Engine Generator Set Inspection Checklist

This document is an inspection checklist for generator set DEG No.5 located at the Garraf Oil Field in LPU2. It was inspected on February 17, 2021 by Laith Ahmed. The generator set was manufactured by Perkins and has a rating of 1600Kw at 0.4Kv. Electrical tests were performed and measurements were recorded. Load tests were also conducted at 25%, 50%, 75%, and 100% of the generator's rating while monitoring voltage, frequency, current, coolant temperature, and oil pressure. Notes specify verifying system check points during load changes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views2 pages

Engine Generator Set Inspection Checklist

This document is an inspection checklist for generator set DEG No.5 located at the Garraf Oil Field in LPU2. It was inspected on February 17, 2021 by Laith Ahmed. The generator set was manufactured by Perkins and has a rating of 1600Kw at 0.4Kv. Electrical tests were performed and measurements were recorded. Load tests were also conducted at 25%, 50%, 75%, and 100% of the generator's rating while monitoring voltage, frequency, current, coolant temperature, and oil pressure. Notes specify verifying system check points during load changes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

ENGINE GENERATOR SET INSPECTION CHECKLIST

SECTION A – GENERAL DATA


1. FACILITY: 2. LOCATION: 3. JOB NUMBER:
LPU2 GARRAF OIL FIELD NA
4. EQUIPMENT: DEG No.5 5. CIRCUIT DESIGNATION: G123 6. DATE: 17 Feb. 2021

7. TEST EQUIPMENT TYPE/BRAND AND CALIBRATION DATE: 8. TESTED BY:


FLUKE 1550c Laith Ahmed
SECTION B – EQUIPMENT DATA
9. MANUFACTURER: 10. STYLES/S.O. 11. VOLTAGE RATING 12. KW RATING
Perkins N/A 0.4Kv 1600 Kw
13. CIRCUIT BREAKER SIZE/INTERRUPTING RATING 14. WET BULB TEMP. 15. DRY BULB TEMP.
Schneider, Merlin Gerin,3200A N/A N/A
SECTION C – VISUAL AND ELECTRICAL/MECHANICAL INSPECTION
16. CHECK POINT COND* NOTES CHECK POINT COND* NOTES
EXTERIOR OF EQUIPMENT A EQUIPMENT IDENTIFICATION A
COMPLETENESS OF BRACING
A A
ASSEMBLY
EQUIPMENT ROTATION PROPER PHASE
A A
CONNECTIONS
CHECK OIL LEVEL A REFERENCE DRAWING N/A
CHECK FUEL LEVEL A WORKING CLEARANCE A
PROPER EQUIPMENT ANCHORAGE
A N/A
GROUNDING
CHECK METERS/GAUGES ALL FILTERS AND VENTS
A A
CLEAR
TIGHTNESS OF BOLTED CHECK EQUIPMENT
CONNECTIONS A ENVIRONMENTAL N/A
CLASSIFICATION
VERIFY GOVERNOR AND CHECK FOR PROVISIONS OF
A A
REGULATOR SPILL CONTAINER
CHECK VIBRATION A CONTROL SYSTEM A
CHECK BATTERIES A CHECK FUEL FILTER A
CHECK RADIATOR FLUID CHECK ALARM INDICATORS:
A PROPER COLOR FOR EACH N/A
FUNCTION
PROPER SYSTEM GROUND A
SECTION D – ELECTRICAL TESTS
R - Phase S - Phase T - Phase
17. INSULATION RESISTANCE
RATIO = 10 MIN. /1 MIN. 2.88 GΩ 2.98 GΩ 3.08 GΩ
EXCITER STATOR WINDING 0.45 GΩ 0.0.42 GΩ 0.53 GΩ
ALTERNATOR 3.71 GΩ
DIODE BRIDGE ASSEMBLY (SHORT OUT
3.69 GΩ
DIODE)
18. NOTES:
1- PERFORM 5 MEASUREMENTS AT ONE-MINUTE INTERVALS.
2- DC HIPOT MEASUREMENTS SHOULD BEGIN AT 20% OF MAXIMUM TEST VOLTAGE AND
INCREASE IN EQUAL INTERVALS.
MAX DC TEST VOLTAGE = R (2X NAMEPLATE RATING) X 1.6
19. MEASUREMENT
DESCRIPTION VOLTAGE
R-N S-N T-N R-S S-T R-T
232 234 231 416 414 413

21. LOAD TESTS AS PERCENTAGE OF GENERATOR RATING (EACH 15m)


# Items Voltage Frequency Ampere Coolant Temp. Oil Pressure
1 NO LOAD 400 V 50 Hz 0A 47 C 4.8 bar
2 50% 400 V 50 Hz 1128 A 48 C 4.8 bar
3 75% 400 V 50 Hz 1670 A 50 C 4.9 bar
4 100% 400 V 50 Hz 2122 A 51 C 4.8 bar
22. NOTES:

1- VERIFY ALL SYSTEM CHECK POINTS DURING LOAD CHANGE AND RECORD PER SPECIFIED
REQUIREMENTS AND/OR EQUIPMENT MANUFACTURER.
2- PERFORM AND RECORD ENGINE MANUFACTURER’S RECOMMENDED CHECKS AND
INSPECTIONS.
*CONDITION: A=ACCEPTABLE; R=NEEDS REPAIR, REPLACEMENT OR ADJUSTMENT; C=CORRECTED; NA
NOT APPLICABLE.