Full Documentation of Resume Builder Project
Full Documentation of Resume Builder Project
KUDANKULAM NPP
Units 3-6
Package Number T2
Number of the Document Total Number of Pages Date Revision
Number
R01.KK36.0.0.OO.KKS.P002 144 04.2018 0
Package Number T2
ANNOTATION
The present document is approved by Indian customers by letter № NPCIL/ENGG-
LWR/KKNPP5&6/2018/M/673 dated 28.03.2018.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 2
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTENTS
Definitions................................................................................................................................5
List of Abbreviations................................................................................................................6
1 Application requirements.......................................................................................................9
1.1 General requirements..........................................................................................................9
1.2 Basic principles and fields of application.........................................................................10
1.3 Procedure of producing....................................................................................................11
1.4 Procedure of coordination and approval...........................................................................11
1.5 Procedure of dictribution..................................................................................................11
1.6 Responsibility...................................................................................................................11
2 Subjects to finalize...............................................................................................................12
3 Requirements agreed upon..................................................................................................14
4 List of codes for process systems, buildings and structures................................................22
5 list of equipment codes......................................................................................................102
6 List of codes for equipment parts......................................................................................111
Appendix A Structure of functional-technological code KKS.............................................118
Appendix B Numbering in the equipment code...................................................................119
Appendix C Correlation between the service elevations and grade levels...........................131
Appendix D Principles of cable coding................................................................................132
Appendix E Coding principle of ULCS video frames.........................................................141
Appendix F Principles for coding ventilation system plants and equipment.......................142
Distribution list.....................................................................................................................143
Revision list..........................................................................................................................144
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 3
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
DEFINITIONS
Term Definition
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 4
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
LIST OF ABBREVIATIONS
APC automatic power controller;
ARSMS automated system of radiation situation monitoring;
ACS automated control system;
APCS automated process control system;
BRU-A fast-acting steam dump system with discharge into atmosphere;
BRU-D fast-acting steam dump valve for discharge into deaerator;
BRU-K fast-acting steam dump valve with discharge to turbine
condenser;
BRU-SN fast-acting steam dump unit with discharge to auxiliary header;
ELH essential loads header;
EPSS emergency power supply system;
CCR central control room;
CES central engineering storage;
CMS control and monitoring system;
CMS D control, monitoring and diagnostics system;
CRWS central repair workshops;
CS computer system;
CSS control safety system;
CTW chemically treated water;
EP emergency protection;
GIS gas-insulated switchgear;
GCB generator circuit breaker;
FA fuel assembly;
FE fuel element;
FPS TD feed pump set – turbine driven
FRWS fresh radioactive waste storage;
HPH high pressure heater;
HPC high pressure cylinder;
ISCS initiating safety control system;
IAS integrated analysis system;
I&C instrumentation and control system;
ICSS initial control safety system;
IRG inert radioactive gases;
ISH in-house supply header;
KKS classification and coding system;
LCB local control Board
LMS leak monitoring systems;
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 5
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
77-255/1624000 T2 04.2018 0 6
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
TDP
TPTS turbine-driven feed water pump set;
standard computerized automation facilities;
UDP unit demineralizing plant.
ULCS upper level control system.
USH unified Set of Hardware
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 7
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
1 APPLICATION REQUIREMENTS
1.1.2 The KKS classification and codification system is a universal system that enables
it to identify any process system, facility, structure or component in the process of designing,
erection and operation of a power plant.
1.1.3 The «Agreement on KKS codification system appliance in the NPP
“Kudankulam” Project in India» (hereinafter the Agreement) regulates activity of organizations
involved in development of NPP “Kudankulam” project as for application of the classification
and coding system KKS. The agreement has been developed in compliance with requirements
of standard regulations for KKS application.
1.1.4 The standard regulations for KKS application are stipulated in KKS
documents:
«Guidelines for KKS Application», 4-th version of 1995;
«KKS Application Commentaries. Part A General», version of 1988;
«KKS Application Commentaries. Part B Engineering Discipline-Specific. Part B1
Identification in Mechanical Engineering», version of 1988;
«KKS Application Commentaries. Part B Engineering Discipline-Specific. Part B2
Identification in Civil Engineering», version of 1988;
KKS Application Commentaries. Part B Engineering Discipline-Specific. Part B3
Identification in Electrical and Instrumentation and Control Engineering», version of 1988;
«Usage Instructions. Part B Engineering Discipline-Specific Application
Commentaries. Part B4 Identification of I&C Tasks and Functions in Process Systems and of
Functions in I&C Systems», version of 1993;
«KKS Keys», version of 1991;
1.1.5 Structure of functional-technological code KKS is addressed in
appendix А.
1.1.6 Section 3 of this document «Requirements agreed upon» contains a list of non-
regulated by KKS provisions, which is a subject of agreement. This list may be extended if new
provisions appeared in the course of work.
1.1.7 Since the full number of process systems, buildings and structures can be known
and coded only when the detailed design is finalized this document presents the list of codes
adopted at the stage of first-period design works.
The full list of codes for process systems, buildings and structures shall be issued at
the working documentation stage.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 8
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
1.1.8 To meet any additional identification requirements, the KKS codes, or parts
thereof, can be combined with other coding systems. This shall be reported to the Customer and
all participants of the project in writing.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 9
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
1.6 RESPONSIBILITY
1.6.1 The General Designer of the Power Plant is responsible for development and
revision of this document.
1.6.2 The Customer (JSC «Аtomstroyexport») and the General Designer of the Power
Plant are responsible for providing their subcontractors with the document.
1.6.3 Developer of particular documentation of Kudankulam Project is responsible for
accuracy of structure and coding of KKS.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 10
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
2 SUBJECTS TO FINALIZE
2.1 The conditions of application are strictly and explicitly covered by the KKS
system as a whole and only in particular cases general recommendations regarding possible and
expedient ways of coding the NPP components are provided. These KKS regulations shall be
mutually agreed between all designing participants which ensures the uniformity of the KKS
coding system application, to extend the information content of the codes and will ensure
unambiguous understanding of the technical documentation by the Principal.
2.2 The list of codes not specified in KKS and being subject to agreement between all
the participants of design development is given below.
General conditions
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 11
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 12
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 13
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 14
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 15
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 16
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 17
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
77-255/1624000 T2 04.2018 0 18
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 19
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 20
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 21
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
A.. Networks and switchgears
AC. 400 kV gas insulated switchgear and control gear
ACA Bus system I
ACB Bus system II
ACE 400 kV gas-insulated bus duct
ACL 400 kV power transmission line
ACQ 400 kV switch
ACR 400 kV reactor
ACT 400/220 kV autotransformer
AD. 220 kV gas insulated switchgear and control gear
ADA 220 kV bus system I
ADB 220 kV bus system II
ADE 220 kV SFG bus duct
ADL 220 kV power transmission line
ADQ 220 kV switch
AF. Systems at 60 kV and less
AFA Section 0,38 kV (from AFT11)
AFB Section 0,38 kV (from AFT21)
AFT Auxiliary transformers 6/0.4 кV, belonging to power output system
AH. Standby power supply of power output delivery system
AHA Trunk line of standby power supply of common-station load from
AHT10
AHT Stand-by transformers 6/0.4 kV of normal operation
AR. Auxiliary low-voltage switchgear, uninterruptible (inverter)
power supply of the power output system
ART Inverter of normal common plant system
AT. Installation of storage batteries of power output delivery system
ATA 220 V batteries of normal common plant system
ATL Boost charging & battery charging rectifier of normal common
plant system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 22
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
AUS Portable system for cable fault detection
B.. Power transmission and auxiliary power supply
BA. Energy removal, generator voltage conductors
BAA Removal from generator, generator voltage conductors
BAB Foundation cells
BAC 24 kV GCB, including chilling installations
BAT Generator transformers, including chilling installations
BAY Control monitoring and relay protection system of electric
equipment
BB. 6 kV auxiliary sections and transformers. Normal operation
system
BBA 6 kV switchgears for normal operation system (Unit section 1)
BBB 6 kV switchgears for normal operation system (Unit section 2)
BBC 6 kV switchgears for normal operation system (Unit section 3)
BBD 6 kV switchgears for normal operation system (Unit section 4)
BBT 24/6,3-6,3 kV working transformer for power auxiliaries for normal
operation system
BBY Control monitoring and relay protection system of electric
equipment
BC. Standby power supply section for the common-station load and
standby power supply transformers of 6 kV buses. Normal
operation system.
BCA 6 kV standby power supply section (network 1)
BCB 6 kV standby power supply section (network 2)
BCC 6 kV standby power supply section (network 3)
BCD 6 kV standby power supply section (network 4)
BCE 6 kV section 1 for common-station load
BCF 6 kV section 2 for the whole plant load
BCG 6 kV section 4 for the whole plant load
BCH 6 kV section 3 for the whole plant load
BCJ 6 kV section for common-station load
BCK 6 kV section for common-station load
BCL 6 kV standby power supply line
BCT 220/6,3-6,3 kV standby and common-station auxiliary transformers
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 23
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BD. Switchgears 6 kV of emergency power supply system
BDA Emergency power supply system (EPSS) switchgears (safety
channel 1)
BDB Emergency power supply system (EPSS) switchgears (safety
channel 2)
BDC Emergency power supply 6 kV system (EPSS) switchgears (safety
channel 3)
BDD Emergency power supply 6 kV system (EPSS) switchgears (safety
channel 4)
BDE Section 1 of emergency power supply (diesel common-station
network) of normal operation system
BDF Section 2 of emergency power supply (diesel common-station
network) of normal operation system
BDG 6 kV cable assembly of XKA 50 diesel-generator
BDH 6 kV cable assembly of XKA 60 diesel-generator
BDL 6 кV section power supply line of EPSS and 6 kV section power
supply line of NOS reliable power supply
BF. 0,4 kV auxiliary unit sections and 6/0,4 kV transformers.
Normal operation system
BFA Unit section from BFT11
BFB Unit section from BFT21
BFC Unit section from BFT31
BFD Unit section from BFT41
BFE Unit section from BFT12
BFF Unit section from BFT22
BFG Unit section from BFT32
BFH Unit section from BFT42
BFJ Pressurizer section from BFT13
BFK Pressurizer section from BFT23
BFL Pressurizer section from BFT33
BFM Unit section from BFT41
BFN Lighting section from BFT14
BFP Control and protection system section from BFT24
BFR Control and protection system section from BFT44
BFT 6/0,4 kV auxiliary transformer of Main Building
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 24
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BFW Lighting section from BFТ34
BG. Sections 0,38 kV and transformers 6/0,4 kV of normal reliable
power supply system
BGE Section 0,38 kV from BGT11
BGF Section 0,38 kV from BGT21
BGJ Section 0,38 kV from BGT12
BGK Section 0,38 kV from BGT22
BGN Section 0,38 kV from BGT13
BGP Section 0,38 kV from BGT23
BGT Auxiliary 6/0,4 kV transformer, belonging to normal reliable power
supply system
BH. Main standby power supply low-voltage networks 0,38 kV and
standby transformers 6/0,4 kV
BHA Standby auxiliary section 0,38 kV from BHT11
BHC Standby auxiliary section 0,38 kV from BHT31
BHD Standby auxiliary section 0,38 kV from BHT43
30BHE Standby auxiliary section 0,38 kV from 30BHT51
40BHE Standby auxiliary section 0,38 kV from 40BHT21
30BHF Standby auxiliary section 0,38 kV from 30BHT61
40BHF Standby auxiliary section 0,38 kV from 40BHT41
40BHG Standby auxiliary section 0,38 kV from 40BHT51
BHH Standby auxiliary section 0,38 kV from BHT62
BHK 0,38 kV section of NO reliable power supply from BHT71
BHL 0,38 kV section of NO reliable power supply from BHT72
BHT Standby auxiliary transformer 6/0,4 kV
BJ. Low-voltage subdistribution boards and transformers 6/0,4 kV,
normal operation system
BJB Section 0,38 kV from BJT21 main pump station
BJC Section 0,38 kV from BJT31 main pump station
BJT Transformers 6/0,4 kV main pump station
BK. Sections 0,38 kV and transformers 6/0,4 kV of common-station
load
BKD 0,38 kV section of common-station load from ВКT15
BKE Section 0,38 kV from ВКT11
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 25
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BKF 0,38 kV section of common-station load from ВКT11
BKG Section 0,38 kV from ВКT12
BKH Section 0,38 kV from ВКT22
BKJ Section 0,38 kV from ВКT13
BKK 0,38 kV section of common-station load from ВКT23
BKL 0,38 kV section of common-station load from ВКT14
BKM 0,38 kV section of common-station load from ВКT24
BKN Section 0,38 kV from ВКT15
BKQ 0,38 kV section of common-station load from ВКT11
BKS Section 0,38 kV from BKT17
BKT Transformer 6/0,4 kV of common-station load
BKU Section 0,38 kV from BKT27
BL. Low voltage subdistribution boards and transformers
BLT 0,38/0,415 kV matching transformer for electric lighting supply
BM. Low-voltage switchgears 0,38 kV and transformers 6/0,4 kV.
Emergency power supply system
BMA Section 0,38 kV from BMT11
BMB Section 0,38 kV from BMT21
BMC Section 0,38 kV from BMT31
BMD Section 0,38 kV from BMT41
BME Section 0,38 kV from BMT12
BMF Section 0,38 kV from BMT22
BMG Section 0,38 kV from BMT32
BMH Section 0,38 kV from BMT42
BMJ Section 0,415 kV from BMT13 (6/0,433 kV)
BMK Section 0,415 kV from BMT23 (6/0,433 kV)
BML Section 0,415 kV from BMT33 (6/0,433 kV)
BMM Section 0,415 kV from BMT43 (6/0,433 kV)
BMT Auxiliary transformer 6/0,4 kV for power supply to sections
0,38 kV
BR. Auxiliary low-voltage switchgears, uninterrupted (inverter-
type) power supply to both EPSS and NOS
BRA Power supply cabinets for MCR/SCR Channel 1 safety panel
instrumentation
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 26
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BRB Power supply cabinets for MCR/SCR Channel 2 safety panel
instrumentation
BRC Power supply cabinets for MCR/SCR Channel 3 safety panel
instrumentation
BRD Power supply cabinets for MCR/SCR Channel 4 safety panel
instrumentation
BRG Power supply cabinets for MCR components (NO) and service
devices
BRH TPTS power supply cabinets
BRT Inverter of emergency power supply system, normal operation
system
BRU Inverter of emergency power supply system
BT. Storage battery installations
BTA Storage batteries 220 V, normal operation network
BTB Storage batteries 110 V, reactor control and protection system
BTD EPSS storage batteries 220 V
BTL Charging rectifier 220 V for normal operation system
BTM Charging-recharging rectifier 110 V, reactor control and protection
system
BTP EPSS boost charging & battery charging rectifier
BU. DC boards, normal operation system
BUA DC board 220 V from BTA10
BUB DC board 220 V from BTA20
BUC DC board 220 V from BTA30
BUD DC board 220 V from BTA40
BUE DC board for chlorination plant
BUF DC board for chlorination plant
BUL Control and protection system DC board 110 V
BUM Control and protection system DC board 110 V
BUS Portable system for cable fault detection
BV. DC boards, emergency power supply system
BVA DC boards 220 V from BTD11
BVB DC boards 220 V from BTD21
BVC DC boards 220 V from BTD31
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 27
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BVD DC boards 220 V from BTD41
BVE DC boards 220 V from BTD13
BVF DC boards 220 V from BTD23
BVG DC boards 220 V from BTD33
BVH DC boards 220 V from BTD43
BVJ DC boards 220 V from BTD12
BVK DC boards 220 V from BTD22
BVL DC boards 220 V from BTD32
BVM DC boards 220 V from BTD42
BVS Portable system for cable fault detection
C.. I&C equipment
CD. Drives control (control circuits decoupling cabinets)
CDA Alarm and control circuits decoupling cabinets of safety systems
(channel 1)
CDB Alarm and control circuits decoupling cabinets of safety systems
(channel 2)
CDC Alarm and control circuits decoupling cabinets of safety systems
(channel 3)
CDD Alarm and control circuits decoupling cabinets of safety systems
(channel 4)
CE. Alarm system
CEJ Operation important parameters registration system
CER IAEA Surveillance system
CF. Measurement, recording
CFL Radiation monitoring cabinets (for gateway)
CFM Radiation monitoring cabinets (for data storage and processing
device)
CFN Radiation monitoring cabinets (for switching device)
CFP Radiation monitoring cabinets (for alarm device)
CFQ Archiver with time server
CH. Protection (excl. reactor protection)
CHC Main protections of the power unit (electric equipment)
CHE Main protections of the power unit (generator excitation system)
CK. Process computer system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 28
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CKA MCR working stations of Reactor Building
CKB MCR working stations of Turbine Building
CKC Common-unit working stations
CKD MCR (rear control panels) working stations
CKE Electrical shop workstations
CKF Even documenting devices (printers)
CKG Workstations
CKH Workstations
CKK Upper unit level devices (commutators)
CKL Computers for electrical part
CKM Upper unit level devices (servers)
CKN Computer aids interfacing device (safety system)
CKP Computer aids interfacing device (normal operation)
CKQ ECR working stations
CKY Cabinets of special hardware for fire alarm devices
CL. Reactor protection
CLA Reactor protection
CLA01-02 Emergency command cabinet
CLA03-04 Power supply cabinet with AC interrupting contactors
CLA05-06 Power supply cabinet with DC interrupting contactors
CLA11-13 Software and hardware system for protection
CLA14-16 Terminal cabinet
CLA21-22 Fiber-optic cross-terminal cabinet
CLA31-33 Data accumulation and processing unit
CLA41-43 Data accumulation and processing unit
CLA51-65 Characteristic conversion unit
CLB Reactor Protection-Actuating Part
CLB01-02 Power supply and control cabinet
CLB07 Set disabling cabinet
CLN Reactor protection
CLN11-14 Data accumulation and processing unit
CLN15-16 Interfacing and data exchange unit
CLN17 Reactor internals monitoring equipment
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 29
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 30
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CMG Gas/powder fire suppression controllers
CMH Cabinets of monitoring and control systems for instrumentation
shop
CMK Cabinets of monitoring and control systems delivered in complete
set with equipment (SG PSD, PRZ PSD etc.)
CMR Cabinets for control and monitoring systems of Reactor Building
normal operation equipment
CMS Cabinets for control and monitoring systems of normal operation
fire-fighting equipment
CMT Cabinets for control and monitoring systems of Turbine Building
normal operation equipment
CMV Cabinets for control and monitoring systems of normal operation
ventilation equipment
CMW Cabinets for control and monitoring systems of normal operation
SVO equipment
CMX Cabinets for control and monitoring systems of normal operation
turbogenerator equipment
CMY Cabinets for control and monitoring systems of normal operation
turbine governing equipment
CN. Diagnostics cabinets for special systems and analogue signal
monitoring cabinets for safety systems
CNA Cabinets of analogue signal control from safety systems (channel 1)
CNB Cabinets of analogue signal control from safety systems (channel 2)
CNC Cabinets of analogue signal control from safety systems (channel 3)
CND Cabinets of analogue signal control from safety systems (channel 4)
CNN Special systems diagnostics cabinets on leaks, vibration and loose
parts
CNP Normal operation I&C equipment
CNQ Equipment of normal operation I&C important for safety, and
normal operation I&C
CNR Commissioning measurement system
CP. I&C equipment
CPA I&C converter cabinets for safety systems (channel 1)
CPB I&C converter cabinets for safety systems (channel 2)
CPC I&C converter cabinets for safety systems (channel 3)
CPD I&C converter cabinets for safety systems (channel 4)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 31
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CPM I&C converter cabinets for normal operation systems of turbine
building
CPR I&C converter cabinets for normal operation systems of reactor
compartment
CPW I&C converter cabinets for normal operation active water
purification systems
CV. Racks for information receiving and transmission equipment
CVA Safety systems cross-terminal cabinets (channel 1)
CVB Safety systems cross-terminal cabinets (channel 2)
CVC Safety systems cross-terminal cabinets (channel 3)
CVD Safety systems cross-terminal cabinets (channel 4)
CVE Cross-terminal cabinets of monitoring and control system for
electric equipment
CVF Distribution cabinets for fire fighting system
CVG Cabinets of signal input from common station systems
CVK Electro-optic signals receiving and transmission equipment
CVR Reactor Building normal operation cross-terminal cabinets
CVS Normal operation cross-terminal cabinets (fire-fighting)
CVT Turbine Building normal operation cross-terminal cabinets
CVT60 Cross cabinet (counter for binding of TPTS with EMT (BRU-K) of
normal operation of turbine building
CVV Normal operation ventilation equipment cross-terminal cabinets
CVW Normal operation SVO cross-terminal cabinets
CVX Normal operation turbogenerator cross-terminal cabinets
CVY Normal operation turbine governing cross-terminal cabinets
CVZ Cross-terminal cabinets, supplied complete with the equipment
CW. Control room
CWA MCR consoles (Reactor Building)
CWB MCR consoles (Turbine building)
CWC ECR consoles
CWD Boards of unit shift supervisor
CWE01-09 Boards and panels of GCC
CWE10-49 Boards of technical maintenance center, software engineer,
instrumentation shop shift supervisor
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 32
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CWE51-91 Boards and panels of GCC
CWF MCR consoles (safety system)
CWG Generalized mimic diagram
CWH MCR consoles (normal operation)
CWH01-29 MCR consoles at area of rear control panels of MCR
CWH30-39 Radiation monitoring boards
CWH41-99 MCR consoles at area of rear control panels of MCR
CWK SCR boards
CWL Boards of local crisis center, NPP shift supervisor
CWM Boards of water purification facility
CWS Panels of control board for cooling water intake systems
CX. Local control boards
CXA Cabinets for emergency power supply and control safety system
buildings
CXB Cabinets for radwaste collection, processing and storage systems
CXC Control cabinets of the reloading machine
CXD Gates control system
CXF Control cabinets for cooling seawater purification systems
CXF75-80 Local boards for chlorination plant
CXG Compressor control cabinets
CXH Cabinets for liquid radwaste processing systems
CXJ Cabinets for auxiliary steam production systems
CXM Cabinets for chiller monitoring and control system
CXN Control cabinets for diesel fuel supply and used oil collection plants
CXQ Cabinets for liquid waster disposal
CXR Control cabinets for demineralizing plant regeneration system
CXS Cabinets for cooling water supply system
CXT Cabinets for chemical reagent supply and dosing systems
CXU Cabinets for fire fighting water and service water supply system
CXV Ventilation system control cabinets
CXW Power supply and control cabinets for fire retarding valves and
smoke removing valves
CXY Control cabinets for drains water collection and purification systems
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 33
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CY. Communication equipment
CYA Common-station telephone communication
CYB Telephone operative communication
CYC Operative loud speaking duplex communication
CYD Searching command communication
CYE Fire alarm system
CYG Common time system
CYH Announcing
CYJ Operating radio telephone system
CYL Record of the operating personnel commands
CYP Industrial television system
CYP10-20 Operative personnel actions videorecording system
CYP50-90 Surveillance System of IAEA
CYR Physical protection system
CYS Stand-by internal radio communication
CZ. Technical means of security
CZD Local annunciation system
D.. I&C equipment
DR. Low level of ARSMS
DRM Data acquisition and processing unit
DRN Switching unit/Controller
DW. High level of ARSMS
DWD30 ARSMS central monitoring station
DWD31 Reserve monitoring station
E.. Fuel feed
EG. Diesel fuel oil supply for the auxiliary boiler house
EGB Tank facilities
EGB01-40 Diesel fuel supply system to auxiliary boiler installation House
EGT Fuel system for the auxiliary boiler house
EGY Control, regulating and protection system
ER. Boiler kindling fuel feed
ERC Gas feed system
ERY Control, regulating and protection system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 34
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 35
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
FCC Core detail moving equipment (except for FCA and FCB)
FCD Reloading devices in storage for fuel assemblies and other core
elements
FCF Equipment lock
FCJ Handling devices for fuel assemblies and other core details between
various storage facilities
FCL Cooling and pressurization system for fuel assemblies handling
devices (Not Used)
FCT Supply (evacuation) of substances for cooling, heating and flushing
(Not Used)
FCY Control, regulation and protection devices
FJ. Fuel element and core element erection and retest systems
FJA Tooling and equipment for installation and maintenance of RPV
and reactor cover
FJB Tooling and equipment for installation and maintenance of reactor
internals
FJC RPV and reactor cover retest equipment
FJE Equipment and tooling for maintenance of primary components
FJF Primary component retest equipment
FJM Devices for reactor containment
FK. Equipment and room decontamination systems
FKA Reactor building equipment and room decontamination system
FKJ Active laundry (SVO-7) system
FKJ50 The system for preparing and supplying chemical agents to the
active laundry waste water purification system
FKK RCP removable parts and other machine details decontamination
devices system
FKK10-19 Controlled-access area control workshops decontamination system
FKN Mobile decontamination units system
FKT Decontamination solution preparation and supply system
FKT70-99 Decontamination solution supply system in buildings 00UKS,
00UKU, 00UYB
G.. Water supply and water discharge
GA. Fresh water acquisition (water supply and water discharge)
GAC System for seawater supply to desalination plant 00UGX
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 36
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
GAF Pump units for seawater supply to desalination plant 00UGX
GC. Process water demineralization systems
GCB Influent water mechanical cleaning system
GCF Influent water ion-exchange cleaning system
GCF00 Influent water ion-exchange cleaning system on trestle 00USY
GCF83-84 Demineralized water supply system
GCR Water treatment plant waste water neutralization system
GCR00 Water treatment plant waste water neutralization system on trestle
00USY
GD. Sludge demineralization systems
GH. Non-potable water distribution systems
GHA Cooling water piping for servomotor
GHC Non-potable water distribution systems after demineralization
GHC10-20 Makeup water for the auxiliary boiler house
GK. Service and potable water supply systems
GKD The domestic-drinking water pipeline
GKE Source water pipeline
GKF Hot water supply
GM. Plant drainage system
GMA Oil-containing water sewerage system
GMC Pump set system for oil-contaminated drains evacuation
GML System for leak collecting, removal and extraction of industrial
waste waters from the main pump house 30UQA (40UQA)
GML10 Waste water collection and disposal system after automatic fire
fighting of cable tunnels of the main pump house 30UQA
(40UQA) (gravity system)
GML20 Waste water collection and disposal system after automatic fire
fighting of cable tunnels of the main pump house 30UQA (40UQA)
(pressure system)
GML30 Drainage pumping out system of the main pump house 30UQA
(40UQA) (pressure system)
GMM Fire fighting, tanks emptying and drainage water collection and
discharge system
GMN Pipelines of exhaust system from instrumentation compartments and
compartments of secondary circuit emergency cooling-down
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 37
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
GMP Drain system of diesel and oil storage facilities
GN. Used process water treatment systems
GNR Flushing water and residues removal system incl. Neutralization
GNR00 Waste water after chemical flushing and preservation of equipment
neutralization system on trestle 00USY
GNR10-40 Waste water after chemical flushing and preservation of equipment
neutralization system
GQ. Service waste water collection and discharge systems
GQA Free access area service sewerage system
GQB Pump set system for common-access area domestic drains
evacuation
GQC Pump set system for controlled-access area domestic drains
evacuation
GQD Controlled access area service sewerage system
GQE Domestic sewerage of control-access area for hand-wash basins
GR. Service waste purification systems
GT. Water acquisition from industrial aqueous waste systems
GU. Rain water drain systems, including waste treatment
GUD Storm water sewerage
GUF Pump set system for rainstorm water evacuation
GUU NPP ground water drains system
H.. Conventional heat generation
HH. Main combustion system
HHA Main burners
HHL Secondary air supply (combustion air)
HHM Spraying medium supply (steam)
HHR Purging medium supply (steam)
HJ. System of ignited combustion
HJA Ignition device
HJQ Cooling medium supply (air)
J.. Nuclear generation of heat
JA. Reactor systems
JAA Reactor pressure vessel, including unions and welded parts
JAB Reactor pressure vessel closure head (upper unit), including flanges,
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 38
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
seals, studs
JAC Reactor internals
JAH Reactor external insulation
JAT Leak monitoring systems
JB. Reactor vessel internals
JBA Reactor vessel surveillance specimens
JD. Reactor control and shutdown devices
JDA CPR drive system
JDJ Fast boron concentrate injection to trip reactor
JE. Reactor cooling system (primary circuit)
JEA Steam generation system
JEA01 Air removal system from SGs on secondary circuit
JEA10-40 Steam generation system
JEA50-90 Steam generator level monitoring and pipeline steam line humidity
JEB Reactor coolant pump system
JEC Reactor coolant piping system
JEF Pressurization system
JEF10-40 Pressurization system
JEF50-80 Pressurizer pulse safety devices system
JEG Steam receipt from pressurizer dumping devices system
JET Reactor coolant controlled leak-off system
JEV RCP motor lubrication system
JEV50 Lubricating oil supply system to the RCP set oil tanks
JEW RCP sealing water system (Not Used)
JK. Reactor core with appurtenances
JKA Reactor core
JKM System for retention and cooling of reactor molten core (JKM)
JKS In-core instrumentation system
JKT Ex-core instrumentation system
JKU Fuel element cladding tubes monitoring system
JM. Containment with internals
JMA Reactor building containment shells system
JME Equipment airlock
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 39
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 40
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
system)
JNK Borated water storage system.
JY. Control and protection equipment (other than “JR”, “JS”,
“JT”)
JYF Loose parts monitoring system
JYG Vibration monitoring system
K.. Reactor plant auxiliary systems
KA. Component cooling systems
KAA Component cooling system for reactor plant loads
KAA51, Component cooling system for reactor plant loads (heat exchangers
61,81 of systems KUA10-50, KUE)
KB. Reactor coolant treatment system
KBA Volume and chemical control system
KBB Operating grade coolant storage system
KBC Boric acid and demineralized water control system
KBC10-30 Distillate system
KBC40-60 Boron concentrate system
KBC70 System of vertical stand hydraulic testing
KBD System for addition of chemical reagents to primary coolant
KBE Coolant purification system
KBE10-40 High temperature purification system of primary coolant
KBE50-60 Low temperature purification system of primary coolant
KBF Coolant purification system
KBH Fuel pond water purification system
KBW System of sealing fluid supply to *KB.* systems
KL. Ventilation plants in controlled area
KLA Containment (reactor building) ventilation systems
KLB Annulus space ventilation systems
KLB50-80 Annulus passive filtering system
KLC Ventilation plants for safety (controlled access area) process
systems
KLE Ventilation plants for normal operation process systems, active
water treatment and dirty workshop building
KLF Ventilation plants for solid radwaste treatment and storage building
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 41
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
KLP Ventilation plants for purification works for domestic sewage from
controlled access area
KLR Ventilation plants for laboratory and service building and active
laundry
KLS Ventilation plants for controlled access area of sanitary and service
building
KP. Radioactive waste handling
KPA Solid radwaste processing system
KPA10-40 Solid radwaste classifying system
KPA50 Solid radwaste pressing system
KPC Concentrating plant
KPE Solid radwaste storage system
KPF Liquid radwaste processing system
KPF00 Floor water treatment system (SVO-3) on trestle 00USY
KPF10-60 Floor water treatment system
KPF70-79 Floor water collecting system in building 00UKS, 00UKU
KPH Solid radwaste burning system
KPJ Reagent preparation and supply system
KPJ70 20 % NaOH supply system
KPK Temporal liquid radioactive fluid storage system
KPL Burning system for hydrogen from radioactive process blow-offs
KPM Radioactive process blow-offs purification system
KPM40 System for purifying blow-offs from the equipment pertaining to
the liguid radioactive media
KPN Cementation unit
KPP Solid radwaste fragmentation system
KPW Supply system of sealing fluid to *KP.* systems
KR. Gasses supply and removal system
KRA Nitrogen supply to flow-offs from reactor equipment
KRA00 Nitrogen supply to flow-offs from reactor equipment on trestle
0 USY
KRA10-20 System of nitrogen supply to blow-off from reactor building
equipment
KRP Oxygen supply system for hydrogen after-burning systems in main
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 42
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
building
KRQ Oxygen supply system for hydrogen burning system in special
building
KRQ00 Oxygen supply system for hydrogen burning system in special
building on trestle 00USY
KT. Nuclear auxiliary systems
KTA Primary drains and controlled leaks system
KTB Gaseous blow-off system
KTC Collecting system for disposal from reactor systems
KTC10-20 Collecting system of boron-containing water from reactor systems
KTF Active drainage pipework system for containment
KTH Active floor drainage system from buildings 30UJA (40UJA,
50UJA, 60UJA) and 30UKC (40UKC, 50UKC, 60UKC) (pressure)
KTM Drains system for plants of radioactive waste processing building
KTN Active drainage pipework system (traps) of 30UKC (40UKC,
50UKC, 60UKC) building
KTP Emergency gas removal system
KTQ Fuel storage pool lining integrity monitoring system
KTR Active floor drainage system from building 00UYB
KU. Sampling systems
KUA Sampling system for primary circuit
KUA10-50 Reactor building equipment sampling system
KUA60-80 Automated chemical monitoring system for primary circuit
KUE Sampling system from purification plants
KUJ Radioactive gaseous sampling system
KUJ11-15 Gaseous radioactive media sampling system
KUJ16 Ventilation stack gaseous radioactive media sampling system
KUK Sampling system for building 00UYB
KW. Nuclear sealing and flushing fluid supply systems
KWA System of I&C transducers hydraulic testing and flushing by
distillate
KWB System of I&C transducers flushing
KWB50 Secondary-side steam generators hydraulic testing system
KWB60 Secondary-side steam generator hydraulic testing pump piping
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 43
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
system
KWC System of hydraulic testing of the primary circuit and I&C
transducers flushing
KWJ10-15 Piping system of CPS actuators stand
L.. Steam, water, gas cycles
LA. Feedwater systems
LAA Feedwater collecting and deaeration system
LAB Main feedwater piping system
LAC Feedwater pump system
LAD HP regeneration system
LAH Auxiliary feedwater piping system
LAJ Auxiliary feedwater pump system
LAY Control and protection equipment
LAY10 Monitoring, control and diagnostic system for the feed water pumps
turbine drive
LAY20 Monitoring, control and diagnostic system for the feed water pumps
LB. Steam piping system
LBA Main steam piping system
LBB System of superheat steam piping in LP cylinder (including steam
reheater)
LBC Steam supply piping system from turbine to reheater (Not Used)
LBD Steam extraction to deaerator piping system, ISH, heating water
converters and so on.
LBF High pressure reducing system
LBF10 BRU-SN system
LBF50-60 BRU-D system
LBG Auxiliary steam piping system
LBG00 Auxiliary steam line system on trestle 00USY
LBG10-70 Auxiliary steam line system
LBG80 Steam supply system in 00UKS, 00UKU, 00UYB
LBG90 Pre-start heat-up system for pipe interspace of high pressure
preheater
LBH Start-up, using external source, and shutdown steam system
LBJ Steam moisture separation system in LP cylinder
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 44
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
LBK BRU-A system
LBQ HP steam extraction piping system
LBR Piping system for TDP turbine
LBS LP steam extraction piping system
LBT BRU-K system
LBU SG safety valves system, including exhaust pipelines
LBW Turbine sealing steam system
LBW10-20 Turbine sealing steam system (including valve stems)
LBW30-50 TDP sealing steam system (including valve stems)
LC. Condensate systems
LCA Main condensate piping system
LCA70 System of main condensate supply to the deaerator and of auxiliary
pipelines
LCA90 System for pre-starting fishing of the condensate and feeding line
LCB Main condensate pump system
LCC LP heaters system
LCE Condensate injection to BRU-K system
LCF TDP turbine condensate piping system
LCG TDP turbine condensate pump system
LCH HP heater condensate system
LCJ LP heater condensate system
LCL Steam generator drains system
LCL70 Steam generator water removal pump tank piping system
LCM Turbine hall drains system
LCM00 Turbine hall drains system (condensate collecting and return for
active water treatment) on trestle 00USY
LCM10-70 Turbine hall drains system (condensate collecting and return)
LCM73-79 Heating steam condensate return system in 00UKS, 00UKU,
00UYB
LCM80-90 Turbine hall drains system (condensate collecting and return for
active water treatment)
LCN HP steam piping drains system
LCP Turbine hall demineralized water system
LCQ Steam generator blowdown system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 45
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
LCQ10-40 Steam generator blowdown and drains system
LCQ50-80 Steam generators blowdown water purification system
LCR TDP turbine condensate system
LCS Reheater heating steam condensate system
LCT MS/SR moisture separator condensate system
LCT51-53 MS/SR moisture separator condensate pumps system
LCW Sealing and cooling steam drains system
LCX Non-return valves control system
LD. Condensate polishing systems (UDP)
LDB Autonomous dematerializing plant system
LDB00 Autonomous dematerializing plant system on trestle 00USY
LDF Turbine condensate deironing and polishing demineralization
system (UDP)
LDN Component cooling water chemistry control system
LDP Spent resins from UDP regeneration and flushing system
LDR UDP washing and regeneration water system
LDR00 UDP washing and regeneration water system on trestle 00USY
LF. Common installations for steam, water, gas cycles
LFC Drain and vent (steam, water, gas) system
LFG Steam generators chemical flush
LFJ Steam generator layup system
LFN Secondary working fluid correction treatment system
M.. Main machine sets
MA. Steam turbine plant
MAA HP cylinder system
MAC LP cylinder system
MAD Turbine bearings system
MAG Turbine condensers system
MAJ Air removal system
MAK Rotor hydraulic hoisting gear and turbogenerator turning gear
system
MAL Turbine drain system
MAM Seal leak-off steam system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 46
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
MAN Turbine bypass (BRU-K)
MAQ Oil tanks ventilation system (lubrication oil tank, control oil tank,
BRU-K control oil tank)
MAV Turbogenerator lubricant facility system
MAX Turbine control lubricant supply system
MK. Generator plant
MKA Generator system
MKC Generator excitation system
MKD Generator bearings system
MKF Generator stator windings water cooling system
MKF10-50 Generator stator windings water cooling system
MKG Generator hydrogen cooling system
MKW Generator shaft sealing oil system
MKW10-40 Generator shaft sealing oil system
MKW50 System of generator shaft sealing oil emergency discharge
MM. Compressed air compressor plant systems
MP. Common installations for main machine sets
MPA10 Foundation of turbo set
MPA20-30 Foundation of turbo pump set
MPA40-60 Foundation of electric pump set
MV. Lubricant supply system
MVA Turbine hall loads lubricant supply system
MVA10-40 Turbine hall loads lubricant supply system
MVA50 Emergency lubricant discharge system
MVA60-70 Mineral oil supply system
MVB Auxiliary lubrication oil system
MVC Auxiliary control oil system
MVD Auxiliary BRU-K control oil system
MX. Fluid supply system for control and protection equipment
MXN BRU-K control oil supply system
P.. Cooling water plants
PA. Main cooling water system
PAA System of mechanical cleaning devices
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 47
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
PAB Main cooling water system
PAB90 System for air inlet-outlet from turbine condensers
PAC Pump units
PAH Turbine condenser ball cleaning system
PAS Ejector lifting pumps system
PAX Air supply system for pressure drop and water levels monitoring in PAA
system (Not Used)
PAY Measuring system of pressure difference across screens and water
levels in cooling water intake and delivery structures
PB. Main cooling water treatment system
PBB Mussels cleaning system
PBF Sodium hypochlorite mixing system
PBK Sodium hypochlorite solution delivery system to consumer
PC. Cooling water systems of non-essential loads
PCB Cooling water system for non-essential loads
PCB51-52 Cooling water system for common-station diesel electric station
PCC Pump units
PCD Service water supply system
PCH Heat exchanger cleaning system (Not Used)
PD. Main cooling water treatment of non-essential loads
PDB Mussels cleaning system
PE. Cooling water system for secured area
PEA System of mechanical cleaning devices
PEB Cooling water system for essential loads
PEC Pump units
PEH Heat exchanger cleaning plant (Not Used)
PEX Air supply system for pressure drop and water levels monitoring in
PEA system (Not Used)
PEY Pressure drop and water levels monitoring in PEA system
PF. Treatment of cooling water of essential loads
PFB Mussels cleaning system
PG. Closed cooling water system for conventional area
PGB Closed cooling water system for conventional area
PGB00-70 Closed cooling water system for normal operation loads
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 48
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
PGB71-79 Closed cooling water system for normal operation loads in buildings
00UKS, 00UKU, 00UYB
PGB80-90 Closed cooling water system for oil coolers
PGB99 Closed cooling water system for normal operation loads on trestle
00USY
PGC Сlosed cooling water pumps system
PGD Сlosed cooling water heat exchangers system
PU. Common devices for cooling water systems
PUA Dewatering system for PAC and PCC pump units water path
PUB Dewatering system for common structures of PA, PC and PE
systems
PUD Dewatering system for PEC pump units water path
PUE Drainage water pumping out from essential loads pump houses
PUJ Washing system of secondary screens flume of PAA system
PUK Washing system of fine-mesh rotary screens of PAA system
PUL Fish diverter ejector power supply system
PUM Fish diverter air lift power supply system
PUN System for supplying sea water to chlorine dosing plant
PUP Washing system of secondary screens flume and rotary meshes of
PEA system
PUQ Essential consumers tunnels drainage and drying system
PUS Ejector pumps bearings cooling system
PUT Fish barrier rooms drainage system
PUV Oil supply system of pump units of pump stations
PUX Air supply system for pressure drop and water levels monitoring in
intake structure (Not Used)
Q.. Auxiliary systems
QC. Central chemicals supply
QCB Nitric acid preparation and receipt system
QCB00 Nitric acid preparation and receipt system on trestle 00USY
QCD Caustic soda receipt and preparation system
QCD00 Caustic soda receipt and preparation system on trestle 00USY
QCE Hydrazine receipt and preparation system
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 49
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
QCE00 Hydrazine receipt and preparation system on trestle 00USY
QCF Ammonia receipt and preparation system
QCF00 Ammonia receipt and preparation system on trestle 00USY
QCQ Sulfuric acid receipt and preparation system
QCQ00 Sulfuric acid receipt and preparation system on trestle 00USY
QCR Trisodium phosphate receipt and preparation system
QCR00 Trisodium phosphate receipt and preparation system on trestle
00USY
QF. Air supply for pneumatic drives
QFA Compressed air system for valve pneumatic drives
QFA00 Compressed air system for valve pneumatic drives on trestle 00USY
QFA20 Compressed air supply system to the secondary circuit SG for
intercircuit tightness control
QG. Central gas supply for closed gas cycles
QGA Emergency Freon discharge pipelines
QH. Auxiliary steam generation
QHA Pressure system
QHA01-03 Steam boiler
QHC Equipment for cleaning the flue gas side of the heating surfaces
QHG Boiler water circulation system
QHG10-30 Boiler continuous and periodic blowdown system
QHL Combustion air system
QHN Flue gas exhaust
QHS Feedwater chemical treatment
QHY Control, regulating and protection system
QJ. Central gas supply, also inert gas
QJB Nitrogen supply and distribution in turbine hall
QJB00 System for keeping nitrogen and supplying it in the turbine hall on
trestle 00USY
QJB30 System for keeping nitrogen and supplying it in the turbine hall
QJB50 System for supplying nitrogen and distribution it in the turbine hall
(for generator gas station)
QJC Hydrogen supply
QJC00 System for keeping hydrogen and supplying it in the turbine hall on
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 50
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
trestle 00USY
QJC10 System for supplying hydrogen and distribution it in the turbine hall
(for generator gas station)
QJC30 System for keeping hydrogen and supplying it in the turbine hall
QK. Cold supply systems
QKA Cold supply system for ventilation systems in conventional area
(chilling machine and header pipes)
QKA00 Cold supply system for ventilation systems in conventional area
(chilling machine and header pipes) on trestle 00USY
QKA01-69 Cold supply system for ventilation systems in conventional area
(chilling machine)
QKA70-90 Cold supply system for ventilation systems in conventional area
(header pipes)
QKB Cold supply system for ventilation systems in secured area (safety
chilling machine and header pipes)
QKC Cold supply system for ventilation systems in building 30UBA
(40UBA, 50UBA, 60UBA)
QKD Cold supply system for ventilation systems in control safety system
(CSS) and safety chilling machine emergency power supply
building
QKE Cold supply system for ventilation systems in transformer building
QKF Cold supply system for ventilation systems in building of auxiliary
equipment for NFS fuel element warehouses
QKJ Cold supply system for ventilation systems in reactor building
QKK Cold supply system for ventilation systems in auxiliary reactor
equipment building, the NO building of control system
QKM Cold supply system for ventilation system in turbogenerator and oil building
QKN Cold supply system for ventilation system in shielded control
building 00UZM
QKR Cold supply system for laboratory buildings
QKS Cold supply system for ventilation systems in building of auxiliary
reactor systems
QKT Cold supply system for ventilation systems in controlled-access area
central workshops building
QKZ Cold supply system for ventilation systems in cable and pipe
tunnels, trains and rooms
QL. Feedwater, steam and condensate circuits for the generation
and distribution of the auxiliary steam
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 51
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
QLA Feedwater system
QLB Steam system
QLC Condensate system
QLY Control, regulating and protection system
QS. Central oil supply and disposal system
QSB Waste oil system
QSB10-46 System of OMTI, GK, T-22 waste oil
QU. Secondary automated chemical monitoring system
QUA Automated chemical monitoring system for feedwater systems
QUB Automated chemical monitoring system for steam systems
QUC Automated chemical monitoring system for condensate systems
QUD Sampling system for the auxiliary steam generation
QUG Automated chemical monitoring system for unit demineralizing
plant systems
QUH Sampling system for secondary cycle and condensate polishing
plant
QUJ The system for monitoring leak tightness of SG joints in the
secondary coolant circuit
QUK Automated chemical monitoring system for steam generator
blowdown systems
S.. Ancillary systems
SA. Ventilation technical plants for conventional area
SAA Ventilation plants in non-contaminated areas with safety process
systems, steam line areas
SAB Ventilation plants for conventional area in sanitary and service
building
SAC Ventilation plants for electrical rooms of normal operation, MCR,
grid control center, ancillary outdoor switchgear installation,
switchgear and control gear, control safety systems
SAD Ventilation systems for emergency power supply buildings
SAF Ventilation plants for building of auxiliary equipment for NFS fuel
element warehouses
SAH Ventilation system for start-up and standby boiler house
SAJ Ventilation plants in normal operation chilling machine buildings
SAK Ventilation plants in industrial and laboratory building for I&C and
electronics, training center and engineering and laboratory building
SAM Ventilation plants in turbogenerator and oil building
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 52
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SAP Ventilation plants for sewerage pump stations
SAQ Ventilation plants for pump stations
SAS Ventilation plants for auxiliary equipment buildings
SAV Ventilation installations for the cable channels and rooms pertaining
to the SCR
SAZ Ventilation plants for cable and pipe tunnels, trains and rooms
SB. Space heating plants for ancillary system buildings
SBH NPP heating systems
SC. Stationary process air systems
SCA Process air generation systems
SCB Compressed air system for process services
SCB10 Compressed air supply and distribution systems in turbine hall (for
generator gas station)
SCB20 Compressed air supply and distribution systems in building 00UKS
SCB25 Compressed air supply and distribution systems in building 00USV
SCB30 Compressed air supply and distribution systems in building 00UKU
SCB40 Compressed air supply and distribution systems in building 00UYB
SCC Compressed air supply system for containment testing
SCC00 Compressed air supply system for containment testing on trestle
00USY
SCD Compressed air supply system for maintenance
SCD00 Compressed air supply system for maintenance on trestle 00USY
SCR Supplementary control room
SG. Stationary fire protection systems
SGA Common-plant fire water system
SGB Fire water system for safety systems
SGC Automatic fire water plants for rooms and equipment of normal
operation systems
SGD Automatic fire water plants for rooms and equipment of safety
systems
SGE Fire gas plants
SGF Foam fire-fighting systems
SGH Device for self-extinguishing of poured combustible liquids (SED)
SGK Automatic finely-dispersed water fire-fighting plants
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 53
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SGL Powder fire-fighting systems
SM. Cranes, stationary hoists and conveying appliances
SMA Cranes, stationary hoisting devices and transport equipment in the
00UAB, 00UAC, 00UAD buildings
SMA20 Electric traveling cranes in buildings 00UAB, 00UAC, 00UAD
SMA21 Hand-operated traveling cranes in buildings 00UAB, 00UAC,
00UAD
SMA22 Hand-movable hoists in buildings 00UAB, 00UAC, 00UAD
SMA23 Hand hoists (fixed) in buildings 00UAB, 00UAC, 00UAD
SMA24 Movable electric cable hoists in buildings 00UAB, 00UAC,
00UAD
SMA25 On-floor transport in buildings 00UAB, 00UAC, 00UAD
SMA26 Hoisting sling in buildings 00UAB, 00UAC, 00UAD
SMA27 Crabs in buildings 00UAB, 00UAC, 00UAD
SMA28 Winches in buildings 00UAB, 00UAC, 00UAD
SMA29 Cross-beams in buildings 00UAB, 00UAC, 00UAD
SMA30 Grips in buildings 00UAB, 00UAC, 00UAD
SMB Cranes, stationary hoisting devices and transport equipment in the
30UBA (40UBA, 50UBA, 60UBA) building
SMB20 Electric traveling cranes in building 30UBA (40UBA, 50UBA,
60UBA)
SMB21 Hand-operated traveling cranes in building 30UBA (40UBA,
50UBA, 60UBA)
SMB22 Hand-movable hoists in building 30UBA (40UBA, 50UBA,
60UBA)
SMB23 Hand hoists (fixed) in building 30UBA (40UBA, 50UBA, 60UBA)
SMB24 Movable electric cable hoists in building 30UBA (40UBA, 50UBA,
60UBA)
SMB25 On-floor transport in building 30UBA (40UBA, 50UBA, 60UBA)
SMB26 Hoisting sling in building 30UBA (40UBA, 50UBA, 60UBA)
SMB27 Crabs in building 30UBA (40UBA, 50UBA, 60UBA)
SMB28 Winches in building 30UBA (40UBA, 50UBA, 60UBA)
SMB29 Cross-beams in building 30UBA (40UBA, 50UBA, 60UBA)
SMB30 Grips in building 30UBA (40UBA, 50UBA, 60UBA)
SMС Cranes, stationary hoisting devices and transport equipment in the
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 54
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
30UСC (40UСC, 50UСC, 60UСC), 30UCA (40UCA, 50UCA,
60UCA) buildings
SMC20 Electric traveling cranes in buildings 30UСC (40UСC, 50UСC,
60UСC), 30UCA (40UCA, 50UCA, 60UCA)
SMC21 Hand-operated traveling cranes in buildings 30UСC (40UСC,
50UСC, 60UСC), 30UCA (40UCA, 50UCA, 60UCA)
SMC22 Hand-movable hoists in buildings 30UСC (40UСC, 50UСC,
60UСC), 30UCA (40UCA, 50UCA, 60UCA)
SMC23 Hand hoists (fixed) in buildings 30UСC (40UСC, 50UСC, 60UСC),
30UCA (40UCA, 50UCA, 60UCA)
SMC24 Movable electric cable hoists in buildings 30UСC (40UСC, 50UСC,
60UСC), 30UCA (40UCA, 50UCA, 60UCA)
SMC25 On-floor transport in buildings 30UСC (40UСC, 50UСC, 60UСC),
30UCA (40UCA, 50UCA, 60UCA)
SMC26 Hoisting sling in buildings 30UСC (40UСC, 50UСC, 60UСC),
30UCA (40UCA, 50UCA, 60UCA)
SMC27 Crabs in buildings 30UСC (40UСC, 50UСC, 60UСC), 30UCA
(40UCA, 50UCA, 60UCA)
SMC28 Winches in buildings 30UСC (40UСC, 50UСC, 60UСC), 30UCA
(40UCA, 50UCA, 60UCA)
SMC29 Cross-beams in buildings 30UСC (40UСC, 50UСC, 60UСC),
30UCA (40UCA, 50UCA, 60UCA)
SMC30 Grips in buildings 30UСC (40UСC, 50UСC, 60UСC), 30UCA
(40UCA, 50UCA, 60UCA)
SMD Cranes, stationary hoisting devices and transport equipment in the
00UYB building
SMD20 Electric travelling cranes in building 00UYB
SMD21 Hand-operated traveling cranes in building 00UYB
SMD22 Hand-movable hoists in building 00UYB
SMD23 Hand hoists (fixed) in building 00UYB
SMD24 Movable electric cable hoists in building 00UYB
SMD25 On-floor transport in buildings 00UYB
SMD26 Hoisting sling in building 00UYB
SMD27 Crabs in buildings 00UYB
SMD28 Winches in building 00UYB
SMD29 Cross-beams in building 00UYB
SMD30 Grips in building 00UYB
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 55
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 56
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SMG20 Electric traveling cranes in buildings 00UGE, 00UGD, 01UGF-
03UGF, 01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW,
03UGT
SMG21 Hand-operated traveling cranes in buildings 00UGE, 00UGD,
01UGF-03UGF, 01UGH-02UGH, 01UGM, 00UGV, 01UGW-
02UGW, 03UGT
SMG22 Hand-movable hoists in buildings 00UGE, 00UGD, 01UGF-
03UGF, 01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW,
03UGT
SMG23 Hand hoists (fixed) in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMG24 Movable electric cable hoists in buildings 00UGE, 00UGD,
01UGF-03UGF, 01UGH-02UGH, 01UGM, 00UGV, 01UGW-
02UGW, 03UGT
SMG25 On-floor transport in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMG26 Hoisting sling in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMG27 Crabs in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMG28 Winches in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMG29 Cross-beams in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM 00UGV, 01UGW-02UGW, 03UGT
SMG30 Grips in buildings 00UGE, 00UGD, 01UGF-03UGF,
01UGH-02UGH, 01UGM, 00UGV, 01UGW-02UGW, 03UGT
SMJ Cranes, stationary hoisting devices and transport equipment in the
30UJA (40UJA, 50UJA, 60UJA), 30UJB (40UJB, 50UJB, 60UJB),
30UJC (40UJC, 50UJC, 60UJC), 30UJE (40UJE, 50UJE, 60UJE)
buildings
SMJ20 Electric traveling crans in buildings 30UJA (40UJA, 50UJA,
60UJA), 30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC,
60UJC), 30UJE (40UJE, 50UJE, 60UJE)
SMJ21 Hand-operated traveling crans in buildings 30UJA (40UJA, 50UJA,
60UJA), 30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC,
60UJC), 30UJE (40UJE, 50UJE, 60UJE)
SMJ22 Hand-movable hoists in buildings 30UJA (40UJA, 50UJA, 60UJA),
30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC),
30UJE (40UJE, 50UJE, 60UJE)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 57
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SMJ23 Hand hoists (fixed) in buildings 30UJA (40UJA, 50UJA, 60UJA),
30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC),
30UJE (40UJE, 50UJE, 60UJE)
SMJ24 Movable electric cable hoists in buildings 30UJA (40UJA, 50UJA,
60UJA), 30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC,
60UJC), 30UJE (40UJE, 50UJE, 60UJE)
SMJ25 On-floor transport in buildings 30UJA (40UJA, 50UJA, 60UJA),
30UJB (40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC),
30UJE (40UJE, 50UJE, 60UJE)
SMJ26 Hoisting sling in buildings 30UJA (40UJA, 50UJA, 60UJA), 30UJB
(40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC), 30UJE
(40UJE, 50UJE, 60UJE)
SMJ27 Crabs in buildings 30UJA (40UJA, 50UJA, 60UJA), 30UJB
(40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC), 30UJE
(40UJE, 50UJE, 60UJE)
SMJ28 Winches in buildings 30UJA (40UJA, 50UJA, 60UJA), 30UJB
(40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC), 30UJE
(40UJE, 50UJE, 60UJE)
SMJ29 Cross-beams in buildings 30UJA (40UJA, 50UJA, 60UJA), 30UJB
(40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC), 30UJE
(40UJE, 50UJE, 60UJE)
SMJ30 Grips in buildings 30UJA (40UJA, 50UJA, 60UJA), 30UJB
(40UJB, 50UJB, 60UJB), 30UJC (40UJC, 50UJC, 60UJC), 30UJE
(40UJE, 50UJE, 60UJE)
SMK Cranes, stationary hoisting devices and transport equipment in the
30UKA (40UKA, 50UKA, 60UKA), 30UKB (40UKB, 50UKB,
60UKB), 30UKC (40UKC, 50UKC, 60UKC), 31UKD-34UKD
(41UKD-44UKD, 51UKD-54UKD, 61UKD-64UKD), 05UKD,
00UKU buildings
SMK20 Electric travelling cranes in buildings 30UKA (40UKA, 50UKA,
60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC,
50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-
54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK21 Hand-operated traveling cranes in buildings 30UKA (40UKA,
50UKA, 60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC
(40UKC, 50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD,
51UKD-54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK22 Hand-movable hoists in buildings 30UKA (40UKA, 50UKA,
60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC,
50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-
54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK23 Hand hoists (fixed) in buildings 30UKA (40UKA, 50UKA,
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 58
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC,
50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-
54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK24 Movable electric cable hoists in buildings 30UKA (40UKA,
50UKA, 60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC
(40UKC, 50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD,
51UKD-54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK25 On-floor transport in buildings 30UKA (40UKA, 50UKA,
60UKA), 30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC,
50UKC, 60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-
54UKD, 61UKD-64UKD), 05UKD, 00UKU
SMK26 Hoisting sling in buildings 30UKA (40UKA, 50UKA, 60UKA),
30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC, 50UKC,
60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-54UKD,
61UKD-64UKD), 05UKD, 00UKU
SMK27 Crabs in buildings 30UKA (40UKA, 50UKA, 60UKA), 30UKB
(40UKB, 50UKB, 60UKB), 30UKC (40UKC, 50UKC, 60UKC),
31UKD-34UKD (41UKD-44UKD, 51UKD-54UKD, 61UKD-
64UKD), 05UKD, 00UKU
SMK28 Winches in buildings 30UKA (40UKA, 50UKA, 60UKA), 30UKB
(40UKB, 50UKB, 60UKB), 30UKC (40UKC, 50UKC, 60UKC),
31UKD-34UKD (41UKD-44UKD, 51UKD-54UKD, 61UKD-
64UKD), 05UKD, 00UKU
SMK29 Cross-beams in buildings 30UKA (40UKA, 50UKA, 60UKA),
30UKB (40UKB, 50UKB, 60UKB), 30UKC (40UKC, 50UKC,
60UKC), 31UKD-34UKD (41UKD-44UKD, 51UKD-54UKD,
61UKD-64UKD), 05UKD, 00UKU
SMK30 Grips in buildings 30UKA (40UKA, 50UKA, 60UKA), 30UKB
(40UKB, 50UKB, 60UKB), 30UKC (40UKC, 50UKC, 60UKC),
31UKD-34UKD (41UKD-44UKD, 51UKD-54UKD, 61UKD-
64UKD), 05UKD, 00UKU
SMM Cranes, stationary hoisting devices and transport equipment in the
30UMA (40UMA, 50UMA, 60UMA), 30UMV (40UMV, 50UMV,
60UMV) buildings
SMM20 Electric travelling cranes in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM21 Hand-operated traveling cranes in buildings 30UMA (40UMA,
50UMA, 60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM22 Hand-movable hoists in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM23 Hand hoists (fixed) in buildings 30UMA (40UMA, 50UMA,
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 59
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM24 Movable electric cable hoists in buildings 30UMA (40UMA,
50UMA, 60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM25 On-floor transport in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM26 Hoisting sling in buildings 30UMA (40UMA, 50UMA, 60UMA),
30UMV (40UMV, 50UMV, 60UMV)
SMM27 Crabs in buildings 30UMA (40UMA, 50UMA, 60UMA), 30UMV
(40UMV, 50UMV, 60UMV)
SMM28 Winches in buildings 30UMA (40UMA, 50UMA, 60UMA),
30UMV (40UMV, 50UMV, 60UMV)
SMM29 Cross-beams in buildings 30UMA (40UMA, 50UMA, 60UMA),
30UMV (40UMV, 50UMV, 60UMV)
SMM30 Grips in buildings 30UMA (40UMA, 50UMA, 60UMA), 30UMV
(40UMV, 50UMV, 60UMV)
SMM50 Assembly trolleys in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM51 Hydraulic loaders in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM52 Coupler device in buildings 30UMA (40UMA, 50UMA, 60UMA),
30UMV (40UMV, 50UMV, 60UMV)
SMM53 A set of testing equipment in buildings 30UMA (40UMA, 50UMA,
60UMA), 30UMV (40UMV, 50UMV, 60UMV)
SMM54 Anchor thrust in buildings 30UMA (40UMA, 50UMA, 60UMA),
30UMV (40UMV, 50UMV, 60UMV)
SMP Cranes, stationary hoisting devices and transport equipment in the
30UPC (40UPC, 50UPC, 60UPC), 30UPX (40UPX, 50UPX,
60UPX), 30UPU (40UPU, 50UPU, 60UPU), 00UPK buildings
SMP20 Electric travelling cranes in buildings 30UPC (40UPC, 50UPC,
60UPC), 30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU,
50UPU, 60UPU), 00UPK
SMP21 Hand-operated traveling cranes in buildings 30UPC (40UPC,
50UPC, 60UPC), 30UPX (40UPX, 50UPX, 60UPX), 30UPU
(40UPU, 50UPU, 60UPU), 00UPK
SMP22 Hand-movable hoists in buildings 30UPC (40UPC, 50UPC,
60UPC), 30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU,
50UPU, 60UPU), 00UPK
SMP23 Hand hoists (fixed) in buildings 30UPC (40UPC, 50UPC, 60UPC),
30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU,
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 60
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
60UPU), 00UPK
SMP24 Movable electric cable hoists in buildings 30UPC (40UPC, 50UPC,
60UPC), 30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU,
50UPU, 60UPU), 00UPK
SMP25 On-floor transport in buildings 30UPC (40UPC, 50UPC, 60UPC),
30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU,
60UPU), 00UPK
SMP26 Hoisting sling in buildings 30UPC (40UPC, 50UPC, 60UPC),
30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU,
60UPU), 00UPK
SMP27 Crabs in buildings 30UPC (40UPC, 50UPC, 60UPC), 30UPX
(40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU, 60UPU),
00UPK
SMP28 Winches in buildings 30UPC (40UPC, 50UPC, 60UPC), 30UPX
(40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU, 60UPU),
00UPK
SMP29 Cross-beams in buildings 30UPC (40UPC, 50UPC, 60UPC),
30UPX (40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU,
60UPU), 00UPK
SMP30 Grips in buildings 30UPC (40UPC, 50UPC, 60UPC), 30UPX
(40UPX, 50UPX, 60UPX), 30UPU (40UPU, 50UPU, 60UPU),
00UPK
SMQ Cranes, stationary hoisting devices and transport equipment in the
00UQR, 30UQA (40UQA, 50UQA, 60UQA), 31UQC-32UQC
(41UQC-42UQC, 51UQC-52UQC, 61UQC-62UQC), 31UQX-
34UQX (41UQX-44UQX, 51UQX-54UQX, 61UQX-63UQX)
buildings
SMQ20 Electric travelling cranes in buildings 00UQR, 30UQA (40UQA,
50UQA, 60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-
52UQC, 61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX,
51UQX-54UQX, 61UQX-63UQX)
SMQ21 Hand-operated traveling cranes in buildings 00UQR, 30UQA
(40UQA, 50UQA, 60UQA), 31UQC-32UQC (41UQC-42UQC,
51UQC-52UQC, 61UQC-62UQC), 31UQX-34UQX (41UQX-
44UQX, 51UQX-54UQX, 61UQX-63UQX)
SMQ22 Hand-movable hoists in buildings 00UQR, 30UQA (40UQA,
50UQA, 60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-
52UQC, 61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX,
51UQX-54UQX, 61UQX-63UQX)
SMQ23 Hand hoists (fixed) in buildings 00UQR, 30UQA (40UQA,
50UQA, 60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-
52UQC, 61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX,
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 61
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
51UQX-54UQX, 61UQX-63UQX)
SMQ24 Movable electric cable hoists in buildings 00UQR, 30UQA
(40UQA, 50UQA, 60UQA), 31UQC-32UQC (41UQC-42UQC,
51UQC-52UQC, 61UQC-62UQC), 31UQX-34UQX (41UQX-
44UQX, 51UQX-54UQX, 61UQX-6UQX)
SMQ25 On-floor transport in buildings 00UQR, 30UQA (40UQA, 50UQA,
60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC,
61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-
54UQX, 61UQX-63UQX)
SMQ26 Hoisting sling in buildings 00UQR, 30UQA (40UQA, 50UQA,
60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC,
61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-
54UQX, 61UQX-63UQX)
SMQ27 Crabs in buildings 00UQR, 30UQA (40UQA, 50UQA, 60UQA),
31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC, 61UQC-
62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-54UQX,
61UQX-63UQX)
SMQ28 Winches in buildings 00UQR, 30UQA (40UQA, 50UQA, 60UQA),
31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC, 61UQC-
62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-54UQX,
61UQX-63UQX)
SMQ29 Cross-beams in buildings 00UQR, 30UQA (40UQA, 50UQA,
60UQA), 31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC,
61UQC-62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-
54UQX, 61UQX-63UQX)
SMQ30 Grips in buildings 00UQR, 30UQA (40UQA, 50UQA, 60UQA),
31UQC-32UQC (41UQC-42UQC, 51UQC-52UQC, 61UQC-
62UQC), 31UQX-34UQX (41UQX-44UQX, 51UQX-54UQX,
61UQX-63UQX)
SMS Cranes, stationary hoisting devices and transport equipment in the
00USK, 00USV, 30USA (40USA, 50USA, 60USA) buildings
SMS20 Electric travelling cranes in buildings 00USK, 00USV, 30USA
(40USA, 50USA, 60USA)
SMS21 Hand-operated traveling cranes in buildings 00USK, 00USV,
30USA (40USA, 50USA, 60USA)
SMS22 Hand-movable hoists in buildings 00USK, 00USV, 30USA
(40USA, 50USA, 60USA)
SMS23 Hand hoists (fixed) in buildings 00USK, , 00USV, 30USA (40USA,
50USA, 60USA)
SMS24 Movable electric cable hoists in buildings 00USK, 00USV, 30USA
(40USA, 50USA, 60USA)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 62
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SMS25 On-floor transport in buildings 00USK, 00USV, 30USA (40USA,
50USA, 60USA)
SMS26 Hoisting sling in buildings 00USK, 00USV, 30USA (40USA,
50USA, 60USA)
SMS27 Crabs in buildings 00USK, , 00USV, 30USA (40USA, 50USA,
60USA)
SMS28 Winches in buildings 00USK, 00USV, 30USA (40USA, 50USA,
60USA)
SMS29 Cross-beams in buildings 00USK, 00USV, 30USA (40USA,
50USA, 60USA)
SMS30 Grips in buildings 00USK, 00USV, 30USA (40USA, 50USA,
60USA)
SMT Cranes, stationary hoisting devices and transport equipment in the
00UTF building
SMT20 Electric travelling cranes in buildings 00UTF
SMT21 Hand-operated traveling cranes in buildings 00UTF
SMT22 Hand-movable hoists in buildings 00UTF
SMT23 Hand hoists (fixed) in buildings 00UTF
SMT24 Movable electric cable hoists in buildings 00UTF
SMT25 On-floor transport in buildings 00UTF
SMT26 Hoisting sling in buildings 00UTF
SMT27 Crabs in buildings 00UTF
SMT28 Winches in buildings 00UTF
SMT29 Cross-beams in buildings 00UTF
SMT30 Grips in buildings 00UTF
SMU Cranes, stationary hoisting devices and transport equipment in the
00UKS, 31UUQ-37UUQ (41UUQ-47UUQ, 51UUQ-57UUQ,
61UUQ-67UUQ), 31UUP-37UUP (41UUP-47UUP, 51UUP-
57UUP, 61UUP-67UUP), 31UUZ-38UUZ (41UUZ-48UUZ,
51UUZ-58UUZ, 61UUZ-68UUZ), 02UUB, 04UUB-06UUB,
31UUB-36UUB (41UUB-46UUB, 51UUB-56UUB, 61UUB-
66UUB), 30UUA (40UUA, 50UUA, 60UUA) buildings
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 63
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SMU20 Electric travelling cranes in buildings 00UKS, 31UUQ-37UUQ
(41UUQ-47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-
37UUP (41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP),
31UUZ-38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-
68UUZ), 02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-
46UUB, 51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA,
50UUA, 60UUA)
SMU21 Hand-operated traveling cranes in buildings 00UKS, 31UUQ-
37UUQ (41UUQ-47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ),
31UUP-37UUP (41UUP-47UUP, 51UUP-57UUP, 61UUP-
67UUP), 31UUZ-38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ,
61UUZ-68UUZ), 02UUB, 04UUB-06UUB, 31UUB-36UUB
(41UUB-46UUB, 51UUB-56UUB, 61UUB-66UUB), 30UUA
(40UUA, 50UUA, 60UUA)
SMU22 Hand-movable hoists in buildings 00UKS, 31UUQ-37UUQ
(41UUQ-47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-
37UUP (41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP),
31UUZ-38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-
68UUZ), 02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-
46UUB, 51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA,
50UUA, 60UUA)
SMU23 Hand hoists (fixed) in buildings 00UKS, 31UUQ-37UUQ (41UUQ-
47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP
(41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-
38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ),
02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB,
51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA,
60UUA)
SMU24 Movable electric cable hoists in buildings 00UKS, 31UUQ-37UUQ
(41UUQ-47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-
37UUP (41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP),
31UUZ-38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-
68UUZ), 02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-
46UUB, 51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA,
50UUA, 60UUA)
SMU25 On-floor transport in buildings 00UKS, 31UUQ-37UUQ (41UUQ-
47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP
(41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-
38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ),
02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB,
51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA,
60UUA)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 64
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
SMU26 Hoisting sling in buildings 00UKS, 31UUQ-37UUQ (41UUQ-
47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP
(41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-
38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ),
02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB,
51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA,
60UUA)
SMU27 Crabs in buildings 00UKS, 31UUQ-37UUQ (41UUQ-47UUQ,
51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP (41UUP-
47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-38UUZ
(41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ), 02UUB,
04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB, 51UUB-
56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA, 60UUA)
SMU28 Winches in buildings 00UKS, 31UUQ-37UUQ (41UUQ-47UUQ,
51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP (41UUP-
47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-38UUZ
(41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ), 02UUB,
04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB, 51UUB-
56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA, 60UUA)
SMU29 Cross-beams in buildings 00UKS, 31UUQ-37UUQ (41UUQ-
47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP
(41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-
38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ),
02UUB, 04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB,
51UUB-56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA,
60UUA)
SMU30 Grips in buildings 00UKS, 31UUQ-37UUQ (41UUQ-47UUQ,
51UUQ-57UUQ, 61UUQ-67UUQ), 31UUP-37UUP (41UUP-
47UUP, 51UUP-57UUP, 61UUP-67UUP), 31UUZ-38UUZ
(41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-68UUZ), 02UUB,
04UUB-06UUB, 31UUB-36UUB (41UUB-46UUB, 51UUB-
56UUB, 61UUB-66UUB), 30UUA (40UUA, 50UUA, 60UUA)
SMU50 Hydraulic loaders in buildings 00UKS
SMU51 A set of testing equipment in buildings 00UKS
SMU52 Anchor bars in buildings 00UKS
SR. Workshops, warehouses, laboratories and staff amenities inside
controlled area
SRA20 Lathe equipment in the building 00UKU
SRA30 System of lacquer emergency discharge
SRG10 Chemical laboratory equipment of primary circuit water chemistry
operative monitoring
SRG20 Equipment of laboratory health physics building 00UYB
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 65
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 66
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
61UAZ Power output system 400 kV busduct tunnels
32UAZ Power output system 400 kV busduct tunnels (for C (B) phase of
unit transformer)
42UAZ Power output system 400 kV busduct tunnels (for C (B) phase of
unit transformer)
52UAZ Power output system 400 kV busduct tunnels (for C (B) phase of
unit transformer)
62UAZ Power output system 400 kV busduct tunnels (for C (B) phase of
unit transformer)
33UAZ Power output system 400 kV busduct tunnels (for B (Y) phase of
unit transformer)
43UAZ Power output system 400 kV busduct tunnels (for B (Y) phase of
unit transformer)
53UAZ Power output system 400 kV busduct tunnels (for B (Y) phase of
unit transformer)
63UAZ Power output system 400 kV busduct tunnels (for B (Y) phase of
unit transformer)
34UAZ Power output system 400 kV busduct tunnels (for A (R) phase of
unit transformer)
44UAZ Power output system 400 kV busduct tunnels (for A (R) phase of
unit transformer)
54UAZ Power output system 400 kV busduct tunnels (for A (R) phase of
unit transformer)
64UAZ Power output system 400 kV busduct tunnels (for A (R) phase of
unit transformer)
UB. Structures for power transmission and auxiliary power supply
30UBA Normal Operation Power Supply Building
40UBA Normal Operation Power Supply Building
50UBA Normal Operation Power Supply Building
60UBA Normal Operation Power Supply Building
30UBF Unit Auxiliary Transformers and Generator Transformers Structures
40UBF Unit Auxiliary Transformers and Generator Transformers Structures
50UBF Unit Auxiliary Transformers and Generator Transformers Structures
60UBF Unit Auxiliary Transformers and Generator Transformers Structures
01UBG* Reserve power supply building
02UBG* Reserve power supply building
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 67
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
03UBG* Common-unit power supply building
04UBG* Reserve and common-unit transformers structures
02UBH* Oil and water emergency discharge tanks
03UBH* Oil and water emergency discharge tanks
04UBH* Oil and water emergency discharge tanks
05UBH* Oil and water emergency discharge tanks
31UBH Oil and water emergency discharge tanks
41UBH Oil and water emergency discharge tanks
51UBH Oil and water emergency discharge tanks
61UBH Oil and water emergency discharge tanks
30UBJ Rolling tracks for transformers
40UBJ Rolling tracks for transformers
50UBJ Rolling tracks for transformers
60UBJ Rolling tracks for transformers
00UBS Electrical substation
31UBZ Cable channels of normal operation systems
41UBZ Cable channels of normal operation systems
51UBZ Cable channels of normal operation systems
61UBZ Cable channels of normal operation systems
32UBZ Cable channels of normal operation systems
42UBZ Cable channels of normal operation systems
52UBZ Cable channels of normal operation systems
62UBZ Cable channels of normal operation systems
33UBZ Cable channels of normal operation systems
43UBZ Cable channels of normal operation systems
53UBZ Cable channels of normal operation systems
63UBZ Cable channels of normal operation systems
34UBZ Cable channels of normal operation systems
44UBZ Cable channels of normal operation systems
54UBZ Cable channels of normal operation systems
64UBZ Cable channels of normal operation systems
35UBZ Cable channels of normal operation systems
45UBZ Cable channels of normal operation systems
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 68
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 69
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 70
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 71
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
60UGC Contaminated condensate tank structures
00UGD DM water plant building & post treatment plant facility
01UGD Chemical storage building
02UGD Chemical laboratory
01UGE Waste water neutralization building
02UGE Waste water tank structure from chemical backwashing and
conservation
03UGE Waste water tank structure from chemical backwashing and
conservation
04UGE Neutralizing tank structure
05UGE Neutralizing tank structure
01UGF Fire-fighting water tank
02UGF Fire-fighting water tank
03UGF Fire-fighting service water pump station
31UGH Drainage pump station
41UGH Drainage pump station
51UGH Drainage pump station
61UGH Drainage pump station
32UGH Drainage pump station
42UGH Drainage pump station
52UGH Drainage pump station
62UGH Drainage pump station
33UGH Drainage pump station
43UGH Drainage pump station
53UGH Drainage pump station
63UGH Drainage pump station
01UGH* Storm water pump house
02UGH* Storm water pump house
01UGM* Oil containing water treatment structures
02UGM* Pump station
00UGR* Sludge damp
31UGS Backwashing water collection tank structures
41UGS Backwashing water collection tank structures
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 72
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
51UGS Backwashing water collection tank structures
61UGS Backwashing water collection tank structures
30UGS Backwashing water collection tank structures
40UGS Backwashing water collection tank structures
50UGS Backwashing water collection tank structures
60UGS Backwashing water collection tank structures
01UGT* Silt platform
02UGT* Gas-discharge stack
03UGT* Pump station of purified waste water
01UGU* Storm water reservoir
02UGU* Storm water reservoir
00UGV* Common-access area domestic waste water purification structures
77-255/1624000 T2 04.2018 0 73
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
UJ. Structures for nuclear heat generation
30UJA Reactor building/Inner containment
40UJA Reactor building/Inner containment
50UJA Reactor building/Inner containment
60UJA Reactor building/Inner containment
30UJB Outer containment
40UJB Outer containment
50UJB Outer containment
60UJB Outer containment
30UJC PHRS heat exchangers room
40UJC PHRS heat exchangers room
50UJC PHRS heat exchangers room
60UJC PHRS heat exchangers room
30UJE Steam cell
40UJE Steam cell
50UJE Steam cell
60UJE Steam cell
30UJG Transport Portal
40UJG Transport Portal
50UJG Transport Portal
60UJG Transport Portal
00UJY* Gallery of the controlled access area
UK. Structures for reactor auxiliary systems
30UKA Reactor safety system. Basement
40UKA Reactor safety system. Basement
50UKA Reactor safety system. Basement
60UKA Reactor safety system. Basement
30UKB Ancillary systems. Lean-to building
40UKB Ancillary systems. Lean-to building
50UKB Ancillary systems. Lean-to building
60UKB Ancillary systems. Lean-to building
30UKC Reactor Auxiliary & Main Control Room Building
40UKC Reactor Auxiliary & Main Control Room Building
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 74
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 75
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 76
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 77
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 78
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 79
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 80
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 81
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 82
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 83
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 84
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 85
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
02UUB* Plenum vent center of NO cable tunnels (01UBZ, 02UBZ)
03UUB Exhaust vent center of NO cable tunnels (01UBZ, 02UBZ) (Not
used)
04UUB* Vent shaft of NO cable tunnels (03UBZ, 04UBZ)
05UUB* Vent shaft of NO cable tunnel (06UBZ)
06UUB* Plenum vent center of NO cable tunnel (07UBZ)
31UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
41UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
51UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
61UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
32UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
42UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
52UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
62UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
33UUP Plenum vent center essential loads pipelines tunnels (32UQZ)
43UUP Plenum vent center essential loads pipelines tunnels (42UQZ)
53UUP Plenum vent center essential loads pipelines tunnels (52UQZ)
63UUP Plenum vent center essential loads pipelines tunnels (62UQZ)
34UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
44UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
54UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
64UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
35UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
45UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
55UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
65UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
36UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
46UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
56UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
66UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
37UUP Exhaust vent center essential loads pipelines tunnels (32UQZ)
47UUP Exhaust vent center essential loads pipelines tunnels (42UQZ)
57UUP Exhaust vent center essential loads pipelines tunnels (52UQZ)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 86
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
67UUP Exhaust vent center essential loads pipelines tunnels (62UQZ)
31UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
41UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
51UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
61UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
32UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
42UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
52UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
62UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
33UUQ Plenum vent center essential loads pipelines tunnels (31UQZ)
43UUQ Plenum vent center essential loads pipelines tunnels (41UQZ)
53UUQ Plenum vent center essential loads pipelines tunnels (51UQZ)
63UUQ Plenum vent center essential loads pipelines tunnels (61UQZ)
34UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
44UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
54UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
64UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
35UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
45UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
55UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
65UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
36UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
46UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
56UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
66UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
37UUQ Exhaust vent center essential loads pipelines tunnels (31UQZ)
47UUQ Exhaust vent center essential loads pipelines tunnels (41UQZ)
57UUQ Exhaust vent center essential loads pipelines tunnels (51UQZ)
67UUQ Exhaust vent center essential loads pipelines tunnels (61UQZ)
31UUZ Exhaust ventilation centre of SS cable tunnel (31UKZ)
41UUZ Exhaust ventilation centre of SS cable tunnel (41UKZ)
51UUZ Exhaust ventilation centre of SS cable tunnel (51UKZ)
61UUZ Exhaust ventilation centre of SS cable tunnel (61UKZ)
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 87
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 88
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
77-255/1624000 T2 04.2018 0 89
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
XAX Control, protection and lubrication system
XJ. Systems of emergency diesel power plant
XJA Diesel engine
XJG Inner water circuit
XJN Fuel and oil storage facilities
XJN00 Fuel and oil storage facilities on trestle 0 USY
XJQ Air intake system
XJR Exhaust gas system
XJV Lubricant supply system
XJX Start-up air system
XK. Generator plant of emergency diesel generator station
XKA Generator frame, including stator, rotor and all integral cooling
equipment up to leads
XL. Electric drive equipment
XLA Assembled diesel-generator
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 90
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 91
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
A. Mechanical equipment
AA Valves, dampers, etc., incl. actuators, also manual; rupturedisk
equipment
AB Isolating elements, air locks
AC Heat exchanger without a dedicated power source1) (except with
ventilation system plants and equipment)
AE Turning, driving, lifting and slewing gear (also manipulators)
AF Continuous conveyors, feeders (escalators)
AG Generator units
AH Heat exchanger with a dedicated power source and/or drive2) (except
with ventilation systems plants and equipment3))
AJ Crushing units
AK Compacting and packaging equipment, only as part of process
AM Mixers, agitators
AN Compressor units, fans
AP Pump units
AS Adjusting and tensioning equipment for non-electrical variables (to
be applied only, if the actuator forms itself a constructive unit with
another equipment unit)
AT Cleaning, drying, filtering and separating equipment
AU Braking, gearbox, coupling equipment, non-electrical converters
AV Combustion equipment
AW Stationary tooling, treatment equipment, laboratory furniture
AX Test and monitoring equipment for plant maintenance, laboratory
instruments and equipment
________________________
1)
A heat exchanger without a dedicated power source is understood to mean an apparatus heat
transfer in which takes place directly from a heat carrier to a coolant.
2)
A heat exchanger with a dedicated power source is understood to mean an apparatus heat
transfer in which takes place with conversion of the energy of admitted medium into energy transferred
to the medium for which this energy is required.
3)
The principles for coding ventilation system plants and equipment are given in Appendix F
B. Mechanical equipment
BB Storage equipment (tanks), chamber
BE Shafts (for erection and maintenance only)
BF Foundations
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 92
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
BN Jet pumps, ejectors, injectors, deflectors, hoods
BP Flow restrictors, limiters, orifices (not metering orifices)
BQ Supports
BR Piping, ductwork, chutes
BS Silencers
BT Flue gas catalytic converter modules
BU Insulation, sheathing
C. Direct measurement circuits
CD Density
CE Electrical variables (e.g. current, voltage, power, electr. frequency)
CF Flow, rate
CG Distance, length, position, direction of rotation
CH Manual control
CK Time
CL Level (also for dividing line)
CM Moisture, humidity
CP Pressure
CQ Quality variables (analysis, material properties), other than *CD*,
*CM*, *CV*
CR Radiation variables (irradiation)
CS Velocity, speed, frequency (mechanical), acceleration
CT Temperature
CU Combined and other variables
CV Viscosity
CW Weight, mass, effort
CX Neutron flux
CY Vibration, expansion
D. Control circuits
DD Density
DE Electrical variables (e.g. current, voltage, power, elect. frequency)
DF Flow, rate
DG Distance, length, position, direction of rotation
DK Time
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 93
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
DL Level (also for dividing line)
DM Moisture, humidity
DP Pressure
DQ Quality variables (analysis, material properties), other than *DD*,
*DM*, *DV*
DR Radiation variables (irradiation)
DS Velocity, speed, frequency (mechanical), acceleration
DT Velocity, speed, frequency (mechanical), acceleration
DU Combined and other variables
DV Viscosity
DW Weight, mass
DX Neutron flux
DY Vibration, expansion
E. Analog and discrete signal processing (normalizing)
EA Head protections of the power unit
EB Control, group control
EC Control, subgroup control
ED Switching of the pre-selection of control modes, switching of the
pre-selection (main/standby) of control valves
EE Mode interlocks
EH Alarm algorithms
EJ Emergency and warning alarm system
EK Generalized emergency and warning alarm system (failure)
EM Process computer (control over personnel and special tasks for
NPP)
EN Process computer (criterion display)
EP Process computer (control), video shots
ER Reactor protection
EU Combined analog and binary signal conditioning
EY Common part of the algorithms that do not directly affect specific
units
EZ Protection of equipment
F. Indirect measuring circuits
FD Density
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 94
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
FE Design-basis electrical variables (e.g. efficiency, power)
FF Flow, rate
FG Distance, length, position, direction of rotation
FK Time
FL Level (also for dividing line)
FM Level (also for dividing line)
FP Pressure
FQ Quality variables (analysis, material properties), other than *FD*,
*FM*, *FV*
FR Radiation variables
FS Velocity, speed, frequency (mechanical), acceleration
FT Temperature
FU Combined and other variables
FV Viscosity
FW Weight, mass
FX Neutron flux (reactor power)
FY Vibration, expansion
G. Electrical equipment
GA Connection boxes / penetrations for binary transducers related to
actuators
GB Connection boxes / penetrations for binary transducers not related
to actuators
GC Connection boxes / penetrations for analogue transducers of control
safety systems
GD Connection boxes / penetrations for power cable > 1 kV
GE Connection boxes / penetrations for power cable < 1 kV
GF Connection boxes / general purpose penetrations (<60 V)
GG Penetrations, which are mechanical protection for cable and
mechanical protection of cable
GH Independently installed electric measuring modules and control
modules, which are coded according to the process system (cabinets
and boxes, for which no indication of installation place is needed)
GK Information display and operator control equipment for process
computers and automation systems
GM Junction boxes for light-current systems of national
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 95
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
telecommunication services
GP Subdistribution and junction boxes for lighting
GQ Subdistribution and junction boxes for power sockets
GR DC generating equipment, batteries
GS Switchgear equipment if not identified under process equipment
GT Transformer equipment
GU Converter equipment (dynamotors, chargers)
GV Structure-related earthing and lightning protection equipment, surge
arrestors
GW Cabinet power supply equipment
GX Switching equipment (for electric variables)
GY Junction boxes for light-current systems (not of national
telecommunication services)
GZ Hangers, supports and racks for electrical and instrumentation and
control equipment
H. Parts of main and heavy machines (only to be used in
conjunction with *M* = Main machine sets and *X* = Heavy
machinery)
HA Parts of casing
HB Parts of rotor
HD Bearings
J. Nuclear equipment
JA Absorbers
JB Fuel assemblies (also includes block-type, cluster-type and spherical
fuel elements)
JC Multiplication elements
JD Throttling grills (elements)
JE Burnable absorbers
JF Reflecting elements
JG Plenum assemblies
JM Moderator assemblies
JN Neutron sources
JS Screening devices
JZ Special elements
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 96
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 97
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
К. Mechanical parts of equipment
KA Gate valves, valves, , cocks, rupture disks, orifices
KB Gates, doors
KC Heat exchangers
KD Vessels/tanks, pools, surge tanks (fluid systems)
KE Turning, hoisting and rotary mechanisms and running gears
KF Conveyors, proportioners (escalators)
KJ Size reduction machines
KK Compacting, packaging machines
KM Mixers, agitators
KN Compressors, blowers, fans
KP Pumps
KT Cleaning machines, dryers, separators, filters
KV Burners, grate bars
KW Stationary machine tools and treatment machines for maintenance
М. Mechanical parts of equipment
MB Brakes
MF Foundations
MG Gearboxes
MK Clutches, couplings
MM Engines, not electrical
MR Piping components, ductwork components
MS Shuffling drives (non-electric)
MT Turbines
MU Transmission gear, non electrical, converters and boosters other
than couplings and gearboxes
Q. Instrumentation and control components (non-electrical)
QB Transducers if not structurally integral with *QP*, metering orifices
QH Signalling devices
QN Regulators
QP Measuring instruments, testing equipment
QR Instrument piping
QS Condensation chambers (datum reservoir) in measuring circuits
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 98
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
QT Protection tubes, sleeves (only as protection of delicate
components)
-. Electrical parts of equipment
-A Assemblies and parts of assemblies
-B Transducers for non-electrical to electrical variables and vice-versa
-C Capacitors
-D Logic elements, delay devices, memory devices
-E Special components
-F Protective devices
-G Generators, power supplies
-H Signalling devices
-K Relays, contactors
-L Inductors
-M Motors
-N Amplifiers, controllers
-P Measuring instruments, testing equipment
-Q Power switchgear
-R Resistors
-S Switches, selectors
-T Transformers
-U Modulators, convertors from electrical to other electrical variables
-V Tubes, semiconductors
-W Transmission channels, waveguides, aerials
-X Terminals, plugs, sockets
-Y Electric shuffling drives, e.g. magnet, solenoid
-Z End devices, extension devices, filters, limiters, cable sleeves
X. (Output) signal sources
XA From functional-group control
XB From drive control modules
XC From usual controllers
XD From reactor protections, binary processing signals
XE From reactor protection, signals from analogue and binary parts
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
77-255/1624000 T2 04.2018 0 99
JSC “Atomenergoproekt” NPP “Kudankulam” R01.КК36.0.0.OO.KKS.P002
Code Name
XF From priority control modules
XG Discrete signals from sensors
XH Analogue signals. Threshold element actuation signal for parameter
value decrease or increase against the rated value.
XJ Potential signals from special devices (e.g. black box)
XK Signals generated by reactor protection
XL Signals from control boards and control panels, but not for
functioning of control system itself
XM Potential static signals from emergency alarm
XN Signals from the information computer for determination of state of
facility, criterion displays
XP Signals from supervisory control computer
XQ Analogue signals
XR Signals from above-standing controllers (PLC), controllers except
ХС, ХТ, УС, УТ, ZC, ZT
XS Stepwise signals from functional-group control
XT Binary signals generated by turbine control hardware
XU Potential dynamic signals from alarm system
XV Discrete signals
XW From usual signalling unit
Y. (Input) signal receivers
YA For purposes of functional-group control
YB For purposes of drive control
YC For purposes of usual regulation
YD For purposes of reactor protection, binary processing signals
YE For purposes of reactor protection, signals from analogue and
binary parts
YF From priority voltage modules
YJ Potential signals from special devices (e.g. black box)
YL Signals from control boards and control panels, but not for
functioning of control system itself
YN Signals from the information computer for determination of state of
facility, criterion displays
YP Signals from supervisory control computer
YQ Analogue signals
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Code Name
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX A
Structure of functional-technological code KKS
Serial no of
breakdown 0 1 2 3
level
Title of
Component
breakdown Total plant System code Equipment unit code
code
level
Designation of
G F0 F1F2F3 FN A1A2 AN A31) B1B2 BN
data character
1)
Please see usage of code А3 in Items 6,10, Section 3 "Agreed provisions".
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX B
Numbering in the equipment code
АА - Valves
Numerical Equipment
part of code
001-099 Motor –operated valves
101-199 Hand-operated valves
201-299 Сontrol valves
301-399 I&C valves
401-499 Structural pipeline drains. Fire and smoke dampers for ventilation systems
501-599 Hydraulic and pneumatic valves (except isolating valve)
601-699 Check valves, pressure relief valves (PRVs), ventilation channel closing devices
701-799 Internal valves
801-899 Containment isolating valves
901-999 Safety valves
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
АВ – Isolating elements
Numerical Equipment
part of code
001-099 Wooden, metal, PVC, mesh doors
101-199 Hermetic metal doors
201-299 Protective doors
301-399 Shock wave resistant doors
401-499 Fire doors
501-599 Gates
601-699 Hatches
701-799 Windows, louver grills etc.
801-899 Reserve
901-999 Reserve
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Numerical Equipment
part of code
001-099 Cranes, lifting and transportation facilities in the buildings 00UAD, 30UBA
(40UBA, 50UBA, 60UBA), 30UCC (40UCC, 50UCC, 60UCC), 00UEL,
00UGE, 30UJA (40UJA, 50UJA, 60UJA), 30UKC (40UKC, 50UKC, 60UKC),
30UMA (40UMA, 50UMA, 60UMA), 00UQR, 30UPC (40UPC, 50UPC,
60UPC)
100-199 Cranes, lifting and transportation facilities in the buildings 00UAB,00UGD,
30UJC (40UJC, 50UJC, 60UJC), 31UKD-34UKD (41UKD-44UKD, 51UKD-
54UKD, 61UKD-64UKD), 30UMV (40UMV, 50UMV, 60UMV), 00USK,
00UTF, 00UKS, 30UPU (40UPU, 50UPU, 60UPU), 30UQA (40UQA, 50UQA,
60UQA), 30UCA (40UCA, 50UCA, 60UCA), 30UUA (40UUA, 50UUA,
60UUA)
200-299 Cranes, lifting and transportation facilities in the buildings 00UAC,
01UGH-02UGH, 30UJE (40UJE, 50UJE, 60UJE), 05UKD, 00USV, 30UPX
(40UPX, 50UPX, 60UPX), 30UQC (40UQC, 50UQC, 60UQC), 31UUQ-37UUQ
(41UUQ-47UUQ, 51UUQ-57UUQ, 61UUQ-67UUQ)
300-399 Cranes, lifting and transportation facilities in the buildings 01UGF -03UGF,
00UKU, 30UQX (40UQX, 50UQX, 60UQX), 30USA (40USA, 50USA,
60USA), 31UUP-37UUP (41UUP-47UUP, 51UUP-57UUP, 61UUP-67UUP),
30UJB (40UJB, 50UJB, 60UJB), 00UPK
400-449 Cranes, lifting and transportation facilities in the building 30UKA (40UKA,
50UKA, 60UKA), 31UUZ-38UUZ (41UUZ-48UUZ, 51UUZ-58UUZ, 61UUZ-
68UUZ), 30UFC (40UFC, 50UFC, 60UFC)
450-499 Cranes, lifting and transportation facilities in the building 30UKB (40UKB,
50UKB, 60UKB), 02UUB, 04UUB-06UUB
500-539 Cranes, lifting and transportation facilities in the buildings 01UGM,
31UUB-36UUB (41UUB-46UUB, 51UUB-56UUB, 61UUB-66UUB)
540-559 Cranes, lifting and transportation facilities in the building 00UGV
560-599 Cranes, lifting and transportation facilities in the building01-04UGW
600-699 Lifts
700-799 Reserve
800-899 Reserve
900-999 Reserve
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Numerical Equipment
part of code
001-199 Lathe equipment in the buildings 00UKU, 00USK, laboratory furniture in the
buildings 30UKC (40UKC), 30UMA (40UMA)
200-249 Lathe equipment in the building 00USV, 00UGD
250-699 Lathe equipment in the building 00UST
700-799 Reserve
800-899 Reserve
900-999 Reserve
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Numerical Equipment
part of code
001-099 Supports
100-199 Pipes and air ducts embedded in concrete
200-599 Embedded parts for pipelines, air ducts, instrument pipes for measuring
process parameters etc passing through walls and floors
600-699 Embedded parts for equipment and pipelines of the reactor plant
700-799 Penetrations
800-899 Non-classified fastening equipment
900-999 Reserve
В.1 Embedded parts and penetrations are coded generally in sector 1 of KKS
functional code depending on their belonging to the structural system.
Fasteners serving for the particular system can be classified under this system.
В.2 Additional information not stipulated by KKS code, if required, can be introduced
beyond the limits of KKS code. The structure of KKS code combination and additional
information is given below:
Additional information
KKS code Sector I Sector II
1 2 3 1 2
AA(А) (А) N(NNN АА N(N)
)
Sector I *
Sector II
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Example 1
30UJA27BQ700/EMG24
KKS code /Primary switching of electrical devices, sealed penetration №24.
Example 2
30UKC10BQ320/WK227/TD25
KKS code /Water supply and waste water disposal systems, embedded part for pipe
№227/ Typical embedded part for penetration № 25.
Example 3
30UKC10BQ750/TMS7
KKS code /Mechanical part, stem penetration №7.
Example 4
30UJA12BQ605/RPВ235
KKS code /Reactor plant design, embedded part of reactor internals well №235.
В.4 Single type embedded parts (straps, squares, angles), steel structures and articles
as well are marked outside KKS with obligatory indication of explanatory data in working
document sets.
Structure of embedded part designations is Table B.1.
Structure of steel structure and article designations is Table B.2.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Table B.1
Code of basic
embedded part
length beginning
with 1 (taken
Identification of File number of basic embedded
Dash arbitrarily with
embedded part part beginning with 1
obligatory
representation of
data on the
drawing)
ТА N(NN) - N(N)
Table B.2
А(ААА) N(N)
Table B.3
Name Conventional alphabetical designation
Beam B
Framing beam FB
Console beam CB
Console C
Monorail beam MB
Monorail M
Crane-runway beam CRB
Truss Tr
Purling P
Strut Str
Tie bar TB
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
BR – Pipelines
Numerical Equipment
part of code
001-199 Main pipelines
200-299 Reserved
300-399 Auxiliary , supply and I&C pipelenes connections
400-499 Discharge, drenage and air exhaust pipelines
500-599 Reserved
600-699 Sampling and chemicals measuring pipelines
700-799 Internal instrumentation pipelines
800-899 Reserved
900-999 Safety valves inlet and discharge pipelines
Note - air ducts are coded with reference to the ventilation and air conditioning systems
using the range 001-999 in the *BR* code numerical part.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Numerical
Measuring circuit
part of code
001-099 Absorbed dose rate of photon radiation, neutron flux
100-199 Reserve
200-299 Iodine volumetric activity in air
300-399 Reserve
400-499 Aerosol volumetric activity in air
500-599 Reserve
600-699 Inert radioactive gases volumetric activity in air
700-799 Reserve
800-899 Liquid or steam volumetric activity
900-999 Reserve
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX C
Correlation between the service elevations and grade levels
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX D
Principles of cable coding
D.1 Cable code consists of the functional technological indication and digital part
divided by dash: «-» between them.
N N A A A N N ( A A N N N ) – N N ( N N A A)
Number of Unit (3-6), common-unit (0),
common-plant device (0 or 9)
Digital part
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
30BFT11-01В;
30BFT11-01С.
Digital part of the cable code is adopted according to Table D.1.
Table D.1
Digital part of code
Cable groups
NN(NNA)
Power cables (01 is recommended for assembly cables of
01-99
working power supply, 02 – for back-up power supply)
DC cables 101-999
Reserve 1001-1999
Control cables for control, indication, automation, relay 2001-2999,
protection of electrical part 3001-3999
Cables of process monitoring and control systems 4001-4999
5001-5999
Control cables of ULCS and special systems 6001-6999
Communication cables 7001-7999
Fire alarm and AFPS control cables 8001-8999
Reserve 9001-9999
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Digital part of codes of control cables for control, indication and relay protection are
subdivided into groups with regard to directions according to Table D.2.
Table D.2
Digital part of code
Control cable groups
NN(NNA)
Cables to relay board, standing apart from switchgear
2001-2139
apparatuses and generator outlets
Cables from penetration to mechanism 2001G-2139G
Cables to central control board from switchgears of all 2141-2169
voltages, generator terminals, relay boards etc.
Jumper cables within stand along relay board 2171-2189
Jumper cables within switchgear 2191-2269
Jumper cables within central control board 2271-2299
Measurements, control, indication and technological
protection cables from all switchgears, generator terminals, 2301-2399
local boards and cabinets to cross terminal cabinets of MCR
Measurements, control and indication cables, jumper cables
2401-2499
between local boards, cabinets
2501-2599
2601-2699
Reserve 2701-2799
2801-2899
2901-2999
Cables from cross cabinets to TPTS cabinets (discrete) 3001-3299
Jumper cables between TPTS cabinets 3301-3499
Cables from TPTS to MCR 3501-3599
Cables from TPTS to SCR 3601-3699
3701-3799
Reserve 3801-3899
3901-3999
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Digital part of codes of cables of process monitoring and control systems are
subdivided into groups with regard to directions according to Table D.3:
Table D.3
Digital part of code
Control cable groups
NN(NNA)
Jumper cables between:
- TPTS and TPTS, USH and USH, USH and TPTS, TPTS
and interposing relay cabinets;
- TPTS and TPTS power supply cabinets; 4001-4099
- TPTS and cross terminal cabinet;
- USH and RCD;
- RCE and RCD
Cable between:
- TPTS and MCR; 4101-4149
- RCD and MCR
Cables between:
- TPTS and SCR; 4151-4199
- RCD and SCR
Cables between cross terminal cabinets, USH cabinets and LVCD
4201-4299
0,4 kV
Cables between cross terminal cabinets, USH cabinets,
4301-4399
interposing relay cabinets and switchgear and control gear 6 kV
Cables between cross terminal cabinets, USH cabinets and valves
4401-4499
or penetrations
Cables from penetrations (from cross terminal cabinets) to valves
4401G-4499G
inside the hermetic part
Cables between cross terminal cabinets, USH cabinets and LCB 4501-4599
Cables between LVCD 0,4 kV and valves outside hermetic part or
4601-4699
penetrations
Cables from penetrations (from LVCD 0,4 kV) to valves inside
4601G-4699G
hermetic part
Cables between LCB and valves or LVCD 0,4 kV 4701-4799
Reserve 4801-4849
Reserve 4851-4899
Jumper cables inside MCR 4901-4949
Jumper cables inside SCR 4951-4999
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Cables between sensors and TPTS, USH. Hermetic part – nonhermetic part
Cables between sensors and junction boxes in hermetic part 5001-5019
Cables between junction boxes and penetrations in hermetic
part 5021G-5049G
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Digital part of codes of control cables of ULCS and special systems are subdivided into
groups with regard to directions according to Table D.4.
Table D.4
Digital part of code
Control cable groups
NN(NNA)
ULCS cables 6001-6199
NFME, CPSE-ESFIP cables 6201-6499
CPS electric equipment cables 6501-6699
MCDS cables 6701-6899
Reserve 6901-6999
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
Digital part of codes of fire alarm and AFPS cables are subdivided into groups with
regard to directions according to Table D.5.
Table D.5
Digital part of code
Control cable groups
NN(NNA)
Fire alarm cables 8001-8099
Cables between junction boxes 8101-8199
Cables from junction boxes to fire station / controller 8201-8299
Cables to fire station / controller 8301-8399
Cables from fire station / controller to cross terminal
cabinets of MCR 8401-8499
D.2 Cable routes shall be coded outside the KKS system, as per the pattern given below:
NN.(N)AAA NNNN(A)
Number of Unit (3-6), common-
unit or common-plant facility (0)
Designation of
normal operation system (0) or
safety train (1, 2, 3, 4)
Functional code (building, structure)
Serial number of route
Direction of route:
- vertical: V;
- horizontal: no sign is used.
Cable routes shall be coded building level-wise, from bottom to top (within the bottom
and top floors):
- building level 1 – 0001 to 1000, 0001V to 1000V;
- building level 2 – 1001 to 2000, 1001V to 2000V;
- building level 3 – 2001 to 3000, 2001V to 3000V, etc.
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
D.3 Coding of electric equipment, containing code of building, structure (e.g. lighting
equipment, welding equipment) with regard to cabling is to be done outside KKS in
compliance with the following way:
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX E
Coding principle of ULCS video shots
NNAAANN A A N N N
Symbol group, repeating the KKS designation
of the first APC working station,
where this video shot is located
(for example, 30CWA10 for SER APC video shots)
Example 1 - SER APC video shot of the third level of the hierarchy.
30CWA10EP312
Example 2 - SET APC video shot of the third level of the hierarchy.
30CWB10EP305
Example 3 - APC CTAI video shot of the second level of the hierarchy
30CWE40EP201
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
APPENDIX F
Principles for coding ventilation system plants and equipment
The codes of heating, cooling, air conditioning plants, and ventilation system filtering
plants, as well as codes of equipment items used as part of these plants are assigned to them as
follows:
а) Codes of plants are written in the sector of equipment unit code using the following
codes:
1) *АН* with the digital range from 100 to 199 for heating, cooling and air
conditioning plants;
2) *АТ* with the digital range from 100 to 199 for filtering plants;
b) Equipment items that are part of the plants, except with independent air
conditioners and split systems are also encoded in the sector of equipment unit code with the
digital range from 001 to 099 with application of equipment unit codes*АС* and *АН* for heat-
transfer equipment according to the following principle:
1) *АС* for cooling equipment (air coolers);
2) *АН* for heating equipment (air heaters, including electric heaters).
Example 1 Ventilation system plenum plant 30SAC97AH100 consisting of:
- the 30SAC97AA001 air valve;
- the 30SAC97AT001 filter;
- the 30SAC97AH001 electric air heater;
- the 30SAC97AA201 control air valve;
- the 30SAC97AH002 air heater;
- the 30SAC97AC001 air cooler;
- the 30SAC97AT002 separator;
- the 30SAC97AH003 spray chamber;
- the 30SAC97AP001 spray chamber pump;
- the 30SAC97AT003 separator;
- the 30SAC97AN001 fan.
Example 2 The ventilation system filtering plant 30KLA22AT100 consisting of:
- the 30KLA22AH001 electric air heater;
- the individual aerosol and iodine purification sections 30KLA22AT001,
30KLA22AT002, etc.;
Example 3. Coding of the independent air conditioner inner and outer units
20SAC98AH110 (120, 130,…) of the ventilation system:
- inner unit 20SAC98AH111 (121, 131,…);
- outer unit 20SAC98AH112 (122, 132,…).
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER
REVISION LIST
CONTRACT NUMBER PACKAGE NUMBER DATE OF ISSUE REVISION NUMBER PAGE NUMBER