1436 Cpos: Intelligent Positioner
1436 Cpos: Intelligent Positioner
Intelligent Positioner
and integrated Process Controller
GB OPERATING INSTRUCTIONS
Status 23.09.16
From version 2.0.3.0
1436 cPos
Quick commissioning of the GEMÜ 1436 cPos:
Prerequisites:
● Mounted to the valve.
● Air supply, max. 7bar, connected.
● 24 V DC supply voltage connected.
● Set value and actual value signals need not be connected.
● For correct commissioning proceed as described in the following flow chart:
2 / 64
1436 cPos
Contents 11.6 Menu structure 4 SetCalibration 22
1 General safety information 4 11.7 Menu structure 5 Communication 23
1.1 General information 4 12 Parameter table 24
1.2 Explanation of symbols and signs 4 13 Explanation of parameters 28
1.3 Safety notes 4 13.1 1 Service 28
1.4 Correct use 5 13.1.1 Scanning the input and output signals 28
1.5 Information on use in damp conditions 5 13.1.2 Activating or deactivating the user access 29
1.6 Mounting position 5 13.1.3 Reading out, deleting and deactivating error
1.7 Tools required for installation and assembly 5 messages 30
2 Manufacturer's information 5 13.1.4 Display serial number, software version and ID and
2.1 Transport 5 enter TAG no. 30
2.2 Delivery and performance 5 13.2 2 SetBasics 31
2.3 Storage 5 13.2.1 Definition of actual value and set value inputs 31
2.4 Function 5 13.2.2 Reset 31
2.5 Fail safe function 5 13.2.3 Initialisation 31
3 Diagrammatic view of the inputs and outputs 6 13.2.4 Making the display settings 31
4 Mechanical mounting 7 13.3 3 SetFunction 32
4.1 Mounting to linear actuators 7 13.3.1 Setting the process controller parameters (optional) 32
4.1.1 Preparation of the valve actuator 7 13.3.2 Setting the positioner parameters 33
4.1.2 Assembling the travel sensor 7 13.3.3 Setting the dead zone 33
4.1.3 Mounting the positioner 7 13.3.4 Setting the optional digital input parameters 33
4.2 Mounting to quarter turn actuators 7 13.3.5 Setting output functions and switch points 34
4.2.1 Preparation of the valve actuator 7 13.3.6 Setting the error time and error action 35
4.2.2 Assembling the travel sensor 7 13.3.7 Storing parameter sets 35
4.2.3 Mounting the positioner 8 13.3.8 Defining the actual value output 35
4.2.4 Checking the mounted assembly 8 13.4 4 SetCalibration 36
4.3 Remote mounting to linear or quarter turn actuators 8 13.4.1 Determining the direction of actual value and set
4.3.1 Preparation of the valve actuator 8 value 36
4.3.2 Assembling the travel sensor 8 13.4.2 Defining the characteristics of the control curve 36
4.3.3 Checking the mounted assembly 8 13.4.3 Defining the direction of the travel sensor 37
4.3.4 Mounting the mounting bracket 8 13.4.4 Defining the actual value output signal 37
4.3.5 Connecting the travel sensor 8 13.4.5 Determining switch points for error monitoring 37
5 Pneumatic connections 8 13.4.6 Scaling the actual value and set value display 37
6 Electrical connections 8 13.5 5 Communication 38
6.1 Version with external actual value potentiometer 13.5.1 Setting the fieldbus parameters 38
(code S01) 9 13.5.2 Setting the communication parameters 38
6.2 Supply voltage 9 14 Error messages 39
6.3 Set value input 15 Quick guide 40
(only effective for AUTO operating mode) 9 15.1 Changing the set value signal and actual value
6.4 Actual value input signal 40
(sensor signal when operating as a process controller) 9 15.2 Switching the process controller on or off (optional) 40
6.5 Actual value output 9 15.3 Changing the control parameters (Proc P, Proc I,
6.6 Outputs 9 Proc D and Proc T) 41
6.7 Digital inputs 9 16 General information regarding control
6.7.1 Use of actual value and set value inputs as digital engineering 42
inputs 10 16.1 The control circuit 42
6.8 Digital inputs (optional) 10 16.2 Control engineering terminology 42
6.9 RS232 – Interface 10 16.3 Control parameters 42
7 Operation 11 16.4 Adaptation of the controller to the controlled system 43
7.1 Operating and display elements 11 16.5 Differential equation for the GEMÜ 1436 cPos 43
7.2 Menu levels 11 16.6 Effects of the control parameters on the control
7.2.1 Working level (Mode) 11 system 43
7.2.2 Configuration level (Setup) 11 16.7 Control characteristics and transitory responses 44
8 Changing parameters 11 17 Table for changes to the factory settings 45
9 Commissioning 12 17.1 Changed control parameters 45
9.1 General information 12 17.2 Set values for the freely programmable
9.2 Initial commissioning without factory setting characteristic curve 47
(when supplied without a valve) 12 18 Disposal 47
9.2.1 Automatic initialisation 12 19 Returns 47
9.2.2 Manual initialisation 12 20 Information 47
9.2.3 Menu structure automatic and manual initialisation 13 21 Technical data 48
9.2.4 Error messages during initialisation 14 22 Order data 49
9.2.5 Initialisation parameters 15 23 Fail safe function 59
9.3 Initial commissioning with factory setting 24 Application examples 60
(positioner supplied mounted to the valve) 15 24.1 GEMÜ 1436 cPos as process controller with
10 Operating modes 17 4-wire transmitter (GEMÜ 3021) 60
10.1 Operating mode selection 17 24.2 GEMÜ 1436 cPos s process controller with
10.2 Automatic operation (A:) 17 2-wire transmitter (GEMÜ 3020) 60
10.3 Manual operation (M:) 17 25 EU Declaration of Conformity 61
10.4 Manual operation with flexible List of terms 62
set value specification (F:) 17
10.5 Test mode (T:) 17
10.6 Pause mode (OFF) 17
11 Configuration menu (Setup) 18
11.1 Changes in the configuration menu 18
11.2 Access authorisation in the configuration menu 18
11.3 Menu structure 1 Service 19
11.4 Menu structure 2 SetBasics 20
11.5 Menu structure 3 SetFunction 21
3 / 64
1436 cPos
1 General safety information 1.2 Explanation of symbols and signs
Please read the following notes carefully and observe them. Important information is identified in these operating
instructions by the following symbols:
The GEMÜ 1436 cPos must be used in accordance with This symbol indicates notices which
these directions. All information in these operating give important information regarding your
instructions regarding operation, servicing and GEMÜ 1436 cPos.
maintenance must be observed and applied. If the
information is not observed, the operator's guarantee
rights and the manufacturer's legal liability cease. 1.3 Safety notes
The manufacturer shall undertake no responsibility ● Only qualified and trained personnel should
for the GEMÜ 1436 cPos if these safety notes are not assemble, electrically connect and commission
observed. the GEMÜ 1436 cPos.
DANGER Use qualified personnel for operation,
Therefore, you must observe: servicing, inspection and assembly. The areas
● the contents of these operating instructions of responsibility, the monitoring of personnel
● the relevant safety regulations for the installation and and their competence areas should be defined
operation of electrical systems precisely by the operator. Train personnel with
● that this device must not be used in potentially explosive insufficient knowledge or, if necessary, have
areas. them trained by the manufacturer / supplier on
order of the operator. Ensure that all members of
The regulations, standards and guidelines named in these personnel understand the safety instructions.
operating instructions are only applicable in Germany. If ● Ensure that the power supply equipment is
the GEMÜ 1436 cPos is used in other countries, the local electrically safe.
applicable regulations must be observed. When dealing with ● Ensure that the electrical values are correct.
harmonised European norms, standards and guidelines, these
apply within the Single European Market. The operator must Exhaust air and cycle duties generate noise!
also adhere to national rules and guidelines, if applicable. ä Hearing damage.
The descriptions and instructions in these operating ● Wear hearing protection.
instructions refer to the standard version. DANGER
In cases of uncertainty:
7 Consult the nearest GEMÜ sales office.
4 / 64
1436 cPos
1.4 Correct use 2 Manufacturer's information
7 The GEMÜ 1436 cPos is suitable for use as defined in the
data sheet. In order to ensure correct product function, the
following notes should be observed. Pay attention to the 2.1 Transport
information on the product labels. l Only transport the positioner by suitable means. Do not
7 Non-observance of these notes and the notes in the general drop. Handle carefully.
operating instructions will lead to a loss of the guarantee on l Dispose of packing material according to relevant local or
the GEMÜ 1436 cPos and of legal liability. national disposal regulations / environmental protection
7 The GEMÜ 1436 cPos serves solely as a positioner and laws.
process controller and must be used according to the data
sheet.
7 Any other use or use above and beyond this is not 2.2 Delivery and performance
permitted. GEMÜ shall not be liable for any consequential l Check that all parts are present and check for any damage
damage which is solely at the user's risk. immediately upon receipt.
7 Please pay attention to the pertinent technical safety l The scope of delivery is apparent from the dispatch
regulations when planning both the use and operation of documents and the design from the order number.
the device. The designer, plant constructor or operator is l The performance of the positioner is checked at the factory.
always responsible for positioning and mounting of the ● If the GEMÜ 1436 cPos positioner is ordered as a complete
GEMÜ 1436 cPos. unit with a valve, these parts and the accessories belonging
to them are supplied ready assembled and factory set. The
GEMÜ positioner is then ready for immediate operation.
1.5 Information on use in damp conditions
Under no circumstances whatsoever may the 2.3 Storage
GEMÜ 1436 cPos be cleaned with a high pressure
cleaning device because the protection class IP 65 l Store the positioner free from dust and moisture in its
is not sufficient for this. original packaging.
l Avoid UV rays and direct sunlight.
l Maximum storage temperature: 60 °C.
The following information is intended to help when mounting
and operating the GEMÜ 1436 cPos in damp conditions:
● Lay cables and and pipework so that condensate or rain 2.4 Function
water that remains on the pipework / cables cannot enter
The GEMÜ 1436 cPos is an intelligent electro-pneumatic
the cable glands of the M12 plugs of the GEMÜ 1436 cPos.
positioner designed for mounting to pneumatic actuators. It can
● Check that all cable glands of the M12 plug and the fittings
be operated as a positioner or a process controller depending
are mechanically secured.
on the design.
Normally the GEMÜ 1436 cPos is mounted directly to the
1.6 Mounting position actuator. The travel sensor is already integrated in the
positioner (GEMÜ 1436 cPos can be optionally ordered with an
The mounting position of the GEMÜ 1436 cPos is optional.
M12 connector for remote mounting of the travel sensor).
When mounted upside down it must be ensured that no liquids
The travel sensor measures the current position of the valve
or dirt can enter the outlet of the pressure relief valve.
and relays this position to the electronic control system of the
GEMÜ 1436 cPos which correlates the actual value of the
1.7 Tools required for installation and assembly valve with the set value and adjusts the valve if necessary.
The tools required for installation and assembly are not
included in the scope of delivery. If the positioner is ordered with an additional process controller
(optional), a current actual value signal (e.g. level, pressure,
temperature, flow) is evaluated and the positioner adopts the
function of a process controller.
5 / 64
1436 cPos
3 Diagrammatic view of the inputs and outputs
Outputs
0-20 mA
4-20 mA Binary outputs
Actual value input for process
24 V DC
control
Inputs
0-20 mA
4-20 mA e.sy-com
Supply voltage
Supply
24 V DC
Operation
Keypad
6 / 64
1436 cPos
4 Mechanical mounting ● Mount the positioner 1 by screwing the travel sensor
hexagonal nut M27 2 into the actuator 3.
4.1 Mounting to linear actuators The positioner must not be fixed by turning
the housing as this may result in the danger of
4.1.1 Preparation of the valve actuator overturning the internal stop.
1. The actuator must be in the zero position (actuator vented).
2. Should there be an optical position indicator in the actuator If correctly mounted to the valve, the positioner can be turned
(a red spindle), it must be removed. 370°.
4.1.2 Assembling the travel sensor 4.2 Mounting to quarter turn actuators
Pretensioned spring!
4.2.1 Preparation of the valve actuator
ä Damage to the device.
DANGER
● Slowly relax spring. 6
1. Pull out the spindle of the travel sensor up to the limit stop.
2. Push the spring over the spindle. 3
90°
3. Fix the spindle at point a
(the spindle must not be damaged during this pro-
cess)
4. Screw the operating bush onto the spindle.
1
2
2 1. Before mounting the travel sensor to the actuator, make
sure that the shaft height and the hole pattern in the actua-
tor match the dimensions of the mounting bracket 1.
3 2. The travel sensor shaft 2 is marked. If this marking corres-
ponds with the marking at the bottom of the travel sensor
housing 3, the travel sensor is in the 0° position.
3. The electrical turn range is 90° clockwise of this position.
7 / 64
1436 cPos
4.2.3 Mounting the positioner 4.3.5 Connecting the travel sensor
The 5-pin M12 travel sensor plug must be connected to the
5-pin M12 positioner socket.
5 Pneumatic connections
View X
1. Place the adapter 4 on the shaft of the travel sensor.
4 3
2. Place the positioner with the travel sensor and mounting 1
5
2
4.3.4 Mounting the mounting bracket To ensure safe restarting of the positioner following
interruption of the power supply, the power
7 Ensure adequate stability of the base used for interruption must be longer than 3 seconds.
attachment.
7 The positioner must be protected against 1. Connect 24V DC supply voltage to plug X1.
mechanical stress by the operator. 2. Connect analogue input (set value input) 0/4-20 mA to plug
7 Do not use the positioner as a climbing support. X3.
3. If operating as a process controller, connect analogue input
1. Push the positioner connection adapter through the hole in (actual value input) 0/4-20 mA to plug X3.
the mounting bracket and attach it with the enclosed nut.
2. Use the bolt holes and appropriate fixings to attach the
mounting bracket securely.
8 / 64
1436 cPos
6.2 Supply voltage
Plug Pin Signal name Wiring
internal external
4
5
3 X1 1 24 V DC supply voltage 24 V DC
1 2 +
power
4 3 4 3
-
supply
1
5
2 X2 1
5
2 X1 3 GND
X1 X3
6.3 Set value input
(only effective for AUTO operating mode)
Plug Pin Signal name Wiring
internal external
X3 1 I+, set value input + 0/4 - 20 mA
- GND
X3 2 I-, set value input
9 / 64
1436 cPos
6.7.1 Use of actual value and set value inputs as digital Use of actual value input as digital input "In X"
inputs Plug Pin Signal name Wiring
The actual value and set value inputs can be used as digital internal external
X3 4 I-, actual value input + High-level (14...28 V DC)
inputs under the following conditions: Low-level (0...8 V DC)
Positioner AUTO 3
Digital inputs 1 and 2
Positioner MANUAL 3 3 Plug Pin Signal name Wiring
High
6.9 RS232 – Interface
Plug Pin Signal name Wiring
Low
8mA 11mA
X2 3 RxD, Receive Data
In order to address the two digital inputs "In W" and "In X" a
resistor (R=1.2KΩ±5%) must be connected in series with the X2 4 TxD, Transmit Data
input according to the wiring diagram. The switching levels are
> 11mA for a High-Signal and < 8mA for a Low-Signal. X2 5 GND
Special wiring – Use of set value input as digital input M12 socket, B-coded, 5-pin D-SUB connector 9-pin
"In W" X2
Plug Pin Signal name Wiring
internal external
X3 1 I+, set value input + 24 V DC voltage
(e.g. digital output PLC)
R=1.2KΩ±5%
Pv=1W
X3 2 I-, set value input - GND
X2 D-SUB
Special wiring – Use of actual value input as digital input X2 : 1 1
"In X" X2 : 2 2
X2 : 3 3
Plug Pin Signal name Wiring
X2 : 4 4
internal external
X3 3 I+, actual value input + 24 V DC voltage X2 : 5 5
(e.g. digital output PLC)
R=1.2KΩ±5%
Pv=1W
6
X3 4 I-, actual value input - GND
7
8
9
6.8 Digital inputs (optional)
The GEMÜ 1436 cPos has four digital inputs when a digital
input card is installed.
The actual value and set value inputs can be used as digital
inputs under the following conditions:
Control Operating Set value input as Actual value input as
system mode digital input "in W" digital input "in X"
Positioner AUTO 3
Positioner MANUAL 3 3
Process
AUTO
controller
Process
MANUAL 3
controller
X1 3 GND - GND
10 / 64
1436 cPos
7 Operation 7.2.2 Configuration level (Setup)
Various parameters can be set at this level (see Menu structure
7.1 Operating and display elements chapter 11.3) in order to realise optimal adaptation to the
2-line display application conditions.
8 Changing parameters
For the GEMÜ 1436 cPos the keys + ـ
are used to select the various menus according to chapter
11. Configuration menu.
The changes to the parameters required are made using
brackets that are put round the respective parameters.
Example:
7.2 Menu levels The operating mode is to be changed from OFF to Auto.
The GEMÜ 1436 cPos uses two menu levels. These are the
working level (Mode) and the configuration level (Setup).
A (AUTO):
The positioner is triggered by an external set value signal when
using the AUTO operating mode.
The positioner also processes an external actual value signal
when operated as a process controller.
M (MANUAL):
If MANUAL is selected together with operation as a positioner,
the valve can be opened and closed manually using the + and
– keys.
If MANUAL is selected together with operation as a process
controller, the set value can be changed manually using the +
and – keys.
F (MANUAL-FLEX):
If MANUAL-FLEX is selected together with operation as a
positioner, the valve can be opened and closed manually using
the + and – keys.
If MANUAL-FLEX is selected together with operation as a
process controller, the set value can be changed manually
using the + and – keys.
T (Test):
In TEST mode in the standard setting as positioner the device
may be operated manually for test purposes.It does not
process any external input signals
and works as a mere positioner.
OFF:
If switched to OFF the positioner is in pause mode and then
does not react to any changes to the input signals.
11 / 64
1436 cPos
9 Commissioning 9.2.1 Automatic initialisation
If the GEMÜ 1436 cPos is delivered fully mounted Tip for use:
to a valve ex works, it is already preset at the During automatic initialisation of actuators whose
factory (at a control pressure of 5.5 - 6 bar without travel is not continuous (i.e. with undefined stops,
operating pressure) and is therefore ready for e.g. with large size butterfly valves) the end
operation. A reinitialisation (see chapter 9.2.1) positions cannot be clearly detected.
is recommended if the plant is operated with a In this case manual initialisation by the operator
different control pressure or if the mechanical with sequential movement through the menu (see
end positions have been changed (e.g. seal chapter 9.2.2) should be used.
replacement on the valve or actuator replacement).
1. Turn on the pneumatic control air supply (observe maxi- Automatic initialisation can also be carried out by
mum control pressure for the positioner and the valve!). quick commissioning (see Quick Commissioning
2. Switch on the 24V DC power supply [plug X1, pin 1 (+) and on page 2 of the GEMÜ 1436 cPos).
pin 3 (-)]. The positioner adapts to the valve when automatic initialisation
3. Specify an analogue set value 0/4-20 mA. is started. All parameters are automatically scanned.
4. Specify an analogue actual value (only when operating as a This procedure can take a few minutes, dependent on the
process controller) 0/4-20 mA. valve.
● Prior to commissioning, familiarise yourself with the
9.1 General information operation of the GEMÜ 1436 cPos (see chapter 7).
● For automatic initialisation proceed as described on the next
Exhaust air and cycle duties generate noise!
page.
ä Hearing damage.
● Wear hearing protection.
DANGER 9.2.2 Manual initialisation
When manual initialisation is started, the positioner runs
In order to be able to make changes to settings and
through an initialisation program that is similar to the automatic
parameters for the GEMÜ 1436 cPos no parts of
initialisation. However the different program steps for the
the housing need be taken apart or opened!
manual initialisation must be started and confirmed by the
All parameter settings and the initialisation are
retained even in the event of voltage cutoff. operator using the + key.
● Manual initialisation should only be used if the automatic
initialisation does not achieve satisfactory control features or
9.2 Initial commissioning without factory setting
in case of leakage problems.
(when supplied without a valve) ● The menu items goClose and goOpen should be carried
It may be necessary to close the internal positioner out several times for very small valve strokes in order to
throttles a little (V1 and V2 for single acting ensure an optimum adaptation of the positioner to the valve.
actuators and V1, V2, V3 and V4 for double acting ● Emergency operation of the automatic control system is
actuators) if the actuator volume is very low in possible, if at least the goClose and goOpen menu items
order to increase the valve operating time. This are carried out.
can be done during initialisation in "adjTime". A ● In order to prevent incorrect operation, the parameters from
modification to the throttle setting independent of manual initialisation are only accepted when they comply
initialisation may lead to error messages and/or with the requirements for correct function.
poor control results. It is therefore recommended ● Prior to commissioning, familiarise yourself with the
to carry out initialisation again after every throttle
operation of the GEMÜ 1436 cPos (see chapter 7).
change.
● For manual initialisation proceed as described on the next
Experience has shown that valve operating times of page.
about 1-2 seconds lead to optimal control results.
It may not be possible to reach this operating time
range for large-volume actuators.
12 / 64
1436 cPos
Valve can
be opened
and closed
Auto NO B
goClose XX.X% goOpen XX.X%
Auto DNO
DNO Valid? OK ESC Valid? OK ESC
NC
NO
13 / 64
DA
Boost NC
Boost NO
initialisation
1436 cPos positioner 1436 cPos positioner Init Valve Man Init Pilot findCoeff X.X % adjTime X.X: X.X
OK ESC OK ESC OK ESC
is ready for operation is ready for operation
and reacts to the and reacts to the
externally specified externally specified
Manual initialisation
set value. set value.
Automatic Initialisierung
It must be activated It must be activated
separately for the
"process controller"
ManuelelInitialisierung separately for the
"process controller"
2 x betätigen
Press twice
Automatische
option (see chapter option (see chapter
15.2). 15.2).
Press twice
1436 cPos
9.2.4 Error messages during initialisation
No. Error text Description Condition for the occurrence of the Error cause
error
Parameter "CtrlFn" is set to AUTO
and a valve with control function 3 is
The pneumatic connections for
The potentiometer has recognised, from which the actuator has
"CLOSED" and "OPEN" on the
Pot wrong dir recognised the wrong moved in the wrong direction.
020 valve have been switched or the
Error control function during Parameter "CtrlFn" is set for a fixed
parameter "Pot Dir" is set on "fall".
initialisation. control function. This set control function
The wrong control function is set.
is not in accordance with the control
function determined during initialisation.
The wrong control function is
set in the "CtrlFn" parameter. If
the parameter is set to AUTO,
An incorrect control Parameter "CtrlFn" is set for a fixed the 1436 cPos determines the
Wrong function function was recognised control function. This set control function corresponding control function and
021
Error during automatic is not in accordance with the control leaves it there (this does not apply
initialisation. function determined during initialisation. for control function 8 – carry out
manual initialisation in this case,
or set the parameter "CtrlFn" to
"DNO").
During automatic
● The minimum stroke was undershot Check the stroke of the pneumatic
Pneumatic Error initialisation of the valve
022 ● End positions cannot be reached system. Check leakage and end
Error a pneumatic error was
● Leakage in the system positions.
detected.
During automatic Check the pneumatic system for
Leakage
023 initialisation of the valve The positioner is in initialisation mode. leakage and carry out initialisation
Error
leakage was detected. again.
A cable break or short-
Cable break or short-circuit in the
TrvlSensErr circuit in the sensor
060 sensor connection (travel sensor)
Error connection (travel
detected.
sensor) was detected.
14 / 64
1436 cPos
9.2.5 Initialisation parameters Init Valve Error:
InitValve: An error was determined during initialisation.
Automatic or manual initialisation (adaptation of the positioner Operation is not possible.
to the valve) is started. Check the mechanical mounting and the pneumatic system.
Then carry out the initialisation again.
CtrlFn: Carrying out manual initialisation enables emergency
The control function type for the valve can be selected during operation.
manual initialisation (see table on page 16).
This setting also influences subsequent automatic Init Valve ESC:
initialisations. The initialisation was aborted by the user.
Emergency operation of the automatic control system is
goClose: possible, if at least the goClose and goOpen menu items are
The closed valve position is scanned during initialisation. carried out.
This function must be started with the + key if initialising
manually and then confirmed.
9.3 Initial commissioning with factory setting
goOpen: (positioner supplied mounted to the valve)
The open valve position is scanned during initialisation.
This function must be started with the + key if initialising If the GEMÜ 1436 cPos was already fully mounted
manually and then confirmed. to a valve in the factory, it is already factory
preset and therefore immediately operable. We
findFnct: recommend reinitialisation in order to compensate
(only available for automatic initialisation) control pressure differences.
The valve control function is determined. Please proceed as described in chapter 9.2.1.
findCoefficent: M
(only displayed if "adjTime" was carried out) or
The valve is checked for control features at various positions
between the end positions.
A: Positioner in M: Positioner in manual
CalPointQty: automatic mode mode
The quantity of calibration points when initialising can be
changed.
Example:
QtyCalPoint=9 means:
The valve will be examined for control features between the
end position stops in 9 positions (10 % steps here).
Init Pilot:
The minimum operating times for the internal pilot valves are
adjusted to the process valve.
This function must be started with the + key if initialising
manually.
After initialisation various messages may appear in the display
depending on the status determined at initialisation:
15 / 64
1436 cPos
Overview of initialisation parameter CtrlFn
Automatic initialisation Manual initialisation
Parameter Value Description
function function4)
Automatic search of the control
Complies with NC2) setting.
function during automatic
Automatic detection of the If the valve control function
Auto initialisation. Complies with manual
control function differs, do not use this
initialisation of control function 1
setting.
(NC).
Control function 1 (closed by
Automatic detection and
spring force) with automatic Control function 1 (normally
Auto NC modification of the control
adaptation/modification for closed)
function
automatic initialisation
Control function 2 (opened by
Automatic detection and
spring force) with automatic Control function 2 (opened by
Auto NO modification of the control
adaptation/modification for spring force)
function
automatic initialisation
Control function 3 (double acting)
Automatic detection and
with automatic adaptation/ Control function 3 (double
Auto DA modification of the control
modification for automatic acting)
function
initialisation
Control function 1 (closed by spring
Control function 1 (closed by
force) – for increased controller Automatic detection and
spring force) – with increased
Auto NC B3) air output (only 300 l/min) with modification of the control
controller air output (only 300
automatic adaptation/modification function
l/min)
during automatic initialisation
Control function 2 (opened by
CtrlFn
2)
Fixed control functions (NC, NO, DA, Boost NC and Boost NO) must match in terms of the actuator's control function. An incorrect assignment may lead to faults and/
or inverted action, and should therefore only be used if the correct control function is known. In case of doubt, give preference to an "auto" detection.
3)
On versions with 300 l/min flow capability (booster), double the number of pilot valves is fitted and connected in parallel. If, in these versions, a control function is set
for simple pilot valves, this leads to a reduction in the flow capability.
4)
A manual initialisation should only ever be carried out if you have not achieved satisfactory control characteristics with the automatic initialisation or this was aborted
due to an error message.
16 / 64
1436 cPos
10 Operating modes 10.5 Test mode (T:)
The GEMÜ 1436 cPos uses the operating modes A: AUTO, Test mode serves for test purposes to enable quick access to
M: MANUAL, F: MANUAL-FLEX, T:TEST and OFF. the basic settings as a positioner. Parameter changes in the
test mode are valid only in this operating mode.
Automatic operation
Automatikbetrieb
r3w3
Manual operation
manueller Betrieb
Mode
OFF
Service
1
Configuration menu
Konfigurationsmenü
17 / 64
1436 cPos
11 Configuration menu (Setup)
Various parameter values of the GEMÜ 1436 cPos can be changed in the configuration menu. The parameter name appears in
the top left line of the display and the parameter value on the right.
In order to enable immediate use of the GEMÜ 1436 cPos, the most common values were entered as factory settings.
The submenus which are only required for the process controller are only available for the design with integrated
process controller (PA01).
IR-Port Fieldbus
5.1 5.2
The configuration menu consists of five submenus with the following functions:
1. Service
This menu is used to read out all information/diagnostics regarding the positioner, the connected signals and errors that occur.
2. SetBasics
SetBasics is used to set the basic settings for the GEMÜ 1436 cPos such as the initialisation, selection of input signals and
resetting to factory settings.
3. SetFunction
The special positioner functions are activated or deactivated here and the control parameters set.
4. SetCalibration
SetCalibration is used to set the directions of action, characteristic curves, stroke limits and closing limits and error limit values.
5. Communication
The different communication options for the GEMÜ 1436 cPos can be set here.
After entering the factory codes, these codes can be changed by the operator at any time.
The access priorities needed are marked in the configuration menu.
In order to change the access codes, please refer to 13.1.2. Activating or deactivating the user access.
18 / 64
1436 cPos
Service
1
19 / 64
Active Level: 3
(0...10000) OK 0...10000 0...10000 0...10000
ActiveParaSet P1 min - Pot - max I w: XX.X mA I x: XX.X mA W Proc X W Pos X Pot Abs XX.X % Valve 1:2:3:4
0,0 % 100 % XX.X % XX.X % XX.X % XX.X%
Return Relais K1 : K2 In w : x : 1 : 2 Pos Ctrl Out Pos Ctrl In Proc Ctrl Out Proc Ctrl In
XX.X % XX.X %
1436 cPos
1436 cPos
11.4 Menu structure 2 SetBasics
20 / 64
r0w0 r0w0 r0w2 r0w2
Return Helptext ON HelpLanguage D AutoReturn 5min DLight On Key
ON...OFF D 1...60min On Key
GB On
N
Nur verfüg ba r wenn K1/K2 Func dies erford ert.
Only
Only available
ava ilab le when
whenrequired
req uired by
byK1/K2 func tion.
K1/K2 function.
r0w1 r0w1 R0w
AlarmMinK1 10.0 % AlarmMaxK1 10.0 % SSE1Time 5.0 s
X max X max
X min/max X min/max
SSE min SSE min
SSE max SSE max
SSE min/max SSE min/max
Active Active
Error Error
Warning Warning
SetFunction
3
Nur verfügb ar b ei Proc CtrlMode: ON
Only
Only aavailable
vaila ble when
when ProcCtrlMode:
Proc CtrlMode: ON
ON
r0w3 r0w2 r0w2 r0w3 r3w3 r3w3
ProcCtrlMode: OFF ProcCtrl PosCtrl DeadBand 1.0 % DigitalInput DigitalOutput CpyParaSet OFF AnalogOut Poti Return
21 / 64
P1<=P2
Only available
Nur verfüg ba r for
b eipositioner design
Reglera usführung P1=>P3
PA01 (m it integriertem
PA01 (with Prozessregler)
integrated process P1<=P3
Only ava ila b le for p ositioner d esign
controller) P1=>P4
PA01 (with integ ra ted p roc ess P1<=P4
Controller)
r0w3 r0 w 3 r0 w3 r0w3
In W OFF In X OFF In 1 OFF In 2 OFF Return
r0 w3 r0 w3 r0 w 3 r0w3
Pos P 1.0 Pos D 1.0 Pos T 100 ms MinPos 0.0 %
r0 w1 r0 w 1 r0w3
Return OpenTight: 100% CloseTight: 0% MaxPos 100.0 %
1436 cPos
1436 cPos
r0w3 r0w3 r0w3 r0w3 r0w3
Scaling OFF Decimalpoint 1 4mA = 0% 20mA = 100.0 % Return
Only
Nuravailable
verfügbar when ProcCtrlMode:
bei ProcCtrlMode: On ON
r0w3 r0w3 r0w3 r0w3 r0w3 r0w2 r0w2
X-Direction: rise W-Direction: rise W-Function: lin. Y-Direction: rise PotiDir rise OutMinPos 0.0 % OutMaxPos 100.0 %
22 / 64
SetCalibration Nur
Onlyverfügbar wenn
available W-Funktion:
when W-function:
free free
4 r0w3
Set W-free
Fieldbus WebServer
5.1 5.2
r0w3 r0w3
RS 232 Auto Bdrate RS 115200 ComPort Bluetooth BT Function PC/PDA State BT Name BT Code 0000 Return
PC/PDA
Auto 38400 Bluetooth Phone 1436 cPos 0000...9999
23 / 64
Serial 57600
115200
r0w3
Fieldbus OFF Return
ON / OFF
1436 cPos
12 Parameter table
Configuration
Display Function Value range Factory setting
level
AUTO
MAN
Mode Select operating mode MAN-FLEX AUTO
TEST
OFF
1 Service Submenu for displaying inputs and outputs
Displays the current active
ActiveParaSet P1 ... P4 P1
parameter set
Displays travel sensor
min-Pot-max
position in percent
Value of set value signal in
Iw
mA
Value of actual value signal in
I x*
mA as a process controller
Value of set value signal in
W Proc X*
relation to actual value signal
Comparison of set value and
W Pos X
valve position
Pot Abs Travel sensor position
I / O Status
V:1.1.1.1
version
Displays current serial
S/N xxx
number
TAG1 11-digit ID number can be set
TAG2 11-digit ID number can be set
*Only for activated process controllers
24 / 64
1436 cPos
Configuration
level Display Function Value range Factory setting
Init Valve
FindFunct The valve control function is
determined
AdjTime Scanning the operating times
Optimising the control
FindCoefficent
features
Setting the minimum operat-
Init Pilot ing times for internal pilot
valves
CalPointQty Quantity of calibration points 1...19 9
when initialising
D.Refresh Time for display refresh 0.1...1.0 s 0.1 s
DLight Setting the display lighting OnKey / On OnKey
Time for an automatic return
AutoReturn 1...60min 5min
to the working level - Setup
HelpLanguage Text language D / GB / N D
HelpText Display the help text ON / OFF ON
Configuration Display Function Value range Factory setting
level
3 SetFunction ProcCtrlMode* Switch process controller on ON / OFF OFF
or off
Submenu for setting process controller parameters
Proc-P KP amplification of the 0.0...100.0 0.5
process controller
Proc-I KI reset time for the process 0.0...999.9s 2.0s
ProcCtrl*
controller
Proc-D KD component of the process 0.0...100.0 0.0
controller
Proc-T Process controller Tv time 1...10000 ms 1000 ms
IxType Defines the type of actual OFF / RC / avr OFF
value filter
IxTime Filter time for actual value 0.10...20.00 s 0.10 s
input
Submenu for setting positioner parameters
Pos P P amplification of the 0.0...100.0 1.0
positioner
Pos D D amplification of the 0.0...100.0 0.0
positioner
Decay time of the D
PosCtrl
25 / 64
1436 cPos
Configuration Display Function Value range Factory setting
level
3 SetFunction Submenu for setting the digital outputs
K1 Switch Defines the type of output NC / NO NO
NO
P min
P max
P min/max
W min
W max
W min/max
Determines the function of X min
K1 Fn no
output K1 X max
X min/max
SSE min
SSE max
SSE min/max
Active
Error
Warning
Switch point that switches
AlarmMaxK1 0.2...99.8 % 10.0 %
after K1 is exceeded
Switch point that switches
AlarmMinK1 0.2...99.8 % 90.0 %
after K1 is undershot
Delay time between error
SSE1Time recognition and error 0.1…100.0 s 5.0 s
Digital Output
message to K1
K2 Switch Defines the type of output NC / NO NO
no
P min
P max
P min/max
W min
W max
W min/max
Determines the function of X min
K2 Fn no
output K2 X max
X min/max
SSE min
SSE max
SSE min/max
Active
Error
Warning
Switch point that switches
AlarmMaxK2 0.2...99.8 % 10.0 %
after K2 is exceeded
Switch point that switches
AlarmMinK2 0.2...99.8 % 90.0 %
after K2 is undershot
Delay time between error
SSE2Time recognition and error 0.1…100.0 s 5.0 s
message to K2
Delay time between error
ErrorTime recognition and error 0.5...100 s 0.2 s
message
Function of the process valve
ErrorAction Close/Open/Hold Close
if there is an error message
Copies parameters to various
CpyParaSet working memories (P1/P2/
P3/P4)
Sets the function of analog
AnalogOut Poti / Ix Poti
output
26 / 64
1436 cPos
Configuration Display Function Value range Factory setting
level
Determines the direction of
4 SetCalibration
X-Direction* the actual value signal (rising/ rise / fall rise
falling)
Determines the direction of
W-Direction the set value signal (rising/ rise / fall rise
falling)
W-Function The control curve is defined Lin./1:25/1:50/free lin.
W 0 % 0...100 % 0.0 %
W 10 % 0...100 % 10.0 %
W 20 % 0...100 % 20.0 %
W 30 % 0...100 % 30.0 %
W 40 % 0...100 % 40.0 %
10 control curve points can
Set W-free W 50 % 0...100 % 50.0 %
be programmed as desired
W 60 % 0...100 % 60.0 %
W 70 % 0...100 % 70.0 %
W 80 % 0...100 % 80.0 %
W 90 % 0...100 % 90.0 %
W 100 % 0...100 % 100.0 %
Determines the direction of
Y-Direction* the process controller output rise / fall rise
(rising/falling)
Defines the direction of the
PotiDir actual value potentiometer of rise / fall rise
the valve
Valve position at actual value
OutMinPos 0...100 % 0.0 %
output signal 0/4mA
Valve position at actual value
OutMaxPos 0...100 % 100.0 %
output signal 20mA
Switch-off limit for cable
I Min W break recognition of the set 0.0...22.0 mA 3.5 mA
value
Switch-off limit for excess
I Max W current recognition of the set 0.0...22.0 mA 20.5 mA
value
Switch-off limit for cable
I Min X break recognition of the 0.0...22.0 mA 3.5 mA
actual value
Switch-off limit for excess
I Max X current recognition of the 0.0...22.0 mA 20.5 mA
actual value
Submenu for scaling the actual value and set value display
Scaling Switches the scaled display on ON / OFF OFF
Determines the number of
Scaling
Configuration
Display Function Value range Factory setting
level
Fieldbus
27 / 64
1436 cPos
13 Explanation of parameters
Mode:
It is possible to choose between the operating modes AUTO (A:), MANUAL (M:), MANUAL-FLEX (F), TEST (T:) and OFF
(pause mode).
13.1 1 Service
I / O Status
1.1
ActiveParaSet:
Displays the current active memory which is read off.
min-Pot-max:
Displays the minimum and maximum travel sensor position in percent. For perfect operation, this value must lie between 2 % and
98 %.
I w:
Displays the value of the current set value signal in mA.
I x:
Displays the value of the current actual value signal (when operated as a process controller).
W Proc X:
Displays the value of the current set value signal compared to the current actual value signal (when operated as a process
controller).
W Pos X:
Displays the value of the current set value signal compared to the current valve position in %.
Pot Abs:
Displays the current travel sensor position (Caution, this value may be different to the Pos x value as the valve does not
make full use of the full 0-100 % range of the travel sensor).
Valve:
Displays the current position of the internal pilot valves ( = valve open).
If the deviation is too large, this is shown by a dot on the left-hand side or right-hand side of the display. In this case, the
controller can no longer work. All parameters on the control system route must be checked.
If the deviation is too large, this is shown by a dot on the left-hand side or right-hand side of the display. In this case, the
controller can no longer work. All parameters on the control system route must be checked.
In w:x:1:2
Displays the current conditions of the digital inputs ( = Signal High).
Relay:
Displays the current position of the internal relays K1 and K2 ( = Relay switched).
28 / 64
1436 cPos
13.1.2 Activating or deactivating the user access
SETUP
I / O Status Login
1.1 1.2
The configuration level of the GEMÜ 1436 cPos is protected in certain areas by various codes against improper changing of
parameters.
All menu items are marked by symbols indicating their write and read protection.
Example:
r0w2
X-Input: 4-20 mA
0-20 mA
4-20 mA
Code:
Enter code for user access. The currently released user level is displayed at Active Level.
Example:
In Active Level 0 the positioner is disabled in all three user levels.
Only the parameters marked by the symbol r0w0 can be read and changed.
Logout:
Serves to log out of write protected and read protected areas in the menu. This function disables various menus depending on the
user level activated.
User level 0 is displayed in parameter Active Level.
NewCode1:
Enter the new code for the lowest user level (user level 1) (factory setting 0).
NewCode2:
Enter the new code for the medium user level (user level 2) (factory setting 0).
NewCode3:
Enter the new code for the top user level (user level 3) (factory setting 0).
Factory setting 0 means that all three codes are assigned 0. This means that all parameter menus are released.
29 / 64
1436 cPos
Example:
If user level 2 is to be disabled, user level 2 and also user level 3 must be assigned a code.
During activation or deactivation of the user levels via the RS232-interface other codes can be assigned in the same
way as the direct input of codes via the GEMÜ 1436 cPos keypad.
This ensures specific disabling of the use of the positioner either directly via the positioner or via the RS232-interface
depending on the type of operation.
The codes for operation via the RS232-interface can only be assigned, activated or deactivated via the RS232-interface. The
codes for direct operation via the GEMÜ 1436 cPos keypad can only be assigned, activated or deactivated via the keypad on the
unit itself.
ErrorList:
The positioner stores all error messages in this menu.
hrs:
The positioner operating hours are counted here.
Warnings:
The warning messages can be masked or displayed.
The positioner continues normal operation when a warning is given. Messages are stored in the ErrorList (see chapter 14 Error
messages).
Errors:
Error messages can be masked or displayed.
The positioner goes to the error mode when there is an error message and moves to the position defined under ErrorAction.
Messages are stored in the ErrorList (see chapter 14 Error messages).
SensTest:
Switches the monitoring of the sensor (travel sensor) ON or OFF.
The positioner goes to the error mode when there is an error message and moves to the position defined under ErrorAction.
Messages are stored in the ErrorList (see chapter 14 Error messages).
Enable1: Sensor monitoring activated
Disable: Sensor monitoring deactivated
ClearErrorList:
Use + to delete the positioner error list.
13.1.4 Display serial number, software version and ID and enter TAG no.
SETUP
V: X.X.X.X:
Displays the current software release.
S/N:
Displays the positioner serial number.
TAG1:
An 11-digit TAG number can be entered for identification of the positioner.
TAG2:
An 11-digit TAG number can be entered for identification of the positioner.
30 / 64
1436 cPos
13.2 2 SetBasics
SETUP
X-Input:
Defines the type of actual value input signal 0-20 mA / 4-20 mA.
13.2.2 Reset
Default:
Serves to reset the positioner to the factory settings. All values changed by the operator are consequently deleted. An initialisation
that has already taken place will also be deleted.
Only the parameter set currently stored in the working memory is reset, however. Stored parameter sets remain unchanged (see
chapter 13.3.7).
13.2.3 Initialisation
InitValve:
Automatic or manual initialisation (adaptation of the positioner to the valve) is started.
See chapter 9.2.1 - 9.2.3.
DLight:
The features of the display lighting can be switched between the following settings:
OnKey – Display lighting is activated by pressing a key. The display lighting remains activated after the last key is pressed for the
period set using AutoReturn.
On – The display lighting is permanently activated.
AutoReturn:
The time for the automatic return to the working level after last activating a key can be set. This time setting is also effective for the
display lighting (DLight).
HelpLanguage:
The help text language may be selected between D-German,
GB-English and N-Norwegian.
HelpText:
The help texts that appear as a default in the second line of the display can be masked.
If the help texts are masked, the key assignment is displayed.
31 / 64
1436 cPos
13.3 3 SetFunction
SETUP
ProcCtrlMode:
Switches the process controller on or off.
ProcCtrl:
Submenu for setting process controller parameters. Only available when ProcCtrlMode: is ON.
Proc-P:
Indicates the KP amplification of the process controller.
Proc-I:
Indicates the Ti reset time for the process controller.
Proc-D:
Indicates the Kd process controller differential component.
Proc-T:
Indicates the Tv delay time for the process controller. Only available if Proc-D > 0.
IxType:
Defines the type of actual value input filter.
OFF:
Actual value input filter deactivated.
Unfiltered signal input
IxType [OFF]
IxType [OFF]
RC:
The actual value input signal is filtered via a low-pass filter.
Unfiltered signal input
IxType [RC]
IxTime
Filtered signal input
Avr:
The actual value input signal is calculated by averaging.
Unfiltered signal input
Unfiltered signal input
IxType [avr]
IxType [avr]
IxTime IxTime
Filtered signal input Filtered signal input
IxTime:
Defines the filter time for the actual value input.
32 / 64
1436 cPos
13.3.2 Setting the positioner parameters 13.3.3 Setting the dead zone
PosCtrl: DeadBand:
Provides parameters for the positioner. Defines the permissible deviation – dead zone between set
value and actual value.
Pos P: Effects both the positioner and the process controller.
Corresponds to the positioner’s KP amplification.
The optimum value is determined by the positioner during The height of the system deviation should always
initialisation. correspond to the requirements of the valve and the
control circuit. It is recommended that you do not
Pos D: set a value of < 1.0% since this could (especially
Corresponds to the positioner’s D amplification. for actuators with discontinuous movement profiles)
cause oscillating control characteristics. This could
Pos T:
Corresponds to the decay time for the positioner’s D put a great deal of stress on the internal pilot valves
component. and cause them to reach the end of their service
life more quickly.
MinPos: Basically: the smaller the fixed value, the higher the
Defines the lower position of the control range (serves as a wear and the shorter the service life. Therefore, the
closing limit). value should be set only as accurate as needed.
MaxPos:
Defines the upper position of the control range (serves as a 13.3.4 Setting the optional digital input parameters
stroke limit). Digital Input:
Physical Submenu for setting the digital inputs
stroke
x [%]
In W:
100 Defines the functions of the High signal at digital input In
Unlimited stroke
W (connection at set value input, only effective for manual
80 operation).
In X:
60 Defines the functions of the High signal at digital input In X
(connection at actual value input, only effective when operating
Limited stroke
40 as a positioner)
In 1:
20 Defines the functions of the High signal at digital input 1
Set value w [%]
In 2:
0 Defines the functions of the High signal at digital input 2
20 40 60 80 100
OpenTight and CloseTight: Function at Function at
Parameter Function
Determines the close tight function areas (complete Low signal level High signal level
pressurization or ventilation of the actuator). Digital
With this function the valve can be moved into the seat using OFF inputs
the maximum possible actuator force.The close tight function deactivated
can be activated for one end or both end positions. Sets the
Example: positioner OFF:
ON:
If the setting CloseTight 0.5 % and OpenTight 99.5 % is made, OFF/ON to the Positioner in
the valve closes or opens fully according to the following Positioner active
pause pause mode
diagram. mode
The hysteresis is 1 %. Safe:
Moves the
Positioner moves
Stroke x positioner ON:
[%] Safe/ON to the position
into a safe Positioner active
100 defined under
position
Error Action
Loads
parameter
ParmSetB0 sets into
working
memory
See following table
Loads
parameter
ParmSetB1 sets into
working
memory
0
0.5 1.5 98.5 99.5 Set value w [%] Function of
Ix:
the actual Poti:
If the control characteristic curve (W function chapter 13.4.2) is Poti / Ix Process actual
value Valve position
changed to the values 1:25 or 1:50, the CloseTight value should value
output
be set at >2.0 (if the characteristic curve is 1:50) or >4.0 (if the
characteristic curve is 1:25), in order to shut the valve fully. Current signal for Current signal for Memory which is
ParmSetB1 ParmSetB0 read out
0 0 P1
0 1 P2
1 0 P3
1 1 P4
33 / 64
1436 cPos
Before a different parameter set can be loaded, K2 Switch:
it must first be copied to the appropriate memory Defines the output contact type.
(see chapter 13.3.7 CpyParamSet). NO – make contact or NC – break contact
AlarmMinK1:
Sets the switch point in % under which output K1 is switched.
AlarmMaxK1:
Sets the switch point in % over which output K1 is switched.
SSE1Time:
Determines the delay time for output K1 between error
recognition and error message for a permanent system
deviation.
34 / 64
1436 cPos
Switching behaviour of outputs K1 and K2 when scanning the system deviation SSE:
AlarmMaxKx
AlarmMinKx
SSEmax
SSEmin
SSEminMax
ErrorAction:
Defines the behaviour of the valve if there is an error message.
Close: Valve is vented
Open: Valve is pressurized
Hold: Valve remains at its current position.
The GEMÜ 1436 cPos automatically stores all parameters in working memory P1.
35 / 64
1436 cPos
13.4 4 SetCalibration
SETUP
X-Direction:
Defines the direction of the actual value signal (rising / falling). Only available when positioner is working as a process controller.
60 12 X- DirecƟon [fall]
40 8
20 4
Stroke
Hub x [%]x [%] Linear and
Lineare Equal-Percentage
u. gleichprozentige characteristic control curves
Kennlinien
120,0
100,0 100,0
100
90
Linear
linear
80,0 80
72,5
70
67,6
60,0 60
50
1:25 52,5
45,7
40,0 40
38,1
30 30,9
27,6
1:50
20,0 20 20,0 20,9
14,5 14,1
10 10,5 9,6
7,6 6,5
4,0 5,5 4,4
2,0 3,0
0,0 0
0 20 40 60 80 100 120
Set value
Sollwert w [%]
w [%]
In order to be able to close the valve fully at an equal % selection of 1:25 or 1:50, the close tight function (see chapter 13.3.2) must
be set to the value >2.0 (for characteristic 1:50) or >4.0 (for characteristic 1:25).
SetW-free:
Eleven calibration points on the control curve can be programmed as required.
Y-Direction:
Defines the direction of the process controller output (rising / falling). An inverted process control system can be realized.
36 / 64
1436 cPos
13.4.3 Defining the direction of the travel sensor 13.4.6 Scaling the actual value and set value display
Pot Dir: Scaling:
The direction of the actual value potentiometer can b Submenu for scaling the actual value and set value display.
e defined.
Scaling:
13.4.4 Defining the actual value output signal Defines whether the actual and set value display is to be
displayed as scaled variable or in percent.
If a higher value is entered for OutMinPos than for ON:display as scaled variable; OFF: display in percent
OutMaxPos, the direction of the output signal is
inverted. Decimalpoint:
Determines the number of digits displayed after the decimal
OutMinPos: point.
Defines the valve position at which an actual value signal of
4 mA is emitted at the output. 4 mA :
Defines the value which is displayed when there is a 0/4mA
OutMaxPos: signal.
Defines the valve position at which an actual value signal of
20 mA is emitted at the output. 20 mA :
Defines the value which is displayed when there is a 20mA
13.4.5 Determining switch points for error monitoring signal.
I Min W:
Defines the point below which the set value signal activates an
error message
I Max W:
Defines the point above which the set value signal activates an
error message.
I Min X:
Defines the point below which the actual value signal activates
an error message.
I Max X:
Defines the point above which the actual value signal activates
an error message.
Possible setting values for the freely scalable actual and set value inputs:
r0w3 r0w3 r0w3 r0w3 r0w3
Scaling OFF Decimalpoint 1 4mA = 0% 20mA = 100.0 % Return
r0w3 r0w3
4mA = 0% 20mA = 100.0 %
Return Scaling
Zurück zu SetCalibrat.
Setting range:
Einstellbereich: Available characters:
Verfügbarer Zeichenvorrat:
r0w3
-99.9...999.9
-99,9...999,9 0...9
X-Direction: rise at bei Decimalpoint
Decimalpoint 0: 0: A...Z
-9999...9999
-9999...9999 a...z
rise...fall
%
/
:
.
SetCalibration X°
4 X²
X³
Display when Scaling OFF is set: Display when Scaling ON (e.g. mbar) is set:
r3w3 r3w3
Mode A: w XX.X: x XX.X SETUP A: W XX.X mbar SETUP
Mode
AUTO AUTO X XX.X mbar
Automatikbetrieb Automatikbetrieb
Automatic operation Automatic operation
r3w3 r3w3
Manual operation
manueller Betrieb
Manual operation
manueller Betrieb
Mode Mode
OFF OFF
Service Service
1 1
Configuration
Konfigurationsmenü
menu Configuration
Konfigurationsmenü
menu
37 / 64
1436 cPos
13.5 5 Communication
SETUP
Bdrate RS:
Defines the baudrate of the serial connection.
38400 baud
Bdrate RS 57600 baud
115200 baud (Werkseinstellung)
ComPort:
Defines the type of communication connection
Bluetooth If you use a Bluetooth connection with a PC/
laptop, PDA or mobile phone
BT Function:
Defines the type of Bluetooth connection (only available for
positioner version with integrated bluetooth interface).
PC/PDA If you use a connection with a PC/laptop or PDA
Phone If you use a connection with a mobile phone
State:
Shows the current connection status (only available for
positioner version with integrated bluetooth interface).
Message No Module no communication module connected
connected communication module is
Init
initialised
ScanPhone Scanning available mobile phones
communication module was initialised
Init OK
correctly
Connect connection was established
BT Name:
The device name can be entered for a Bluetooth connection
(only available for positioner version with integrated bluetooth
interface). The parameter value [1436 cPos] is set at the
factory. In the ComPort [Auto] / Port [RS 232] setting the BT
name cannot be changed.
BT Code:
The PinCode can be entered for a Bluetooth connection
(only available for positioner version with integrated bluetooth
interface). The parameter value [0000] is set at the factory.
In the ComPort [Auto] / Port [RS 232] setting the PinCode
cannot be changed.
38 / 64
1436 cPos
14 Error messages
No. Error text Description Condition for the occurrence of the Error cause
error
000 NO ERROR There are no errors
010 Iw < 4 mA The set value signal is The positioner is in automatic mode A cable break at the set value input
Error lower than 4mA
011 Iw > 20 mA The set value signal is The positioner is in automatic mode The set value signal is higher than
Error higher than 20mA 20mA
012 Ix < 4 mA The actual value signal The process controller is active A cable break at the actual value
Error is lower than 4mA input
013 Ix > 20 mA The actual value signal The process controller is active The actual value signal is higher
Error is higher than 20mA than 20mA
Parameter "CtrlFn" is set to AUTO
and a valve with control function 3 is The pneumatic connections for
The potentiometer has recognised, from which the actuator has "CLOSED" and "OPEN" on the
020 Pot wrong dir recognised the wrong moved in the wrong direction. valve have been switched or the
Error control function during Parameter "CtrlFn" is set for a fixed parameter "Pot Dir" is set on "fall"
initialisation. control function. This set control function The wrong control function is set.
is not in accordance with the control
function determined during initialisation.
The wrong control function is
set in the "CtrlFn" parameter. If
the parameter is set to AUTO,
An incorrect control Parameter "CtrlFn" is set for a fixed the 1436 cPos determines the
021 Wrong function function was recognised control function. This set control function corresponding control function and
Error during automatic is not in accordance with the control leaves it there (this does not apply
initialisation. function determined during initialisation. for control function 8 – carry out
manual initialisation in this case,
or set the parameter "CtrlFn" to
"DNO").
During automatic ● Control air failed Check the stroke of the pneumatic
022 Pneumatic Error initialisation of the valve ● The minimum stroke was undershot system. Check leakage and end
Error a pneumatic error was ● End positions cannot be reached positions. Observe minimum actua-
detected. ● Leakage in the system tor control pressure.
Leakage During automatic Check the pneumatic system for
023 Error initialisation of the valve The positioner is in initialisation mode. leakage and carry out initialisation
leakage was detected. again.
The 1436 cPos tries to change the valve
position, but it changes in the wrong ● Leakage in the system
Air missing A failure of the direction. ● No compressed air
030 Warning compressed air was Warning: Dependent on the positioner’s ● Failure of the internal pilot valves
discovered. set value reaction time, the error may be ● Valve mechanically locked
acknowledged in the meantime. It then
recurs.
A cable break, short-
circuit or exceeded ● Wrong mounting kit
060 TrvlSensErr range in the travel ● Incorrect mounting
Error sensor connection or in ● Faulty travel sensor
the travel sensor was ● Faulty travel sensor connection
detected.
The error is only displayed for
1 minute when the controller is
200 Error EEPROM An error has occurred This error is generated if the calibration switched on and then disappears
with the external data from the IO card EEPROM could automatically. The automatic con-
Error EEPROM not be read. trol system still operates correctly,
but the controller must be sent to
GEMÜ for examination.
The message is generated if an
201 Intern.Error An error has occurred This has
information is displayed if an error
occurred while attempting to access EEPROM could not be read from or
Info with an EEPROM. an EEPROM. written to. Send the controller to
GEMÜ for repair.
Error text Description Condition for the occurrence of the Error cause
error
No signal at digital input Parameter In 1 is set to OFF / ON or
In 1 no Signal Connect signal to digital input In 1
In 1 Safe / ON
No signal at digital input Parameter In 2 is set to OFF / ON or
In 2 no Signal Connect signal to digital input In 2
In 2 Safe / ON
No signal at digital input Parameter In W is set to OFF / ON or
In W no Signal Connect signal to digital input In W
In W Safe / ON
No signal at digital input Parameter In X is set to OFF / ON or
In X no Signal Connect signal to digital input In X
In X Safe / ON
All error messages can be read in the menu item ErrorList (1 Service / 1.3 Diagnosis).
The menu item ClearErrorList (1 Service / 1.3 Diagnosis) can be used to clear the internal error memory.
39 / 64
1436 cPos
Occurence of the error in the "NoInit" menu
The error message is displayed in the "NoInit" menu. Pressing the + or ـkey switches off the error display and "NoInit" and the
current valve position are displayed. The valve can be moved/operated using the + and ـkeys.
The error message is superimposed again when the movement is finished. To complete the action the menu must be exited by
pressing the oder key.
NoInit XX.X%
15 Quick guide
15.1 Changing the set value signal and actual value signal
r0w0
Mode A: w XX.X: x XX.X SETUP
AUTO
Automatic operation
Automatikbetrieb
r0w3
Mode M: w XX.X: x XX.X
Man
Manual operation
manueller Betrieb
Mode
OFF
Service SetBasics
1 2
r0w3 r0w3
W-Input: 4-20 mA X-Input: 4-20 mA
0-20 mA 0-20 mA
4-20 mA 4-20 mA
Automatic operation
Automatikbetrieb
r0w3
ManualBetrieb
manueller operation
Mode
OFF
r0w3
ProcCtrlMode: OFF
ON...OFF
40 / 64
1436 cPos
r0w0
Automatikbetrieb
Automatic operation
r0w3
manueller Betrieb
Manual operation
Mode
OFF
Nur
Onlyverfügbar when
availablebei ProcCtrlMode:
ProcCtrlMode: ON ON
r0w3
ProcCtrlMode: OFF ProcCtrl
ON...OFF
41 / 64
r0w3
Proc-P: 0.50
0.1...100.0
r0w3
Proc-I: 2,0 s
15.3 Changing the control parameters (Proc P, Proc I, Proc D and Proc T)
0,1...999,9 s
r0w3
Proc-D: 0.0
0.0...100.0
r0w3
Proc-T: 1000 ms
1...10000 ms
1436 cPos
16 General information regarding control engineering
Reference variable w
Desired volumetric flow
Positioner
GEMÜ 1436 cPos
Controlled variable x
Current volumetric flow
16.2 Control engineering terminology controller reacts more swiftly and harder with a small
Reference variable (set value) w: proportional band. If a too small proportional band is chosen,
The input variable (set value) for the control circuit. The this leads to oscillation of the control circuit.
controlled variable x should follow it with a pre-determined
dependency. Proportional action factor Kp:
Instead of the description proportional band, the expression
proportional-action factor Kp is used frequently.
Controlled variable (actual value) x:
The volumetric flow currently measured.
Conversion of Xp to Kp is:
Xp = 100[%] / Kp
Control difference xd:
or
The difference between reference variable w and controlled
Kp = 100[%] / Xp
variable x, xd = w - x
The Kp value tells us to what degree the controlled variable x
Manipulated variable y:
changes if the manipulated variable y is adjusted.
Input variable for the controlled system. The process controller
guidance to the positioner regarding the position in which the
Kp = ∆x / ∆y = x2 – x1 / y2 – y
triggered control valve must be driven in order to achieve the
desired volumetric flow.
In order to obtain a unit-independent relationship in the
equation above, x and y must be divided by their respective
Disturbance variable z:
maximum values (100 %).
An external variable that influences the controlled system that In this case, a high Kp value results in smaller deviation.
normally cannot be influenced (e.g. volume flow fluctuations). However, if the Kp value is set too high, it leads to an increased
tendency for the control circuit to oscillate.
16.3 Control parameters
Derivative action time Tv:
Explanation of parameters of GEMÜ 1436 cPos:
It is used to set the intensity of the D component.
Proc P: KP
Differential component (D component):
Proc I: Tn For an inverse controller (heating) the D component has the
Proc D: KD following effects:
Proc T: Tv ● If the controlled variable is reduced due to a disturbance
in the controlled system, the D component counteracts the
Proportional band Xp: change by creating a positive regulation ratio.
The proportional band tells us the extent to which the ● If the controlled variable increases due to a disturbance in
controlled variable x changes when the manipulated variable y the controlled system, the D component counteracts this
is adjusted. change by creating a negative regulation ratio.
Xp can be used to adapt the controller amplification to the The higher the derivative action time Tv is set, the stronger the
controlled system. dampening reaction.
If a small proportional band is selected, it has a large
manipulated variable y (e.g. 20mA) as a result, i.e. the
42 / 64
1436 cPos
Integral-action component (I component) Ki: Kp = Proc P Tn = Proc I Proc D Tv = Proc T
The I component Ki changes the controller regulation ratio
continuously until the actual value reaches the set value. P 0.50 x Kp,krit 0 0 0
The regulation ratio will be integrated upwards or downwards PI 0.45 x Kp,krit 0.85 x Tkrit 0 0
as long as a system deviation exists. The influence of the I PID 0.59 x Kp,krit 0.50 x Tkrit 0.59 x Kp,krit 0.12 x Tkrit
component will become larger the longer a system deviation
exists. The shorter the reset time Tn and the larger the system
deviation, the stronger (faster) the effect of the I component. ● If necessary, re-adjust the Kp and Tn values a little until the
The I component hinders a constant system deviation. control system shows satisfactory behaviour
43 / 64
1436 cPos
16.7 Control characteristics and transitory responses
xd Transit function
Sprungfunktion
XD
t
Control response
Regelverhalten Transitory response
Sprungantwort
P Kp * xd
Y0
t
Y
PD
Kp * xd ; y0 = 0
t
Y
PI
Kp * xd
t
Tn
DD-Anteil
component
Y
II-Anteil
component
PID
Kp * xd P component
P-Anteil
≈T v
t
Tn
44 / 64
1436 cPos
17 Table for changes to the factory settings
Configuration
Display Function P1 P2 P3 P4 Factory settings
level
2 SetBasics W-Input Type of set value signal 4-20 mA
X-Input Type of actual value signal 4-20 mA p
Quantity of calibration points when
CalPointQty 9
initialising
D.Refresh Time for display refresh X X X 0.1s
DLight Setting the display lighting OnKey
Time for an automatic return to the
AutoReturn 5min
working level
HelpLanguage Text language D
HelpText Display the help text ON
Configuration
Display Function P1 P2 P3 P4 Factory settings
level
3 SetFunction ProcCtrlMode Switch process controller on or off OFF
Proc-P KP amplification of the process controller 0.5
Proc-I KI reset time for the process controller 2.0s
Proc-D KD component of the process controller 0.0
Proc-T Process controller delay time 1000 ms
IxType Type of actual value filter OFF
IxTime Filter time for actual value input 0.10 s
Pos P P amplification of the positioner 1.0
Pos D D amplification of the positioner 0.0
Decay time of the D component of the
Pos T 100 ms
positioner
Lower position for stroke limitation as a
MinPos 0.0 %
control range
Upper position for stroke limitation as a
MaxPos 100 %
control range
CloseTight Lower close tight function 0%
OpenTight Upper close tight function 100 %
DeadBand Permissible system deviation 1.0 %
Determines the function of the digital
In W X X X OFF
input "In W"
Determines the function of the digital
In X X X X OFF
input "In X"
Determines the function of the digital
In 1 X X X OFF
input "In 1"
Determines the function of the digital
In 2 X X X OFF
input "In 2"
K1 Switch Defines the type of output K1 NO
K1 Fn Determines the function of output K1 no
45 / 64
1436 cPos
Configuration Display Function P1 P2 P3 P4 Factory settings
level
Switch point that switches after K1 is
AlarmMaxK1 10.0 %
exceeded
Switch point that switches after K1 is
AlarmMinK1 90.0 %
undershot
Defines the delay time between error
SSE1Time 5.0s
recognition and error message to K1
K2 Switch Defines the type of output K2 NO
K2 Fn Determines the function of output K2 no
Switch point that switches after K2 is
AlarmMaxK2 10.0 %
exceeded
Switch point that switches after K2 is
AlarmMinK2 90.0 %
undershot
Defines the delay time between error
SSE2Time 5.0s
recognition and error message to K2
Determines the delay between error
Error Time 0.2s
recognition and error message
Function of the process valve if there is
ErrorAction Close
an error message
Defines the function of the actual value
AnalogOut Poti
output
Configuration
Display Function P1 P2 P3 P4 Factory settings
level
Submenu for setting the fieldbus
5 Communication Fieldbus X X X OFF
address if available
Defines the type of communication
ComPort X X X BT
connection
Defines the type of Bluetooth
BT Function X X X PC/PDA
connection
The device name can be entered for a
BT Name X X X 1436 cPos
Bluetooth connection
The PinCode can be entered for a
BT Code X X X 0000
Bluetooth connection
46 / 64
1436 cPos
17.2 Set values for the freely programmable charac-
teristic curve
Configuration
level Display Characteristic curve point P1 P2 P3 P4 Factory settings
4 SetCalibration Set W-free 0% 0%
10 % 10 %
20 % 20 %
30 % 30 %
40 % 40 %
50 % 50 %
60 % 60 %
70 % 70 %
80 % 80 %
90 % 90 %
100 % 100 %
18 Disposal
l All parts must be disposed of according to
relevant local or national disposal regulations /
environmental protection laws.
l Pay attention to adhered residual material and
gas diffusion from penetrated media.
19 Returns
l Clean the positioner.
l Request a goods return declaration form from GEMÜ.
l Returns must be made with a completed declaration of
return.
If not completed, GEMÜ cannot process
7 credits or
7 repair work
but will dispose of the goods at the operator’s expense.
20 Information
Note on staff training:
Please contact us at the address on the last page for
staff training information.
47 / 64
1436 cPos
21 Technical data
General information Electrical data
Protection class to EN 60529 IP 65 Power supply
Weight approx. 600 g Power supply Uv = 24 V DC +10 % / -5 %
Dimensions L x W x H See dimensional drawing Duty cycle continuous duty
Installation position Optional Reverse battery protection yes
Directives Current consumption for flow rate code 01, 02
EMC Directive 2014/30/EU Ityp = 140 mA (@ 24 V DC)
Particulars for flow rate code 03
Ityp = 175 mA (@ 24 V DC)
Fail safe function in case of compressed air or power supply
failure (see table on page 59) Input signals
Analogue inputs
Operating conditions Set value / actual value 0/4 - 20 mA (selectable)
Input resistance 120 Ω
Ambient temperature 0 ... +60 °C (for device version code PA01)
Storage temperature 0 ... +60 °C Accuracy / Linearity ± 0.3 % of full flow
Control medium Quality classes to Temperature drift ± 0.3 % of full flow
DIN ISO 8573-1: 2010 Resolution 12 bit
Dust content ≤ 10 mg/m³/particle size ≤ 40 µm Reverse battery protection yes
(class 7)
Overload proof yes (up to ± 24 V DC)
Pressure dew point ≤ +3 °C (class 4)
Oil concentration ≤ 5 mg/m³ (class 4) Travel sensor input*
Air supply 1.5 ... 7 bar External travel sensor input 0…10 V DC
(for travel length code S01)
Air consumption 0 l/min (when idle)
Supply voltage output UP+ typ. 10 V DC
Air output 150 / 200 / 300 l/min
depending on version Short-circuit proof: yes
Resistance range ext. potentiometer 1…10 kΩ
Materials Input voltage range 0… UP+
Accuracy / Linearity ± 0.3 % of full flow
Housing cover PSU
Temperature drift ± 0.3 % of full flow
Housing base PP 30
Resolution 12 bit
Overload proof yes (up to ± 24 V DC)
Travel sensor integrated in directly mounted version
* Travel sensor input galvanically isolated from supply voltage,
Linear design not galvanically isolated from the set value/actual value inputs
Stroke 0-30 / 0-50 / 0-75 mm and actual value output.
Resistance R 3 / 5 / 5 kΩ Digital inputs
Minimum stroke ≤ 8 % of the travel length Function selectable via software
≥ 1 % of the travel length (DigIn 1; DigIn2; DigInW; DigInX) (Reference: GND X1:3)
Quarter turn design Voltage 24 V DC
Angle of rotation 0-93° Logic level "1" >14 V DC
Resistance R 3 kΩ Logic level "0" < 8 V DC
Input current typ. 2.5 mA DC (at 24 V DC)
Controller data Output signals
Analogue outputs
Positioner Actual value 4…20 mA
System deviation ≥ 0.1% (adjustable) Output type active
PD parameters adjustable Accuracy ± 1 % of full flow
Initialisation automatic or manual Temperature drift ±0.5 % of full flow
Process controller can be connected (version PA 01) Load resistor 600 Ω
Controller type continuous controller Resolution 12 bit
PID parameters adjustable Overload proof yes (up to ± 24 V DC)
Parameterisation at the device: Menu selection Short-circuit proof yes
context sensitive or help texts Digital outputs
at the PC: Internet MS Internet Explorer Switching output K1/K2 selectable via software
Operating and display elements Type of contact PNP
Text display Alphanumeric, 2-line display with 16 Switching voltage Power supply
digits each Switching current 0.5 A
with background light Drop voltage max. 2.5 V DC at 0.5 A
LED front, top Status, for Profibus-DP Overload proof yes (up to ± 24 V DC)
and DeviceNet option Short-circuit proof yes
LED front, bottom Status, for Bluetooth option Pull down resistance 120 kΩ
Keys 4 membrane protected fascia keys
Interfaces Functions
RS232 Parameterisation via web browser - Positioner + process controller combined and
Profibus DP Parameterisation / process data synchronized with each other
Transmission rates 9.6k /19.2k / 45.45k / 93.75k / 500k - Automatic or manual optimizing initialisation
1.5M / 3M / 6 M / 12 M Baud - Multiple point calibration for optimized valve control
DeviceNet Parameterisation / process data - Diagnostics, alarm messages
Transmission rates 125k / 250k / 500k Baud - Operation possible when controller is active
Bluetooth Parameterisation via web browser - 3 parameter sets can be saved and reloaded
- 3 user levels (access authorization)
- Operating hours counter, event list (for details see
operating instructions)
- Digital inputs (option) for variable function control for
automation
48 / 64
1436 cPos
22 Order data
Note
The GEMÜ 1436 cPos positioner can be directly or remotely mounted to linear or quarter turn actuators
Direct mounting
For direct mounting the following components are required which must be ordered separately:
B
D
GEMÜ 1436 S01Z...
GEMÜ 1436 PTAZ
Travel sensor mounting kit
Travel sensor mounting kit
C
GEMÜ 1436 S02Z
Connection kit
49 / 64
1436 cPos
A Order data - Positioner for direct mounting
50 / 64
1436 cPos
B Order data - Mounting kit for linear actuators
Footnote
Footnote
func tion
func tion
Actuator
Actuator
Control
Control
length
length
Travel
Travel
size
size
Type DN Order number Type DN Order number
51 / 64
1436 cPos
B Order data - Mounting kit for linear actuators
Footnote
func tion
Actuator
Control
length
Travel
size
Type DN Order number
Footnote
1) For control function DA use double acting positioner
(action code 3).
4) For control applications use positioner
with K number 2442
52 / 64
1436 cPos
C Order data - Connection kit
53 / 64
1436 cPos
Order data for remote mounting
For remote mounting the following components are required which must be ordered separately:
54 / 64
1436 cPos
E Order data - Positioner for quarter turn actuators
55 / 64
1436 cPos
G Order data - Mounting kit for linear actuators
Footnote
Footnote
func tion
func tion
Actuator
Actuator
Control
Control
length
length
Travel
Travel
size
size
Type DN Order number Type DN Order number
56 / 64
1436 cPos
G Order data - Mounting kit for linear actuators
Footnote
Footnote
func tion
func tion
Actuator
Actuator
Control
Control
length
length
Travel
Travel
size
size
Type DN Order number Type DN Order number
57 / 64
1436 cPos
H Order data - Travel sensor for quarter turn actuator
58 / 64
1436 cPos
23 Fail safe function
Fail safe function
No. Error Outlet A1 Outlet A2
Single acting: vented Single acting: non existent
1 Power supply failure
Double acting: vented Double acting: pressurized
Single acting: vented Single acting: non existent
2 Compressed air supply failure
Double acting: not defined Double acting: closed
This fail safe function is not a substitute for specific plant safety requirements.
59 / 64
1436 cPos
24 Application examples
24.1 GEMÜ 1436 cPos as process controller with 4-wire transmitter (GEMÜ 3021)
24 V DC
24 V DC
1436 cPos Intelligenter
1436 cPos Intelligent positioner
Stellungsregler Power supply
Spannungsversorgung
Intelligenter Stellungsregler
Intelligent positioner Spannungsversorgung
power supply
- +
-
+
4-20 mA
4 - 20 mA
Istwert
- Actual value
actual value
+
X3 Istwert
4-20 mA
- 4Sollwert
- 20 mA
+ Set value
setpoint
Sollwert
GEMÜ globe
GEMÜ Sitz-/ diaphragm valve+
/ Membranventil
+ GEMÜ
GEMÜ1436
1436cPoscPos
24.2 GEMÜ 1436 cPos s process controller with 2-wire transmitter (GEMÜ 3020)
1436
1436cPos
cPosIntelligent positioner
Intelligenter Stellungsregler
Intelligenter Stellungsregler
Intelligent positioner
- 2424VV DC
DC
Power supply
Spannungsversorgung
+ Spannungsversorgung
power supply
+
X1
- + Two wire
4-Leiter flowmeter
Durchflussmessgeräte
four wire flowmeter
2-Leiter Durchflussmessgeräte
4-20 mA
4 - 20 mA
- Actual value
Istwert
+
X3 Istwert
actual value
- 4-20 mA
4 - 20 mA
Set value
Sollwert
+ setpoint + 24 VDC
24 V DC
Sollwert Power supply
Spannungsversorgung
- Spannungsversorgung
power supply
GEMÜ
GEMÜ globe
Sitz- / /Membranventil
diaphragm valve
+
+ GEMÜ1436
GEMÜ 1436cPoscPos
60 / 64
1436 cPos
25 EU Declaration of Conformity
EU Declaration of Conformity
Hereby we, GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8
D-74653 Ingelfingen
declare that the product listed below complies with the following directive:
Joachim Brien
Head of Technical Department
61 / 64
1436 cPos
List of terms E
Electrical connections 8
A ErrorAction 26, 35, 46
Access authorisation 18 ErrorList 30
Actual value input 9 Errors 24, 31, 45
Actual value output 9 Error Time 46
Additional air throttle for A1 8 Exhaust air throttle for A1 8
Additional air throttle for A2 8 Explanation of signs 4
adjTime 16
Air missing 39 F
AlarmMaxK1 26, 34, 46 Fail safe function 5, 59
AlarmMaxK2 26, 35, 46 Fehlermeldungen 39
AlarmMinK1 26, 34, 46 Fieldbus 27, 38, 46
AlarmMinK2 26, 35, 46 findCoefficent 16, 32
Application examples 60 findFnct 16, 32
Applikationsbeispiele 60 Function 5
AUTO 16
Automatic operation 17 G
AutoReturn 25, 32, 45
Avr 33 goClose 16
goOpen 16
B
H
Bestelldaten 49
Boost NC 32 HelpLanguage 25, 32, 45
Boost NO 32 HelpText 25, 32, 45
BT Name 38, 46 hrs 24, 30
C I
CalPointQty 25, 32, 45 I Max W 27, 37, 46
Clear Error List 24 I Max X 27, 37, 46
CloseTight 25, 33, 45 I Min W 27, 37, 46
Code 30 I Min X 27, 37, 46
Commissioning 11 In 1 34
Communication 38 In 2 34
ComPort 27 Initialisation parameters 16
Configuration level 11 Init Pilot 16
Configuration menu 17 InitValve 16, 32
Control difference 42, 43–64 Init Valve Error 16
Controlled variable 42 Init Valve ESC 16
Control parameters 42 Init Valve Man 16
Control pressure 11 Init Valve OK 16
CpyParaSet 26, 35 Integral-action component 43
CtrlFn 16 Integral Anteil 43
In W 25
D In X 25
I w 28
DA 32 I x 28
DeadBand 25, 33, 45 IxTime 33
Decimalpoint 27, 37, 46 IxType 33
Default 25, 32
Delivery 5 K
Derivative action time 42
Diagnosis 39 K1 Fn 26, 45
Differential component 42 K1 Switch 9, 26, 34, 45
Differential equation 43 K2 Fn 26, 46
Digital Input 25, 34
Digital inputs 9
L
DigitalOutput 34 Leakage 12, 14, 39
Disturbance variable 42 Logout 30
Dlight 32
DLight 32, 45
D.Refresh 25, 32, 45
62 / 64
1436 cPos
M R
Manipulated variable 42 RC 33
MANUAL 11 Reference variable 42
Manual initialisation 14 Relay 29
Manuelle Initialisierung 12 Reset 32
Manufacturer's information 5 Reset time 43
MaxPos 33 RS232 10
Mechanical mounting 7
Menu levels 10 S
MinPos 33 Scaling 37
min-Pot-max 24, 28 Service 17, 19, 24
Mode 10 SetBasics 17, 20, 25
Mounting 7 SetCalibration 17, 22, 27, 36
Mounting bracket 8 SetFunction 17, 21, 25
Set value input 9
N Set W-free 27, 47
NC 16 S/N 31
New Code 18, 24, 45 Special wiring 10
NO 16 State 27, 38
NO ERROR 39 Storage 4
Non-return valve 8 Supply voltage 9
O T
OnKey 32 TAG1 31, 45
OpenTight 33 TAG2 31, 45
Operating modes 16 Technische Daten 48
Operation 10 Test 11
Optimisation of the controller 43 Test mode 17
Outgoing air throttle for A2 8 Transitory responses 44
OutMaxPos 27, 37, 46 Transport 4
OutMinPos 27, 37, 46 Travel sensor 7
Outputs 9
V
P Valve 28
Parameterbedeutung 28 Venting connection 8
Parameter change 17
Pause mode 17 W
PinCode 38, 46 Warnings 24, 31, 45
Plug X1 8 W-Direction 27, 36, 46
Plug X3 8 Webserver 38
Pneumatic connections 8 WebServer 38
Pneumatic Error 12, 14, 39 W-Function 27, 36
PosCtrl 33 W-Input 25, 31, 45
PosCtrlOut 24 Working connection 8
Pos D 33 W Pos X 24, 28
Positioner 8 W Proc X 24, 28
Pos P 33 Wrong function 12, 14, 39
Pos T 33
Pot Abs 24, 28 X
PotDir 46
Pot wrong dir 12, 14, 39 X-Direction 27, 36, 46
ProcCtrl 32 X-Input 25, 31, 45
ProcCtrlMode 32
ProcCtrlOut 24 Y
Proc-D 33 Y-Direction 27, 36, 46
Proc-I 25, 32, 45
Proc-P 25, 32, 45 Z
Proc-T 25, 33, 45
Ziegler-Nichols 43
Proportional action factor 42, 43
Proportional band 42
63 / 64
1436 cPos
Subject to alteration · 09/2016 · 88243865
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG · Fritz-Müller-Str. 6-8 · D-74653 Ingelfingen-Criesbach
Telefon +49(0)7940/123-0 · Telefax +49(0)7940/123-192 · [email protected] · www.gemu-group.com