0% found this document useful (0 votes)
194 views4 pages

AireAcondicionado (Chiller 1)

The document provides technical specifications for GS3B series air conditioners in 3, 4, and 5 ton capacities for light commercial applications. Key features include galvanized steel construction, copper tube coils, permanently lubricated motors, and accessibility for easy service. Dimensions, electrical data, refrigerant line sizes and weights are specified for both 10 SEER and 12 SEER models.

Uploaded by

Baltazar Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
194 views4 pages

AireAcondicionado (Chiller 1)

The document provides technical specifications for GS3B series air conditioners in 3, 4, and 5 ton capacities for light commercial applications. Key features include galvanized steel construction, copper tube coils, permanently lubricated motors, and accessibility for easy service. Dimensions, electrical data, refrigerant line sizes and weights are specified for both 10 SEER and 12 SEER models.

Uploaded by

Baltazar Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

TECHNICAL

SPECIFICATIONS

GS3BA Series 10 SEER


GS3BC Series 12 SEER
3 Phase Light Commercial
High Efficiency Air Conditioner
3, 4, 5 Ton Capacities
The GS3B(A,C) Series of air conditioners offers
exceptional performance from a small, compact
package. The unit, when combined with our
engineered coils or air handlers, offers a full line
of quality, split system cooling equipment. Units
are ideally sized for slab or rooftop mounting in
light commercial applications.

FEATURES and BENEFITS


• Designed using galvanized steel – with a polyester • Removable Top Grille Assembly – Allows ease of
urethane coat finish. The 950 hour salt spray finish service from the top without disconnecting fan motor
resists corrosion 50% better than comparable units. leads.

• Copper Tube / Aluminum Fin Coils – Both indoor and • One Piece Top/Orifice – Designed for maximum airflow
outdoor coils are designed to optimize heat transfer, and quiet operation.
minimize size and cost, and increase durability and
reliability. • 2-1/2" Pedestal Base – The sturdy base keeps the
bottom of the coil out of harms way. Secondly, the base
• Permanently Lubricated Motor – A heavy duty PSC has weep holes along the edge to allow the water from
motor for long lasting reliability and quiet operation. rain to flow away from the unit.
Requires no maintenance and is completely protected
from rain and snow. • Easy Compressor and Control Access – Designed to
make servicing easier for the contractor, access panels
• Full Service Valves – These brass valves are easily are provided to all controls and the compressor from the
accessible and simplify servicing of the refrigeration side of the unit.
system.
• Warranty – One year commercial parts warranty.
• Plastic Mesh Hail Guard – A guard that will never rust
and protects the units coil from being damaged.
MODEL IDENTIFICATION CODES

EX: GS3BA-036C
GS 3 B A - 036 C A
Nominal Style
GS - Air Conditioner A, B, etc.
Product Capacity
GT - Heat Pump
Identifier (000) BTU

Generation 1, 2, 3. etc. Electrical Code


C = 208/230-60-3
D = 460-60-3
BA = Braze 10 SEER
BC = Braze 12 SEER

DIMENSIONS
OUTDOOR SECTION
GS3BA- 036(C,D)A 048(C,D)A 060(C,D)B GS3BC- 036CA 048CA 060CA
H 22-1/2 34-1/2 30-1/2 H 34-1/2 34-1/2 42-1/2
W 22-1/2 22-1/2 30-1/2 W 22-1/2 30-1/2 30-1/2
D 22-1/2 22-1/2 30-1/2 D 22-1/2 30-1/2 30-1/2

Air Discharge
Allow Adequate
Clearance for Airflow

;
y ;;
yy
D W

;
y
;
y ;;
yy
;;
yy H

2
;
y ;;
yy
PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
10 SEER — High Efficiency — Three Phase
Model Number GS3BA- 036CA 048CA 060CB 036DA 048DA 060DB
Volts-Cycles-Phase (1) 208/230-60-3 208/230-60-3 208/230-60-3 460-60-3 460-60-3 460-60-3
Electrical Total Amps 11.3 14.2 20.1 4.9 7 9.8
Data Delay Fuse Max. (2) 20 30 40 15 15 20
Min. Circuit Ampacity 13.9 17.4 24.7 6 8.6 12
Area 8.3 15.3 17.7 8.3 15.3 17.7
Coil Rows-FPI 1-14 1-18 1-22 1-14 1-18 1-22
Tube Dia 3/8 O.D. 3/8 O.D. 3/8 O.D. 3/8" O.D. 3/8" O.D. 3/8" O.D.
Type PSC PSC PSC PSC PSC PSC
Condenser Fan Motor Amps 1.13 1.4 1.5 1.4 1.4 1.4
Data Watts-HP 93.25 - 1/8 186.5 - 1/4 186.5 - 1/4 93.25 - 1/8 186.5 - 1/4 186.5 - 1/4
Dia-# Blades 18 in. - 3 18 in. -4 24 in. - 3 18"- 3 18" - 4 24"- 3
Fan Blade
SCFM 2500 3000 4000 2500 3000 4000
Compresser RLA 10.2 12.8 18.6 4.3 6.4 9
Data LRA 75 91 128 40 46 63
Refrigerant suction line 0-24 ft. 3/4" 7/8" 7/8" 3/4" 7/8" 7/8"
O.D.(all length of liquid 25-39 ft. 3/4" 7/8" 1-1/8" (5) 3/4" 7/8" 1-1/8" (5)
line are 3/8" O.D.) 40-75 ft. 7/8"(4) 7/8" 1-1/8" (5) 7/8" (4) 7/8" 1-1/8" (5)
Refrigerant charge (R-22) in ounces for
outdoor unit, indoor unit and 15' lineset. 69 115 114 69 115 114
Weignt Net 128 166 190 128 166 190
Approximate (lbs.) Ship 134 178 202 134 178 202

12 SEER — High Efficiency — Three Phase


Model Number GS3BC- 036CA 048CA 060CA COPPER WIRE SIZE — AWG
Volts-Cycles-Phase (1) 208/230-60-3 208/230-60-3 208/230-60-3 (1% Voltage Drop)
Electrical Total Amps 11 13.8 18.7 Supply Wire Length-Feet Supply Circuit
Data Delay Fuse Max. (2) 20 25 40
200 150 100 50 Ampacity
Min. Circuit Ampacity 13.4 16.9 23
Area 13.2 20.3 25.4 6 8 10 14 15
Coil Rows-FPI 1-22 1-22 1-22 4 6 8 12 20
Tube Dia 3/8" O.D. 3/8" O.D. 3/8" O.D. 4 6 8 10 25
Type PSC PSC PSC 4 4 6 10 30
Condenser Fan Motor Amps 1.4 1.4 1.4
3 4 6 8 35
Data Watts-HP 186.5 - 1/4 186.5 - 1/4 186.5 - 1/4
Dia-# Blades 18"- 4 24"- 3 24"- 3
3 4 6 8 40
Fan Blade 2 3 4 6 45
SCFM 2800 4000 4000
Compresser RLA 9.6 12.4 17.3 2 3 4 6 50
Data LRA 77 88 123
Refrigerant suction line 0-24 ft. 3/4" (4) 7/8" 7/8" Wire Size based on N.E.C. for 60° type copper
O.D.(all length of liquid 25-39 ft. 7/8" 7/8" 1-1/8" (5) conductors.
line are 3/8" O.D.) 40-75 ft. 7/8" 7/8" 1-1/8" (5)
Refrigerant charge (R-22) in ounces for
outdoor unit, indoor unit and 15' lineset. 82 110 155
Weignt Net 142 186 238
Approximate (lbs.) Ship 151 198 250
(1) Operating voltage range: 208/230 volts 187 V minimum - 253 V maximum
460 volts 414 V minimum - 506 V maximum
(2) HACR type circuit breakers may be used
(3) Requires 3/4" to 5/8" reducer from unit to lineset.
(4) Requires 7/8" to 3/4" reducer from unit to lineset.
(5) Requires 1-1/8 to 7/8" reducer from unit to lineset.

3
SYSTEM HEATING & COOLING CAPACITIES
10 SEER — High Efficiency — Three Phase

Outdoor Unit With This Coil


Required
Model Number Coil Cooling Nominal
SEER EER Orifice
GS3BA- GC3BA- Btuh CFM
Size
036(C,D)A 036C/U-B (2) 34,600 10 9.0 1350 .067 (1)
048(C,D)A 048C/U-B (2) 46,000 10 9.0 1500 .080 (1)
048(C,D)A 048C/U-C 46,000 10 9.0 1500 .080 (1)
060(C,D)B 060C/U-C (2) 57,000 10 9.0 1800 .093 (1)

Outdoor Unit With This Air Handler


Required
Model Number Air Handler Cooling Nominal
SEER EER Orifice
GS3BA- GB3B(M,V)- Btuh CFM
Size
036(C,D)A 036K-B 34,600 10 9.0 1350 .067 (1)
048(C,D)A 048K-B 46,000 10 9.0 1600 .080 (1)
060(C,D)B 060K-C 57,000 10 9.0 1700 .093 (1)

12 SEER — High Efficiency — Three Phase

Outdoor Unit With This Coil


Required
Model Number Coil Cooling Nominal
SEER EER Orifice
GS3BC- GC3BA- Btuh CFM
Size
036CA 042(C,U)-B 34,600 12 9.0 1250 .075 (1)
048CA 060(C,U)-C (2) 46,000 12 9.0 1600 .082 (3)
060CA 060(C,U)-C+TDR (2) 56,000 12 9.0 1700 .093 (1)

Outdoor Unit With This Air Handler


Required
Model Number Air Handler Cooling Nominal
SEER EER Orifice
GS3BC- GB3B(M,V)- Btuh CFM
Size
036CA 042K-B+TDR 34,600 12 10.6 1250 .075 (1)
048CA 060K-C 46,000 12 11.0 1730 .082 (3)
060CA 066K-C+TDR 56,000 12 10.5 1600 .099 (3)

(1) Supplied with indoor section.


(2) Also available as GC3BH Horizontal Case Coil.
(3) Field supplied.
See current ARI Directory for certified combinations and ratings.

498B-0104 (Replaces 498B-0503)


CERTIFICATION APPLIES
Beforepurchasingthisappliance,readimportantenergy
ONLY WHEN THE cost and efficiency information available from your
COMPLETE SYSTEM retailer. Specifications and illustrations subject to
IS LISTED WITH ARI
change without notice and without incurring obligations.
Printed in U.S.A. (01/04)
O'Fallon, MO

You might also like