Control�relay,�24�V�DC,�12DI(4AI),�6DO�relays,�1AO,�display,�time,

expandable,�easyNet

Part�no.  EASY820-DC-RC
Article�no.  256271
 
Delivery�programme
Basic function     easy800 (expandable, easyNet)

Description     Expandable: Digital inputs/outputs, bus systems AS-Interface, PROFIBUS-DP,


CANopen®, DeviceNet
Bus system easyNet on board
customized laser inscription or delivery with user program possible with EASY-
COMBINATION-* product (article No. 2010781)

Inputs      

Digital     12

of which can be used as analog     4

Additional�features      

Display     with display, with keypad

Supply voltage     24 V DC

Technical�data
General
Standards     EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27

Dimensions (W x H x D)   mm 107.5 x 90 x 72 (6 PE)

Weight   kg 0.3

Mounting     Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Terminal�capacities
Solid   mm
2 0.2/4 (AWG 22 - 12)

Flexible with ferrule   mm


2 0.2/2.5 (AWG 22 - 12)

Standard screwdriver   mm 3.5 x 0.8

Max. tightening torque   Nm 0.6


Climatic�environmental�conditions
Operating ambient temperature   °C In accordance with IEC 60068-2-1, -25 - +55

Condensation     Take appropriate measures to prevent condensation

LCD display (clearly legible)   °C 0 - 55

Storage ϑ °C In accordance with IEC 60068-2-1, -2, -14


-40 - +70

relative humidity   % in accordance with IEC 60068-2-30, IEC 60068-2-78


5 - 95

Air pressure (operation)   hPa 795 - 1080


Ambient�conditions,�mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)     IP20

Vibrations   Hz In accordance with IEC 60068-2-6


constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150

Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms   Impacts 18

Drop to IEC/EN 60068-2-31 Drop height mm 50

Free fall, packaged (IEC/EN 60068-2-32)   m 1

Mounting position     Vertical or horizontal


Electromagnetic�compatibility�(EMC)
Overvoltage category/pollution degree     III/2

Electrostatic discharge (ESD)      

applied standard     according to IEC EN 61000-4-2

Air discharge   kV 8

Contact discharge   kV 6

Electromagnetic fields (RFI) to IEC EN 61000-4-3   V/m 0.8 - 1.0 GHz: 10


1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1

Radio interference suppression     EN 55011 Class B

02/13/2015 256271 - HPL-ED2014 V9.0 EN 1/6


Burst   kV according to IEC/EN 61000-4-4

power pulses (Surge)     according to IEC/EN 61000-4-5


1 kV (supply cables, symmetrical)

Immunity to line-conducted interference to (IEC/EN 61000-4-6)   V 10


Insulation�resistance
Clearance in air and creepage distances     EN 50178, UL 508, CSA C22.2, No. 142

Insulation resistance     EN 50178


Back-up�of�real-time�clock
Back-up of real-time clock    

     
Backup time (hours) with fully charged double layer capacitor

Service life (years)

Accuracy of real-time clock to inputs   s/day typ. ± 2 (± 0.2 h⁄Year)

      depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year)


are possible
Repetition�accuracy�of�timing�relays
Accuracy of timing relays (of values)   % ± 0.02

Resolution      

Range “S”   ms 5

Range “M:S”   s 1

Range “H:M”   min 1


Retentive�memory
Write cycles of the retentive memory     12
10 (read⁄write cycles)
Power�supply
Rated operational voltage Ue V 24 DC (-15/+20%)

Permissible range Ue   20.4 - 28.8 V DC

Residual ripple   %
5

Siemens MPI, (optional)     yes

Input current     140 mA at Ue

Voltage dips   ms ≤ In accordance with IEC 61131-2


≤ 20

Fuse   A
1A (T)

Power loss P W Normally 3.4


Digital�inputs�24�V�DC
Number     12

Inputs can be used as analog inputs     4 (I7, I8, I11, I12)

Status Display     LCD-Display

Potential isolation     from power supply: no


between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes

Rated operational voltage Ue V DC 24

Input voltage   V DC
Signal 0: 5 (I1 - I6, I9, I10, 8 (I7, I8, I11, I12)

Signal 1: 15 (I1 - I6, I9, I10), 8 (I7, I8, I11, I12)

Input current at signal 1   mA I1 - I6, I9, I10: 3.3 (at 24 V DC)


I7, I8, I11, I12: 2.2 (at 24 V DC)

Deceleration time   ms 20 (0 -> 1/1 -> 0, Debounce ON)


normally 0.025 (0 -> 1/1 -> 0, Debounce OFF, I1 - I4)
normally 0.25 (0 -> 1/1 -> 0, Debounce OFF, I5, I6, I9, I10)
normally 0.15 (0 -> 1/1 -> 0, Debounce OFF, I7, I8, I11, I12)

Cable length   m 100 (unshielded)

Frequency counter      

Number     4 (I1, I2, I3, I4)

Counter frequency   kHz


5

Pulse shape     Square

Pulse pause ratio     1:1

02/13/2015 256271 - HPL-ED2014 V9.0 EN 2/6


Cable length   m
20 (screened)

Incremental counter      

Number of counter inputs     2 (I1 + I2, I3 + I4)

Counter frequency   kHz


3

Pulse shape     Square

Signal offset     90°

Pulse pause ratio     1:1

Rapid counter inputs      

Number     4 (I1, I2, I3, I4)

Cable length   m
20 (screened)

Counter frequency   kHz <5

Pulse shape     Square

Pulse pause ratio     1:1


Digital�inputs�24�V�DC
Status Display     LCD-Display
Analog�inputs
Number     4 (I7, I8, I11, I12)

Potential isolation     from power supply: no


between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes

Input type     DC voltage

Signal range     0-10 V DC

Resolution     0.01 V analog


0.01 V digital
10 Bit (value 0 - 1023)

Input impedance   kΩ 11.2

Accuracy of actual value      

Two EASY devices   % ±3

Within a single device   % ± 2, (I7, I8, I11, I12) ± 0.12 V

Conversion time, analog/digital   ms each CPU cycle

Input current   mA <1

Cable length   m
30, screened
Analog�outputs
Number     1

Potential isolation     from power supply: no


To the digital inputs: no
From the digital outputs: yes
to interface/memory card: yes
to easyNet: yes
to easyLink: yes

Output type     DC voltage

Signal range     0-10 V DC

Max. output current   A 0.01

Load resistance     1 kΩ

Overload and short-circuit protection     Yes

Resolution     0.01 V DC analog


10 Bit (value 0 - 1023) digital

Recovery time   µs 100

Accuracy      

-25 °C - 55 °C   % 2

25°C   % 1

Conversion time, analog/digital   ms each CPU cycle


Relay�outputs
Number     6

Outputs in groups of     1

Parallel switching of outputs for increased output     Not permissible

Protection of an output relay     Miniature circuit-breaker B16 or fuse 8 A (slow)

02/13/2015 256271 - HPL-ED2014 V9.0 EN 3/6


Potential isolation     from power supply: yes
From the inputs: yes
between digital inputs: yes
to the interface: yes
to easyLink: yes
to easyNet: yes
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC

Lifespan, mechanical Operations x 10


6 10

Contacts      

Conventional thermal current (10 A UL)   A 8

Recommended for load: 12 V AC/DC   mA > 500

Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A   A 16

Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A   A 16

Rated impulse withstand voltage Uimp of contact coil   kV 6

Rated operational voltage Ue V AC 250

Rated insulation voltage Ui V AC 250

Safe isolation according to EN 50178   V AC 300 between coil and contact


300 between two contacts

Making capacity      

AC–-15, 250 V AC, 3 A (600 ops./h) Operations   300000

Operations   200000
DC-13, L/R 150 ms, 24 V DC, 1 A (500 S/h)

Breaking capacity      

AC-15, 250 V AC, 3 A (600 Ops./h) Operations   300000

Operations   200000
DC-13, L/R 150 ms, 24 V DC, 1 A (500 S/h)

Filament bulb load      

1000 W at 230/240 V AC Operations   25000

500 W at 115/120 V AC Operations   25000

Fluorescent lamp load      

Fluorescent lamp load 10 x 58 W at 230/240 V AC      

With upstream electrical device Operations   25000

Uncompensated Operations   25000

Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated Operations   25000

Switching frequency      

Mechanical operations   x 10
6 10

Switching frequency   Hz 10

Resistive load/lamp load   Hz 2

Inductive load   Hz 0.5

UL/CSA      

Uninterrupted current at 240 V AC   A 10

Uninterrupted current at 24 V DC   A 8

AC      

Control Circuit Rating Codes (utilization category)     B 300 Light Pilot Duty

Max. rated operational voltage   V AC 300

max. thermal continuous current cos ϕ = 1 at B 300   A 5

max. make/break cos ϕ ≠ capacity 1 at B 300   VA 3600/360

DC      

Control Circuit Rating Codes (utilization category)     R 300 Light Pilot Duty

Max. rated operational voltage   V DC 300

Max. thermal uninterrupted current at R 300   A 1

Max. make/break capacity at R 300   VA 28/28


Supply�voltage�UAux
Power loss P W 3.4
Network�easyNet
Data transfer rate/distance     1000 KBit/s, 6 m
500 KBit/s, 25 m
250 Kbit/s, 40 m
125 Kbit/s, 300 m
50 KBit/s, 300 m
20 KBit/s, 700 m

02/13/2015 256271 - HPL-ED2014 V9.0 EN 4/6


10 KBit/s, 1000 m
Lengths from 40 m can be obtained only with cables with reinforced cross-section
and terminal adapter.

Potential isolation     from power supply POW: yes


From the inputs: yes
from the outputs: yes
to easyLink: yes
to the interface: yes

Bus termination (first and last station)     yes

Terminal types     RJ45, 8-polig

Terminal capacity     up to 1000 m, < 16 mΩ/m: 1.5 (AWG: 16)


up to 600 m, < 26 mΩ/m: 0.75 - 0.8 (AWG: 18)
up to 600 m, < 26 mΩ/m: 0.5 - 0.6 (AWG: 20, 19)
up to 400 m, < 40 mΩ/m: 0.34 - 0.5 (AWG: 22, 21, 20)
up to 250 m, < 60 mΩ/m: 0.25 - 0.34 (AWG: 23, 22)
up to 175 m, < 70 mΩ/m: 0.13 (AWG: 26)
up to 40 m, < 140 mΩ/m: 1.5 (AWG: 16)

Data�for�design�verification�according�to�IEC/EN�61439
Technical data for design verification      

Rated operational current for specified heat dissipation In A 0

Heat dissipation per pole, current-dependent Pvid W 0

Equipment heat dissipation, current-dependent Pvid W 0

Static heat dissipation, non-current-dependent Pvs W 3.4

Heat dissipation capacity Pdiss W 0

IEC/EN 61439 design verification      

10.2 Strength of materials and parts      

10.2.2 Corrosion resistance     Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures     Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat     Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat     Meets the product standard's requirements.
and fire due to internal electric effects

10.2.4 Resistance to ultra-violet (UV) radiation     Meets the product standard's requirements.

10.2.5 Lifting     Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact     Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions     Meets the product standard's requirements.

10.3 Degree of protection of ASSEMBLIES     Meets the product standard's requirements.

10.4 Clearances and creepage distances     Meets the product standard's requirements.

10.5 Protection against electric shock     Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components     Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections     Is the panel builder's responsibility.

10.8 Connections for external conductors     Is the panel builder's responsibility.

10.9 Insulation properties      

10.9.2 Power-frequency electric strength     Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage     Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material     Is the panel builder's responsibility.

10.10 Temperature rise     The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

10.11 Short-circuit rating     Is the panel builder's responsibility.

10.12 Electromagnetic compatibility     Is the panel builder's responsibility.

10.13 Mechanical function     The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

Approvals
Product Standards     IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-
M1987; CE marking

UL File No.     E135462

UL Category Control No.     NRAQ

CSA File No.     012528

CSA Class No.     2252-01 + 2258-02

North America Certification     UL listed, CSA certified

Degree of Protection     IEC: IP20, UL/CSA Type: -

02/13/2015 256271 - HPL-ED2014 V9.0 EN 5/6


shipping classification     LR
BV
DNV

     

Dimensions

Additional�product�information�(links)
IL05013012Z�(AWA2528-1979)�Control�relay�easy

IL05013012Z (AWA2528-1979) Control relay easy ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013012Z2010_11.pdf

MN04902001Z�(AWB2528-1423)�easy800�control�relay

MN04902001Z (AWB2528-1423) Steuerrelais ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04902001Z_DE.pdf


easy800 - Deutsch

MN04902001Z (AWB2528-1423) easy800 control ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04902001Z_EN.pdf


relay - English

Labeleditor http://downloadcenter.moeller.net/de/software.f6023a63-5acb-42c7-a51c-ccf99091cace

02/13/2015 Eaton Industries GmbH 6/6


http://www.eaton.eu
© 12/2014 by Eaton Industries GmbH
256271 - HPL-ED2014 V9.0 EN

You might also like