We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 7
ans2004 Very Low Frequency (VLF) Withstand Testing - The Basics
Very Low Frequency
(VLF) Withstand Testing
- The Basics
EA Stev2.Seling.eotiow O18 037 0
What is a Very Low Frequency Withstand Test?
A Very Low Frequency (VLF) Withstand Test is an AC Withstand
Test usually carried out at a frequency between 0.1 Hz and 0.01
Hz. This kind of test is suited for testing high capacitance loads
such as cable and rotating machinery. This is a pass fail test i.e.
bad cable will fail during testing rather than in service.
The Theory
Basic electrical theory: xc = i2*pirf*c)
Where:
Xc = Capacitive reactance (Q)
f = Frequency (Hz)
C = Capacitance (F)
It can be seen that capacitive reactance, which is the resistance
across the power supply output, is inversely proportional to
frequency. By reducing the frequency the capacitive reactance is
increased.ansoas Very Low Frequency (VL) Wiad Tsing -The Bases
More basic electrical theory: | = wr
Where:
| = Current (A)
V = Voltage (V)
R = Resistance (Q)
The lower the frequency, the higher the capacitive reactance
(Xc). The higher the Xc the lower the current and power needed
to apply a voltage.
Example:
A length of power cable with capacitance of 1 uF needs to be
tested at 34 kV peak.
Power frequency testing (50 Hz):
Using the above formulae it can be calculated that the
capacitive reactance would be 3.183 kQ so the required current
would be 10.68 A. Therefore, to test a 1 UF cable at a frequency
of 50 Hz the test set would have to be able to give 363 kVA.
When you consider that a 30 kV, 40 kVA AC test set can greatly
exceed 620 kg it puts into perspective the size an AC test set
would have to be to produce 363 kVA.
VLF Testing (0.1 Hz)
Testing the same length of cable at 0.1 Hz would generate 1.59
MQ of capacitive reactance and the required current would be
21 mA. Therefore testing the same length of cable at 0.1 Hz
would require 0.714 kVA, which is 500 times less than at a
power frequency of 50 Hz.
ansuts2001 Very Low Frequency (VL) Wiad Tsing -The Bases
This allows the size of the test apparatus to drop from
something like this:
To 5 something like this High Voltage Inc. VLE- 3AE:
hitpsswwikecin.comipulseivery-low-roquency-vitwithstand-tosting-basicssteve-colins 37ans2004 Very Low Frequency (VLF) Withstand Testing - The Basics
Most test sets have a frequency range of 0.1 Hz to 0.01 Hz and
the most desirable test sets will select the optimum frequency
based upon the capacitance of the cable. The capacitance of the
cable is dependent upon its construction materials and its
length. As cable length increases so does the capacitance so
dropping the frequency allows kilometres of cable to be tested.
Does this difference in test frequency range have any effect on test results?
This was reported on in the National Electric Energy Testing,
Research and Applications Center (NEETRAC) report “Estimating
the Impact of VLF Frequency on Effectiveness of VLF Withstand
hitpsswwinkecin comipulsoivery-low-requency-vitwithstand-tosting-basic.stove-colins anans2004 Very Low Frequency (VLF) Withstand Testing - The Basics
Diagnostics" by N. Hampton et al (2014). This report
concluded “.. there is no distinguishable difference between failure rates on test for the common
VLF test frequencies of 0.05 Hz and 0.1 Hz, from data obtained through laboratory and field tests, and all
insulation types.”
What size VLF test set is required?
Acceptance test voltages are generally 2.5 - 3 times the line to
ground system voltage. A list of field test voltages from 5 kV to
69 kV can be found in IEEE 400.2.
How long should a VLF test last?
According to IEEE 400.2 VLF tests should last between 15 and
60 minutes with a recommended minimum duration of 30
minutes. This length of time hasn't just been plucked out of the
air; there is some theory behind it.
According to IEEE 400, when testing at 3 times the line to
ground system voltage the tree growth rate of XLPE at a 0.1 Hz
sinusoidal test voltage is 10.9 - 12.6 mm/h.
A 15 kV 133% cable has an insulation thickness of 5.9 mm.
Therefore in a 30 minute test nearly all defects will grow to
failure.
What is a Tree?
At stressed points in insulation where there are protrusions,
voids or contaminants a phenomenon called treeing may occur.
Treeing is the preferred name due to the branch like structure of
these trees. There are two types of tree effect:
Water tree: Produced by electro-oxidation fuelled by electrical stress and water ingress within
insulation. Water trees do not emit partial discharges so PD testing cannot be used to test for the
presence of water trees. During service conditions the growth of water trees is extremely slow taking
years to completely penetrate the insulation. Like protrusions, voids and contaminants, water trees act
as stress enhancements. They can increase the local electrical field and also create local mechanical
stresses. If these electrical and/or mechanical stresses are high enough an electrical tree can initiate.
hitpsswwinkecin.comipulseivery-low roquency-vitwithstand-tosting-basicssteve-coling 87ansr0at ory Low Frequency (VLF) Wibstand Testing The Basis
Electrical tree: Micro-channels of carbonisation or non-insulation found within insulation that is
irreversibly damaged. Electrical treeing will lead to a completed failure path and failure of insulation
relatively quickly. Below is an electrical tree that is growing from a water tree.
nd
Why not just test at DC?
DC has been used to test paper insulated lead covered (PILC)
cable for many years. Therefore it is understandable that DC
continued to be used as solid dielectric cable became prevalent.
Unfortunately the first solid dielectric cable started to
prematurely fail 15 - 20 years after being installed. After
extensive testing and research it was found that solid dielectric
cable is prone to develop water trees. DC testing at high
voltages creates negative space charges within these trees, as
highlighted below.
ee im
input
hitpsswwinkecin.comipulseivery-low roquency-vitwithstand-tosting-basicssteve-coling arsrs2001 Very Low Frequency (VL) Wiad Tsing -The Bases
When the testing is complete and the DC is removed these
trapped negative space charges remain. When the AC is
reapplied a high difference in potential exists at points in the
insulation where these trapped negative space charges are
found. These areas that are already suffering from heightened
electrical and mechanical stresses are prone to turn into
electrical trees. Once this point has been reached the cable will
fail because the damage is irreversible.
DC test sets cannot be used as a voltage source for Tan Delta or
Partial Discharge testing. These diagnostic tests are usually
carried out at a frequency of 0.1 Hz.
hitpsswwinkecin.comipulseivery-low roquency-vitwithstand-tosting-basicssteve-coling Ww