Rockinsul RB Slabs - 48 KG Per m3 75 MM - Technical Data Sheet
This technical data sheet provides information on Rockinsul RB Slabs stone wool board insulation. Some key details include:
- The material is composed of rock fibers processed from molten rock into fibrous form and bonded with an organic binder. It has a density of 48 kg/m3 and thickness of 75mm.
- It has a thermal conductivity of 0.035 W/mk and thermal resistance of 2.14 m2k/W. The service temperature is up to 750°C.
- Testing shows it has a non-combustible reaction to fire, zero flame spread and smoke development, and does not promote fungi growth or absorb more than 0.5kg/m2 of
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
636 views1 page
Rockinsul RB Slabs - 48 KG Per m3 75 MM - Technical Data Sheet
This technical data sheet provides information on Rockinsul RB Slabs stone wool board insulation. Some key details include:
- The material is composed of rock fibers processed from molten rock into fibrous form and bonded with an organic binder. It has a density of 48 kg/m3 and thickness of 75mm.
- It has a thermal conductivity of 0.035 W/mk and thermal resistance of 2.14 m2k/W. The service temperature is up to 750°C.
- Testing shows it has a non-combustible reaction to fire, zero flame spread and smoke development, and does not promote fungi growth or absorb more than 0.5kg/m2 of
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Technical Data Sheet
ROCKINSUL RB SLABS
Characteristic Units Quantities and Measured Values Standard
Stone wool board insulation composed of rock fibers processed from the molten state into fibrous form and bonded with an Material Composition - organic binder. Free from asbestos. -
Density Kg/m3 48 Kg/m3 (Tolerance as per ASTM) -
- Thickness mm 75 mm (Tolerance -2 +6 mm)
Facing: - unfaced -
Length : 1.0 m (Tolerance as per ASTM)
Dimension without overlap - Width : 0.6 m (Tolerance as per ASTM) Thermal Conductivity* ASTM C177 & W/mk 0.035 W/mk @mean temp of 250C ASTM C518 Thermal Resistance m2k/W 2.14 m2k/W
Service temperature 0C 750 0C ASTM C411
Melting point 0C >1000 0C ASTM E794
Rigidity Semi rigid to rigid
Reaction to Fire Non-Combustible; A1 when tested as per EN 13501 EN 13501
Surface Burning Flame Spread Index: 0 ASTM E84 / UL Characteristics Smoke Developed Index: 0 723 Water leachable chloride / ppm < 10 ppm; Confirms to stainless steel corrosion specification as ASTM C692 & Corrosiveness per ASTM C 692 & ASTM C 871 ASTM C871
Fungi Resistance Do not promote fungi growth ASTM C1338-00
% Non-fibrous Content Less than 30% ASTM C1335 Water vapour sorption ASTM C1104 / Less than 1% by volume (Moisture resistance) ASTM C1104M Water absorption (partial < 0.5 Kg/m2 BS 2972 Part 11 immersion) Linear Shrinkage % Max 2% ASTM C356 Standard Compliance ASTM C 612
*One of the best values
Rev : 04th Dec 2020
All information and data mentioned in this technical data sheet are based on tests performed in the Laboratory. Nothing herein to be construed as a warranty or representation and however we recommend all potential users of the product to make their own actual tests prior to using it on industrial scale