0% found this document useful (0 votes)
216 views21 pages

Catalogue - MFD-Titan

Uploaded by

Cere_Ceric
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
216 views21 pages

Catalogue - MFD-Titan

Uploaded by

Cere_Ceric
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

MFD-Titan

The power of fusion.

1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1967 1976 1977 1983 1984 1989 1999

There’s a certain energy at Eaton. It’s the power of uniting some of the
world’s most respected names to build a brand you can trust to meet
every power management need. The energy created supports our
commitment to powering business worldwide.
Eaton is dedicated to ensuring that reliable, efficient and safe power is
available when it’s needed most. With unparalleled knowledge of
electrical power management across industries, experts at Eaton deliver
customized, integrated solutions to solve our customers’ most critical
challenges. Eaton.com/Electrical.

All of the above are trademarks of Eaton Corporation or its affiliates. Eaton has
a license to use the Westinghouse brand name in Asia Pacific. ©2012 Eaton Corporation.
Multi-function display

System overview

1 2

3
4
5
6

POW

BUS

MS

NS

2
Multi-function display
Display/operating unit, power supply unit/CPU module

MFD-Titan Ethernet gateway Bus modules


The multi-function display MFD-Titan EASY209-SE 2 EASY204-DP 3
can be used in the following
combinations: 24 V DC PROFIBUS DP connection as slave,
Serial interface, PSU/CPU module to 24 V DC
Power supply unit/CPU
Power supply unit/CPU + I/O modules Ethernet EASY221-CO
Power supply unit/CPU + display and CANopen connection, 24 V DC 5
operating unit EASY205-ASI
Power supply unit/CPU + display and
operating unit + I/O modules AS-Interface connection as slave 4
Page 4 EASY222-DN
I/O modules 1 DeviceNet connection, 24 V DC 6
24 V DC
100 - 240 V AC
12 digital inputs
4 usable as analog inputs
(DC versions)
4 relay outputs (max. 10 A,UL)
or 4 transistor outputs
1 analog output,
optional on DC versions
Spring-loaded terminals
Page 6
I/O modules with temperature 1
measuring
24 V DC
6 digital inputs
2 of which usable as analog inputs
2 Pt 100 or 2 Ni1000 RTD inputs
4 transistor outputs
1 Analog output, optional
Spring-loaded terminals
Page 6
Power supply unit/CPU module 1
24 V DC
100 - 240 V AC
Bus system easyNet optionally
on-board
Page 4
Display/keypad 1
24 V DC
Monochrome display
132 × 64 pixels
With or without keypad
Custom laser labeling possible

3
Multi-function display
Display/operating units, CPU, communication modules

Ordering

Display/keypad
Monochrome display 132 × 64 pixels with switchable backlight
IP65, removable silver front frame
Supply Description Part no. Price Std. pack Information relevant for export to North America
voltage Article no. See price
list
With keypad, with Moeller company MFD-80-B 1 off Product Standards IEC/EN see Technical
logotype 265251 Data; UL 508;
NEMA 4x in conjunction with MFD-XM-80 CSA C22.2 No. 142-M1987;
protective diaphragm 4 CSA C22.2 No. 213-M1987;
With keypad, without Moeller company MFD-80-B-X 1 off CE marking
logotype 284905 UL File No. E135462
NEMA 4x in conjunction with MFD-XM-80 UL CCN NRAQ
protective diaphragm 4 CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP65, in combination
with MFD-XM-80: UL/CSA
Type 4X
Without keypad, with Moeller MFD-80 1 off Product Standards IEC/EN see Technical
company logotype NEMA 4x 265250 Data; UL 508;
CSA C22.2 No. 142-M1987;
Without keypad, MFD-80-X 1 off CSA C22.2 No. 213-M1987;
without Moeller company logotype 284904 CE marking
NEMA 4x UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP65, UL/CSA Type 4X

Power supply unit/CPU module


Can be combined with display and control unit MFD-80-..
and I/O module; expandable: Digital and analog inputs/outputs
and bus systems
AS-Interface, CANopen, PROFIBUS-DP, DeviceNet;
bus system easyNet optional on-board IP20
Spring-loaded terminals
Supply Description Part no. Price Std. pack Information relevant for export to North America
voltage Article no. See price
list
100 - 240 V AC Program and MFD-AC-CP8-NT 1 off Product Standards IEC/EN see Technical
screen memory, 274092 Data; UL 508;
with easyNet CSA C22.2 No. 142-M1987;
100 - 240 V AC Program and MFD-AC-CP8-ME 1 off CSA C22.2 No. 213-M1987;
screen memory, 274091 CE marking
without easyNet UL File No. E135462
UL CCN NRAQ
24 V DC Program and MFD-CP8-ME 1 off CSA File No. 012528
screen memory, 267164 CSA Class No. 2252-01 + 2258-02
without easyNet
NA Certification UL Listed, CSA certified
24 V DC Program and MFD-CP8-NT 1 off Degree of Protection IEC: IP20, UL/CSA Type: -
screen memory, 265253
with easyNet
24 V DC Dual program and MFD-CP10-ME 1) 1 off
screen memory as 133801
MFD-...-CP8...,
without easyNet
24 V DC Dual program and MFD-CP10-NT 1) 1 off
screen memory as 133800
MFD-...-CP8...,
with easyNet
Note 1) For availability please inquire

4
Multi-function display
Communication modules

MFD-Titan
Supply Description For use Part no. Price Std. pack Information relevant for export to
voltage with Article no. See price North America
list

Power supply unit/communication modules


IP20, can be combined with display/operating unit MFD-80...
as remote text display
24 V DC With connection easy500 MFD-CP4-500 1 off Product Standards IEC/EN see Technical
cable easy700 274094 Data; UL 508;
(5 m, can be cut to CSA C22.2 No. 142-M1987;
length) CSA C22.2 No. 213-M1987;
24 V DC With connection easy800 MFD-CP4-800 1 off CE marking
cable EC4P 274095 UL File No. E135462
(5 m, can be cut to ES4P UL CCN NRAQ
length) CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
100 - 240 V AC With connection easy500 MFD-AC-CP4-500 1 off NA Certification UL Listed, CSA certified
cable easy700 286823 Degree of Protection IEC: IP20, UL/CSA Type: -
(5 m, can be cut to
length)
100 - 240 V AC With connection easy800 MFD-AC-CP4-800 1 off
cable EC4P 286824
(5 m, can be cut to ES4P
length)
24 V DC Without connection MFD-CP4 1 off
cable 280888
100 - 240 V AC Without connection MFD-AC-CP4 1 off
cable 286822
Customized inscription, user program
• Customized inscription of multi-function display with MFD-80-... MFD- 1 off UL/CSA certification not required
labeling software Labeleditor or MFD-CP8... COMBINATION-*
• Supply of multi-function display programmed with user MFD-CP10... 265260
program
Notes Procedure and ordering example for Labeleditor inscription software
Individually inscribe your device in 4 stages:
– Download the inscription software: www.eaton.com, keyword: “Labeleditor”
– Creation of label template (menu-guided in the software)
– Send the label template to the factory by email. The email address is automatically set for the selected product by the program. When your
template is sent, the Labeleditor issues a file name such as “EASY_12345.zip”. This file name is part of the article to be ordered (see Ordering
examples).
– Send order to the Eaton office or the electrical wholesalers.

Ordering example: MFD-Titan


MFD-80-B multi-function display with “company name”:
1 x MFD-COMBINATION-*
1 x MFD-80-B
1 x the file name “MFD_xxxxx.zip” issued by the Labeleditor

Accessories
1 Ethernet gateway
3
2 Connection cable
1
3 Programming software
4 PC programming cable
5 Inputs/outputs expansion
6 output expansion, bus module,
4 coupling module
2 4 7 Display/keypad
11 8 Power supply unit/CPU module
easyNet
9 I/O module
10 10 Memory card
11 easyNet
12 Switched-mode power supply unit
MFD Titan
easy 80
5 0 Power

9
8 2, 4
7 10 9 8 12
6
5

5
Multi-function display
I/O modules

MFD-Titan
P o w e r s u p p ly F o r u s e w ith I n p u ts O u tp u ts T e m p e r a tu r e Part no. Price Std. pack
Digital Of which Pt100 Relays 10 Transistor Analog range Article no. See price list
can be A (UL)
used as
analog
I/O modules
IP20, spring-loaded terminals

24 V DC MFD-CP8... 12 4 – 4 – – – MFD-R16 1 off


MFD-CP10... 265254
24 V DC MFD-CP8... 12 4 – – 4 – – MFD-T16 1 off
MFD-CP10... 265255
24 V DC MFD-CP8... 12 4 – 4 – 1 – MFD-RA17 1 off
MFD-CP10... 265364
24 V DC MFD-CP8... 12 4 – – 4 1 – MFD-TA17 1 off
MFD-CP10... 265256
100 - 240 V DC MFD-AC- 12 – – 4 – – – MFD-AC-R16 1 off
CP8... 274093
I/O module with temperature measuring
IP20, spring-loaded terminals
Temperature range configurable

24 V DC MFD-CP8... 6 2 2 – 4 – -40…+90 °C MFD-TP12-PT-A 1 off


as of device 0…+250 °C 106042
version 08, 0…+400 °C
MFD-CP10... 6 2 2 – 4 – -200…+200 °C MFD-TP12-PT-B 1 off
0…+850 °C 106043
6 2 – – 4 – -40…+90 °C MFD-TP12-NI-A 1 off
0…+250 °C 106044
6 2 2 – 4 1 -40…+90 °C MFD-TAP13-PT-A 1 off
0…+250 °C 106045
0…+400 °C
6 2 2 – 4 1 -200…+200 °C MFD-TAP13-PT-B 1 off
0…+850 °C 106046
6 2 – – 4 1 -40…+90 °C MFD-TAP13-NI-A 1 off
0…+250 °C 106047
Information relevant for export to North America

Product Standards IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987;CSA C22.2 No. 213-M1987; CE marking
UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -

6
Multi-function display
Accessories

MFD-Titan
Description For use with Part no. Price Std. pack Information relevant for export to
Article no. See price North America
list

Connecting cables
For connecting the MFD MFD-CP4-500-CAB5 1 off Product Standards IEC/EN see Technical Data;
(-AC)-CP4 or EASY209-SE with 280886 UL 508; CSA C22.2 No. 142-
easy500/easy700, M1987; CSA C22.2 No. 213-
5 m, can be cut to length M1987; CE marking
For connecting the MFD MFD-CP4-800-CAB5 1 off UL File No. E135462
(-AC)-CP4 or EASY209-SE with 280887 UL CCN NRAQ
easy800/MFD-..-CP8/CP10..., CSA File No. 012528
5 m, can be cut to length CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -
Memory cards
256-kB module MFD-…-CP8 EASY-M-256K 1 off Product Standards IEC/EN see Technical Data;
256279 UL 508; CSA C22.2 No. 142-
512-kB module MFD-CP10... EASY-M-512K1) 1 off M1987; CSA C22.2 No. 213-
134969 M1987; CE marking
UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -
Manuals
German MFD-Titan AWB2528-1480D 1 off
267187
E n g lis h M F D - T ita n AWB2528-1480GB 1 off
267188
Network connection cables
Length: 0.3 m Length: 0.3 m EASY-NT-30 1 off Product Standards IEC/EN see Technical Data;
256283 UL 508; CSA C22.2 No. 142-
Length: 0.8 m Length: 0.8 m EASY-NT-80 1 off M1987; CSA C22.2 No. 213-
256284 M1987; CE marking
UL File No. E135462
Length: 1.5 m Length: 1.5 m EASY-NT-150 1 off UL CCN NRAQ
256285 CSA File No. 012528
Bus termination resistor CSA Class No. 2258-02
8 pole, RJ45, 124 Ω easyNet EASY-NT-R 2 off NA Certification UL Listed, CSA certified
Connection to PIN 1 and PIN 2 256281 Degree of Protection IEC: IP20, UL/CSA Type: -
Data cable
4 x 0.14 mm², twisted pair, easyNet EASY-NT-CAB 1 off UL File No. E135462
AWG 26 256286 UL CCN NRAQ
Length: 100 m NA Certification UL Listed
Degree of Protection IEC: IP20, UL/CSA Type: -
Note 1) For availability please inquire

MFD-Titan
Description For use with Part no. Price Std. pack Information relevant for export to North America
Article no. See price
list
Bus connector plug
8 pole, RJ45 easyNet EASY-NT-RJ45 10 off Product Standards IEC/EN see Technical Data;
256280 UL 508; CSA C22.2 No. 142-
M1987; CSA C22.2 No. 213-
M1987; CE marking
UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -
– Crimping tool
For RJ45 plug EASY-NT- EASY-RJ45-TOOL 1 off
CAB 256282
EASY-NT-
RJ45

7
Multi-function display
Accessories

MFD-Titan
Description For use with Part no. Price Std. pack Information relevant for export to North America
Article no. See price
list
Point-to-point connection cable
Serial interface easy800 MFD-800-CAB5 1 off Product Standards IEC/EN see Technical Data;
for connecting MFD-…-CP8 266041 UL 508; CSA C22.2 No. 142-
MFD-…-CP8/CP10... to M1987; CSA C22.2 No. 213-
easy800 or M1987; CE marking
MFD-…-CP8/CP10..., UL File No. E135462
5 m, can be cut to UL CCN NRAQ
length CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -

MFD-Titan
Description Part no. Price Std. pack Information relevant for export to North America
Article no. See price
list
Switched-mode power supply units
Primary-switched mode, stabilized
Rated input voltage: EASY200-POW 1 off Product Standards IEC/EN see Technical Data;
50/60 Hz: 100 - 240 V 229424 UL 508; CSA C22.2 No. 142-
Rated output voltage: M1987; CSA C22.2 No. 213-
24 V/12 V DC M1987; CE marking
Rated output current: UL File No. E135462
0.35 A/20 mA UL CCN NRAQ
CSA File No. 012528
Rated input voltage: EASY400-POW 1 off
CSA Class No. 2252-01 + 2258-02
50/60 Hz: 100 - 240 V AC 212319
NA Certification UL Listed, CSA certified
Rated output voltage (residual ripple):
Power

24 V DC (± 3 %) Degree of Protection IEC: IP20, UL/CSA Type: -


Rated output current:
1.25 A EASY430-POW 1 off Product Standards IEC/EN see Technical Data;
110940 UL 508; CSA C22.2 No.
Rated input voltage: EASY500-POW 1 off 107.1-01; CE marking
50/60 Hz: 100 - 240 V AC 110941 UL File No. E300415
Rated output voltage (residual ripple): UL CCN NMTR,NMTR7
24 V DC (± 3 %) CSA File No. UL report applies to both US
Rated output current: 2.5 A and Canada
CSA Class No. 3211-87,3211-07
Rated input voltage: EASY600-POW 1 off NA Certification UL Listed, certified by UL for
50/60 Hz: 100 - 240 V AC 262399 use UL Listed, certified by
Rated output voltage (residual ripple):
UL for use in Canada
Power
24 V DC (± 3 %)
Degree of Protection IEC: IP20, UL/CSA Type: -
Rated output current: 4.2 A

Ballast
To increase the AC input current
6 channels, cable length up to 100 m EASY256-HCI 1 off Product Standards IEC/EN see Technical Data;
231168 UL 508; CSA C22.2 No. 142-
M1987; CSA C22.2 No. 213-
M1987; CE marking
UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2252-01
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -

8
Multi-function display
Accessories

MFD-Titan
Description For use with Part no. Price Std. pack Information relevant for export to North America
Article no. See price
list
PROFIBUS-DP data cable
Twisted pair, without plug, 2-core, ZB4-900-KB1 100 m
2 x 0.64 mm² 206983
(only suitable for fixed wiring)
100 m
PROFIBUS-DP bus connector plug
Pins, 9 pole ZB4-209-DS2 1 off
Cable entry, angled 90° 206982
Metallised insulated housing ZB4-209-DS3 1 off
Maximum transfer rate 12 MBit/s 217820
Integrated switch (accessible from the
outside) for the bus terminating resistors
Terminal block for two cable entries,
with straight or 90° angled cable entry, as
required
Connection plug
Bus connector plug between base unit and EASY-LINK-DS 1 off UL/CSA certification not required
expansion unit/bus module 221607
Fixing bracket
For screw fixing to mounting plate
3 fixing brackets ZB4-101-GF1 9 off UL/CSA certification not required
per easy400, 500, 600, 700, 800, EC4P, ES4P 061360
2 fixing brackets per easy200
3 fixing brackets per MFD...-CP8/CP10…
Telescopic clip
With 35mm top-hat rail to IEC/EN 60715 for M22-TA 1 off Product Standards IEC/EN 60947-5; UL 508;
mounting depth compensation when rear 226161 CSA-C22.2 No. 14-05;
mounting in CI-K… enclosures and cabinets. CSA-C22.2 No. 94-91;
Stepless adjustment via scale from CE marking
75 – 115 mm. UL File No. E29184
Screw and snap fastening UL CCN NKCR
CSA File No. 012528
CSA Class No. 3211-03
NA Certification UL Listed, CSA certified
Mounting rail to IEC/EN 60715
Mounting rail with cutout specifically for MFD...-CP8/CP10… for fixing
easy expansion units (2 space units)
Length: 142.5 mm
easy200 MFD-TS-144 1 off UL/CSA certification not required
274090
Protective cover
Transparent MFD-80… MFD-XS-80 1 off Product Standards IEC/EN see Technical Data;
Protection against 265259 UL 508; CSA C22.2 No. 142-
accidental actuation M1987; CSA C22.2 No. 213-
sealable M1987; CE marking
Application without front UL File No. E135462
frames UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Protective diaphragm
Transparent version for MFD-80… MFD-XM-80 1 off Product Standards IEC/EN see Technical Data;
harsh environmental 265258 UL 508; CSA C22.2 No. 142-
conditions and application M1987; CSA C22.2 No. 213-
in the food industry M1987; CE marking
For increasing the degree of UL File No. E135462
protection to NEMA 4X for UL CCN NRAQ
MFD-80-B CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL Listed, CSA certified
Degree of Protection IEC: IP65, UL/CSA Type 4X

9
Control relays, multi-function display
Display/operating units, CPU, communication modules

MFD-80, MFD-(AC)-CP...
MFD-80.. MFD-CP4… MFD-AC-CP4.. MFD-CP10..
unit MFD-AC-CP8.. MFD-CP8..
General
Standards EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
D im e n s i o n s ( W x H x D ) mm 86.5 x 86.5 x 21.5 (with 75 x 58 x 36.2 107.5 x 90 x 30 107.5 x 90 x 30
buttons) 86.5 x 86.5 x 20
(without buttons)
W e ig h t kg 0.13 0.16 0.14 0.14
Mounting 2 x 22.5 mm, display Plug-fitted to the Fitted on the fixing Fitted on the fixing
fastened using display fixing shaft shaft of the display shaft of the display
2° threaded fixing or on top-hat rail or on top-hat
rings. according to rail according to
Wall thickness: IEC/EN 60715, 35 mm IEC/EN 60715, 35 mm
without top-hat rail deep (without display) deep (without display)
(CPU) 1 – 6 mm
with top-hat rail
1 – 4 mm
Terminal capacity
S o lid mm2 – – 0.2/4 (AWG 24 - 12) 0.2/4 (AWG 24 - 12)
F le x ib le w ith fe r r u le mm2 – – 0.2/2.5 (AWG 24 - 12) 0.2/2.5 (AWG 24 - 12)
F la t- b la d e s c r e w d r iv e r mm – – 3.5 x 0.6 3.5 x 0.6
M a x . tig h te n in g to r q u e Nm – – – –
Ambient climatic conditions
O p e r a tin g a m b ie n t te m p e r a tu r e °C -25 - 55, low temperatures to IEC 60068-2-1, high temperatures to IEC 60068-2-2
Condensation Prevent condensation by means of suitable measures
LCD display °C -5 - 50
(clearly legible)
S to r a g e °C -40 - 70 -40 - 70 -40 - 70 -40 - 70
Relative humidity, non-condensing % 5 - 95 5 - 95 5 - 95 5 - 95
(IEC/EN 60068-2-30)
A ir p r e s s u r e ( in o p e r a tio n ) hP a 795 - 1080 795 - 1080 795 - 1080 795 - 1080
Ambient mechanical conditions
Protection type IP65 IP20 IP20 IP20
(IEC/EN 60529, EN50178, VBG 4)
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm Hz 10 - 57 10 - 57 10 - 57 10 - 57
Constant acceleration, 2 g Hz 57 - 150 57 - 150 57 - 150 57 - 150
Mechanical shock resistance (IEC/EN Shocks 18 18 18 18
60068-2-27) semi-sinusoidal 15 g/11 ms
Drop to IEC/EN 60068-2-31 Drop mm 50 50 50 50
height
Free fall, packaged (IEC/EN 60068-2-32) m 1 1 1 1
Mounting position Vertical or horizontal

10
Control relays, multi-function display
Display/operating units, CPU, communication modules

MFD-80, MFD-(AC)-CP...
MFD-80.. MFD-CP4… MFD-AC-CP4.. MFD-CP10..
unit MFD-AC-CP8.. MFD-CP8..
Electromagnetic compatibility (EMC)
Overvoltage category/ – – – –
pollution degree
Electrostatic discharge (ESD),
to IEC EN 61000-4-2
A ir d is c h a r g e kV 8 8 8 8
C o n ta c t d is c h a r g e kV 6 6 6 6
Electromagnetic V/m 10 10 10 10
fields (RFI),
to IEC EN 61000-4-2
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst to IEC/EN 61000-4-4
S u p p ly c a b le s kV 2 2 2 2
S ig n a l c a b le s kV 2 2 2 2
High-energy pulses (surge)
(IEC/EN 61000-4-5, Level 2)
Supply cables, symmetrical – 0.5 1 0.5
Radiated RFI, to IEC/EN 61000-4-6 V 10 10 10 10
Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance EN 50178
Back-up/accuracy of the real-time clock
Back-up time – – 1) 1)

Accuracy of the real-time clock at 55 °C s/day – – Normally ±5 s/day Normally ±5 s/day


(±0.5 h/Year) (±0.5 h/Year)
Repetition accuracy of timing relays
Accuracy of timing relay (of value) % – – ± 0.02 ± 0.02
Resolution
Range “S” ms – – 5 5
R a n g e “ M :S ” s – – 1 1
R a n g e “ H :M ” m in – – 1 1
Retentive memory
Write cycles of the retentive memory – – 1010 1010
(minimum) (read/write (read/write
cycles) cycles)
Notes For additional technical data EASY5… and EASY7… AWB2528-1508D, EASY8… AWB2528-1423D

1) 200 Backup time (hours)


25°C
180
160
55°C
Service life (years)
140
120
100
80
60
40
20
0
0 1 2 3 4 5 6 7 8 9 1 0 11 12 13 14 15 16 17 18 19 2 0

11
Control relays, multi-function display
CPU, communication modules

MFD-(AC)-CP...
MFD-CP4.. MFD-CP8.. MFD-AC-CP4..
unit MFD-CP10.. MFD-AC-CP8..
Power supply
Rated operational voltage Ue V 24 DC (-15/+20 %) 24 DC (-15/+20 %) 100/110/115/120//230/240 AC
(+10/-15 %)
P e r m is s ib le r a n g e V AC 85…264
P e r m is s ib le r a n g e V DC 20.4…28.8 20.4…28.8
R ip p le % ≦5 ≦5 –
Frequenc y Hz – – 50/60 (± 5%)
Input current
A t 115/120 V A C 60 H z mA – – Normally 90
A t 230/240 V A C 50 H z mA – – Normally 60
A t 24 V D C mA Normally 185 Normally 200 –
V o lta g e d ip s ( I E C /E N 61131- 2) ms 10 10 10
Heat dissipation
A t 115/120 V A C VA – – Normally 11
At 230/240 V A C VA – – Normally 15
A t 24 V D C W 1.5 3.4 –
Point-to-point connection
Stations 1 – –
Baud rate
e a s y 500, e a s y 700 M B it/s 9.6 kBaud – –
easy800, MFD, EC4P 19.2 kBaud – –
D is ta n c e m Max. 5 Max. 5 Max. 5
Potential isolation
From power supply Yes – –
From the connected device Yes – –
Terminal type Spring-loaded terminals – –
Power pulses
S ta tio n s Num- Max. 1 Max. 8 Max. 8
ber
Data transfer rate/distance – 1000 Kbit/s, 6 m 1000 Kbit/s, 6 m
500 Kbit/s, 25 m 500 Kbit/s, 25 m
250 Kbit/s, 40 m 250 Kbit/s, 40 m
125 Kbit/s, 125 m 125 Kbit/s, 125 m
50 Kbit/s, 300 m 50 Kbit/s, 300 m
20 Kbit/s, 700 m 20 Kbit/s, 700 m
10 Kbit/s, 1000 m 10 Kbit/s, 1000 m
Potential isolation
From power supply – Yes Yes
From the inputs – – Yes
From the outputs – Yes Yes
From PC interface, memory card, easyNet, – Yes Yes
easyLink
Bus termination (first and last station) – Yes Yes
Terminal type – RJ45, 8 pole RJ45, 8 pole

12
Control relays, multi-function display
I/O modules

MFD-(AC)-R..., MFD-T...
MFD-R16 MFD-AC-R16 MFD-T16 MFD-T.P..
unit MFD-RA17 MFD-TA17
General
Standards EN 61000-6-1/-2/-3/-4, EN 61000-6-1/-2/-3/-4, EN 61000-6-1/-2/-3/-4, EN 61000-6-1/-2/-3/-4,
IEC/EN 61000-4, IEC/EN 61000-4, IEC/EN 61000-4, IEC 60068-2-6, IEC
IEC 60068-2-6, IEC 60068-2-6, IEC 60068-2-6, 60068-2-27
IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27
D im e n s i o n s ( W x H x D ) mm 89 x 90 x 44 89 x 90 x 44 89 x 90 x 25 (built-in) 89 x 90 x 25 (built-in)
W e ig h t kg 0.15 0.15 0.14 0.14
Mounting Fitted into the power supply unit.
Terminal capacity
S o lid mm2 0.2/4 (AWG 24 - 12) 0.2/4 (AWG 24 - 12) 0.2/4 (AWG 24 - 12) 0.2/4 (AWG 24 - 12)
F le x ib le w ith fe r r u le mm2 0.2/2.5 (AWG 24 - 12) 0.2/2.5 (AWG 24 - 12) 0.2/2.5 (AWG 24 - 12) 0.2/2.5 (AWG 24 - 12)
F la t- b la d e s c r e w d r iv e r mm 3.5 x 0.6 3.5 x 0.6 3.5 x 0.6 3.5 x 0.6
Power supply
S o lid mm2 – – – –
F le x ib le w ith fe r r u le mm2 – – – –
F la t- b la d e s c r e w d r iv e r mm – – – –
Data cable
S o lid mm2 0.08/2.5 (AWG 28 - 12) 0.08/2.5 (AWG 28 - 12) 0.08/2.5 (AWG 28 - 12) 0.08/2.5 (AWG 28 - 12)
F le x ib le w ith fe r r u le mm2 0.08/1.5 (AWG 28 - 12) 0.08/1.5 (AWG 28 - 12) 0.08/1.5 (AWG 28 - 12) 0.08/1.5 (AWG 28 - 12)
Ambient climatic conditions
O p e r a tin g a m b ie n t te m p e r a tu r e °C -25 - 55, low temperatures to IEC 60068-2-1, high temperatures to IEC 60068-2-2
Condensation Prevent condensation by means of suitable measures
L C D d is p la y ( c le a r ly le g ib le ) °C
S to r a g e °C -40 - 70 -40 - 70 -40 - 70 -40 - 70
Relative humidity, non-condensing % 5 - 95 5 - 95 5 - 95 5 - 95
(IEC/EN 60068-2-30)
A ir p r e s s u r e ( in o p e r a tio n ) hP a 795 - 1080 795 - 1080 795 - 1080 795 - 1080
Ambient mechanical conditions
Pollution degree 2 2 2 2
Protection type (IEC/EN 60529, EN50178, IP20 IP20 IP20 IP20
VBG 4)
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm Hz 10 - 57 10 - 57 10 - 57 10 - 57
Constant acceleration, 2 g Hz 57 - 150 57 - 150 57 - 150 57 - 150
Mechanical shock resistance Shocks 18 18 18 18
(IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Drop to IEC/EN 60068-2-31 Drop mm 50 50 50 50
height
Free fall, packaged (IEC/EN 60068-2-32) m 1 1 1 1
Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD),
to IEC EN 61000-4-2
A ir d is c h a r g e kV 8 8 8 8
C o n ta c t d is c h a r g e kV 6 6 6 6
Electromagnetic fields (RFI), V/m 10 10 10 10
to IEC EN 61000-4-2
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst to IEC/EN 61000-4-4
S u p p ly c a b le s kV 2 2 2 2
S ig n a l c a b le s kV 2 2 2 2
Power pulses (surge) (IEC/EN 61000-4-5)kV kV 2 (supply cables, 2 (supply cables, 2 (supply cables, 2 (supply cables
symmetrical) symmetrical) symmetrical) symmetrical,
MFD-AC-CP8..)
Power pulses (surge), to IEC/EN 61000-4-5kV kV 0.5 (supply cables, 0.5 (supply cables, 0.5 (supply cables, 0.5 (supply cables,
symmetrical) symmetrical) symmetrical) symmetrical,
MFD-CP8..)
Radiated RFI, to IEC/EN 61000-4-6 V 10 10 10 10
Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance EN 50178

13
Multi-function display
I/O modules

MFD-(AC)-R..., MFD-T...
MFD-R16 MFD-T16 MFD-T...P... MFD-AC-R16
unit MFD-RA17 MFD-TA17
Digital inputs 24 V DC
Number 12 12 6
Inputs can be used as analog inputs 4 (I7, I8, I11, I12) 4 (I7, I8, I11, I12) 2 (I11, I12)
Potential isolation
From power supply No No No
Between digital inputs No No No
From the outputs Yes Yes Yes
From PC interface, memory card, Yes Yes Yes
easy NET, easyLink
Rated operating voltage Ue V DC 24 24 24
O n s ig n a l ” 0” Ue V DC < 5.0 (I1 - I6, I9 - I10), < 5.0 (I1 - I6, I9 - I10), < 5.0 (I1 - I4),
< 8 (I7, I8, I11, I12) < 8 (I7, I8, I11, I12) < 8.0 (I11, I12)
O n s ig n a l ” 1” Ue V DC > 15.0 (I1 - I6, I9 - I10), > 15.0 (I1 - I6, I9 - I10), >15.0 (I1 - I4),
> 8.0 (I7, I8, I11, I12) > 8.0 (I7, I8, I11, I12) > 8.0 (I11, I12)
Input current on signal "1"
I 1 to I 6 mA 3.3 (at 24 V DC) 3.3 (at 24 V DC) –
I 1 to I 4 mA – – 3.3 (at 24 V DC)
I 7, I 8 mA 2.2 (at 24 V DC) 2.2 (at 24 V DC) –
I 9, I 10 mA 3.3 (at 24 V DC) 3.3 (at 24 V DC) –
I 11, I 12 mA 2.2 (at 24 V DC) 2.2 (at 24 V DC) 2.2 (at 24 V DC)
Delay time from 0 to 1
Debounc e ON ms 20 20 20
Debounc e OFF ms Normally 0.1 (I1 - I4), normally 0.25 (I5 - I12)
Delay time from 1 to 0
Debounc e ON ms 20 20 20
Debounc e OFF ms Normally 0.1 (I1 - I4), Normally 0.1 (I1 - I4), Normally 0.1 (I1 - I4),
normally 0.4 (I5, I6, I9, normally 0.4 (I5, I6, I9, normally 0.2 (I11, I12)
I10), normally 0.2 I10), normally 0.2
(I7, I8, I11, I12) (I7, I8, I11, I12)
C a b le le n g th ( u n s h ie ld e d ) m 100 100 100
Frequency counters
Number 4 (I1, I2, I3, I4) 4 (I1, I2, I3, I4) 4 (I1, I2, I3, I4)
C o u n te r fr e q u e n c y kHz <3 <3 <3
Pulse shape Square Square Square
Incremental counters
Number 2 (I1 + I2, I3 + I4) 2 (I1 + I2, I3 + I4) 2 (I1 + I2, I3 + I4)
C o u n te r fr e q u e n c y kHz ≦3 ≦3 ≦3
Pulse shape Square Square Square
Signal offset 90° 90° 90°
High-speed counter inputs
Number 4 (I1, I2, I3, I4) 4 (I1, I2, I3, I4) 4 (I1, I2, I3, I4)
C o u n te r fr e q u e n c y kHz <3 <3 <3
Pulse shape Square Square Square
C a b le le n g th , s h ie ld e d m < 20 < 20 < 20
Digital inputs 115/230 V AC
Number 12
Status display LCD display
(if provided)
Potential isolation
From power supply No
Between digital inputs No
From the outputs Yes
From PC interface, memory card, Yes
easyNet, easyLink
Rated voltage L (sinusoidal)
O n s ig n a l ” 0” V AC 0 - 40
O n s ig n a l ” 1” V AC 79 - 264
R a te d fr e q u e n c y Hz 50 - 60
Input current on signal "1"
I 1 to I 12 mA 12 x 0.2 (at 115 V AC,
60 Hz), 12 x 0.5
(at 230 V AC, 50 Hz)
Delay time
Delay time (0 - 1/1 - 0) I1 - I12, 50/60 Hz 10/100
Max. admissible cable length (per input)
I 1 to I 12 m Normally 60

14
Control relays, multi-function display
I/O modules

MFD-R..., MFD-T...
MFD-R... MFD-RA17 MFD-TAP
unit MFD-T... unit MFD-TA17
Analog inputs Analog outputs
Number 4 (I7, I8, I11, I12) Number 1 1
2 (I11, I12) for
MFD-T(A)P
Potential isolation Potential isolation
From power supply No From power supply No No
From the digital inputs No From the digital inputs No No
From the outputs Yes From the digital outputs Yes Yes
From PC interface, memory card, Yes From PC interface, memory card, Yes Yes
easyNet, easyLink easyNet, easyLink
Input type DC voltage Output type DC voltage DC voltage
S ig n a l r a n g e V DC 0 - 10 S ig n a l r a n g e V DC 0 - 10 0 - 10
Resolution, analog V 0.01 Max. output current A 0.01 0.01
Resolution, digital V 0.01 L o a d r e s is ta n c e kΩ 1 1
R e s o lu tio n B it 10 (value 0 - 1023) Overload and short-circuit protection Yes Yes
I n p u t im p e d a n c e kΩ 11.2 Resolution, analog V DC 0.01 0.01
Accuracy of actual value Resolution, digital Bit 10 (value 0 - 1023) 12 (value 0 - 4095)
at QA01, MD
Two MFD devices % ±3 Resolution, digital V DC – 0.1, 0.01, 0.001 at MD
Within a single device % ±2% Recovery time µs 100 100
Conversion time analog/digital ms Each CPU cycle Accuracy
Input c urrent mA <1 - 25 °C - 55 °C % 2 2
Cable length shielded m < 30 25C % 1 1
Conversion time, analog/digital ms Each CPU cycle Each CPU cycle
unit MFD-TP, MFD-TAP
Analog input temperature resistance Pt100 or Ni1000 sensors
Number 2 x Pt 100 or 2 x Ni1000 (according to part no.)
Input type resistance sensor
Platinum sensor Pt100 according to DIN EN 60751, IEC 751 MFD-TP12-PT...
Nickel sensor Ni1000 according to DIN 43760 MFD-TP12-NI...
Temperature range
P t100, r a n g e A , s e le c ta b le °C , ( °F ) -40 - +90, (-40 - 194); 0 - 250, (32 - 482); 0 - 400, (32 - 752)
N i1000, r a n g e A , s e le c ta b le °C , ( °F ) -40 - +90, (-40 - 194); 0 - 250, (32 - 482)
P t100, r a n g e B °C , ( °F ) -0 - +8500, (32 - 1562); -200 - 200, (-328 - 392)
Potential isolation
From power supply No
From the digital inputs No
From the outputs Yes
From PC interface, memory card, easyNet, easyLink Yes
Resolution digital, scaling per sensor
With operands "IA" and "MD", selectable under scaling Bit 12 (0 - 4095)
W ith o p e r a n d "M D ", s e le c ta b le u n d e r s c a lin g °C , ( °F ) 1, 0.1, (1), (0.1)
M e a s u r e m e n t v a lu e r e s o lu tio n a n a lo g /d ig ita l B it Depending upon the scaling
M e a s u r in g c u r r e n t mA < 1.6
Damage limit (in the case of a wiring error) Apply external voltage
Measurement method Two or three wire per sensor, selectable by connection of sensor
Accuracy (without EMC interference)
T w o M F D d e v ic e s o n e a b o v e th e o th e r % Normally 1; maximal 1.6 (Pt), 1.2 (Ni)
Pt100 RTD (offset error, linearity error, repetition accuracy, % ± 0.8 of measurement range
temperature dependency of the device included)
Ni1000 RTD (offset error, linearity error, repetition accuracy, % ± 0,6 of measurement range
temperature dependency of the device included)
Conversion time analog/digital
Without sampling time setting, selectable per sensor ms 200
With sampling time (adjustable), selectable per sensor ms 200 - 65535
Additional measurement aids
Filtering (software), analog input signal smoothing (Pt1 characteristic), Yes
only with set sampling time, selectable for each detector
Filter for suppression of certain frequencies and their multiples Hz 50, 60, 250, 500
Diagnostics
Card diagnostic Yes
Wire break diagnostic per sensor Yes
Wire break diagnostic per sensor Yes
Below lower measurement range Yes
Upper measuring range limit of sensor exceeded Yes
C a b le le n g th s h ie ld e d m < 10
15
Control relays, multi-function display
Basic devices, expansion devices

easy...T..., MFD-T...
MFD-T..
unit
Transistor outputs
Number 4
R a t e d o p e r a t i n g v o lt a g e Ue V DC 24
P e r m is s ib le r a n g e Ue V DC 20.4 - 28.8
R ip p le % ≦5
Supply current
On signal ”0” Normally/ mA 18/32
max.
On signal ”1” Normally/ mA 24 /44
max.
Protection against polarity reversal Yes (Caution: A short circuit will result if 0 V or GND is applied to the
outputs in the event that the supply voltage is connected to the wrong
poles.)
Potential isolation
Potential isolation from power supply, inputs Yes
From PC interface, memory card, easyNet, easyLink –
From the inputs Yes
Rated operational current on signal "1" DC Ie A Max. 0.5
Lamp load without R v W 5 (Q1 - Q4)
R e s id u a l c u r r e n t o n s ig n a l "0" p e r c h a n n e l mA < 0.1
Max. output voltage
On "0" at external load < 10 MΩ V 2.5
On “1” at I e = 0.5 A V U = Ue -1 V
Short-circuit protection Thermal (Q1 – Q4), (analysis via
diagnostics input I16)

Short-circuit tripping current for R a ≦10 mΩ A 0.7≦Ie≦2 per output


T o t a l s h o r t - c ir c u it c u r r e n t A 8
P e a k s h o r t - c ir c u it c u r r e n t A 16
Thermal cutout Yes
Max. operating frequency at constant resistive load Ops/h 40000
R L < 100 kΩ(dependent on program and load)
Parallel connection of outputs
With resistive load, inductive load with external Group 1: Q1 to Q4
suppressor circuit, combination within a group
N u m b e r o f o u tp u ts Max. 4
M a x . to ta l c u r r e n t A

Status indication of the outputs


Inductive load to EN 60947-5-1
Without external suppressor circuit
T 0.95 = 1 ms, R = 48 Ω , L = 16 mH
U t il iz a t i o n f a c t o r g 0.25
D u ty fa c to r % DF 100
Max. operating frequency Operations 1500
f = 0.5 Hz (max. ED = 50 %)
DC-13, T0.95 = 72 ms, R = 48 Ω , L = 1.15 H
U t il iz a t i o n f a c t o r g 0.25
D u ty fa c to r % DF 100
Max. operating frequency Operations 1500
f = 0.5 Hz (max. ED = 50 %)
T 0.95 = 15 ms, R = 48 Ω , L = 0.24 H
U t il iz a t i o n f a c t o r g 0.25
D u ty fa c to r % DF 100
Max. operating frequency Operations 1500
f = 0.5 Hz (max. ED = 50 %)
With external suppressor circuit
U t il iz a t i o n f a c t o r g 1
D u ty fa c to r % DF 100
Max. switching frequency, max. Operations Depending on the suppressor circuit
duty factor
Notes For additional technical data EASY5… and EASY7… AWB2528-1508D, EASY8…
AWB2528-1423D, MFD-Titan AWB2528-1480D

16
Control relays, multi-function display
Basic devices, expansions, display/operating unit

Dimensions

MFD-80... MFD-80 MFD-80-B

17

22.3+0.4
22.3
32

86.5

30
30
MFD-CP... MFD-CP...

28.25 30 28.25 20 13.7 21.5 13.7

62

86.5

17
Control relays, multi-function display
Central processing unit, communicati

MFD-CP...,MFD-AC-CP... MFD-R...,MFD-T...,MFD-AC-R16

90
90

88.1 19 25

38.75 30 ±0.2 38.75 4.5

16.25 75 16.25 29.5

107.5

MFD-80...+MFD-CP...+MFD-R.../MFD-T... MFD-80...+MFD-CP4
MFD-80... + MFD-AC-CP... + MFD-AC-R16

86.5
58
90

75 29.3 36.2

107.5 86.5 65.5

88.2

20 43.2

33.7

18
Control relays, multi-function display
Accessories

Hinged inspection windows


SKF-FF4 SKF-FF6

16 16

76

76
94 25 25
130

Top-hat rail adapter for hinged inspection window


SKF-HA
11
66
48

82

Protective diaphragm Protective cover


MFD-XM-80 MFD-XS-80
95
88.5

88.5 22.5 86.5 25

Mounting rail
MFD-TS-144
60 23.75
35
24

30 ±0.2 38.75
142.5

19
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to
solve our customers’ most critical challenges.
Our focus is on delivering the right solution for the application.
But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eaton.com/electrical.

Electrical Sector Asia Pacific


No.3, Lane 280, Linhong Road,
Changning District, Shanghai

Eaton Industries Pte Ltd


Electrical Sector
4 Loyang Lane #04-01/02
Singapore 508914

© 2012 Eaton Corporation Eaton is a registered trademark


All Rights Reserved of Eaton Corporation.
Printed in Singapore
MFD-SEA-EN All other trademarks are property
July 2012 of their respective owners.

You might also like