Formwork Desogn Calculation Report
Formwork Desogn Calculation Report
Analysis ref; Formwork For Concrete - 7th edition Wall Location Below Grade
Design ref; Formwork_A_Guide_To_Good_Practice - 2nd edition External Lateral Force No.
Whale Circular
D - 2.00 in Depth N.A!!
B - 2.00 in Width N.A!!
φ - 1.90 in Diameter OK!!
t - 0.05 in Thickness
N - 2.00 nos. Number
Sw - 24.00 in Assumed whale spacing
lw - 24.00 in Whale length (same as strong back spacing)
2.) Output
Cw - 1.00 - Unit weight coefficient (Table 5-4)
Cc - 1.00 - Chemistry coefficient (Table 5-4)
H - N.A!! lb/ft Minimum external lateral force (SEI/ ASCE 37)
[100 lb/ft or (100 psf for below grade) x 1 x h x (1/2)]
Pmax - 600.00 lb/ft 2
Maximum lateral pressure (Eq; 2.4)
[Cw x Cc x (150 + 9000 x (R/T)]
hps - 3.87 ft Height of pressure stable point from bottom [h - Pmax / wc]
hts - 4.00 ft Height of pressure stable point from top [Pmax / wc]
Properties of plywood
wp - 600.00 lb/ft Distributed load on plywood per feet
Mu - 37.50 lb-ft/ft Design moment for plywood [wpSv2/9]
Mn - 43.10 lb-ft/ft Moment capacity OK!!
3.) Check
Axial (lb) Moment (lb-ft) Delfection (in) Remark Spacing (in)
Pu Pn Mu Mn δact δallow C/C
- - 37.50 43.10 - -
a.) Plywood - 0.870 - OK!! -
- - 660.38 750.00 - -
b.) Vertical strut - 0.881 - OK!! 9.00
5374.0 10146.0 - - - -
e.) Inclined strut 0.5 - - OK!! 24