0% found this document useful (1 vote)
181 views15 pages

Fire Supperssion Standpipes

FIRE SUPPERSSION STANDPIPES

Uploaded by

Mohammad Sadik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
181 views15 pages

Fire Supperssion Standpipes

FIRE SUPPERSSION STANDPIPES

Uploaded by

Mohammad Sadik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

King Khaled International Airport Development and Expansion

SECTION 211200 - FIRE SUPPERSSION STANDPIPES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Conditions of


Contract, apply to this Section.

1.2 SUMMARY

A. This Section includes piping and equipment for the following building systems:
1. Automatic wet-type, Class III standpipes.

1.3 DEFINITIONS

A. Hose Connection: Valve with threaded outlet matching fire hose coupling thread
for attaching fire hose.

B. Hose Station: Hose connection, fire hose rack, and fire hose.

C. Working Plans: Documents, including drawings, calculations, and material


specifications prepared according to NFPA 14 for obtaining approval from
Engineer and authorities having jurisdiction.

1.4 SYSTEM PERFORMANCE REQUIREMENTS

A. Verify the design of standpipes for compliance with NFPA, and obtain approval
from Engineer and authorities having jurisdiction. Include minimum and
maximum residual pressures at hydraulically remote outlets according to the
following:

1. DN40 (NPS 1-1/2) Hose Connections: 450 kPa (65 psig) minimum and 690
kPa (100 psig) maximum.

2. DN65 (NPS 2-1/2) Hose Connections: 690 kPa (100 psig) minimum and
1200 kPa (175 psig) maximum.

B. Components and Installation: Capable of producing piping systems with 1200-


kPa (175-psig) minimum working-pressure rating, unless otherwise indicated.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 1 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

1.5 SUBMITTALS

A. Product Data: For the following:

1. Pipe and fitting materials and methods of joining for standpipe piping.
2. Pipe hangers and supports.
3. Valves, including specialty valves, accessories, and devices.
4. Alarm devices. Include electrical data.
5. Air compressors. Include electrical data.
6. Fire department connections. Include type; number, size, and arrangement
of inlets; caps and chains; size and direction of outlet; escutcheon and
marking; and finish.
7. Hose connections. Include size, type, and finish.
8. Hose stations. Include size, type, and finish of hose connections; type and
length of fire hoses; finish of fire hose couplings; type, material, and finish
of nozzles; and finish of rack.

B. Welding certificates.

C. Field Test Reports and Certificates: As specified in "Field Quality Control" and
"Commissioning" Articles in Part 3 of this Section. Indicate and interpret test
results for compliance with performance requirements and as described in
NFPA 14. Include "Contractor's Material and Test Certificate for Aboveground
Piping" and "Contractor's Material and Test Certificate for Underground Piping."

D. Operation and Maintenance Data: For each type of standpipe specialty to include
in emergency, operation and maintenance manuals specified in Division 1
including interface with fire alarm system for local and remote system status
monitoring and trouble.

E. Working plan prepared according to NFPA 14 to the authority having jurisdiction.

1.6 QUALITY ASSURANCE

A. Manufacturer Qualifications: Firms whose equipment, specialties, and


accessories are listed by product name and manufacturer in UL's "Fire Protection
Equipment Directory" and FM's "Fire Protection Approval Guide" and that
comply with other requirements indicated.

B. Welding: Qualify processes and operators according to ASME Boiler and


Pressure Vessel Code Section IX.

C. Standpipe Components: Listing/approval stamp, label, or other marking by a


testing agency acceptable to Engineer and authorities having jurisdiction.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined


in NFPA 70, Article 100, by a testing agency acceptable to Engineer.

E. NFPA Standard: Equipment, specialties, accessories, installation, and testing


complying with NFPA 14, "Standpipe and Hose Systems."

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 2 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTIONS

A. Automatic Wet-Type, Class III Standpipe System: Includes NPS 1-1/2 (DN 40) or
DN 25 hose stations and NPS 2-1/2 (DN 65) hose connections. Has open water-
supply valve with pressure maintained and is capable of supplying water demand.

2.2 PIPING MATERIALS

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting,
and joining materials.

2.3 PIPES

A. Underground pipe: Refer specification section 211100–Facility fire suppression


water service piping.

B. Standard-Weight Steel Pipe: ERW pipe / ASTM A 53/A 53M, Type E Grade B
Schedule 40 in DN150 (NPS 6) and smaller, and Schedule 30 in DN200 (NPS 8)
and larger.

2.4 PIPE FITTINGS

A. Underground pipe fittings: Refer specification section 211100–Facility fire


suppression water service piping

B. Steel, Threaded Couplings: ASTM A 865/A 865M.

C. Steel Welding Fittings: ASTM A 234/A 234M, ASME B16.9, or ASME B16.11.

D. Steel Flanges and Flanged Fittings: ASME B16.5.

E. Steel, Grooved-End Fittings: ASTM A 47/A 47M, malleable iron or


ASTM A 536, ductile iron; with dimensions matching steel pipe and ends factory
grooved according to AWWA C606.

(1) Rigid Type: Housings shall be cast with offsetting, angle-pattern bolt pads
to provided system rigidity and support and hanging in accordance with
NFPA 13.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 3 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

(a) 32mm to 100mm: “Installation ready” stab-on design for direct ‘stab’
installation onto grooved end pipe without prior field disassembly and
no loose parts.

(b) 125mm and larger: Standard rigid couplings.

(2) Flexible Type: Use in seismic areas where required by NFPA 13.

(a) 50mm to 200mm: “Installation ready” stab-on design for direct ‘stab’
installation onto grooved end pipe without prior field disassembly and
no loose parts.

(b) All other sizes: Standard flexible couplings.

F. Flange adapters shall be galvanized ductile iron conforming to ASTM A536, flat
faced, designed for incorporating flanged components with Class 125 or 150 bolt-
hole patterns to a grooved piping system.

2.5 JOINING MATERIALS

A. Underground pipe joining material: Refer specification section 211100–Facility


fire suppression water service piping.

B. Steel, Keyed Couplings: AWWA C606, for steel-pipe dimensions. Include


ASTM A 536, ductile-iron housing, rubber gaskets, and steel bolts and nuts.
Include listing for dry-pipe service for couplings for dry piping.

C. Pipe-Flange Gasket Materials: ASME B 16.21, Nonmetallic and asbestos free.

1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges:
Full-face gaskets.
2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges:
Ring-type gaskets.

D. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise
indicated.

E. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding


materials appropriate for wall thickness and chemical analysis of steel pipe being
welded.

2.6 FIRE-PROTECTION-SERVICE VALVES

A. General: UL listed and FM approved, with minimum 2070-kPa (300-psig)


nonshock working-pressure rating. Valves for grooved-end piping may be
furnished with grooved ends instead of type of ends specified.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 4 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

B. Gate Valves, DN50 (NPS 2) and Smaller: UL 262; cast-bronze, threaded ends;
solid wedge; OS&Y; and rising stem.

C. Gate Valves, DN65 (NPS 2-1/2) and Larger: iron body, bronze mounted, taper
wedge, OS&Y, and rising stem. Include replaceable, bronze, wedge facing rings
and flanged ends.

D. Swing Check Valves, DN50 (NPS 2) and Smaller: MSS SP-80, Class 150; bronze
or Brass body with bronze disc and threaded ends.

E. Swing Check Valves, DN65 (NPS 2-1/2) and Larger: cast-iron body and bolted
cap, with bronze disc or cast-iron disc with bronze-disc ring and flanged ends.

F. Split-Clapper Check Valves, DN100 (NPS 4) and Larger: cast-iron body with
rubber seal, bronze-alloy discs, and stainless-steel spring and hinge pin.

G. Indicating-Type Butterfly Valves: DN 50 and Smaller: Body Material, Bronze


end connections: Threaded.

H. Indicating-Type Butterfly Valves: DN 65 and Larger: Body Material: Cast or


ductile iron, end connections: Flanged, grooved, or wafer.

2.7 SPECIALTY VALVES

A. Pressure-Regulating Valves: 2760-kPa (400-psig) minimum rating, brass.


Include DN40 or DN65 (NPS 1-1/2 or NPS 2-1/2), female NPS inlet and outlet;
adjustable setting feature; and straight or 90-degree angle pattern design as
indicated.

1. Finish: Rough chrome-plated.

B. Ball Drip Valves: automatic drain valve, DN20 (NPS 3/4), ball check device with
threaded ends.

C. Pressure-Reducing Valves:

(1) Pressure Rating: 2070 kPa minimum.

(2) Material: Brass or bronze.

(3) Inlet: Female pipe threads.

(4) Outlet: Threaded with or without adapter having male hose threads.

(5) Pattern: Angle or gate.

(6) Finish: Polished chrome plated where exposed to view or Rough brass or
bronze.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 5 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

2.8 MANUAL CONTROL STATIONS

A. Manual Control Stations: Hydraulic operation, with union, DN15 (NPS 1/2) pipe
nipple, and bronze or brass ball valve. Include metal enclosure labeled
"MANUAL CONTROL STATION" with operating instructions and cover held
closed by breakable strut to prevent accidental opening.

2.9 HOSE CONNECTIONS

A. Description: 2070-kPa (300-psig) minimum pressure rating, brass, hose valve for
connection of fire hose. Include 45-degree angle pattern design; female NPS inlet
and male hose outlet; and lugged cap, gasket, and chain. Include DN 25, DN40 or
DN65 (NPS 1-1/2 or NPS 2-1/2) as indicated, and hose valve threads according to
NFPA 1963 and matching local fire department threads.

1. Valve Operation: Nonadjustable type, unless pressure-regulating type is


indicated.
2. Finish: Rough brass or bronze.

2.10 HOSE STATIONS

A. Description: semiautomatic hose stations. Include brass, rack nipple; hose rack;
and the following features:

1. Valves: 2070-kPa (300-psig) minimum pressure rating, 45-degree angle


pattern hose valve with female NPS inlet and outlet, unless otherwise
indicated.

a. Valve Operation: Nonadjustable type, unless pressure-regulating type


is indicated.

2. Threads and Gaskets: NFPA 1963 and matching local fire department
threads.
3. Flow-Restricting Devices: DN40 (NPS 1-1/2) or DN25 brass, adjustable for
DN40 (NPS 1-1/2) fire hose inlet.
4. Fire Hose: NFPA 1961, lined fire hose with couplings, gaskets, and nozzle.
Include the following fire hose materials:
a. Jacket: Combination of natural and synthetic threads.
b. Lining: Rubber, or combination of rubber and plastic compounds
b. Cover: Rubber, plastic, or combination of rubber and plastic
compounds.
5. Mountings: Pipe clamp or wall bracket for freestanding units.
6. Mountings: Pipe escutcheon for cabinet-mounted units.
Contains one multipurpose Dry-Chemical Type (FE-14.5-kg (10-lb)
nominal capacity, in enameled-steel container and Carbon-Dioxide Type
(FE-2): 4.5-kg (10-lb) nominal capacity, in manufacturer's standard
enameled-metal container.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 6 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

B. DN65 and DN40 (NPS 2-1/2 and NPS 1-1/2) Hose Stations: DN65 (NPS 2-1/2)
hose valve with male threaded outlet, cap, and chain and DN40 (NPS 1-1/2) hose
valve; hose rack with water-retention device and pins for folded, DN40 (NPS 1-
1/2) lined hose; and DN40 (NPS 1-1/2) lined hose with swivel inlet coupling and
nozzle.

1. Hose-Rack Finish: Red enamel.


2. Hose Valve and Trim Finish: Polished chrome-plated.
3. Fire Hose: Lined, 30-m (100-foot) length.
4. Pressure Rating: 2070 kPa minimum.
5. Pressure-Control Device: Pressure reducing.
6. Pattern: Angle.Nozzle: Brass, adjustable from shutoff to fog spray or
straight stream.
7. Material: Brass or bronze.
8. Pressure-Control Device:, integral or for field installation if indicated.
9. Size: DN 40 or DN25
10. Inlet: Female pipe threads.
11. Outlet: Male hose threads according to NFPA 1963 and matching local fire-
department threads.

2.11 FIRE DEPARTMENT CONNECTIONS

A. Fire Department Connections: cast-brass body with brass, wall, escutcheon plate;
brass, lugged caps with gaskets and brass chains; and brass, lugged swivel
connections. Include inlets with threads according to NFPA 1963 and matching
local fire department sizes and threads, outlet with pipe threads, extension pipe
nipples, check devices or clappers for inlets, and escutcheon plate with marking
"AUTO SPKR & STANDPIPE."

1. Type: Recessed mounting.

2. Body Material: Corrosion-resistance metal.


3. Escutcheon Plate: Rectangular, brass, wall type.
4. Number of Inlets: Two or three as indicated on the drawings.
5. Finish: Polished chrome-plated.

2.12 ALARM DEVICES

A. General: Types matching piping and equipment connections.

B. Water-Motor-Operated Alarms: UL 753, mechanical-operation type with pelton-


wheel operator with shaft length, bearings, and sleeve to suit wall construction
and 250-mm diameter, cast-aluminum alarm gong with red-enamel factory finish.
Include DN20 (NPS 3/4) inlet and DN25 (NPS 1) drain connections.

C. Water-Flow Indicators: electrical-supervision, paddle operated, vane-type water-


flow detector; with 1725-kPa (250-psig) pressure rating; and designed for

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 7 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

horizontal or vertical installation. Include two single-pole, double-throw, circuit


switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-
V dc; complete with factory-set, field-adjustable retard element to prevent false
signals and tamperproof cover that sends signal if removed.

D. Pressure Switches: electrical-supervision-type, water-flow switch with retard


feature. Include single-pole, double-throw, normally closed contacts and design
that operates on rising pressure and signals water flow.

E. Valve Supervisory Switches: electrical; single-pole, double throw; with normally


closed contacts. Include design that signals controlled valve is in other than fully
open position.

F. Indicator-Post Supervisory Switches: electrical; single-pole, double throw; with


normally closed contacts. Include design that signals controlled indicator-post
valve is in other than fully open position.

2.13 PRESSURE GAUGES

A. Pressure Gauges: 90- to 115-mm diameter dial with dial range of 0 to 2070 kPa
(0 to 300 psig).

(1) Case: ABS (Acrylonitrile Butadiene Styrene)

(2) Window: Polycarbonate

(3) Dial: Black Figures on White Background

(4) Pointer: Black, Aluminum

(5) Movement: Suspended Spring with Polyester Segment

(6) Bourdon Tube: Bronze

(7) Socket: Brass, Soft Soldered

PART 3 - EXECUTION

3.1 PREPARATION

A. Perform fire-hydrant flow test according to NFPA 291. Use results for system
design calculations required in "Quality Assurance" Article in Part 1 of this
Section.

B. Report test results promptly and in writing.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 8 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

3.2 EARTHWORK

A. Refer to Section "Earthwork" for excavating, trenching, and backfilling.

3.3 EXAMINATION

A. Examine roughing-in for hose connections and stations to verify actual locations
of piping connections before installation.

B. Examine walls and partitions for suitable thickness, fire- and smoke-rated
construction, framing for hose-station cabinets, and other conditions where hose
connections and stations are to be installed.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.4 PIPING APPLICATIONS

A. Do not use welded joints with galvanized steel pipe.

B. Flanges, unions, and transition and special fittings with pressure ratings the same
as or higher than system's pressure rating may be used in aboveground
applications, unless otherwise indicated.

C. Piping between Fire Department Connections and Check Valves, and other dry-
type fire-suppression standpipe piping: Use galvanized, standard-weight steel
pipe with threaded ends; cast- or malleable-iron threaded fittings; and threaded
joints.

D. Piping between Fire Department Connections and Check Valves, and other dry-
type fire-suppression standpipe piping: Use galvanized, standard-weight steel
pipe with grooved ends; steel, grooved-end fittings; steel, keyed couplings; and
grooved joints.

E. Underground Service-Entrance Piping: Refer specification section 211100–


Facility fire suppression water service piping.

F. Standpipes: Use the following:

1. DN65 (NPS 2 1/2) and Smaller: Standard-weight steel pipe with threaded
ends, cast- or malleable-iron threaded fittings, and threaded joints.
2. DN80 (NPS 3) and Larger : Standard-weight steel pipe with grooved ends;
steel, grooved-end fittings; steel, keyed couplings; and grooved joints.
3. Optional DN80 (NPS 3) and Larger: Standard-weight steel pipe with plain
ends, steel welding fittings, and welded joints

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 9 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

3.5 VALVE APPLICATIONS

A. Drawings indicate valve types to be used. Where specific valve types are not
indicated, the following requirements apply:

1. Fire-Protection-Service Valves: UL listed and FM approved for


applications where required by NFPA 14.

a. Shutoff Duty: Use gate valves.

2. General-Duty Valves: For applications where UL-listed and FM-approved


valves are not required by NFPA 14.

a. Shutoff Duty: Use gate, ball, or butterfly valves.


b. Throttling Duty: Use globe, ball, or butterfly valves.

3.6 JOINT CONSTRUCTION

A. Underground joint construction: Refer specification section 211100–Facility fire


suppression water service piping.

B. Steel-Piping, Grooved Joints: Use Schedule 40 steel pipe with cut or roll-grooved
ends and Schedule 30 or thinner steel pipe with roll-grooved ends; steel, grooved-
end fittings; and steel, keyed couplings. Assemble joints with couplings, gaskets,
lubricant, and bolts according to coupling manufacturer's written instructions.
Use gaskets listed for dry-pipe service for dry piping.

C. Install couplings, flanges, flanged fittings, unions, nipples, and transition and
special fittings that have finish and pressure ratings same as or higher than
system's pressure rating for aboveground applications unless otherwise indicated.

D. Install unions adjacent to each valve in pipes DN50 and smaller.

E. Install flanges, flange adapters, or couplings for grooved-end piping on valves,


apparatus, and equipment having DN65 and larger end connections.

F. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

G. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and
fittings before assembly.

H. Flanged Joints: Select appropriate gasket material in size, type, and thickness
suitable for water service. Join flanges with gasket and bolts according to ASME
B31.9.

I. Threaded Joints: Thread pipe with tapered pipe threads according to ASME
B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to
remove burrs and restore full ID. Join pipe fittings and valves as follows:

1. Apply appropriate tape or thread compound to external pipe threads.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 10 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

2. Damaged Threads: Do not use pipe or pipe fittings with threads that are
corroded or damaged.

J. Steel-Piping, Cut-Grooved Joints: Cut square-edge groove in end of pipe


according to AWWA C606. Assemble coupling with housing, gasket, lubricant,
and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for
steel-pipe joints.

K. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe


according to AWWA C606. Assemble coupling with housing, gasket, lubricant,
and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for
steel-pipe grooved joints.

L. Grooved joint piping systems shall be installed in accordance with the


manufacturer's guidelines and recommendations. The gasket style and elastomeric
material (grade) shall be verified as suitable for the intended service as specified.
Grooved end shall be clean and free from indentations, projections, and roll marks
in the area from pipe end to groove for proper gasket sealing. A factory-trained
field representative shall provide on-site training for contractor's field personnel in
the proper use of grooving tools and installation of grooved piping products.
Factory-trained representative shall periodically review the product installation.
Contractor shall remove and replace any improperly installed products.

3.7 PIPING INSTALLATION

A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate


general location and arrangement of piping. Install piping as indicated, as far as
practical.

1. Deviations from approved working plans for piping require written approval
from Engineer and authorities having jurisdiction. File written approval
with Engineer before deviating from approved working plans.

B. Install underground service-entrance piping according to NFPA 24 and with


restrained joints.

C. Piping Standard: Comply with requirements in NFPA 14 for installation of fire-


suppression standpipe

D. Use approved fittings to make changes in direction, branch takeoffs from mains,
and reductions in pipe sizes.

E. Install unions adjacent to each valve in pipes DN50 (NPS 2) and smaller. Unions
are not required on flanged devices or in piping installations using grooved joints.

F. Install flanges or flange adapters on valves, apparatus, and equipment having


DN65 (NPS 2-1/2) and larger connections.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 11 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

G. Install drain valves on standpipes.

H. Install ball drip valves to drain piping between fire department connections and
check valves. Drain to floor drain or outside building.

I. Install alarm devices in piping systems.

J. Hangers and Supports: Comply with NFPA 13 for hanger materials. Install
according to NFPA 14.

K. Install piping with grooved joints according to manufacturer's written instructions.


Construct rigid piping joints, unless otherwise indicated.

L. Install pressure gages on riser or feed main, at each sprinkler test connection, and
at top of each standpipe. Include pressure gages with connection not less than
DN8 (NPS 1/4) and with soft metal seated globe valve, arranged for draining pipe
between gage and valve. Install gages to permit removal, and install where they
will not be subject to freezing.

3.8 VALVE INSTALLATION

A. Install fire-protection specialty valves, trim, fittings, controls, and specialties


according to NFPA 13 and NFPA 14, manufacturer's written instructions, and
authorities having jurisdiction.

B. Gate Valves: Install fire-protection-service valves supervised-open, located to


control sources of water supply except from fire department connections. Provide
permanent identification signs indicating portion of system controlled by each
valve.

C. Install listed fire-protection valves, trim and drain valves, specialty valves and
trim, controls, and specialties according to NFPA 14 and authorities having
jurisdiction.

D. Install listed fire-protection shutoff valves supervised-open, located to control


sources of water supply except from fire-department connections. Install
permanent identification signs indicating portion of system controlled by each
valve.

E. Install check valve in each water-supply connection. Install backflow preventers


instead of check valves in potable-water-supply sources.

F. Specialty Valves:

1. General Requirements: Install in vertical position for proper direction of


flow, in main supply to system.

2. Alarm Valves: Install bypass check valve and retarding chamber drain-line
connection.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 12 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

3.9 HOSE-CONNECTION INSTALLATION

A. Install hose connections adjacent to standpipes, unless otherwise indicated.

B. Install freestanding hose connections for access and minimum passage restriction.

C. Install DN40 (NPS 1-1/2) hose-connection valves with flow-restricting device,


unless otherwise indicated.

D. Install wall-mounting-type hose connections in cabinets. Include pipe


escutcheons, with finish matching valves, inside cabinet where water-supply
piping penetrates cabinet. Install valves at angle required for connection of fire
hose. Refer to Section "Fire-Protection Specialties" for cabinets.

3.10 HOSE-STATION INSTALLATION

A. Install freestanding hose stations for access and minimum passage restriction.

B. Install DN40 (NPS 1-1/2) hose-station valves with flow-restricting device, unless
otherwise indicated.

C. Install freestanding hose stations with support or bracket attached to standpipe or


substrate.

D. Install wall-mounting, rack-type hose stations in cabinets. Include pipe


escutcheons, with finish matching valves, inside cabinet where water-supply
piping penetrates cabinet. Install valves at angle required for connection of fire
hose. Cabinets are specified in Division 10 Section "Fire Extinguisher Cabinets."

3.11 CONNECTIONS

A. Connect water-supply piping and standpipes to fire pumps. Include backflow


preventers.

B. Install ball drip valves at each check valve for fire department connection. Drain
to floor drain or outside building.

C. Connect piping to specialty valves, hose valves, specialties, fire department


connections, and accessories.

D. Electrical Connections: Power wiring is specified in Division 26.

E. Connect alarm devices to fire alarm.

3.12 LABELING AND IDENTIFICATION

A. Install labeling and pipe markers on equipment and piping according to


requirements in NFPA 14 and in Section "Identification for Fire-Suppression
Piping and Equipment."

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 13 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

3.13 FIELD QUALITY CONTROL

A. Flush, test, and inspect standpipes according to NFPA 14, "System Acceptance"
Chapter.

B. Replace piping system components that do not pass test procedures and retest to
demonstrate compliance. Repeat procedure until satisfactory results are obtained.

C. Report test results promptly and in writing to Engineer and authorities having
jurisdiction.

D. Fire-suppression standpipe system will be considered defective if it does not pass


tests and inspections.

E. Tests and Inspections:

1. Leak Test: After installation, charge systems and test for leaks. Repair leaks
and retest until no leaks exist.

2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.

3. Flush, test, and inspect standpipe systems according to NFPA 14, "System
Acceptance" Chapter.

4. Energize circuits to electrical equipment and devices.

5. Start and run air compressors.

6. Coordinate with fire-alarm tests. Operate as required.

7. Coordinate with fire-pump tests. Operate as required.

8. Verify that equipment hose threads are same as local fire-department


equipment.

3.14 COMMISSIONING

A. Verify that specialty valves, trim, fittings, controls, and accessories are installed
and operate correctly.

B. Verify that specified tests of piping are complete.

C. Verify that hose connections and fire department connections have threads
compatible with local fire department equipment.

D. Fill wet-pipe standpipe piping with water.

E. Verify that hose connections are correct type and size.

F. Verify that hose stations are correct type and size.

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 14 of 15
© Copyright protected
King Khaled International Airport Development and Expansion

G. Energize circuits to electrical equipment and devices.

H. Adjust operating controls and pressure settings.

I. Coordinate with fire alarm tests. Operate as required.

3.15 DEMONSTRATION

A. Demonstrate equipment, specialties and accessories, and train Employer's


maintenance personnel to adjust, operate, and maintain standpipes and hoses.

END OF SECTION 211200

FIRE SUPPERSSION STANDPIPES 211200


S17058-0100D-FD-SPC-15A2-ME-01 REV B Page 15 of 15
© Copyright protected

You might also like