering an area such as a
foyer, lobby, or hallway through which one must pass (upon entry, after
faulting the entry/exit zone) to reach the keypad to disarm the system. Since
this zone type is designed to pro vide an instant alarm if the entry/exit zone is
not violated first, it will protect an area in the event an intruder hides on the
premises prior to the system being armed, or gains access to the premises
through an unprotected area. This zone type is bypassed automatically
when the panel is armed STAY or INSTANT.
Type 05 This zone type will give an instant alarm if faulted when armed in the AWAY,
Trouble by Day/ STAY, INSTANT or MAXIMUM (night) modes. During the disarmed state
Alarm by Night (day), the system will provide a latched trouble sounding from the keypad
(and a central station report, if desired). This zone type is usually assigned to
a zone which contains a foil-protected door or window (such as in a store), or
to a zone covering a "sensitive" area such as a stock room, drug supply room,
etc. This zone type can also be used on a sensor or contact in an area where
immediate notification of an entry is desired.
Type 06 This zone type sends a report to the Central Station but provides no keypad
24-hour Silent Alarm display or sounding. This zone type is usually assigned to a zone containing
an Emergency button.
Type 07 This zone type sends a report to the Central Station, and provides a rapid
24-hour Audible Alarm beeping sound at the keypad, and an audible external alarm. This zone type
is usually assigned to a zone that has an Emergency button.
Type 08 This zone type sends a report to the Central Station and provides a rapid
24-hour beeping sound at the keypad. (No bell output is provided). This zone type
Auxiliary Alarm is usually assigned to a zone containing a button for use in personal
emergencies, or to a zone containing monitoring devices such as water or
temperature sensors, etc.
Type 09 This zone type provides a fire alarm on short circuit and a trouble condition
Supervised Fire on open circuit. The bell output will pulse when this zone type is faulted. This
zone type is always active and cannot be bypassed. This zone type can be
assigned to control panel wired zone 5 and to certain wireless zones.
Type 10 This zone type gives entry delay (using the programmed entry time), if tripped
Interior w/Delay when the panel is armed in the Away mode, regardless of whether or not an
entry/exit delay zone was tripped first. This zone type is also active during
MAXIMUM mode, but n o entry delay is provided (an alarm occurs
immediately if the zone is tripped). Exit delay is present for any arming
mode. This zone type is bypassed automatically when the panel is
armed Stay or Instant .
– 11 –
Type 20 This is a special-purpose zone type used with 5800 series wireless pushbutton
ArmÐStay units which will result in arming the system in the STAY mode when the
zone is activated. Pushbutton units send zone number as a user number to
central station when arming or disarming.
Type 21 This is a special-purpose zone type used with 5800 series wireless pushbutton
ArmÐAway units which will result in arming the system in the AWAY mode when the
zone is activated. Pushbutton units send zone number as a user number to
central station when arming or disarming.
Type 22 This is a special-purpose zone type used with 5800 series wireless pushbutton
Disarm which will result in disarming the system when the zone is activated.
Type 23 This can be used on a zone when an output relay action is desired, but with
No Alarm Response no accompanying alarm (e.g., lobby door access).
By using a 4281/5881 type RF Receiver and the appropriate 5700/5800 series transmitters, all
of the zone types listed* are available for the wireless portion of the system.
* Note: Zone Types 20, 21, and 22 cannot be used in a 5700 RF system.
– 12 –
DATA FIELD DESCRIPTIONS
The blank programming form in this manual should be used to record the data for this installation.
The following is a list of all data fields in this control (presented in numerical order). This
list provides an explanation of each data field, and will serve as a reference for all fields in
the system. Defaults (where applicable) are indicated in the text for each field in this list.
✱20 INSTALLER CODE Default is 4-1-1-1.
The Installer code is used to program the system, and to assign the
4-digit Master security code in the normal operation mode, via
the keypad See "Master Code" in the SYSTEM OPERATION section
in the Installation Instructions for the procedure. Enter 4 digits, 0Ð9.
✱21 QUICK ARM ENABLE (1-Digit Entry) Default is 0.
If enabled, the [#] key can be used instead of the security code when
arming the system. Enter 0 for disabled or 1 for enabled. This feature
will function only if the Master Code is programmed.
✱22 RF SYSTEM (1-Digit Entry) Default is 0 (none).
This option is enabled if a wireless receiver is used.
Enter 1 for 4281 series RF receivers, 2 for 5881* series RF receivers.
Enter 0 if no receiver is being used.
* 5882 series RF receivers in Canada.
✱23 FORCED BYPASS FUNCTION (1-Digit Entry) Default is 0.
This feature allows all open zones to be bypassed automatically.
Ò1Ó will bypass all open zones, Ò2Ó will bypass all open zones, plus zones
17, 30, 31, 46, and 47 (whether open or not)
All zones that are bypassed by this function will be displayed after the
bypass is initiated:
✱24 RF HOUSE ID CODE (2-Digit Entry) Default is 00 .
The House ID identifies receivers and wireless keypads in a 5700 type
system, and must be assigned (01Ð31).
If a 5827 or 5827BD Wireless keypad is to be used in a 5800 RF system,
a House ID code MUST also be entered (01Ð31), and the keypad should
be set to the same ID. In a 5800 system with no 5827 or 5827BD
wireless keypad, enter 00 (no House ID).
✱25 WIRED EXPANSION/OUTPUT RELAY USEDÊÊÊÊ (1-Digit Entry)
Enter Ò1Ó if a 4219 wired expansion unit is used, Ò2Ó if a 4229 wired
expansion/ relay unit is used, Ò3Ó if a 4204 relay is being used, or Ò0Ó if
none are being used (Ò0Ó is the default).
✱26 VOICE (PHONE) MODULE
ACCESS CODE (2-Digit Entry) Default is 00 .
The use of a 4285 Phone Module requires a 2-digit phone access code.
Enter as follows: ÊFor first digit, enter any digit from 1 to 9; for second
digit, enter # +11 for " ✱ ", or # +12 for "#".
Example: If the desired access code is 7 ✱ , 7 is the first entry, and
# + 11 (for ✱ ) is the second entry.
Ò00Ó = Phone Module disabled. Note: A Ò0Ó in either digit will disable
the 4285 Phone Module.
✱27 OUTPUT TO LONG RANGE RADIO (1-Digit Entry) Default is 0.
0= no, 1 = yes. If output to LRR is selected here (1), all messages that
Note:ÊThe Radio should are programmed to go to the primary telephone line receiver will also be
be programmed for device sent to the radio (e.g., 7720 PLUS or 7820). These messages will always
address 3 on the keypad be in Contact ID format (overriding the selection in field ✱46). The data
lines. line is supervised ,as well as certain functions in the radio.
If communication is lost or a trouble develops, a message will be
attempted to be sent via both radio and telephone to the central station.
Normal trouble restore report ( ✱71) is sent on restore of the condition.
– 13 –
ZONE SOUNDS AND ✱28 SINGLE ALARM SOUNDING PER ZONE Default is 0.
TIMING (Per Armed Period) (1-Digit Entry)
(✱28Ð✱ 39) This field limits external alarm sounding to once per arming period for
a given zone. Enter 1 for yes; 0 for no.
– 14 –
✱45 PHONE SYSTEM SELECT (1-Digit Entry) Default is 0.
If Central Station Receiver is not on WATS line:
0 = Pulse Dial 1 = Tone Dial
If Central Station Receiver is on WATS line:
2 = Pulse Dial 3 = Tone Dial
✱46 REPORT FORMAT (1-Digit Entry) Default is 0.
Determine which format is to be used to report to the central station.
Enter 1 digit (0Ð9).
For an explanation of these 0 = 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default)
formats, see the SYSTEM
1 = 3+1; 4+1 Radionics Standard
COMMUNICATION
section in the Installation 2 = 4+2 ADEMCO Lo Speed Standard
Instructions. 3 = 4+2 Radionics Standard
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID Reporting
8 = 3+1; 4+1 ADEMCO Lo Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
(Enter ✱ as the 4th digit of ✱ 43 if 3+1 dialer reporting is to be used.)
Note: The maximum number of alarm and alarm restore reports
during one armed period is determined by field ✱ 92.
See field ✱ 27, which may override this fieldÕs selection.
✱47 SPLIT/DUAL REPORTING (1-Digit Entry) Default is 0.
Enter 0 to disable (Backup report only).
Entries 1 through 9 can be made, as indicated in the table below. Entries
6 through 9 will send a report to a pager (in addition to the selected
primary phone number), but you must enter the pager number as the
secondary phone number in field ✱42.
TO PRIMARY PHONE # TO SECONDARY PHONE #
Ê1 = Alarms, Restore, Cancel Other Reports
Ê2 = All except Open/Close, Test Open/Close, Test
Ê3 = Alarms, Restore, Cancel All reports
Ê4 = All except Open/Close, Test All reports
Ê5 = All reports All reports
TO PRIMARY PHONE # TO PAGING No. * (Secondary)
Ê* Can only be used if the Ê6 = All reports except Open/Close Alarms/Open/Close, Troubles
Primary reporting format Ê7 = All reports Alarms, Troubles
is Ademco Contact ID. Ê8 = All reports Alarms/Open/Close, Troubles
If reporting to a Pager,
choose from 6, 7, 8, or 9, Ê9 = All reports except Open/Close Alarms, Open/Close for users #5Ð25à,
Troubles
as desired.
à Will report only Users 5, 6 & 8. If using 5800 series wireless button-type
devices, the zone number of the arm or disarm button (10Ð25) will be sent as
the user number.
Entries 6 through 9 will send a report to a pager (in addition to the selected
primary phone number), but you must enter the pager number as the secondary
phone number in field ✱42.
A 10-digit code is sent to the pager which will take the following format:
4-digit Subscriber No . → Ê SSSSÐEEEÐNNN ← 3-digit User or Zone No.
Ê
– 15 –
Example 1.ÊÊ Pager displays:ÊÊ1 23 4Ð911Ð004
This indicates that Subscriber No. 1234Õs system is reporting an
Alarm (911), due to zone 4 being faulted (004).
Example 2.ÊÊPager displays:ÊÊ1 23 4Ð001Ð005
This indicates that Subscriber No. 1234Õs system is reporting an
opening (001) by User 5 (005).
Note that no restore reports are sent to the pager.
Important:
AAV should not be used when Paging or Alarm Reports are being sent to a
Secondary number. If this is done, the call to the Secondary number by the
communicator after the alarm report will prevent the AAV from taking control
of the telephone line, and the AAV ÒListen inÓ session cannot then take place.
– 16 –
TO PROGRAM With a 3+1 or 4+1 Standard Format: Enter a code in the first digit box:
SYSTEM STATUS 1Ð9, 0, B, C, D, E, or F. Enter "# + 10" for 0, "# + 11" for B, "# + 12" for C,
AND RESTORE "# + 13" for D, "# + 14" for E, "# + 15" for F.
REPORT CODES A "0" (not "# + 10") in the first digit box will disable a report.
(✱60 Ð ✱ 68, ✱70 Ð ✱ 75)
A "0" (not "# + 10") in the second digit box (if any) will result in automatic
advance to the next field when programming.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd
digits) for 1Ð9, 0, or BÐF, as de scribed above.
A "0" (not "# + 10") in the second box will eliminate the expanded message
for that report.
A "0" (not "# + 10") in both boxes will disable the report.
With Ademco Contact ID Reporting: Enter any digit (other than "0") in
the first box, to enable zone to report This is an "enabling" code only and is
disregarded in the actual reporting to the central office. Entries in the second
boxes will be ignored.
A "0" (not "# + 10") in the first box will disable the report.
Examples:
For Code 3 (Single Digit), enter: ÊÊÊÊ3ÊÊÊÊ ÊÊÊÊ0ÊÊÊÊ
For Code 32 (Two Digits), enter: ÊÊÊÊ3ÊÊÊÊ ÊÊÊÊ2ÊÊÊÊ
For Code B2 (Hexadecimal) enter: #Ê+Ê11Ê ÊÊÊÊ2ÊÊÊÊ
SYSTEM STATUS ✱60 TROUBLE REPORT CODEÊÊ (See box above.) (2-Digit Entry)
REPORT CODES
✱61 BYPASS REPORT CODEÊ (See box above.) (2-Digit Entry)
(✱60 Ð✱ 68)
✱62 AC LOSS REPORT CODEÊ (See box above.) (2-Digit Entry)
Reports with Subscriber No. Timing of this report is random with up to
a 48-minute delay. The Restore report has a random delay of up to about
12 minutes. If AC restores before the report goes out, there is no AC
restore report.
✱63 LOW BAT REPORT CODE (See box above.) (2-Digit Entry)
Reports with Subscriber No.
✱64 TEST REPORT CODE (See box above.) (2-Digit Entry)
Periodic Reports with Subscriber No.
✱65 OPEN/EXIT ALARM REPORT CODE, 1st DIGITS (2-Digit Entry)
Open Report Code : To enable, enter a code (or 0 to disable) in the left-
hand box (see box above).
For expanded or 4+2 reporting, 2nd digit = User #.
Exit Alarm Report Code: To enable, enter a code (or 0 to disable) in
the right-hand box (see box above).
If enabled, any alarm from an exit or interior zone occurring
within two minutes after the end of the exit delay will send a
special message indicating exit alarm to the central station, and a zone
indication and "Exit Alarm" or "EA" is displayed on the keypad.
If an exit or interior zone contains a fault as the exit delay ends,
the local bell and keypad sound continuously.
a) If the subscriber then disarms the system before the ensuing Entry
delay ends, no message is transmitted to the central station, but a
zone indication and "Canceled Alarm" or "CA" is displayed on the
keypad.
b) If the system is not disarmed before that entry delay ends , a special
message indicating Exit Alarm is sent to the central station and a
zone indication and "Exit Alarm" or "EA" is displayed on the keypad.
For expanded or 4+2 reporting, a 2nd digit is sent, and is the same as the
2nd digit of the zone alarm report code programmed in field ✱56.
For Contact ID reporting, Event code 374 and the zone number is sent.
There is no restore message for an Exit Alarm report.
– 17 –
✱66 AWAY/STAY CLOSE REPORT CODE (2-Digit Entry)
(See box on previous page.) To enable, enter a code (or 0 to disable) in
either or both boxes. For expanded or 4+2 reporting, 2nd digit for each =
User # .
✱67 RF XMTR. LOW BATTERY REPORT CODE (2-Digit Entry)
(See box on previous page).
✱68 CANCEL REPORT CODE (2-Digit Entry) (See box on previous page.)
UL For UL installations, the AAV option cannot be used (do not select 4, 5, 6,
or 7).
AAV should not be used when Paging or Alarm Reports are being sent
to a Secondary number. If this is done, the call to the Secondary
number by the communicator after the alarm report will prevent the
AAV from taking control of the telephone line, and the AAV ÒListen inÓ
session cannot take place.
– 19 –
✱96 INITIALIZE DOWNLOAD ID AND SUBSCRIBER ACCT. No.
FOR DOWNLOADING
(No data entry required; press ✱96)
✱97 SET ALL PROGRAM FIELDS TO DEFAULT VALUES
(No data entry required; pressing ✱ 97 automatically loads all First Alert
defaults). Do not use if previously programmed with other values.
TO EXIT ✱98 EXITS PROGRAMMING MODE and prevents re-entry by :
PROGRAMMING MODE INSTALLER Code + 8 + 0 .
(✱98 or ✱99) To enter the programming mode if ✱98 was used to exit, you must
first power the system down. Then power up again, and depress [✱ ]
and [#] both at once, within 50 seconds of powering up.
✱99 EXITS PROGRAMMING MODE and allows re-entry by:
INSTALLER Code + 8 + 0 or by method described in paragraph
above (power down, power up and depress [ ✱] and [#] both at once,
within 50 seconds of powering up.) .
– 20 –
REMOTE PROGRAMMING AND CONTROL (DOWNLOADING)
General Information
The FA142C can be remotely programmed from an IBM compatible Per sonal
Computer (PC), a HAYES Modem, and Downloading Software (as specified
below).
Programming the control from a remote location is protected against
compromise by someone attempting to defeat the system, using multi-levels of
security protection:
1. Security Code Handshake: An 8-digit download ID code must be
matched between the control and the downloader.
2. Site-Initiated Remote Programming: Telco Hand-off feature allows the
technician at the site to call the downloading facility from the control panel
phone line, initiate a site download (Installer or Master Code + # + 1), and
the control will immediately be on-line with the modem at the downloading
facility. Also, if a local computer has a modem, the telephone line terminals
of the control can be connected to the modem, and a direct download
connection can be established with the new downloader program.
3. Station-Initiated Remote Programming: The operator calls the site
from your office to initiate the download call. The control hangs up and then
calls back the PC via the preprogrammed telephone number. The unit can
then be uploaded, downloaded, or controlled from your office.
The control can also be set for no callback by the downloader.
4. Data Encryption: Data passed between the PC and the control is en -
crypted for security so that it is very difficult for a foreign device tapped
into the phone line to take over communication and substitute system
compromising information.
Equipment Required
At the premises:
• FA142C Control and keypad.
At the installer's of fice/home:
• An IBM PC compatible computer.
• Either a HAYES brand SMARTMODEM 1200 [Level 1.2 or higher external or
Level 1.1 or higher (with 4 position DIP switch) internal style],or a HAYES
brand Optima 24 Plus FAX96 Modem.
• First Alert’s FADL Downloading Software (Rev 4 or higher), or Compass
Windows downloading software (at revision level 1.0.1.0. or higher).
• Appropriate interconnecting cables.
– 21 –
• Inhibit Local Keypad Programming (prevents account takeover).
• Read: Arming Status, AC Power Status, Lists of Faulted Zones, Bypassed
Zones, Zones Currently in Alarm, Zones Currently in Trouble, and RF
Sensors with Low Battery Conditions.
Note: After the control and the PC have established valid communication, each keypad
on the system will become inactive and will display "CC" or " MODEM COMM.".
The control, however, will still be scanning its zones and looking for alarms. If
an alarm does occur, after communication is broken off, alarms are sounded and
the proper dialer reports are sent to the central station. The keypads will
become active after the download communication is terminated.
The detailed operation of the download functions is covered in the installation
instructions for the Downloading Software .
– 22 –
BATTERY FUSE THESE OPTIONAL ITEMS
(e.g. ADEMCO No. 90-12) MAY ALSO BE USED SET UNIT’S DIP
GEL LEAD ACID TYPE. ADEMCO No. 4219 SWITCH
FOR REPLACEMENT
OPTIONAL
AND/OR RED EOL
– BLACK FA4285 -OR- POWER
CHARGING BATTERY GRN ADEMCO No. 4204 RELAY MODULE + SUPER-
VOICE MODULE (160mA)
VOLTAGE 12V, 4AH
(e.g. ADEMCO
+ RED AND/OR
YEL (4 OUTPUT RELAYS) SET RECEIVER’S 4-WIRE SMOKE - VIOLET VISION
RELAY
13.8VDC DIP SWITCH FOR OR COMBUSTION
No. 467) ADEMCO AND/OR DEVICE ADDRESS DETECTOR • MODULE
2000 A77-716B
OR 12V, 1.2AH + – LONG RANGE RADIO
ADEMCO 4281 or 5881* Type OF “0”. 1000
OHMS
OHMS
CONNECTOR TABS RF RECEIVER See receiver’s EOLR •
EOLR
instructions. TO HI SIDE OF SELECTED ZONE
WIRELESS ZONES +
BLK BLK 4281L: UP TO 4 * HEAT EARTH
TO DETERMINE TOTAL STANDBY LOAD 4281M/5881L: UP TO 8 TOZONES
ZONE2–75*
RED RED DETECTOR
GROUND
ON BATTERY, ADD 100mA TO TOTAL OF
GRN GRN 5881M: UP TO 16 -
TO LO SIDE OF SELECTED ZONE TERMINAL
AUX. POWER OUTPUT AND REMOTE 4281H/5881H/5881EH: UP TO 30 * IF PROGRAMMED FOR FIRE
YEL YEL * 5882 TYPE IN CANADA (See Instructions) * IF PROGRAMMED FOR FIRE
KEYPAD CURRENTS.
LO
LO
LO
LO
LO
LO
HI
HI
HI
HI
HI
HI
LOWER RIGHT
TIP RING TIP RING OF CIRCUIT
▲ ▲ (BROWN) (GRAY) (GREEN) (RED)
}
BOARD
}
}
AUX. POWER
OUTPUT HANDSET INCOMING
ZONE 5
ZONE 6
ZONE 1
ZONE 2
ZONE 3
ZONE 4
MUST BE
PLUG-IN INCLUDED WARNING:
IN AUX.
TRANSFORMER
16.5VAC, 25VA CURRENT
TO PREVENT RISK OF SHOCK,
(e.g. ADEMCO DRAIN DISCONNECT TELEPHONE LINE
No. 1321. CALCULATIONS
USE No. 1321CN
1000
OHMS
1000
OHMS
1000
OHMS
1000
OHMS
1000
OHMS
1000
OHMS
AT TELCO JACK BEFORE
IN CANADA)
REMOTE
EOLR EOLR EOLR EOLR EOLR EOLR SERVICING THIS UNIT.
+ – • MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
ALARM OUTPUT
KEYPAD
• RESPONSE, ZONES 1-6: 300-500MSEC
THIS EQUIPMENT SHOULD BE INSTALLED IN
FOR COMPLETE
INFORMATION,
10.5-13.8VDC, 2A MAX.
REMOTE KEYPADS • ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR ACCORDANCE WITH THE NATIONAL FIRE
(600mA MAX FOR UL USAGE, FAST RESPONSE TO AN OPEN: 10MSEC MAX
SEE INCLUDING AUX. POWER)
SYSTEM MUST BE
• ZONE 5 CAN BE PROGRAMMED FOR USE AS PROTECTION ASSOCIATION'S STANDARD 74
PROGRAMMED WITH AN
INSTRUCTIONS
STEADY FOR BURGLARY/PANIC, FA510KP OR FA550KP. IT NEED
A FIRE ZONE. SEE DIAGRAM. (NATIONAL FIRE PROTECTION ASSOC.,
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
PULSING FOR FIRE (e.g. USE NOT REMAIN IN SYSTEM.
OPERATION IS SUBJECT TO THE FOLLOWING TWO BATTERYMARCH PARK, QUINCY, MA 02269).
ADEMCO No. 740 SOUNDER,
No.702 OR 719 SIREN, OR 12V BELL)
AFTER PROGRAMMING,
THE SYSTEM CAN USE:
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTER-
FERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFER-
PRINTED INFORMATION DESCRIBING PROPER
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM
FA210KP (30mA), ENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE INSTALLATION, OPERATION, TESTING,
FA250KP (120mA), OR
HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED FA550KP (140mA).
UNDESIRED OPERATION.
MAINTENANCE, EVACUATION PLANNING AND
ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING
JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE MULTIPLE KEYPADS MAY BE
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
REPAIR SERVICE IS TO BE PROVIDED WITH
CONNECTED TO A POLICE EMERGENCY NUMBER.
USED, BUT USE MAX. OF 220 FT.
OF #22 WIRE OR 550 FT. OF #18.
RINGER EQUIVALENCE: 0.7B. THIS EQUIPMENT.
WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED. WEEKLY
TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM.