0% found this document useful (0 votes)
155 views29 pages

Specifications - All

The document provides a technical specification for various laundry and CSSD equipment. It lists 14 items of laundry equipment such as industrial drying tumblers, flat bed presses, washroom trolleys, etc. and their specifications. It also lists 8 items of CSSD equipment including horizontal sterilizers, stainless steel carriages, control tables, work tables, washer disinfectors, etc. along with their specifications like material, size, electrical requirements, and certifications.

Uploaded by

Ratnesh Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
155 views29 pages

Specifications - All

The document provides a technical specification for various laundry and CSSD equipment. It lists 14 items of laundry equipment such as industrial drying tumblers, flat bed presses, washroom trolleys, etc. and their specifications. It also lists 8 items of CSSD equipment including horizontal sterilizers, stainless steel carriages, control tables, work tables, washer disinfectors, etc. along with their specifications like material, size, electrical requirements, and certifications.

Uploaded by

Ratnesh Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

Technical Specification of LAUNDRY EQUIPMENTS

S.NO. Description of Items Qty. (Nos.)


1 Industrial Drying Tumbler.
Front Loading Open Pocket, Reversible,
Steam Heated 60 KG Capacity,
Automatic Cool Down Feature.
60 kg Capacity, Steam Heated.
2 Flat Bed Press.
Pneumatic, Automatic, Steam heated.
Automatic digital timed. Powerful moisture suction blower.
Pneumatic raising & lowering of spring suspended &
Teflon lined Head. Adjustable ironing pressure
Head Size : 1500 x 750
3 Flat Work Drying Ironer.
1 Roll. Heated Chest Type, Front Feed, Rear Return,
Steam Heated,
4 Washroom Trolley.
S.S. 100 kg capacity
Overall Size : 1250 x 675 x 780 ht.
5 Dry Linen Trolley. 4
S.S. 50 kg capacity
Overall Size : 1100 x 600 x 1500 ht.
6 Shelf Trolley. 2
S.S. 100 kg capacity
Overall Size : 1200 x 600 x 1700 ht.
7 Mobile Table. 2
S.S. Top Size : 1150 x 750
8 Laundry Scrub Station with 2 Sinks. 1
All S.S. Size: 1600 x 550 x 900 height.
9 Vacuum Finishing Table. 2
Table Size : 1200 x 750
Electric Steam Iron, Teflon shoe, aluminium armoured
& Spring loaded Condensate separator.
10 Industrial Washer Extractor. 4
30 kg Capacity High Spin, Suspended.
Computer Controlled, steam heated.
11 Industrial Washer Extractor. 4
60 kg Capacity High Spin, Suspended.
Computer Controlled, steam heated.
12 Mobile Table. 2
S.S.Top Size : 2350 x 750
13 Air Compressor, 3 HP Double Stage, 160 ltrs Tank 2
14 Steam Boiler, 500 kg Capacity with Water Softener 2

Page 1
Sr. Technical Specification CSSD EQUIPMENTS Qty.
No (Nos.)
1 Horizontal Rectangular High Pressure High Vacuum Double 3
Door Sterilizer.
The sterilizer will be manufactured as per IS:No.3829 (Part 1)-1978
with ISI Mark/CE Standards. The unit will be designed for operating
pressure 30 to 32 psi. and corresponding to a temperature of 134oC.
The sterilizer chamber would be formed out of SS 316. The Jacket
will be formed out of mild steel. The jacket outer cover will be of SS
304. The sterilizer will be provided with 2 Nos. pressure locking type
hinged doors. The door plate will be of SS 316 with shooting
bolts,flush mountings and steam generator will be of SS 304. The
stand of the sterilizer will be of mild steel.
The Sterilizer will be automatic with PLC with 5 pre-sets programs
and 1 variable program, MMI with Dot-matrix printer wherein date,
time, load identification no. cycle selected, cycle parameter including
time, temperature and phase etc. Can be seen and documented.
Finally, the automation is so designed that once the program is
selected then no further intervention is required from the operator till
the end of the program.

Steam Generator enclosed inside the sterilizer cabinet and should


have multiple door locking and safety functions.
Should have Double Door for pass through system. Doors should be
fully automatic vertically sliding type with pneumatically controlled
function.

The sterilizer will also be provided with an intelligent transducer for


heater protection

Should be CE certified or FDA approved product conforming to EN


285, MDD 93/42/CEE, CE 97/23 PED for Pressure Vessel, EN
61010-1, EN 61010-2, EN 60204-2, Validated as per EN ISO 17665-
1. Current Valid copy of Certificates to be attached wherever
applicable.

Should have complete monitoring of cycle operation and provided


with at least two Digital Pressure sensors and analog gauges for
chamber pressure & jacket pressure indication.

Should have High Precision Digital Sensors for measure


measurement of chamber Temperature (PT100 type) & Pressure
values.

Should have option for Water conservation approx. 50%. Company


should specify the extent of water saving in their system.
The unit will be complete with vacuum pump and condenser and
inter- connecting piping.

Should be high-grade Stainless steel construction inside and outside


including all internal piping and external panels. Chamber, Jacket &

Page 2
Sr. Technical Specification CSSD EQUIPMENTS Qty.
No (Nos.)
Door Material: Stainless steel 316 Titanium Grade.

Should have all internal Piping components, Pneumatic Valves and


connections made of Stainless Steel AISI 316L grade.

Should have External Panels & Machine Frame: S.S. 304 grade.

Should have at least 50mm thick insulation materials on jacket and in


doors to ensure low thermal losses. Exposed surface temperature
should be approx. 45 deg C.

Manufacturing facility should have ISO 9001:2000 & ISO 13485:2004


Certifications or equivalent. Certificates to be attached wherever
applicable.

Sterilizer as above of chamber size 600 mm x 600 mm x 1200


mm depth (2’x2’x4’) suitable for electrical operation on
400/440 volts, 3 phase, AC supply, electrical load 21 KW.
2 Stainlesss Steel 316 carriage suitable for Rectangular Sterilizer 2
3 Stainlesss Steel 304 trolley suitable for above carriage 3
4 S.S. Control and packing table with drawer 3
table is used for separation, control and packing of various sets of
sterilized goods for wards, clinics, operation theatres etc. and is
designed for standing and sitting workers. A removable hatch made
of laminated particles board is provided. The hatch contains a SS
drawer and a laminated particles board plate. Overall size: 2000mm
L x 1400mm W
5 Stainless steel Work Table 3
Table is used for wet goods with undershelf. The table top is
fabricated out of 16 SWG SS 304 qlty. ground and polished to a
smooth surface without high edge sections. The table top frame is a
complete assembly with front, back and two ends welded together at
corners. Overall size 1500mm x610x890Ht.
6 S.S. Vertical Sliding Door 1
Door is used between clean and dirty areas in hospitals,
pharmaceuticals etc. The sliding door is mounted on an existing wall
opening. The door is made of stainless steel counter-balanced by
built in counterweight. The door is provided with nylon wheels at the
side for easy of movement. The door is made along with stainless
steel cover plates for the wall opening. The door is provided with a
built in safety lock which ensures the door from closing if the
counterweight rope breaks. Opening 500 x 500mm
7 Stainless steel work table with two sink 2
The bench top is fabricated out of 16SWG SS 304 qlty. ground and
polished with smooth surface and edge section. The top is designed
to give a stable work surface. The table top frame is a complete
assembly with front, back and two ends welded together. The sinks
are made of stainless steel with inside ground and polished. Each
sink is provided with a drain valve and a strainer. On the bench top,
just above the sinks mixer for hot and cold water connection is

Page 3
Sr. Technical Specification CSSD EQUIPMENTS Qty.
No (Nos.)
provided. Overall size 2400mmL x650mm Wx900mm Ht

8 Washer Disinfector 2
Washer Disinfector, double door, Horizontal movement with
interlocked doors to avoid simultaneous operation suitable for
cleaning and disaffection of surgical instruments, anesthetic
equipment, suction bottles, cleaning buckets, general circulation
goods, dental tray and glassware with a fully closed process.

The washer disinfector, fully automatic, has an advanced micro-


processor which controls all services, programming and statistic
functions. For safety reasons the service and programming functions
are coded.
The door would be provided with interlocking system.
The chamber is equipped with four spray arms which ensure good
water penetration from all directions. Various attachments are
provided to suit the load to be washed. Suitable dosage of detergent
can be preset with the dosing pump.
The provision of a double wall with insulation in between enables the
Washer Disinfector to run with minimum sound and heat emission.

The wash chamber, the inside the door, the pipework system and the
circulation arms are made entirely of stainless steel.

The Washing chamber & other internal parts should be made up of


316 stainless steel.

Clear visibility of the process through toughened glass door &


illuminated chamber.

With Powerful Water Circulation pump & Built-In Dryer with Powerful
Air Blower Pump.

Suitable for electrical operation on Capacity of 275 ltrs.

Electrical load 30 Kw -3 phase 4 wires,400 to 440 volts 50Hz AC


supply & Should have built-In Boiler.
Will meet standards of quality and safety like ASME,TUV,etc in ISO
9001:2008,ISO 13485:2003 certified facility. Should be CE certified.

9 Ultrasonic Cleaner 2
Ultrasonic Cleaner of overall size 530mm L x 330mm W x350mm H
Internal Dimensions: 505 x 300 x 200 mm, output frequency 35khz.
Capacity 30 litres.
The Ultrasonic cleaners are manufactured using Solid State
technology For the Ultrasonic Generator and PZT Transducers for
converting the electrical energy to mechanical vibrations in the
cleaning liquid.
The unit will be complete with a thermostat and a timer, insert basket
for tank and tank cover. The unit is suitable for electrical operation on

Page 4
Sr. Technical Specification CSSD EQUIPMENTS Qty.
No (Nos.)
220/240 Volts, single phase, 50 cycles, AC supply.

10 Drying Cabinet with single door 1


Digital timer Controlled Drying Cabinet with single door suitable for
easy and quick drying of instruments, utensils, glass wares and
anesthetic accessories such as corrugated hoses, breathing masks,
respiration bags and surgical instruments trays etc.
The unit would be provided with digital display with countdown drying
time and drying time selectors, temperature selector including
indication of selected temperature.
The system would have adjustable adjustment temperature range of
60-90oC.
The system would have drying time range of 0-90 minutes.
The system would take air from the work area and clean it by
appropriate filter. The air is to be heated to an operator selected
temperature by electric heating element. The system would also
have an exhaust connection to vent outside.
The unit would be provided with Cassettes and protective shelves for
instruments, hoses, bladders and catheters as accessories.
Chamber volume 275 litres. Suitable for electrical operation on
230 volts, single phase, 15 Amps. Electric load 3.6 KW.
Will meet standards of quality and safety in ISO 9001:2008,ISO
13485:2003 certified facility. Should be CE certified.
11 Stainless steel racks with bullet feet, overall size
1830x535x1830mmH. 2
12 Stainless steel table trolley with 2 shelves 2
Stainless steel table trolley with 2 shelves is for use in the sterile
goods store when batching sterile goods for delivery and also for
short internal transport. The trolley is also suitable for use as a
temporary storage or utility space at packing tables.
The frame is mounted on 4nos. heavy duty swiveling castors for
easy movement in narrow passages. Overall size 1080x530x800H
13 Gauze cutting machine with SS table size 900x600x750mm 1
14 Single Distilled Water Still 1
Single Distilled Water Still, generally as per the Barnstead Type. The
Still is guaranteed to produce pyrogen free and chemically pure
water to comply with IP/BP Standards.
The Still will be manufactured as per “IS:No.3830” and it will also
bear the Bureau of Indian Standard Certification Mark.
The evaporator, the multi-baffle and the condenser will be made out
of stainless steel with the joints welded. The condenser will be
provided with stainless steel tubes, water inlet and outlet
connection.
The Water Still will be supplied in a ready to use condition mounted
on a suitable stand.
Water Still as above of capacity 20 litres, per hour suitable for
electric operation on 400/440 volts, 3 phase AC supply, electrical
load being 15 KW.
15 Stainless Storage tank, electric load 6 kw., capacity 120 litres. 2

Page 5
Sr. Technical Specification CSSD EQUIPMENTS Qty.
No (Nos.)
16 Spray Gun Rinser 2
Spray Gun Rinser with attachments is used for cleaning syringes,
catheters, endoscopes, cystoscopes and variety of other instruments
and articles used in sterile services.

Technical Specification of Kitchen Equipments


S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
1 MILK BOILER 2
Cap.100Ltrs.
S. S. Sheet insulated body with triple jacket. The water jacket will be fitted
with 2 Kw heating element. Milk outlet, water level indicator & draw off
valve at the bottom & water tank. Phillips element, Elcon thermostat, GVC
rotary switch, LED indicator for Power, 4mm thickness 3 core wire
Rajdoot/ Plaza make
2 TEA BOILER 4
Cap.100Ltrs.
S. S. Sheet insulated body with triple jacket. The water jacket will be fitted
with 2 Kw heating element. Milk outlet, water level indicator & draw off
valve at the bottom & water tank. Phillips element, Elcon thermostat, GVC
rotary switch, LED indicator for Power, 4mm thickness 3 core wire
Rajdoot/ Plaza make
3 MICROWAVE OVEN 4
Cap.20-30Ltrs.

4 PICK UP COUNTER WITH OVERSHELF 4


Size 1800X600X850+300
Top 3 sides, under & over shelf of s.s.sheet, on m.s.angle & s.s.tubular legs
frame work. The counter will have 3 sides fully covered, operator side
open. With one under shelf. One over shelf 300mm wide & running along
the full length of counter u type heating element of 1 Kw is placed under
the one head shelf to keep the dishes warm provided with toggle switch
also connected with 4 mm 3 core wire.
5 WORK TABLE FOR SUPPORT OF TWO BURNER RANGE 4
Size 1350x600x850mm
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,
with adjustable feet. Top to have sound deadning material lining as
required.
6 TWO BURNER COOKING RANGE 4
App. Size 1200X600X850mm

Page 6
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Frame work of m.s.anlge duly painted, mounted on s.steel tubular legs
with adjustable feet. Top & sides & under shelf of s.s.sheet. The range will
be complete with 2nos. Hy-pressure gas burners with individual control
valves. Cast iron pan support
EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) FOR
7 TWO BURNER RANGE 12
Size 1950x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
8 JUICER (table top model) 4
Cast Aluminum/CI body, duly polished / painted, with worm &
perforated insert. Top feeding tray. Worm easily cleanable fitted with
1/2HP elect. motor.
9 CONVEYOR TOASTER 4
App. Cap. 100-125 Toasts/hr.
S.S.Sheet body, having s.s.sheet conveyor belt. App.225mm wide. The unit
will have heating elements on top & lower portion of conveyor belt with
variable heat & speed control switch. (MADE IN ITALY)
10 WORK TABLE WITH SINK FOR JUICER STATION 4
Size 1800x750x850+150
Top & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with
cross bracing at lower portion. Sink bowl will be integrally welded with
top & grinded smooth. Sink bowl size 450x450x250mm.
11 WORK TABLE WITH SINK FOR IDLY STEAMER 4
Size 1950x600x850+150
Top & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with
cross bracing at lower portion. Sink bowl will be integrally welded with
top & grinded smooth. Sink bowl size 450x450x250mm.
12 UNDER COUNTER REFRIGERATOR WITH PICK UP SHELF 4
Size 1200x600x850+450+300
Double walled 'PUF' insulated s.s.sheet outer & inner body of s.s.sheet
0.8mm thick having hinged doors with rubber gascuts. Inside s.s.wire
shelves on adjustable channel frame complete with
'Kirloskar/Tecumesh' make compressor. Having condensor,
13 FOUR DOOR REFRIGERATOR 4
App. Size 1200x675x2000mm
Double walled, insulated 'PUF' body made of 0.8 MM thick s.s. sheet .
Inside chamber to have 4nos. S.s.wire shelves on adjustable channel. The
unit will have 4 doors with magnatic rubber gascuts & locking provision.
The condensing unit, consisting of 'Kirlos
14 WORK TABLE 6
Size 1500X600X850mm
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,
with adjustable feet. Top to have sound deadning material lining as
required.
15 EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) 10

Page 7
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Size 1950x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
16 WORK TABLE 4
Size 1500X600X850mm
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,
with adjustable feet. Top to have sound deadning material lining as
required.
17 DOSA PLATE 6
O/S 1500X600X850
Framework made of m.s. angle of size 38x38x5mm and 25x25x5 mm. Top
made of 16 mm thick m.s. plate with stainless steel channel for draining
the excess oil from fry top. The verticals of the equipment are made of
stainless steel of size 38 mm dia and cross
18 IDLY STEAMER (CAP. - 104 IDLY per batch) 4
STD MODEL
Made of stainless steel sheet, fitted with Elect. Controls.
EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for low
19 height burner 4
Size 1650x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
20 LOW HT. TABLE for supporting low height burner 4
Size 750x750x600mm
Specification same as that of work table but the table will be without
undershelf & will have cross bracing support at lower portion.
21 LOW HT. BURNER 4
Size 750x750x600mm
Specification same as that of cooking range but the unit will be
without undershelf, but will only have cross bracing support at lower
portion.
EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for 03
22 burner cooking range 4
Size 1650x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
23 THREE BURNER COOKING RANGE 2
O/S 1800X600X850
Structure made of m.s. angle of size 38x38x5mm, duly rust proof painted.
Top of 16Swg thick s.s.sheet. All four side covered up to height of app. 10”
by 20Swg stainless steel sheet. Bottom stainless steel stripes sheets
complete with gas burners, valves
24 WORK TABLE for support of 03 burner cooking range 2
Size 1500X600X850mm

Page 8
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,
with adjustable feet. Top to have sound deadning material lining as
required.
EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for
25 bulk cooker/boiler & fryer 2
Size 1950x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
26 BULK COOKER/boiler TILTING TYPE 2
Cap.160Ltrs.
Specification same as Sno.13 but the frying pan will be Of rectangular
shaped with
12”depth & a pouring lip & the unit will be fitted with v type high
pressure gas burner with control valve & pilot lamp.
27 BULK FRYER TILTING TYPE 2
Cap.100Ltrs.
Triple jacketed body of stainless steel sheet, Inner most jacketed of 16g
thick with 12g thick dish ended bottom, second wall for air gap of 18g
stainless steel sheet & outer insulation jacket also of 18g stainless steel
sheet. The unit will have counter
28 WET GRINDER 2
Cap.15ltrs (1.0HP)
Stainless steel sheet constd. Body with s.s.sheet constd. Revolving drum,
chromium plated pillar support on m.s.angle frame work fitted with
electric motor gear box & grinding stones & coconut scraper.
29 DOUGH KNEADING MACHINE 2
(CROMPTON MOTOR 2.0 HP)
App. Cap of Bowl 25Ltrs.
S.S.Mixing bowl, with s.s.rod/strip mixing arm, mounted on steel tubular
& sheet frame work duly painted. Complete with 1.0HP Elect. Motor with
control switch.
30 POTATO PEELER 2
Cap.15Kg./chrgs.(CROMPTON MOTOR 1.0 HP)
16 gauge Stainless steel sheet peeling drum, lined inside with Abrasive
material, stainless steel /cast iron rotating peeling disc. Top of the drum
will have a potato inlet door, waste Inlet provision peeled potato
discharge door & waste water Outlet pipe
31 PULVERISER (Std.) 2
(CROMPTON MOTOR 1.0 HP)
Stainless steel sheet body,20g thick. the unit will have A top feeding tray
& a housing of stainless steel casting With grinding plates & 3 type of
meshes for variable type Of grinding requirements. The unit will be fitted
with 1.0 hp single Phase electri
32 WORK TABLE support of pulverisor 2
Size 1500X600X850mm
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,

Page 9
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
with adjustable feet. Top to have sound deadning material lining as
required.
33 WORK TABLE WITH SINK for vegetable washing 2
Size 1950x600x850+150
Top & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with
cross bracing at lower portion. Sink bowl will be integrally welded with
top & grinded smooth. Sink bowl size 450x450x250mm.
34 CHOPPING BOARD for manual vegetable cutting 3
size:- 1200X600X850mm
Frame work made of s.s.anlge top will have P.P./Nylon Board for
chopping 700x700x100mm chopping board.
35 VEGETABLE CUTTING MACHINE 2
Aluminium casted body with ½ hp electric motor safety switch & double
feed pusher for round flat & vertical shaped food items etc., the unit will
be Table top model with easy to clean provision. Provided with 4 no
cutting discs for slicing grating Dicing
36 CHAPPATI COLLECTION TABLE 2
Size 1500X600X800
Top tray of 16G s.s.sheet, tray will have App.100mm ht. collor all around,
mounted on s.s.tubular legs with adjustable feet & one s.s.sheet
undershelf.
37 CHAPPATI ROLLING TABLE 2
Size 2100x750x850mm
Top & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs,
with adjustable feet. Top to have sound deadning material lining as
required. THREE SIDE CROSS BRACING MADE OF S.S. PIPE 1" DIA FOR
UNDERNEATH STORAGE.
38 CHAPPATI PLATE CUM PUFFER 2
Size 1800x750x850mm
Frame work of m.s.anlge, mounted on s.s.tubular legs frame work. All
sides pannels & undershelf of s.s.sheet, top plate 10mm thick mild steel
with cast iron puffing grills for puffing of chappaties. Complete with 'V'
shape LPG burners with individual cont
EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for
39 chapatti plate 8
Size 1950x750x600mm
Made of s.steel sheet, 20G thick duly welded & pop rivetted as required.
The hood will be complete with s.s.sheet removable type baffle filters.
Complete with greese collection channel & greese collection cup/s.
FOOD TROLLEY WITH 4 ROUND PANS, 1 RICE TRAY & STORAGE
40 beneath 24
O/S 1350X750X900mm
S.S.Sheet insulated body, Frame work of m.s.anlge of size 38x38x5mm,
mounted on 4 castors (2 with brakes) of size 150mm top to have cutout
for 4nos. Round pans for Dal, Subzi etc. with 1 rice tray & storage below.
Three side covered with s.s.sheet with s.
41 TRAY CARRIER TROLLEY 2

Page 10
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Size 1200X600X1200mm
S.S.Bottom base shelf mount at 150mm with all four sides turned down
50mm in 12mm and secured to welded s.s.anlge frame work &
PROVIDED WITH THREE NOS. OF DETACHABLE TRAYS CUM SHELFS
UNIT WILL BE MOUNTED ON 4" PILLAR TYPE CASTORS WHEELS (2 NOS.
WITH BRAKE & 2 NOS. WITHOUT BRAKE)
TRAY SET UP COUNTER WITH BAIN MARIE & DOUBLE
42 OVERSHELVES 4
Size 1800x600x850+375+225
Top of 16G s.s.sheet, Bain Marie water tank of 18G s.s.sheet, fitted with
3.0kw heating element with automatic temperature controller. Water
outlet provision with drain valve, 3 sides covered with 20G s.s.sheet, Top
to accommodate s.s.sheet
Food Pans with GN pan 1x2x4" depth with lid 5 sets.
43 STORAGE CABINET 4
Size 1200X600X850mm
Top of 16Swg S.S.Sheet one over shelf, three sides of 20SWG s.s. sheet.
Dish storage cabinet with 2 shelves and sliding door will be provided on
service side.
44 STORAGE RACK 4
Size 900X450X1800
Vertical of 32 mm dia stainless steel pipe with adjustable feet 4 no of 18
S.S Sheet at equaly distance.
45 INGREDIENT BINS 7
Size 600X600X600mm
Made of S.S. 18 SWG WITH TOP HINGE OPENABLE DOORS SUPPORT
WITH FOUR
NOS. OF CASTORS, anti crack body, top half hinged lid. Provided with a
scoop.
46 DUNNAGE RACK 2
Size 1200X600X500mm
Made of s.s.square pipes of size 32x32mm, with support of 25mm square
s.s.pipe.
47 DIGITAL WEIGHING SCALE 2
CAP. 300KG
48 POT RACK-3 TIER 6
Size 1200X600X1500mm
Verticals of 32mmX32mm square s.s.pipe, 3 shelves welded with vertical
frame of 19mm dia s.s.pipe shelves with equal space between two tubes
mounted on adjustable feet.
49 SOILED DISH LANDING TABLE WITH GARBAGE CHUTE 1
Size 2400x600x850mm
Top of 16G s.s.sheet with 'Sunkun' top. A garbage chute provided on top
with a space below to keep dust bin (Not part of equipment). The top will
be mounted on m.s.anlge, rust proof painted & s.s.vertical tubular legs
with cross bracing support on 3 sides
50 THREE SINK UNIT 2

Page 11
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Size 1800x600x850+150mm
Top & 3 sink bowls of 16G s.s.sheet. Duly welded, grinded & polished
smooth mounted on m.s.anlge & s.s.tubular frame work with 150mm
back splash. Each Sink Bowl Size 500x500x300mm (without sanitory
fittings)
51 CLEAN DISH TABLE 2
Size 2100x600x850mm
Specification same as that of work table but with 2 undershelves.
52 CLEAN DISH RACK 10
Size 900x450x1800mm
Vertical of 32 mm dia stainless steel pipe with adjustable feet 5 no
vertical at equal distance 1st shelf fixed at 150mm from floor level.
53 Pot stacking platform for heavy pot storage 2
Size 1500x750x150mm
S.S Palate frame will be made of 1.5” S.S Square pipe with adjustable
bullet feet. And shelf will be made of 2”x3mm S.S Flat Patti.
54 Masala trolley 2
Size 600x600x750mm
55 Plateform trolley 2
Size 900X600X900mm
Structure will be made of 40x40x5mm duly painted with rust proof paint.
Top will be made of 10 SWG. M.S Sheet. 6” high moving wheel (02 Break
+ 02 Moving)
56 PRE WASH SINK UNIT 2
Size 1800x750x850+150
Top & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with
cross bracing at lower portion. Sink bowl will be integrally welded with
top & grinded smooth. Sink bowl size 450x450x250mm.
57 HOOD TYPE COMMERCIAL DISHWASHER 4
IFB / WINTERHALTER MAKE
Cap. 40-50 Racks per Hr.
CYCLE TIME TOTAL/RINSE (SEC) 60-120-180/20
BASKET SIZE 500X500 MM
WATER CONSUMPTION 3L/CYCLE
TANK CAPACITY 20L
RINSE CAPACITY 12L
WASH PUMP 1.1KW
WASH TANK 3KW
RINSE TANK 8KW
MAXIMUM USED POWER 9.1
WATER HARDNESS 70-140 PPM
WATER PRESSURE 2-4 BAR
POWER SUPPLY 400/3+N-/50
58 DIRTY DISH UNLOADING TABLE 2
Size 1500x600x850mm

Page 12
Technical Specification of Kitchen Equipments
S.NO. Kitchen Equipments which consists of following items Qty.
(Nos.)
Top of stainless steel sheet, mounted on m.s.angle & stainless steel
tubular frame work. One 18g thick stainless steel sheet bottom Shelf will
be fitted on table at a ht dia 150mm from floor.
59 CLEAN DISH TABLE 2
Size 2100x750x850mm
Specification same as that of work table but with 2 undershelves.
60 COLD ROOM SECTION 4
WALK IN CHILLER CUM FREEZER
External Room Dimensions : 3600X3000mm
CHILLER Room Temperature - (+ 2°C to 8 °C)
Product Entering Temp - + 30°C
Pull Down Time - 15hrs.
Product Loading - App.550kg./24hrs.
Wall & Ceiling Panels Insulation - 80mm thick Prefabricated RPUF Panels
Floor Panel Insulation - 80mm thick RPUF Panels with layer of Tarfelt
sheet on both sides.
Panel Finish - Internal :PCGI , External: PCGI
Refrigerant -R-22
No. of Units - 1 (MAKE:- KIRLOSKAR/TECUMSEH/CARRIER
Connected Load - 2.5 KW
61 ALUMINIUM RACK FOR COLD ROOM 5
Size 1100X500X1500
Vertical of 50x50x5mm aluminium angle with adjustable feet 4 no of 18
swg.
Sheet perforated aluminium shelves..
62 ALUMINIUM PALLET FOR COLD ROOM STORAGE 4
Size 1500X450X150MM
Top made of 16 swg aluminum sheet placed with s.s. angle 35x35x4
frame work with adjustable bullet feet.
63 L.P.G GAS PIPE LINE (200 RUNNING FEET APPROX or 60.96 Rmt) 1
ACTUAL MEASUREMENT WILL BE ACCORDING TO As per site conditions
64 CENTRIFUGAL EXHAUST BLOWER 4
20000 CFM
65 S.S GRATING for kitchen drainage trough 1
(APPROX 40 RUNNING FEET or 12.195 Rmt)
ACTUAL MEASUREMENT WILL BE ACCORDING TO As per site conditions
EXHAUST HOOD DUCTING (APPROX 2000 SQUARE FEET or
66 185.806 Sqm) 1
Actual measurement will be according to as per site conditions.

Page 13
Technical Specification of Mortuary
Sr. Qty.
No.
1 MORTAURY CHAMBER 6
Capacity (d) Four Bodies
Features:
Cabinet : Energy Efficient Units
Modular construction with Stainless steel: Efficient Internal lighting
R 22 refrigerants: Vapor proof incandescent lamp
Automatic Temp. control systems: Pull out drawer system
High Density Polyurethane Insulation: Easy to maintain and clean
Stainless Steel door: Extended choice of control options
PUF Insulation temperature: ISO and CE marked
Audio visual alarm for high and low: Corrosion free exterior, Digital
temperature indication
Temperature Range and Control: Mortuary cabinets are available with temperature
range of
2°C to 8°C. For accurate measurement and display of temperature a LED display is
used. These units are equipped with microprocessor based digital control panel which
is operated with push buttons. For security and safe working high and low temperature
alarm system is used. Refrigeration System Mortuary cabinets are equipped with full
functional cold storage facility. Refrigeration system is energy efficient, environment
friendly.
Mortuary chambers are of double walled construction and made of 304 grades
corrosion resistant stainless steel. For insulation high pressure-injected
polyurethane is used for minimizing thermal loss and meeting the particular
requirements of refrigeration in mortuaries. Doors Doors are made of stainless steel.
These doors are situated in front and allows easy loading of Bodies. These doors
feature lining in odorless rubber gasket and anti-condensation resistors.
Internal Lighting Lighting system comes with waterproof fluorescent ceiling lamps
which are fitted with a switch on the control panel.
Technical specification:
Number of Bodies 4
Temperature range 2° C to 8° C
Temperature Control Digital Micro-processor
Temperature Display LED display
Construction Inner & Outer stainless Steel
Insulation High Grade poly Urethane
Doors Made of Steel Sheets & External Lock
Trolleys Made of Steel and sliding on telescopic
rails
Compressor ISI Marked

Evaporation Internal evaporator system Forced


draught
Internal drainage Yes
Integral temp. gauge Yes
Refrigeration System Air cooled Hermetically sealed
Air circulation Forced air Circulation
Alarm High/ Low alarm system

Page 14
Technical Specification of Mortuary
Sr. Qty.
No.
Internal Lighting Waterproof fluorescent ceiling lamps
Locking System Standard key locks
Power supply 220 Volts/ 50 Hz

Page 15
PNEUMATIC TUBE SYSTEM
TECHNICAL SPECIFICATION

Main Controller:
The entire system has to be electronically controlled by microprocessors/ computer. The main control unit, which
controls the sending process and the compressor unit, supervises all system components.

The sending process has to be indicated on display devices. The device also has to provide information to find the
cause of a system malfunction. Customer-specific data such as the system's layout, target numbers, target names,
arrival signals, priority and special functions must be selectable on site without change or external reprogramming
of memory devices. A integrated uninterrupted power supply must provide the requested system back up time to
paste all date before shutting down the system, so after power source is providing energy again a automatic
system start will occur and the system status will get back in the operation mode as before. Chosen targets at
stored containers must be kept in the memory to proceed them automatically after power failure restart.

All components of the pneumatic tube conveyor are constantly monitored; the operating software has to be based
on action reaction control for any device. The status of each device can be checked by the master control unit. A
test program must be included to automatically check, move and supervise all of the system's devices, or specific
selected devices, by access via service code from the Station control panel.

During both normal operation and testing, all devices inform the master control unit that the selected functional
position has been reached. This ensures that this position truly has been reached. The system is designed in such a
way that it does not allow the unobserved pivoting of devices.

The system has to come with an efficient fault-clearance program that automatically recognizes operating errors,
power failures, time-out errors and other system errors. It also allows the system to continue functioning; there is
no need for the operating personnel to intervene.

It should be possible to redirect empty containers which have exceeded the pre-allocated distance limit to a
Station for maintenance to be carried out – new drivers to be fitted for example.
It should include the following:-
• Main Control Unit Hardware for main controller, for maximum of 24 bus systems, for systems up from 128
devices and transfer zone.
• Main Control Unit Hardware - Router for "Main Control" with 4 ports for connection of several Main Control
Units.
• Patchable for connection router to Main Control
• Main Control Unit – Dongle
• UPS Uninterruptable Power Supply for PC-Monitoring
• Software package for main controller includes the following:-
Ø Software for one Line,
Ø Extension Software for further lines,
Ø Software for Code-Tag System/Transponder System,
Ø Software for Visualization & Editor for 1 Client,
Ø Software for History & Evaluation,
• Patchable for Connection PC/Laptop to Power Control
• Power Supply Unit,
• Power Supply Kit External,
• Power Supply connecting cable for Power Control.
• Keyboard SCB2000/3 – Usable for Desktop Installation Only
• To be provided with Wifi connectivity with special ability to view the system movement etc. on wireless tablet &
smart phones.

Page 16
Blower:
It should have a separate Blowers 2.3 kW, 3 phase 400v/50Hz, 2850 rpm, 220 mbar pressure, 5.1 m3/min for flow
rate, with low noise, unidirectional rotation with electronic air switch to switch between compressed air and
vacuum. EQUIVALENT BLOWER SPECS WILL ALSO BE ACCEPTED

Each blower should be provided with Frequency Converter for Control of slow speed for sensitive laboratory
samples by frequency control of Compressor. The blower should be set go up to 75Hz with the help of Frequency
Converter.

Frequency converter should help the system to run on blowers of 2.6 Kw.

It should be provided with all the mounting accessories and soundproof enclosure.

Station 160mm - Pass Through Type:


The Pneumatic Station should be designed as a fully automatic dispatch and receiving unit and used as pass-
through station.

The Pneumatic Station should be able to send and receive carriers.

The conveying direction of the carriers should be both sided (single tube reversing principle).

Inserting a carrier into the Pneumatic Station and selecting a target number should be possible independent from
system status.

The carrier should be loaded on the top side of the Pneumatic Station.

The Pneumatic Station should be controlled by the use of the LCD display memberane key pad in 34 Station areas
and with integrated Touch Panel Display in 5 Station areas. OR EQUIVALENT

The Pneumatic Station should be Steel made, maintenance free gear mechanism, with self adjusting optical
switches, with self adjusting maintenance free gaskets for noise less operations, contact less sensoring of the unit
positions. There should not be any air exiting at the pneumatic station. With RFID readers for carrier ID and
inventory, which should ensure automatic carrier redistribution to its home address & also non-acceptance of any
items than authorized carrier.

The Pneumatic Station should have Air cushioned soft landing facility for arriving carrier to protect samples.
Provided with carrier rack and receiving basket with cushion.

Pass through Type Stations should be in 39 Numbers in quantity.

Dimensions: (80 x 50 x 50 cm) Approx. to occupy least possible space. OR EQUIVALENT

Station 160mm - Multi Receive and Multi Send Station for Laboratory:
The Pneumatic Station should be able to send and receive carriers from the same unit.

Inserting a carrier into the pneumatic station and selecting a target number should be possible independent from
system status.

It should control the condition of the receiving station when sending to the selected receiving station is possible.

It should be Microprocessor-controlled.

Page 17
The Lab should be provided with Multi Receive and Multi Send Station to handle bulk loads.

It should be designed as a fully automatic dispatch and receiving unit and can only be used as end station.

The Pneumatic Station should be Steel made, maintenance free gear mechanism, with self adjusting optical
switches, with self adjusting maintenance free gaskets for noise less operations, contact less sensoring of the unit
positions. With RFID readers for carrier ID and inventory, which should ensure automatic carrier redistribution to
its home address & also non-acceptance of any items than authorized carrier.

It should be built in a way that after a power failure it is self-examining and if necessary self-repairing.

It should have Air cushioned soft landing facility for arriving containers to protect samples.

It should be provided with carrier rack & PVC Slide bend, sliced from the top for soft landing of the samples.

Dimensions: 100 (H) x 32(W) x 30(D) cm OR EQUIVALENT

Station 160mm – Automatic unload:


The Lab should be provided with an Automatic Unload Pneumatic Station.

When the carrier comes into the pneumatic station it should automatically open inside the stations (without
exiting the station), sample bags should slide out, the carrier should automatically return to its origin pneumatic
station based on RFID transponder technology.

The Pneumatic Station should be Steel made, maintenance free gear mechanism, with self adjusting optical
switches, with self adjusting maintenance free gaskets for noise less operations, contact less sensoring of the unit
positions. With RFID readers for carrier ID and inventory, which should ensure automatic carrier redistribution to
its home address & also non-acceptance of any items than authorized carrier.

Should have Air cushioned soft landing facility for arriving containers to protect samples above the station, with
the help of slide gate.

Should be provided with carrier rack & SS Slide for sample soft slide-landing.

Touch Screen Panel for Critical Areas:


PTS Stations of Critical areas i.e. ICU, OT, Pharmacy, Sample Collection & Dialysis should be provided 7’’ touch
screen display with multifunctional operation screens in Pneumatic Station with the following features:

1. LCD display / 7’’ touch screen display with multifunctional operation screens
2. Touch panel operation via finger, safety gloves or styluses
3. Individual programmable user profiles and customized hotkeys
4. Individual authorization levels for personalized users profiles
5. Touch screen surface protection for easy cleaning addressees are individually programmable; Search
button and addressee index simplify the usage.
6. With integrated Bar Code Reader for Pharmacy Stations, Blood Bank Stations, Lab Station and Sample
Collection only.

Inter Connector Zone System:


The system is provided with the State of the Art “Inter Connector Zone System” which provides an excellent
throughput and has fast transfer capabilities.

Page 18
Inter Connector Zone is the only system:

Ø Transfer time per carrier 10 seconds.


Ø Having one storage unit for different carriers.
Ø Occupies a less space.
Ø Can connect up to 6 lines.

Forwarding Tube:
Forwarding tube should include the cost of cable and other tube mounting accessories as are required for
networking between Pneumatic Stations. Every Station and Diverter must provide transparent tube.

The forwarding tube should be made of PVC of 160 mm OD x 153.6 mm ID. Good Physical tensile strength, general
medium density, absorption of water, combustibility self-extinguishing.

Bends:
It should be of 90 deg. with radius not more than 800 mm (centre) with length approx 1.5 mtrs, for optimal space
utilization, grey colour.

Composite System Cable:


It should not be localized and it should be imported with company brand name marked.

Inserts:
Eprouvette Bag PVC for holding vacuutainers.

Diverter:
The forwarding tube diverter must provide one incoming and three outgoing delivery tubes. The Diverter must
provide a smooth connection between incoming and outgoing tube, to prevent impact on transported items. A
maintenance free belt driven rotary oscillating pipe has to be pneumatically sealed to the device housing, to
prevent air loss, self-adjusting Teflon gaskets have to provide airtight operation in vacuum and pressure operation.

Dimensions: 115(H) x 50(W) x 40(D) cm

Carriers:
Carrier for hospital use should be with easy to operate swivel top mechanic, sealed load chamber, to prevent
contamination of tubing in the unlikely event of spill of transported goods. This must be realized only by closing
the sealed swivel top mechanism.

The "closed" position should be fastened in a lock-in position. The lid should be kept in this position by a spring
force and has to be equipped with seals. Furthermore the design of the container must be done in a way that an
open carrier can’t be sent. Any carrier has to be equipped with two free programmable data transponder, system
according to send receive device used by the manufacturer in the Pneumatic Stations send magazines.
Transponders are used to electronically identify any carrier by a unique address and to offer the user automatic
redistribution to home Pneumatic Station and optionally a second address for dedicated locations or special
carrier use. The carriers must provide a easily visible wear and tear resistant colour coding system, which must be
changeable also on site by the user without damage and not requiring special tools.

Normal Carriers should be 134 numbers in quantity.

Inside-loading-dimension for Carrier ∅ 160mm swivel top ∅115 x 400mm

Page 19
Outer-dimension for Carrier ∅ 160mm swivel top ∅150 x 420mm

EQUIVALENT SPECS OF ABOVE WILL ALSO BE ACCEPTED

With suitable holders of vaccutainers and a pair shuttle bung for each container.

Automatic Unload Carriers:


Automatic Unload carrier should be such that no manual handling be required.

The carrier should automatically unload at the Pneumatic Station then automatically close & go back to the origin
Pneumatic Station.

The system should not accept an open carrier.

The carrier should also be able to open manually.

It should have at least two free programmable data transponder system.

Automatic Unload Carriers should be 41 numbers in quantity.

Inside-loading-dimension for System ∅ 160mm swivel top ∅110 x 260mm OR EQUIVALENT

RFID
The system provided should be equipped with RFID reader cards on all stations (except for Stations which are only
for receiving), for a proper management of Carriers with the help of return of empty carriers. All the carriers
should be equipped with RFID Chip on both sides of the carrier and should be programmed for the home station
no.

S. No. Name of Item Qty

1 Main Controller with Wireless Tablet for Maintenance Department 1 Set.

2 Blower 5 Nos.

Station 160mm
3 41 Nos.
(a) Pass Through Type – 39 Nos.
(b) Multi Receive and Multi Send Station (Combo) – 1 No.
(c) Automatic unload – 1 No.
4 Inter Connector Zone System 1 Set.

5 Forwarding Tube 2200 Mtrs.

6 Bends 210 Nos.

7 Composite System Cable 3200 Mtrs.

8 Inserts (per station) 2

Page 20
9 Diverter – 3 Way 14 Nos.

Carriers
10 175 Nos.
(a) Normal Carriers -134 Nos.
(b) Automatic Unload Carriers – 41 Nos.
In all stations
11 RFID (Included)
and carriers.

12 Special Adhesive Glue 110 Ltrs

13 Sleeve 2100 Nos.

LG/Samsung/
14 Monitor/Mouse/Keyboard
HP

Tubing Material & Other Accessories sourced from India, including: Pipe Clamps,
15 Screw Bolts, Conduit for Composite System Cable, Cable Clips, Hose Clamps & Indigenous
Baskets, Cushions and Racks for Stations

Page 21
SPECIFICATION FOR VERTICAL & HORIZONTAL
BED HEAD PANEL
1. Supply Installation Testing & Commissioning of ceiling Mounted Bed Head
Panel
Vertical Bed Head Unit- Imported

The bed head unit will provide a safe, efficient means of delivering services to patients/staff in general
wards application. Original concept “static” equipment (such as inhalers, monitoring) for a better mobility
of the movable equipment (such as infusion pumps, infusion stands).Designed equipment for more
security and comfort for medical staff :static column, movable arm and efficient care lighting (optional).
The bed head unit will meet the following criteria:
1. 3 thick aluminum profiles strong column for a secure load (up to 250 kg) and eventual front bed
shock.
2. Aluminum profiled compartments for electricity and gas (6 separate compartments with clipping
front covers for easy maintenance). Real segregation between electrical components and medical gas
equipment.
3. Its modular design allows any extension of additional equipment (electrical sockets, data sockets,
medical (gas outlets). Without need of manufacturer.
4. Economy: no double wall mounted equipment required (copper piped medical gas outlets).No special
installation required.
5. Large space between outlets allowing a direct connection of the flow meter on column.
6. Medical equipment are placed in the “dead” angles and closer to the bed where “static” equipment
is placed.
7. Easy organization of medical staff around the patient (head and body) and large possibility of control on
equipment on 360° without constraints.
8. Easy access to infusion installation. Full 260°horizontal arm space movement allowing a large circular
movement over the bed (possible height adjustment up and down of 420 mm).
9. The wide shelf can be placed at 6 different places around the column. Many possibilities for all types
of accessories or equipment, by the 3 stainless steel tubes position.
10. New technicity of care requires adapted lighting. The 40 000 lux care lamp is the answer to efficient
lighting.Easy handling and movement (operation theatre lighting technique).
11. Movement on 3 axis and over the whole surface of the bed.
12. ELV halogen lamp. Possible dimming on request.
13. The movable area “head” acceptsa large quantity of required electricalsockets for such infusion areas.
14. The 2 stainless tubes (diameter30 mm - height 700mm) can receiveeither 6 standard Syringe pump
+6 optional or all types of shelves, rails or biomedical equipment(extra infusion rod can completethis
range).
15. Load capacity:40 kg. OR EQUIVALENT
16. Segregation of services i.e. extra voltage (less than 48 volts) low voltage (less than 600 volts but
greater than 48 volts) and medical gases will be maintained throughout. Individual modular fascia plates
will be removed using a screwdriver, allowing easy access for services. The bed head panels will be
European CE marked to medical devices directives and will be duly EN 41312588 certified. OR
EQUIVALENT
17. Color choice is available as per the design/color of wall & flooring of the ICU. Designed equipment for
more security and comfort for medical staff: static stainless steel mounting brackets, rounded shape
design polycarbonate box with cover and efficient care lighting (optional).

2. SPECIFICATION of Horizontal Bed Head Panel

Page 22
Horizontal Bed Head Unit- Imported

The bed head unit will provide a safe, efficient means of delivering services to patients/staff in general
wards application.
The bed head unit will meet the following criteria:

1. Modular system for all brands and type of medical gases outlets, stainless steel mounting brackets,
and rounded shape design polycarbonate box with cover. Possible use of manufacturer’s gas cover.
2. Medical gas and electrical equipment placed on trunking rail individual insulation by plastic box.
3. Total Segregation between IV and elv services. Individual covers for electricity and medical gases with
Efficient and invisible ventilation.
4. The electrical and gas equipment’s should be completely modular which allows the components to be
extended and/or re-moved with individual box.
5. General up lighting by a removal batten equipped with 1 or 2 fluorescent tubes with integration night
light.
6. Direct reading/cares light by 1 or 2 fluorescent tubes on 45 degree sloping panel. Easy access to
lightings with protection of unbreakable polycarbonate diffusers with a double prism.

Page 23
Technical Specifications
For Nurse Call System (Imported)
(The System should confirm ALL INTERNATIONAL
CERTIFICATIONS OF US/UK/GERMANY/EUROPE

PART 1 -- GENERAL

OVERVIEW
Should Furnish and install all equipment, accessories, and materials in accordance with these
specifications and drawings to provide a complete and operating Nurse/Patient

1.1 SCOPE OF WORK:


Should Furnish and install a Nurse / Patient Communications System comprised of nurse consoles,
patient stations, dome lights, entertainment cords, call cords, pull cord stations, emergency push button
stations, bed side-rail interfaces, pocket page interfaces, computer interfaces, printer interfaces,
wireless/telephone network interfaces and wiring as shown on the drawings

The Nurse/Patient Communications System should be installed initially in the specified areas and then
be expanded in the future to additional areas. Systems provided in the initial area shall have the capacity
to expand to provide seem-less service to the entire facility.

All necessary equipment required to meet the intent of these specifications, whether or not
enumerated within these specifications, should be supplied and installed to provide a complete and
operating nurse/patient communications network.

1.2 REFERENCES
A. Underwriter’s Laboratories Standard 1069 (UL1069)
B. Canadian Standards Association
C. National Electrical Code
D. U.S. Dept. of Labor / Occupational Safety and Health Administration
E. State Hospital Code / Joint Commission of Hospitals - Nurses Call Requirements

SYSTEM SUPPLIER QUALIFICATIONS

The System Supplier should be an Authorized Distributor for the product proposed with full
manufacturer's warranty privileges.

The System Supplier should have technicians who have attended and successfully completed the
manufacturer’s technical certification classes for the proposed system.
PART 2 -- PRODUCTS

2.1 QUALITY ASSURANCE

The nurse / patient communications system should be listed by Underwriter’s Laboratories under UL
Standard 1069 - 6th Edition (published March, 2001). Underwriter’s Laboratories shall be the only acceptable
NRTL for system listing.

2.2 HEAD-END CONTROL EQUIPMENT

A. Power Supplies – Should Provide ample power for control equipment, consoles, patient stations,
sub-stations, and corridor lamps. All system power supplies must be UL1069 listed as an integral
part of the core system. Power supplies which carry only component listings or are otherwise not
part of the core system UL listing are not acceptable.

Page 24
B. Should Furnish as needed in each area a nurse/patient communications network hub controller. The
system as a whole shall be capable of supporting at least 25 hub controllers. Each hub controller shall
provide the following:
1. Support for at least 10 console clusters consisting of standard LCD consoles or annunciate panels.
2. Support for at least 150 rooms.
C. It shall be possible for network hub to act as stand alone controller should loss of network
communication occur.
D. System Audio – The system shall be designed to provide audio meeting the minimum standards
detailed by the National Electrical Manufacturers Association standard for nurse call system audio.
1. The system should utilize 25 Volt balanced signal distribution between head end equipment and
room stations.
2. Audio transmission between hub controllers shall be digital.

2.3 CALL ROUTING / PROCESSING

A. Call Routing – The system should support the routing of patient calls to any console, pager, phone or
other annunciating device anywhere in the facility or to any combination of the above regardless of
the location of the calling station. Calls may be routed and processed based on location, priority or
combination.
1. The system should support the ability to swing any individual room or any group of rooms by
touching one labeled touch point. Room(s) and consoles may be located anywhere within hospital
nurse/patient communications network.
2. The system should allow a console to capture an individual nursing unit, selected units, or all units
in hospital by touching single custom labeled touch point.
B. Call Priorities – The system should support a minimum of 200 unique, user-definable call priorities.
1. Each call priority should be reported via a user-defined mnemonic of up to 14 alphanumeric
characters.
2. Selectable call-in tone type, level, and corridor light behavior for each type of call priority.

2.4 STAFF REGISTRATION

The system should support staff registration. Staff members may, by pressing a dedicated button when
entering a room, indicate their presence to the system. Staff presence in the room shall be indicated by
illuminating the room’s green corridor lamp.
A. Users may review the location of staff members using an LCD Console and / or an Annunciate Panel.
B. If a call or service requirement is present in the room when a staff member registers into the room, the
system should automatically cancel the call(s).
C. If a call is placed from a room in which a staff member is already registered, the system should be
capable of automatically upgrading the priority of that call to indicate the need for staff assistance.

2.5 SERVICE REQUIREMENTS

The system shall support service requirement reminders. Staff members may, by pressing a button on the
console, initiate a service requirement reminder.
A. Service Requirements shall be indicated on the corridor lamp by a flashing lamp.
B. Users may review the location of service requirements using an LCD Console and / or an Annunciate
Panel.
C. If a service requirement remains unanswered for a pre-determined period of time, an overtime call
shall automatically be initiated.

2.6 STAFF FOLLOW

The system should support manual or automatic Staff Follow functions. When Staff Follow is enabled, call-
tones for a prescribed area will automatically be forwarded to the room station speaker where staff

Page 25
members are located. Staff location may be determined manually by entering the room number into the
console or automatically using staff register stations. Pressing the call button on that station shall silence the
tones. When a new call is placed, the tones shall automatically be restored.

2.7 ROOM MONITORING

The system should allow staff members to audibly monitor selected rooms.
A. Manual Monitor – Staff members may listen in to a selected room.
B. Sequential Monitor – Staff Members may enter a selected group of rooms for monitoring. The system
will automatically switch from room to room allowing the staff member to sequentially monitor the
rooms.
1. During monitoring, the staff member may press a button on the console to stop on the
current room to listen longer and then press Resume to restart the sequencing.
2. The staff member may adjust the time that the system spends on each room.
3. During Sequential Monitoring, the number of the room currently being monitored shall appear on
the console.

2.8 ROOM PRIVACY

The system should allow staff members to place a room in Privacy Mode to prevent unauthorized or
accidental audible monitoring of the room.
A. Rooms may be entered into or removed from Privacy by staff members using the console.
B. When a room that is in Privacy is dialed from a console or telephone, the staff member may speak into
the room but they may not listen to the room.
1. Privacy in the room may be temporarily suspended to allow two-way communications by pressing
the call-in button in the room. When the conversation is terminated, Privacy shall automatically be
restored.
2. If a call-in is placed from the room, the call may be answered from the console as normal using
two-way communications.
C. The rooms in privacy may be reviewed from the LCD console.
1. During the review process, rooms may be removed from Privacy mode.

2.9 CONSOLES / ANNUNCIATOR PANELS

System consoles should be provided as indicated on the plans and drawings. All system consoles shall be
UL1069 listed as an integral part of the core system. Telephones, personal computers or other devices which
carry only component listings or are otherwise not part of the core system UL listing are not acceptable.

A. LCD consoles:
1. The LCD console should be a small self-contained unit, which shall not occupy more than 87
square inches of desk space. The console shall include an easy-to-read 4-line / 80-character backlit
LCD display.
2. The console should provide function selector buttons and a telephone-style 12-button dial pad.
Selector buttons may be used to access user-configured 24-function menu.
3. The console may display up to three incoming calls each with an individual elapsed timer
indicating how long the call has been pending. Ability to scroll to see additional pending calls.
4. While idle, the console should display the time of day. Time may be displayed in 12 or 24-hour
format. Time display shall be consistent system wide.
5. Console shall include capabilities for both open voice (speaker / microphone) and telephone style
handset. Audio direction (talk / listen) for speaker / microphone and handset may be
accomplished via automatic voice switching (VOX) or manually via a Push-to-Talk button.
6. The highest priority (or longest pending) call may be answered automatically by lifting the handset
or by pressing the Push-to-Talk button. Calls may be answered out of sequence using line selector
buttons or by dialing the desired room number.

Page 26
7. Console shall provide independent volume controls for day/night call-in tones. A Mute button
shall be provided to temporarily suppress tones for pending calls.
8. The console may be desk or wall mounted.
9. The console should employ a modular quick-disconnect connector. It shall be possible to remove
and / or replace the console without removing power from the system.
B. Annunciator Panels
1. Annunciator Panels should be small self-contained units.
2. Each Panel will include 36 room indicator points. Each point will include two LED indicators and
space for labeling the point.
a. The LED’s should provide visual annunciation of room status. Indications will include
calls pending, service requirements pending and staff presence.
b. Variable colors and flash rates should provide differentiation of annunciation. A
Minimum of six distinct tone types shall be available for different types of calls.
3. Up to eleven expanders may be added to the panel each adding the ability to process 36 additional
room points per expander.
4. Panel shall provide independent volume controls for day/night call-in tones. A Mute button shall
be provided to temporarily suppress tones for pending calls.
5. The panel may be desk or wall mounted.
6. The panel shall employ a modular quick-disconnect connector. It shall be possible to remove and /
or replace the panel without removing power from the system.

2.10 CORRIDOR LAMPS / ROOM CONTROLLERS


Corridor Lamps ( 4-lamp style) should be provided as indicated on the plans and drawings.
A. Corridor Lamps shall utilize LED’s for high visibility, long life and low maintenance. Corridor Lamps
utilizing incandescent lamps shall not be acceptable.
1. The corridor lamp shall make use of multiple colors and programmable flash rates and patterns
to indicate pending calls, service requirements and staff presence.
B. Corridor Lamps shall serve as the hub for all room wiring. All field wire connections shall be
accomplished using modular connectors.
C. Any Corridor Lamp shall be able to function as a Zone Lamp that shall visually annunciate calls
from assigned rooms / stations without the use of a Zone Lamp controller such as a duty station.
D. The Corridor Lamp shall be equipped with a heart-beat LED (visible to service personnel) to indicate
that the unit is functioning properly.
E. The Corridor Lamp shall accommodate a paper label to indicate the room number. The manufacturer
shall provide, at no cost, laser-printing template software to create custom room labels.

2.11 ROOM STATIONS


Room Stations (single) should be provided as indicated on the plans and drawings.
A. Room Stations shall be equipped with:
1. DIN style receptacle(s) for call cord or pillow speaker.
2. Stations in areas requiring two-way communication shall be equipped with a speaker
microphone with level matching transformer.
a. Minimum speaker size shall be 3.0” / 7.6 cm
3. Reset Button to cancel pending calls. Reset button shall be able to cancel calls from other stations in
the room if desired.
4. Green LED to indicate that audio to the station is active.
5. Red LED(s) to indicate call placement from one or both of the call points.
6. Push call button with cancel button Patient station .
B. Room Station functions shall include:
1. Calls from dual stations should be annunciated independently.
2. Removing a call cord shall place a Cord Out call.

Page 27
a. Cord Out calls may be cancelled locally using the Cancel Button. No Dummy Plugs shall
be required.
C. Room Stations should employ modular connectors. It should be possible to service Room Stations
without removing power from the system.
D. Room Stations should support inputs frosm local equipment alarm contacts (e.g. ventilator, IV drip,
fire detector, etc.) to notify console of local alarm condition in patient room. There shall be at least four
auxiliary call in identifications available.

2.12 SUB-STATIONS
Provide Sub-stations as indicated on the plans and drawings. Sub-station types shall include:
A. Pull Cord Stations - Pull cord sub-stations should be water resistant with a PVC (poly-vinyl chloride)
pull-cord, membrane reset button and covered call assurance LED. Unit may utilize remote cancel
button for ease of nurse cancel when pull cord station is mounted in inaccessible location (e.g. ceiling).
B. Dual Call Pushbutton Stations - Dual Call Pushbutton stations should be equipped with two call
buttons, reset button and call assurance LED’s.
1. Call Button shall be labeled to clearly define its function.
2. Call Buttons shall annunciate independently of one another.
3. Call Buttons shall be backlit for easy location / identification in reduced light settings and shall be
labeled to clearly define its function.
4. Reset button should be able to cancel calls from other stations in the room if desired.
5. Bottom Call Button can start a digital clock/timer is shown on plan, sub-station shall interface (10
mA, opto-isolated output) for count up timer feature.

2.13 PATIENT ENTERTAINMENT SPEAKER/CALL CORDS


Patient Entertainment Speakers / Call Cords should be provided as indicated on the plans and drawings.
All Patient Entertainment Speakers / Call Cords shall be UL1069 listed as an integral part of the core
system. Devices which carry only component listings or are otherwise not part of the core system UL listing
are not acceptable.
A. Patient Entertainment Speakers – Patient Entertainment Speakers should be provided for patient call-in
and entertainment system control / audio.
1. All control buttons including call button should be raised and textured membrane style. Buttons
shall be labeled graphically for easy identification of functions. Control buttons shall be Braille
embossed.
2. Control buttons shall include:
a. Single easy to activate call button
b. Television / Radio controls as required.
3. The TV control mechanism shall be analog or digital as required by the facility televisions.
4. Cord shall be 10’ / 300cm and shall be modular for replacement by maintenance personnel. A
sheet clip shall be attached to the cord.
5. Speaker (minimum size 2.25” / 5.7cm) shall be liquid resistant. Thumb-wheel volume control shall
be provided.
6. Call Assurance LED shall be integral to the unit.
7. Cord Saver - All Patient Entertainment Speakers shall be provided with a 15” / 38cm DIN
style Cord Saver.
8. Patient Entertainment Speaker Hanger - All Patient Entertainment Speakers shall be provided with
a wall hanging bracket.

2.14 REPORTING SOFTWARE


Reporting Software should be provided with the system to allow for recording and reporting of
system activity.
A. The Reporting Software should be installed on a Personal Computer which shall in turn be connected
to the Nurse / Patient Communications System.
B. Reporting Software should support real time system activity display.

Page 28
1. Real time call waiting display with the ability to filter by call types and nursing units.
Call information shall be displayed and call-in tones shall be sounded.
2. Real time Nurse Communications Network service reminder display and staff locations.
3. Should the connection between the nurse / patient communications system and the
Reporting Software PC be lost, a warning signal shall be generated by the Reporting
Software.
C. Reporting Software should allow users to generate / print reports on system activity. Access to
reports shall be controlled based on user name and password. Reports shall be capable of indicating
call priority, room number and patient information, call placed time, service reminder set, staff
registration.
1. Reporting Detailed Analysis of Call Data by Area
2. Analysis of Call Data by Area
3. Analysis of Call Data by Room/Bed
4. Analysis of Call Data by Resident
5.Resident Check-In Exception
D. Reporting Software shall support a networked operation in which the Management Software
PC is connected to the hospital LAN. Users with access to the LAN can then generate reports
from local work stations.

2.15 CHASSIS FAULT, POWER MONITOR, AND SUPERVISED CODE


Provide a separate chassis short / power fault monitor to monitor integrity of network wiring for
short(s) to earth ground and to notify staff of loss of power. An audible alert tone shall sound if short or
loss of power is detected. Provide test button to test operation.

2.16 SYSTEM DIAGNOSTICS


The system should provide continuous self-diagnostics. The system shall also support advanced
computer diagnostics by local or remote technical personnel.
A. All components in the system shall be continuously supervised for both power and signal to
ensure proper operation and in the case of system faults to aid in troubleshooting.
B. The system shall have the ability to diagnose all network active components, controllers, control
stations, and sub-station operation from any designated network data interface location, on or off
site. Network administrator shall be able to:
1. Review system faults reported (i.e. station failure)
C. The system shall provide the ability to automatically notify maintenance personnel via pocket
page in the event of a system trouble or failure.
NOTE: EQUIVALENT OR SIMILAR NURSE CALL SPECIFICATION CAN ALSO BE
QUOTED WHICH CONFORM TO INTERNATIONAL STANDARDS FROM
US/UK/DIN/EN ISO/EUROPE

Page 29