Lesson7-Advanced Function Blocks

This document provides exercises on advanced function blocks for process control, including SPLIT, RATIO, SIGNAL SELECT, FUNC-VAR, and Foundation Fieldbus I/O blocks. The SPLIT block allows splitting a signal into two outputs. The RATIO block defines the relationship between two flows. SIGNAL SELECT automatically chooses the higher of two process signals. FUNC-VAR provides linearization for a non-linear device. FF-AI and FF-AO represent analog input and output blocks for Foundation Fieldbus devices.

Uploaded by

adams
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
312 views6 pages

Lesson7-Advanced Function Blocks

This document provides exercises on advanced function blocks for process control, including SPLIT, RATIO, SIGNAL SELECT, FUNC-VAR, and Foundation Fieldbus I/O blocks. The SPLIT block allows splitting a signal into two outputs. The RATIO block defines the relationship between two flows. SIGNAL SELECT automatically chooses the higher of two process signals. FUNC-VAR provides linearization for a non-linear device. FF-AI and FF-AO represent analog input and output blocks for Foundation Fieldbus devices.

Uploaded by

adams
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

This is a series of smaller exercises that incorporate additional controls common to process
control. The following exercises will also require more investigation in the on-line manuals
on your part to
part  to create these function blocks.
• You may have to adjust tuning parameters to get these blocks to work.
work.

SPLIT [Regulatory control/ Signal distributors]

This function block allows an upstream function block to output to two different modules or
function blocks. The two outputs can overlap to give a “blending” of steam and water, if used in
that manner.
• Define the outputs so that MV1
MV1 is reverse acting and operates between 0-75%
0-75% of the SPLIT
SPLIT
MV range.
• Define the outputs so that MV2
MV2 is direct acting and operates between 25-100% of the SPLIT
SPLIT
MV range.

On-line Manual Question:


In the SPLIT “Tuning Panel”, there is an item called “SW
“ SW”,
”, what does it do and what should it be
set to output to both PVIs?

SIMULATION

I COO

PV
M
MV
HEAT- SPLIT-
OU SE

MV
PI SPLI
I
HEA
I

PV

CENTUM VP Engineering 1 TE 33M80N10-10EN-A


CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

RATIO [Regulatory control/ Signal s etters]

The “RATIO” block allows the user to define the relation between two flows. In this simulation
you will create two PID function blocks, one with a flow of 0-100 G PM, and the other with a flow of
0-75 GPM. Use the “On-line Manual” to help build this function block and answer these questions.
• What does the RATIO “SV” do?
• Change the “Gain” in the “RATIO” block. What happens?

• Return the “Gain” to its initial value, and then change the “Bias” in the “RATIO” block. What
happens?

SIMULATION

0-100

M
FLOW- RATIO- 0-2
P I

PI RATI
I
OU

SE
M
FLOW- 0-75

PI
I

CENTUM VP Engineering 2 TE 33M80N10-10EN-A


CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

SIGNAL SELECT [Regulatory control/ Signal selectors]


There may be times when a process signal (high/ medium/ or low) is to be automatically selected
and displayed.
In the following simulation, use the function blocks created in the “SPLIT” exercise. You will
create an “AS-H” to automatically select the higher of the t wo PVs and display that signal on a
PVI attached to the selector block.
What data items must be set to allow the block to automatically select the highest signal?

SIMULATION

I COO P

PV
M
MV
HEAT- SPLIT-
OU SE

MV
PI SPLI
I
HEA
I P

PV

IN
SELEC
HIGHES I P

PV AS-
IN

CENTUM VP Engineering 3 TE 33M80N10-10EN-A


CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

FUNC-VAR [Regulatory control/ Calculation]


The “FUNC-VAR” function block allows a linearization table to be created for a non-linear device
such as a cylindrical vessel. Create the simulation below and enter the data in the chart.
On-line Manual Question:
Referring to the data below:
• What does the “X” register do?
• What does the “ Y” register do?
• What does “SECT” on the “FUNC-VAR” tuning panel refer to?
• What must “SECT” be set to for this block to work?

Enter the following data in the “FUNC-VAR” tuning panel.

X01 = 0.00 Y01 = 0.00


X02 = 12.50 Y01 = 7.20
X03 = 25.00 Y03 = 20.40
X04 = 37.50 Y04 = 34.80
X05 = 50.00 Y05 = 50.00
X06 = 62.50 Y06 = 65.20
X07 = 75.00 Y07 = 79.60
X08 = 87.50 Y08 = 92.80
X09 = 100.00 Y09 = 100.00

SIMULATION

0-100 %
MV IN
LEVEL LINEAR

IN CPV
PID FUNC-VAR

Create a sequence table and a BDSET-1L that will change the “P” of the level controller when
the level changes between:
Level=0-30 P=100
Level=31-70 P=250
Level=71-100 P=100

CENTUM VP Engineering 4 TE 33M80N10-10EN-A


CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

FOUNDATION FIELDBUS I/O - (FF-AI); (FF-AO)


The input to the FF-AI block comes from the analog input function block in the Foundation
Fieldbus transmitter. Basic settings of the FF-AI block include Tag, Tag Comment, Scale High
and Low and Engineering Units. Detailed settings include Tag Mark, Alarm Level, Hierarchy and
Security Level.
On Figure 1 below FF-AI reflects the AI (Analog Input) function block inside the Flow Transmitter
FT100, the PID function block resides in the CPU of the CS 3000 system and the FF-AO reflects
the AO (Analog Output) function block inside the valve positioner FV100.
On Figure 2 below FF-AI reflects the AI (Analog Input) function block inside the Flow Transmitter
FT100, the FF-PID function block and the FF-AO function block reside inside the valve positioner
FV100.

Flow Transmitter Flow Transmitter

FT100 FT100

FF-AI FF-AI

OUT OUT

IN IN

FIC100 FIC100

PID
}  CS 3000
FF-PID

OUT OUT

SET SET

FV100 FV100

FF-AO FF-AO

Valve Positioner Valve Positioner

Figure 1 Figure 2

CENTUM VP Engineering 5 TE 33M80N10-10EN-A


CENTUM VP ADVANCED FUNCTION BLOCKS LESSON 7

Empty page

CENTUM VP Engineering 6 TE 33M80N10-10EN-A