Belimo Actuator Catalogue

This document provides information on Belimo damper actuators, including their naming conventions and product specifications. The naming convention indicates the torque level (2Nm to 40Nm), power supply (24V or 230V), and additional features. It then describes the specifications of each actuator model for general and mechanical fail-safe damper actuators across a range of torque levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
978 views68 pages

Belimo Actuator Catalogue

This document provides information on Belimo damper actuators, including their naming conventions and product specifications. The naming convention indicates the torque level (2Nm to 40Nm), power supply (24V or 230V), and additional features. It then describes the specifications of each actuator model for general and mechanical fail-safe damper actuators across a range of torque levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 68

Damper Actuators

Technical Databook
Version
Ver. 2 4

Belimo Asia Pacific


Damper Actuator standard type naming

Product Naming L M U 24 -SR

Torque

General Damper Actuator


40Nm G
20Nm S
10Nm N
5Nm L
2Nm C
Mechanical Fail-Safe Damper Actuator
20Nm S
10Nm N
4Nm L
2Nm T

General Damper Actuator M


Mechanical Fail-Safe Damper Actuator F

New Generation General Damper Actuator for Asia Pacific

Power Supply
AC/DC 24V 24
AC 100...240V (AC 230 for Mechanical Fail-Safe Damper Actuator) 230
General Damper Actuator
Open/Close, 3-point Blank
Open/Close (only for CMU230..) -RES
Modulating DC 2(0)...10V Control -SR
Auxiliary Switch -S
Form fit -F
Terminal Connection -T
Mechanical Fail-Safe Damper Actuator
Open/Close Blank
Modulating DC 2(0)...10V Control -SR
3-point -3
Auxiliary Switch -S, -S2

For customising types of Damper Actuators please contact your nearest Belimo sales representative.
V4. 12. 2010 . Subject to modification

2
Contents

Product overview 4
General Damper Actuator, 2Nm
CMU24(-F8/-F10)(-T) 6
CMU24-SR-R 7
CMU230(-F8/-F10) 8
CMU230(-F8/-F10)-RES 9
General Damper Actuator, 5Nm
LMU24(-S/-F/-T) 10
LMU24-SR 11
LMU230(-S/-F) 12
LMU230SR 13
General Damper Actuator, 10Nm
NMU24(-S/-F/-T) 14
NMU24-SR 15
NMU230(-S/-F) 16
NMU230SR 17
General Damper Actuator, 20Nm
SMU24(-S/-F/-T) 18
SMU24-SR 19
SMU230(-S/-F) 20
SMU230SR 21
General Damper Actuator, 40Nm
GMU24 22
GMU24-SR 23
GMU230 24
Fast Running Damper Actuator, 4Nm
LMQU24 25
LMQU24-SR 26
Fast Running Damper Actuator, 8Nm
NMQU24 27
NMQU24-SR 28
Fast Running Damper Actuator, 16Nm
SMQU24 29
SMQU24-SR 30
Mechanical Fail-Safe Damper Actuator, 2Nm
TF24(-S) 31
TF24-3 32
TF24-SR 33
TF230(-S) 34
TF230-SR 35
Note: Mechanical Fail-Safe Damper Actuator, 4Nm
LF24(-S) 36
Using Belimo Damper Actuators: LF24-3 37
• The actuators listed in this catalogue are intended for the LF24-SR 38
operation of air dampers in HVAC systems. LF230(-S) 39
• The Damper Actuator is not allowed to be used outside the
Mechanical Fail-Safe Damper Actuator, 10Nm
specified field of application, especially in aircraft.
NFU 40
• The enclosure of the actuator equipment may only be
NFU-S2 41
opened by the manufacturer. It contains no components NFU24-SR 42
which the user can replace or repair.
Mechanical Fail-Safe Damper Actuator, 20Nm
• The device contains electrical and electronic
SFU 43
components and is not allowed to be disposed of as
SFU-S2 44
household refuse. All locally valid regulations and SFU24-SR 45
requirements must be observed.
Mounting instructions 46
Wiring diagrams 56
Torque requirements:
Auxiliary switch adjustment 61
• When calculating the torque required to operate
Electrical accessories 62
dampers, it is essential to take into account all the data
Mechanical accessories 63
V4. 12. 2010 . Subject to modification

supplied by the damper manufacturer concerning cross


Replacement table (for Mechanical Fail-Safe Damper Actuators) 65
sectional area, design, mounting and air flow condition.

3
Damper Actuator product overview

General Damper Actuator CMU.. LMU.. NMU.. SMU.. GMU..


Open/Close, 3-point 2Nm 5Nm 10Nm 20Nm 40Nm
AC/DC 24V 50/60Hz CMU24(-F8/-F10)(-T) LMU24(-F/-T) NMU24(-F/-T) SMU24(-F/-T) GMU24*
Auxiliary switch built-in 1 SPDT LMU24-S NMU24-S SMU24-S
AC 100...240V 50/60Hz CMU230(-F8/-F10) LMU230 NMU230 SMU230 GMU230*
AC 230V 50Hz (Open/Close) CMU230(-F8/-F10)-RES*
Auxiliary switch built-in 1 SPDT LMU230-S NMU230-S SMU230-S
Modulating
Control signal DC 2(0)...10V, feedback DC 2...10V
AC/DC 24V 50/60Hz CMU24-SR-R** LMU24-SR NMU24-SR SMU24-SR GMU24-SR
AC 100...240V 50/60Hz LMU230SR NMU230SR SMU230SR
Running time 75s 150s
Shaft diameter 6...12.7mm 6...20mm 8...26mm 10...20mm 14...26mm
Sound power level Max. 35dB(A) Max. 35dB(A) Max. 35dB(A) Max. 48dB(A) Max. 48dB(A)
Manual override Gear disengaging by magnet Gear disengaging by pushbutton
Electrical connection Cable 1m (-T: Terminal)
Direction of rotation Selected by switch
Angle of rotation Max. 95°, can be limited at both ends with mechanical adjustable end stops
Position indication Mechanical, plug-on
Degree of protection IP54 in any direction (-T: IP20)
EMC CE according to 89/336/EEC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (to EN 60730-1)
* Only Open/Close, no 3-point.
** CMU24-SR-R: Control signal 2(0)V at the right side, and the left side is available on request.

General Damper Actuator LMQU.. NMQU.. SMQU..


Open/Close 4Nm 8Nm 16Nm
AC 24V 50/60Hz, DC 24V LMQU24 NMQU24 SMQU24
Modulating
AC 24V 50/60Hz, DC 24V
Control signal DC 2(0)…10V, feedback signal DC 2…10V LMQU24-SR NMQU24-SR SMQU24-SR
Running time 2.5s 4.0s 7.0s
Shaft diameter 8…26.7mm 12…25.5mm
Sound power level Max. 52dB(A)
Manual override Disengaging the gearing latch by means of a pushbutton, self-resetting
Electrical connection Cable 1m
Direction of rotation Selected by switch
Angle of rotation Max. 95°, can be limited at both ends with mechanical adjustable end stops
Position indication Mechanical, plug-on
Degree of protection IP54 in any direction
EMC CE according to 2004/108/EC
Ambient temperature -30…+40°C (without restrictions); +40…+50°C (with restrictions)
Non-operation temperature -40…+80°C
Humidity test 95% RH, non-condensing (to EN 60730-1)
V4. 12. 2010 . Subject to modification

4
Damper Actuator product overview

Mechanical Fail-Safe Damper Actuator TF.. LF..


Open/Close 2Nm 4Nm
AC/DC 24V 50/60Hz TF24 LF24-S
Auxiliary switch built-in 1 SPDT TF24-S LF24-S
AC 230V 50/60Hz TF230 LF230
Auxiliary switch built-in 1 SPDT TF230-S LF230-S
3-point TF24-3 LF24-3*
Modulating
AC/DC 24V 50/60Hz
Control signal DC 2(0)...10V, feedback DC 2...10V TF24-SR LF24-SR
Running time -Motor < 75s* 40-75s*
-Spring return < 25s ~20s
Shaft diameter 6...12mm 8...16mm
Sound power level -Motor Max. 50dB(A)
-Spring return 62dB(A)
Electrical connection Cable 1m
Direction of rotation Selected by mounting L/R
Angle of rotation Max. 95°
Mechanical limiter YES
Position indicator YES
Degree of protection IP42 IP54
EMC CE according to 89/336/EEC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (to EN 60730-1)

* LF24-3 and all -SR types are 150s.


** TF24-3 nominal voltage is AC 24V, TF230 nominal voltage is AC 100...240V.

Machanical Fail-Safe Damper Actuator NFU.. SFU..


Open/Close 10Nm 20Nm
AC 24...240V DC 24...125V NFU SFU
Auxiliary switch built-in 2 SPDT NFU-S2 SFU-S2
Modulating
AC/DC 24V 50/60Hz
Control signal DC 2(0)...10V, feedback DC 2...10V NFU24-SR SFU24-SR
Running time -Motor Open/Close 75s; modulating 150s
-Spring return <20s
Shaft diameter / 10...12mm / 14...25.4mm
Sound power level -Motor Open/Close Max. 50dB(A)/Modulating Max. 40dB(A) Open/Close Max. 50dB(A)/Modulating Max. 40dB(A)
-Spring return Max. 62dB(A)
Electrical connection Cable 1m
Direction of rotation Selected by mounting L/R
Angle of rotation Max. 95°
Mechanical limiter YES
Position indicator YES
Degree of protection IP54
EMC CE according to 2004/108/EEC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (to EN 60730-1)
V4. 12. 2010 . Subject to modification

5
LMU230(-S/-F)

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 5Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close or 3-point

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 1.5W @ running / 0.5W @ holding
Wire/transformer sizing 3.5VA
Auxiliary switch LMU230-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection: Motor Cable 1m, 3x0.75mm2
Auxiliary switch LMU230-S Cable 1m, 3x0.75mm2
Functional data Torque 5Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) See 'Dimensions'
Shaft length: LMU230(-S) Min. 37mm
LMU230-F Min. 20mm
Shaft : LMU230(-S) 6...20mm
LMU230-F 8x8mm
Weight Approximately 550g

Dimensions [mm]

LMU230(-S) LMU230-F
61
61

47
47

1620 116
116
28.5 100.5
66

5.2
66
30

V4. 12. 2010 . Subject to modification

22 94 41 22 94 41

12
LMU230SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 5Nm
•ΓNominal voltage: AC 100...240V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 2.0W @ running / 1W @ holding
Wire/transformer sizing 4VA
Connection cable: Power supply Cable 1m, 2x0.75mm2
Signals Cable 1m, 4x0.75mm2
Functional data Torque 5Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 179x66x60mm
Shaft length Min. 37mm
Shaft 6...20mm
Weight Approximately 700g

Dimensions [mm]
61
47

116
66
V4. 12. 2010 . Subject to modification

22 116 41

13
NMU24(-S/-F/-T)

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 10Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close or 3-point

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 1.5W @ running / 0.2W @ holding
Wire/transformer sizing 3VA
Auxiliary switch NMU24-S 1 SPDT, 1mA...3 (0.5)A, AC 250V , adjustable
Connection : Motor NMU24(-S/-F) Cable 1m, 3x0.75mm2
Auxiliary switch NMU24-S Cable 1m, 3x0.75mm2
Terminals NMU24-T Max. 3x1.5mm2
Functional data Torque 10Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection: NMU24(-S/-F) IP54 in any direction
NMU24-T IP20
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) See 'Dimensions'
Shaft length Min. 40mm (20mm with K-NA for reverse mounting - optional)
Shaft: NMU24(-T/-S) 8...26.7mm (8...20mm with K-NA)
NMU24-F 8x8mm
Weight Approximately 750g

Dimensions [mm]

NMU24(-S) NMU24-T NMU24-F


62
65.6
62
60

60

38

124 18 124 16
124
32 102
V4. 12. 2010 . Subject to modification
80

30
5.2
80
80

25 99 41 25 99 25 99 41

14
NMU24-SR

• For operation of air control dampers in HVAC system


• Torque: 10Nm
• Nominal voltage: AC/DC 24V
• Control signal: DC 2(0)...10V
• Position feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 2W @ running / 0.4W @ holding
Wire/transformer sizing 4VA
Connection Cable 1m, 4x0.75mm2
Functional data Torque 10Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 165x80x62mm
Shaft length Min. 40mm (20mm with K-NA for reverse mounting - optional)
Shaft 8...26.7mm (8...20mm with K-NA)
Weight Approximately 800g

Dimensions [mm]
62
60

124
80
V4. 12. 2010 . Subject to modification

25 99 41

15
NMU230(-S/-F)

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 10Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close or 3-point

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 2.5W @ running / 0.6W @ holding
Wire/transformer sizing 5.5VA
Auxiliary switch NMU230-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection : Motor Cable 1m, 3x0.75mm2
Auxiliary switch NMU230-S Cable 1m, 3x0.75mm2
Functional data Torque 10Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) See 'Dimensions'
Shaft length Min. 40mm (20mm with K-NA for reverse mounting - optional)
Shaft: NMU230(-S) 8...26.7mm (8...20mm with K-NA)
NMU230-F 8x8mm
Weight Approximately 800g

Dimensions [mm]

NMU230(-S) NMU230-F
62
62
60

38

124 18 124 16
32 102
30
5.2
80

V4. 12. 2010 . Subject to modification


80

25 99 41 25 99 41

16
NMU230SR

For operation of air control dampers in HVAC system


Torque: 10Nm
Nominal voltage: AC 100... 240V
Control signal: DC 2(0)...10V
Position feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 3.5W @ running / 1W @ holding
Wire/transformer sizing 6.5VA
Connection cable: Power supply Cable 1m, 2x0.75mm2
Signals Cable 1m, 4x0.75mm2
Functional data Torque 10Nm
Control signal DC2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 35dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 187x80x62mm
Shaft length Min. 40mm (20mm with K-NA for reverse mounting - optional)
Shaft 8...26.7mm (8...20mm with K-NA)
Weight Approximately 950g

Dimensions [mm]
62
60

124
V4. 12. 2010 . Subject to modification

80

25 121 41

17
SMU24(-S/-F/-T)

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 20Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close or 3-point

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 2W @ running / 0.2W @ holding
Wire/transformer sizing 4VA
Auxiliary switch SMU24-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection : Motor Cable 1m, 3x0.75mm2
Auxiliary switch SMU24-S Cable 1m, 3x0.75mm2
Terminals SMU24-T Max. 3x1.5mm2
Functional data Torque 20Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection: SMU24(-S/-F) IP54 in any direction
SMU24-T IP20
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) See 'Dimensions'
Shaft length Min. 42mm (20mm for reverse mounting)
Shaft: SMU24(-S) 10...20mm
(10...26.7mm with K-ENSA - optional)
SMU24-F 12x12mm
Weight Approximately 1050g

Dimensions [mm]

SMU24-F SMU24(-S) SMU24-T


67.6
64
56

56

30 109

23 97 139 139
88

88

V4. 12. 2010 . Subject to modification


75

4.2 30 109 41 30 109


8.8

18
SMU24-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 20Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 2W @ running / 0.4W @ holding
Wire/transformer sizing 4VA
Connection cable Cable 1m, 4x0.75mm2
Functional data Torque 20Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 180x88x64mm
Shaft length Min. 42mm (20mm for reverse mounting)
Shaft 10...20mm
(10...26.7mm with K-ENSA - optional)
Weight Approximately 1050g

Dimensions [mm]
64
56

139
V4. 12. 2010 . Subject to modification

88

30 109 41

19
SMU230(-S/-F)

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 20Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close or 3-point

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 2.5W @ running / 0.6W @ holding
Wire/transformer sizing 6VA
Auxiliary switch SMU230-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection : Motor Cable 1m, 3x0.75mm2
Auxiliary switch SMU230-S Cable 1m, 3x0.75mm2
Functional data Torque 20Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) See ‘Dimensions’
Shaft length Min. 42mm (20mm for reverse mounting)
Shaft: SMU230(-S) 10...20mm
(10...26.7mm with K-ENSA - optional)
SMU230-F 12x12mm
Weight Approximately 1050g

Dimensions [mm]
SMU230-F SMU230(-S)
64
56

30 109
139
23 97
75

88

V4. 12. 2010 . Subject to modification

4.2
30 109 41
8.8

20
SMU230-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 20Nm
•ΓNominal voltage: AC 100...240V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 3.5W @ running / 1W @ holding
Wire/transformer sizing 6.5VA
Connection cable: Power supply Cable 1m, 2x0.75mm2
Signals Cable 1m, 4x0.75mm2
Functional data Torque20Nm 20Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 202x88x64mm
Shaft length Min. 42mm (20mm for reverse mounting)
Shaft 10...20mm
(10...26.7mm with K-ENSA - optional)
Weight Approximately 1200g

Dimensions [mm]
64
56

139
V4. 12. 2010 . Subject to modification

88

30 131 41

21
GMU24

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 40Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 4W @ running / 2W @ holding
Wire/transformer sizing 6VA
Connection cable Cable 1m, 3x0.75mm2
Functional data Torque 40Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x70mm
Shaft length Min. 52mm (20mm for reverse mounting)
Shaft 12...26.7mm/12...25.2mm
Weight Approximately 1700g

Dimensions [mm]

Standard :

Damper spindle Length


70

>52 12...26.7 >12 <25


60

>20 12...26.7 >12 <25

179

12...22mm 12...18mm
116

V4. 12. 2010 . Subject to modification

22...26.7mm 12...18mm

36 143 41

22
GMU24-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 40Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC/DC 19.2...28.8V
Power consumption 4.5W @ running / 2W @ holding
Wire/transformer sizing 6.5VA
Connection cable Cable 1m, 4x0.75mm2
Functional data Torque 40Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Position accuracy ±5%
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class III (safety low voltage)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x70mm
Shaft length Min. 52mm (20mm for reverse mounting)
Shaft 12...26.7mm/12...25.2mm
Weight Approximately 1700g

Dimensions [mm]

Standard :

Damper spindle Length


70
60

>52 12...26.7 >12 <25


>20 12...26.7 >12 <25

179

12...22mm 12...18mm
116
V4. 12. 2010 . Subject to modification

22...26.7mm 12...18mm 36 143 41

23
GMU230

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 40Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Nominal voltage range AC 85...265V
Power consumption 5W @ running / 2W @ holding
Wire/transformer sizing 9VA
Connection cable Cable 1m, 3x0.75mm2
Functional data Torque 40Nm
Direction of rotation Selectable by switch
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95°, adjustable by mechanical stops
Running time 150s for 95°
Sound power level Max. 48dB(A)
Position indication Mechanical, remote visible
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x70mm
Shaft length Min. 52mm (20mm for reverse mounting)
Shaft 12...26.7mm/12...25.2mm
Weight Approximately 1700g

Dimensions [mm]

Standard :

Damper spindle Length


70
60

>52 12...26.7 >12 <25


>20 12...26.7 >12 <25

179

12...22mm 12...18mm
116

V4. 12. 2010 . Subject to modification

22...26.7mm 12...18mm
36 143 41

24
LMQU24

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 4Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close (not made for 3-point applications)

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 13W @ running / 1.5W @ holding
Wire sizing 23VA (I max. 20A @ 5ms)
Connection Cable 1m, 3x0.75mm2
Functional data Torque (nominal torque) Min. 4Nm @ nominal voltage
Direction of rotation Reversible with switch 0 or 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 2.5s for 90°
Automatic adjustment of operating range and Manual triggering of the adaption by pressing the
measuring signal U to match the mechanical «Adaption» button
angle of rotation
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤ 50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1 (EN 60730-1)
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 187x80x75mm
Weight Approximately 850g

Dimensions [mm]
75
52

124
V4. 12. 2010 . Subject to modification

Damper spindle Length


80

≥40 8...26.7 ≥8 ≤26.7


* ≥20 8...20 ≥8 ≤20
* Option (accessory K-NA)

25 121 41

25
LMQU24-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 4Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl modulating: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 13W @ running / 1.5W @ holding
Wire sizing 23VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 4Nm @ nominal voltage
Control signal DC 2(0)...10V, input impedance 100kΩ
Feedback signal DC 2...10V, max. 0.5mA
Position accuracy +5%
Direction of rotation Reversible with switch 0/1
Direction of motion at Y = 0 V At switch position 0 resp. 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical stops
Running time 2.5s for 90°
Automatic adjustment of operating Manual triggering of the adaption by pressing the
range and measuring signal U to match «Adaption» button
the mechanical angle of rotation
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, only AC) = 50%
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Mode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 187x80x75mm
Weight Approximately 850g

Dimensions [mm]
75
52

124
V4. 12. 2010 . Subject to modification

Damper spindle Length


80

≥40 8...26.7 ≥8 ≤26.7


* ≥20 8...20 ≥8 ≤20
* Option (accessory K-NA)

25 121 41

26
NMQU24

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 8Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close (not made for 3-point applications)

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 13W @ running /1.5W @ holding
Wire sizing 23VA (I max. 20A @ 5ms)
Connection Cable 1m, 3x0.75mm2
Functional data Torque (nominal torque) Min. 8Nm @ nominal voltage
Direction of rotation Reversible with switch 0 or 1ΓΓΓΓ
Manual override Gearing latch disengaged with pushbutton self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 4s for 90°
Automatic adjustment of operating range and Manual triggering of the adaption by pressing the
measuring signal U to match the mechanical «Adaption» button
angle of rotation
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤ 50% from nominal torque (with restrictions)
Working conditions Protection class III Safety extra-low voltage
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Mode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 202x88x77mm
Weight Approximately 970g

Dimensions [mm]
77
52

139
V4. 12. 2010 . Subject to modification

Damper spindle Length


≥42 8...26.7 ≥8 ≤26.7
88

* ≥20 8...20 ≥8 ≤20


* Option (accessory K-SA)

30 131 41

27
NMQU24-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 8Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl modulating: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 13W @ running / 1.5W @ holding
Wire sizing 23VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 8Nm @ nominal voltage
Control signal DC 2(0)...10V, input impedance 100kΩ
Feedback signal DC 2...10V, max. 0.5mA
Position accuracy +5%
Direction of rotation Reversible with switch 0/1
Direction of motion at Y = 0 V At switch position 0 resp. 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical stops
Running time 4s for 90°
Automatic adjustment of operating range
Manual triggering of the adaption by pressing the
and measuring signal U to match the
«Adaption» button
mechanical angle of rotation
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, only AC) = 50%
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Mode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 202x88x77mm
Weight Approximately 970g

Dimensions [mm]
77
52

139
V4. 12. 2010 . Subject to modification

Damper spindle Length


≥42 8...26.7 ≥8 ≤26.7
88

* ≥20 8...20 ≥8 ≤20


* Option (accessory K-SA)

30 131 41
28
SMQU24

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 16Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close (not made for 3-point applications)

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 15W @ running /1.5W holding
Wire sizing 26VA (I max. 20A @ 5ms)
Connection Cable 1m, 3x0.75mm2
Functional data Torque (nominal torque) Min. 16Nm @ nominal voltage
Direction of rotation Reversible with switch 0 resp. 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 7s for 90°
Automatic adjustment of operating range to Manual triggering of the adaption by pressing the
match the mechanical angle of rotation «Adaption» button
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤ 50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage / UL Class 2 supply)
Degree of protection IP54 in any mounting position
NEMA 2, UL Enclosure Type 2
EMC CE according to 2004/108/EC
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1 to EN 60730-1
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operating temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x83mm
Weight Approximately 1.7kg

Dimensions [mm]
83
62

Damper spindle Length


≥52 12...26.7 ≥12 ≤25.5
≥20 12...26.7 ≥12 ≤25.5

179
V4. 12. 2010 . Subject to modification

12...22mm 12...18mm
116

22...26.7mm 12...18mm 36 143 41

29
SMQU24-SR

•ΓFor operation of air control dampers in HVAC system


•ΓTorque: 16Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl modulating: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 15W @ running / 1.5W @ holding
Wire sizing 26VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 16Nm @ nominal voltage
Control signal Y DC 2(0)...10V, input impedance 100kΩ
Position feedback (Measuring voltage) DC 2...10V, max. 0.5mA
Position accuracy +5%
Direction of rotation Reversible with switch 0/1
Direction of motion at Y = 0 V At switch position 0 or 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 7s for 90°
Automatic adjustment of operating range Manual triggering of the adaption by pressing the
and measuring signal U to match the «Adaption» button
mechanical angle of rotation
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, only AC) = 50%
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage / UL Class 2 supply)
Degree of protection IP54 in any mounting position
NEMA 2, UL Enclosure Type 2
EMC CE according to 2004/108/EC
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1 (EN 60730-1)
Ambient temperature –30...+40°C (without restrictions)
! +50°C (with restrictions)
Non-operating temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x83mm
Weight Approximately 1.7kg

Dimensions [mm]
83

Damper spindle Length


62

≥52 12...26.7 ≥12 ≤25.5


≥20 12...26.7 ≥12 ≤25.5

179
V4. 12. 2010 . Subject to modification

12...22mm 12...18mm
116

22...26.7mm 12...18mm 36 143 41


30
Mechanical Fail-Safe Damper Actuator TF24(-S)

•ΓFor operation of air control dampers that perform safety function


•ΓTorque: 2Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close
•ΓIntegrated auxiliary switch (TF24-S)

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Power supply range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption 2.5W @ running / 1.5W @ holding
Wire/transformer sizing 5VA
Auxiliary switch TF24-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection cable - Motor Cable 1m, 2x0.75mm2
- Auxiliary switch TF24-S Cable 1m, 3x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 75s
- Spring return 25s @ -20...50°C / max. 60s @ -30°C
Sound power level Motor max. 50dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP42 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1. AA to EN 60730-1
Ambient temperature range -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 600g

Dimensions [mm]
17

6...12
84
61
6

104
V4. 12. 2010 . Subject to modification

77

20 84 36

31
Mechanical Fail-Safe Damper Actuator TF24-3

•ΓFor operation of air control dampers that perform safety function


•ΓTorque: 2Nm
•ΓNominal voltage: AC 24V
•ΓControl: 3-point

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz


Nominal supply range AC 19.2...28.8V
Power consumption 2.5W @ running / 1W @ holding
Wire/transformer sizing 4VA
Connection : Motor Cable 1m, 4x0.75mm
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 150s ( 0...2Nm)
- Spring return 25s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 35dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP42 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1. AA to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 600g

Dimensions [mm]
17

6...12
84
61
6

104
V4. 12. 2010 . Subject to modification
77

20 84 36

32
Mechanical Fail-Safe Damper Actuator TF24-SR

•ΓFor operation of air control dampers that perform safety function


•ΓTorque: 2Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Power supply range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption 2.5W @ running / 1W @ holding
Wire/transformer sizing 4VA
Connection cable Cable 1m, 4x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 150s (0...2Nm)
- Spring return 25s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 35dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP42 in any direction
EMC CE according to 89/336/EEC
Mode of operation Type 1.AA to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 600g

Dimensions [mm]
17

6...12
84
616

104
77
V4. 12. 2010 . Subject to modification

20 84 36

33
Mechanical Fail-Safe Damper Actuator TF230(-S)

•ΓFor operation of air control dampers that perform safety function


•ΓTorque: 2Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close
•ΓIntegrated auxiliary switch (TF230-S)

Technical data
Electrical data Nominal voltage AC 100...240V 50/60Hz
Nominal supply range AC 85...265V
Power consumption 2.5W @ running / 1.5W @ holding
Wire/transformer sizing 5VA
Auxiliary switch TF230-S 1 SPDT, 1mA...3 (0.5)A, AC 250V , adjustable
Connection cable - Motor Cable 1m, 2x0.75mm2
- Auxiliary switch TF230-S Cable 1m, 3x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Direction of rotation - Motor Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 75s
- Spring return 25s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 50dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP42 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1. AA to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 600g

Dimensions [mm]
17

6...12
84
61
6

104
V4. 12. 2010 . Subject to modification
77

20 84 36

34
Mechanical Fail-Safe Damper Actuator TF230-SR

•ΓFor operation of air control dampers that perform safety function


•ΓTorque: 2Nm
•ΓNominal voltage: AC 100...240V
•ΓControl signal: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 100...240V 50/60Hz


Power supply range AC 85...265V
Power consumption 2.5W @ running / 2W @ holding
Wire/transformer sizing 5.5VA
Connection power supply Cable 1m, 2x0.75mm2
Cable 1m, 3x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Control signal DC 2(0)...10V (input impedance 100kΩ)
Feedback signal DC 2...10V
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 150s (0...2Nm)
- Spring return 25s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 35dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP42 in any direction
EMC CE according to 2004/108/EEC
Low-voltage directive CE according to 2006/95/EC
Mode of operation Type 1.AA to EN 60730-1
Ambient temperature range -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 630g

Dimensions [mm]
17
84

6...12
61 6

104
V4. 12. 2010 . Subject to modification

77

20 84 36

35
Mechanical Fail-Safe Damper Actuator LF24(-S)

•ΓFor the operation of air dampers that perform safety function


•ΓTorque: 4Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close
•ΓIntegrated auxiliary switch (LF24-S)

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Power supply range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption 5W @ running / 2.5W @ holding
Wire/transformer sizing 7VA
Auxiliary switch LF24-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection cable - Motor Cable 1m, 2x0.75mm2
- Auxiliary switch LF24-S Cable 1m, 3x0.75mm2
Functional data Torque - Motor 4Nm @ nominal voltage
- Spring return 4Nm
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 40...75s (0...4Nm)
- Spring return Approximately 20s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 50dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any direction
EMC CE according to 2004/108/EC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 181x98x82mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 8...16mm
Weight Approximately 1400g

Dimensions [mm]
18.5
82

8...16
57
6.5

181

155
25 12.6
6.5
.8
.6
.4
1

.2
0

V4. 12. 2010 . Subject to modification


98
80

49

18 93

125

36
Mechanical Fail-Safe Damper Actuator LF230(-S)

•ΓFor the operation of air dampers that perform safety function


•ΓTorque: 4Nm
•ΓNominal voltage: AC 230V
•ΓControl: Open/Close
•ΓIntegrated auxiliary switch (LF230-S)

Technical data

Electrical data Nominal voltage AC 230V 50/60Hz


Nominal supply range AC 198...264V
Power consumption 5W @ running / 3W @ holding
Wire/transformer sizing 7VA
Auxiliary switch LF230-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
Connection cable - Motor Cable 1m, 2x0.75mm2
- Auxiliary switch LF230-S Cable 1m, 3x0.75mm2
Functional data Torque - Motor 4Nm @ nominal voltage
- Spring return 4Nm
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 40...75s (0...4Nm)
- Spring return Approximately 20s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 50dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP54 in any direction
EMC CE according to 2004/108/EC
Low voltage directive CE according to 2006/95/EC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 181x98x82mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 8...16mm
Weight Approximately 1550g

Dimensions [mm]
18.5
82
57

8...16
6.5

181
155

25 12.6
6.5
V4. 12. 2010 . Subject to modification

.8
.6
.4
1

.2
0
80

98

18 93
125

39
Mechanical Fail-Safe Damper Actuator NFU

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations

•ΓTorque: 10Nm
•ΓNominal voltage: AC 24...240V/DC 24...125V
•ΓControl: Open/Close

Technical data

Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V


Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Power consumption In operation 6.0W @ running/2.5W @ holding
For wire sizing 9.5VA
Connection Cable 1m, 2x0.75mm2
Functional data Torque - Motor Min. 10Nm @ nominal voltage
- Spring return Min. 10Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor < 75s (0...10Nm)
- Spring return < 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 50dB(A)
- Spring return ~62dB(A)
Position indication Mechanical
Life time >60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP54
EMC CE according to 2004/108/EC
Low voltage directive CE according to 2006/95/EC
Control pollution degree 3
Rated Impulse Voltage 4kv
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2000g

Dimensions [mm]
20

Standard :
¾”- clamp (with insert)
85
59

Damper shaft Length


≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4

Optional 1:
1”- clamp (without insert)
2-FRONT

Damper shaft Length


≥85 19...25.4 12...18
≥15 19...25.4 12...18
98
80

V4. 12. 2010 . Subject to modification

Optional 2:
½” - clamp (optional via configuration)
Damper shaft Length
≥85 10...19 14...20
≥15 10...19 14...20 32 
162
172
182
236

40
Mechanical Fail-Safe Damper Actuator NFU-S2

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations

•ΓTorque: 10Nm
•ΓNominal voltage: AC 24...240V/DC 24...125V
•ΓControl: Open/Close
•Γ2x SPDT auxiliary switches built-in

Technical data

Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V


Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Power consumption 6.0W @ running / 2.5W @ holding
For wire sizing 9.5VA
Auxiliary switch 2x SPDT, 1mA...3(0.5)A, AC 250V
one fixed at 10°, one adjustable 10°...90°
Connection Cable 1m, 2x0.75mm2
Functional data Torque - Motor Min. 10Nm @ nominal voltage
- Spring return Min. 10Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor < 75s (0...10Nm)
- Spring return < 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 50dB(A)
- Spring return ~62dB(A)
Position indication Mechanical
Life time >60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP54
EMC CE according to 2004/108/EC
Low voltage directive CE according to 2006/95/EC
Control pollution degree 3
Rated Impulse Voltage Supply: 4kV
Switch: 2.5kV
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2200g

Dimensions [mm]
20

Standard :
85
59

¾”- clamp (with insert)


Damper shaft Length
≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4
RONT
V4. 12. 2010 . Subject to modification

Optional 1:
2-F

1”- clamp (without insert)


Damper shaft Length
98
80

≥85 19...25.4 12...18


≥15 19...25.4 12...18

Optional 2:
½”- clamp (optional via configuration) 32 27
162
Damper shaft Length 172
≥85 10...19 14...20 182

10...19 14...20 236


≥15
41
Mechanical Fail-Safe Damper Actuator NFU24-SR

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations

•ΓTorque: 10Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: modulating DC 2(0)...10V
position feedback DC 2...10V

Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption in operation 3.5W @ running/2.5W @ holding
For wire sizing 6.0VA
Connection Cable 1m, 4x0.75mm2
Functional data Torque - Motor Min. 10Nm @ nominal voltage
- Spring return Min. 10Nm
Control Control signal Y DC 0...10V, typical input impedance 100KΩ
Working range DC 2...10V
Position feedback (Measuring voltage) DC 2...10V, max. 1mA
Position accuracy ±5%
Direction of rotation - Motor Reversible with switch or
- Spring return Selectable by mounting L/R
Direction of rotation at Y=0V At switch position resp. 1
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor 150s/90°
- Spring return < 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 40dB(A)
- Spring return ~62dB(A)
Working conditions Position indication Mechanical
Protection class III (safety extra-low voltage)
Degree of protection IP54
EMC CE according to 2004/108/EC
Control pollution degree 3
Rated Impulse Voltage 800V
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2000g

Dimensions [mm]
20

Standard :
¾”- clamp (with insert)
85
59

Damper shaft Length


≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4

Optional 1:
1”- clamp (without insert)
2-FRONT

V4. 12. 2010 . Subject to modification

Damper shaft Length


≥85 19...25.4 12...18
≥15 19...25.4 12...18
98
80

Optional 2:
½” - clamp (optional via configuration)
Damper shaft Length
≥85 10...19 14...20 32 
≥15 10...19 14...20 162
172
182
42 236
Mechanical Fail-Safe Damper Actuator SFU

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations

•ΓTorque: 20Nm
•ΓNominal voltage: AC 24...240V
DC 24...125V
•ΓControl: Open/Close

Technical data

Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V


Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Power consumption 7.0W @ running / 3.5W @ holding
Wire/transformer sizing 7.0VA @ AC 24V
8.5VA @ AC 120V
18.0VA @ AC 240V
Connection Cable 1m, 2x0.75mm2
Functional data Torque - Motor Min. 20Nm @ nominal voltage
- Spring return Min. 20Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor Max. 75s (0...20Nm)
- Spring return Max. 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 45dB(A)
- Spring return Max. 62dB(A)
Position indication Mechanical
Working conditions Protection class II (Totally insulated)
Degree of protection IP54
EMC CE according to 2004/108/EC
Low voltage directive CE according to 2006/95/EC
Control pollution degree 3
Rated Impulse Voltage 4kv
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2200g

Dimensions [mm]
20
85
59

Standard :
¾”- clamp (with insert)
Damper shaft Length
≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4
2-FRONT

Optional 1:
V4. 12. 2010 . Subject to modification

1”- clamp (without insert)


Damper shaft Length
98
80

≥85 19...25.4 12...18


≥15 19...25.4 12...18

Optional 2:
½”- clamp (optional via configuration)
32 
Damper shaft Length
162
≥85 10...19 14...20 172
≥15 10...19 14...20 182
236
43
Mechanical Fail-Safe Damper Actuator SFU-S2

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations

•ΓTorque: 20Nm
•ΓNominal voltage: AC 24...240V
DC 24...125V
•ΓControl: Open/Close
•Γ2x SPDT auxiliary switches built-in

Technical data

Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V


Nominal voltage range AC 19.2...264V, DC 21.6...143V
Power consumption 7.0W @ running / 3.5W @ holding
Wire/transformer sizing 7.0VA @ AC 24V
8.5VA @ AC 120V
18.0VA @ AC 240V
Auxiliary switch 2X SPDT, 1mA...3(0.5)A, AC 250V
on fixed at 10%, one adjustable 10...90%
Connection - Motor Cable 1m, 2x0.75mm2
- Auxiliary switches Cable 1m, 6x0.75mm2
Functional data Torque - Motor Min. 20Nm @ nominal voltage
- Spring return Min. 20Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor Max. 75s (0...20Nm)
- Spring return Max. 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 45dB(A)
- Spring return Max. 62dB(A)
Working conditions Position indication Mechanical
Protection class II (totally insulated)
Degree of protection IP54
EMC CE according to 2004/108/EC
Low voltage directive CE according to 2006/95/EC
Control pollution degree 3
Rated Impulse Voltage Supply: 4kV
Switch: 2.5kV
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2400g

Dimensions [mm]
20

Standard :
¾”- clamp (with insert)
85

Damper shaft Length


59

≥85 10...22 10 14...25.4


≥15 10...22 10 14...25.4
N
OT

Optional 1:
R
F
2

V4. 12. 2010 . Subject to modification


-

1”- clamp (without insert)


Damper shaft Length
≥85 19...25.4 12...18
98
80

≥15 19...25.4 12...18

Optional 2:
½”- clamp (optional via configuration)
Damper shaft Length 32 27
14...20 162
≥85 10...19
172
≥15 10...19 14...20 182
236
44
Mechanical Fail-Safe Damper Actuator SFU24-SR

Modulating Mechanical Fail-Safe Actuator with emergency function for


adjusting air dampers in ventilation and air conditioning systems in buildings

•ΓTorque: 20Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl Modulating: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V


Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption 5.0W @ running / 3.5W @ holding
Wire/transformer sizing 7.0VA
Connection Cable 1m, 4x0.75mm2
Functional data Torque - Motor Min. 20Nm @ nominal voltage
- Spring return Min. 20Nm
Control signal DC 2(0)...10V, input impedance 100kΩ
Feedback signal DC 2...10V, max. 0.5mA
Position accuracy ±5%
Direction of rotation Reversible with switch /
Selectable by mounting L/R
Manual override With hand crank and interlocking switch
Angle of rotation Max. 95° , can be limited
by means of adjustable, mechanical end stops
Running time - Motor 150s/90°
- Spring return Max. 20s @ -20...60°C/max. 60s @ -30°C
Sound power level - Motor Max. 40dB(A) @ 150s running time
- Spring return Max. 62dB(A)
Position indication Mechanical
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54
EMC CE according to 2004/108/EC
Control pollution degree 3
Rated Impulse Voltage 0.8kV
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2200g

Dimensions [mm]
20
85
59

Standard :
¾”- clamp (with insert)
Damper shaft Length
≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4
2-FRONT

Optional 1:
1”- clamp (without insert)
V4. 12. 2010 . Subject to modification

Damper shaft Length


98
80

≥85 19...25.4 12...18


≥15 (26.7) 12...18

Optional 2:
½” - clamp (optional via configuration)
32 
Damper shaft Length
162
≥85 10...19 14...20 172
≥15 10...19 14...20 182
236
45
CMU.. mounting instructions

1 2 3

>32 2.5°
m m 90°
75 60 45
90 30
5
10

6...12.7mm

15
12
2.5°

15
12
5 30
10 45
0
75 9 60

70 ± 20mm 1
2 90
75
60 45 3
0

5
10
0
12
60 45 30
75
90

5
10
0
12
5
10

0
90

12
60 45 3
75 0

90

3.1...3.2mm

5
10
0
12

0
5
10

12
90

1 2 12
0
5
90
10

8
60 45 3
75 0

90
60 45 3
5
10

75 0
0
12

90
5
10
0
12

6Nm 12
0

90 1
05

!
0
12
05
90 1

75 60 45
120° 60°
90 30
5
10
0

15
12

75
90
5
10
0

15
12

5 30
12

10
60
45

75
0
75 9 60

90 45
5 30
10
0

15
12

5 30
10 45
75 90 60
15

75 60 45
90 30
5
10
0

15
12

60 45 3
75 0

90
0

15
12

60 45 3
5

75 0
10

5 30
10
90 45
0

0
75 9
12

60
5
10
0
12

0
12
05
90 1
0

ma
CMU24-SR.. x
.9

75 60 45
90
5 30
10
0

15
12 0

15
12

5 30
10 45
0
75 9 60

A
V4. 12. 2010 . Subject to modification

24V
0

46
LMU../LMS.. mounting instructions

1 2

> 37

6...20 >6 < 20

3 4
6 Nm

10
1

1m m

2 1

Z-PI
65°
V4. 12. 2010 . Subject to modification

47
NMU../NMS.. mounting instructions

1 2

40

8...26

10...26

3 4
9Nm

10

10
1
1mm

Z-PI

65°
V4. 12. 2010 . Subject to modification

48
SMU../SMS.. mounting instructions

1 2

48

10...20

10...20

3 4 9Nm

10

10
1 1 mm

Z-PI

65°
V4. 12. 2010 . Subject to modification

49
GMU../GMS.. mounting instructions

1 2

>52
2

12...22 mm 12...18 mm

4
2

13
22...26.7 mm 12...18 mm

1
3 15Nm

1m m

1 1

2
2 1

2
>20 1
Z-PI 4
5
2
V4. 12. 2010 . Subject to modification

65° 3

50
LMQU24../NMQU24.. mounting instructions

1 2

>52
2

12...22mm 12...18mm

4
2

13
22...26.7mm 12...18mm

1
3 15Nm

1m m

1 1

2
2 1

2
>20 1
Z-PI 4
V4. 12. 2010 . Subject to modification

5
2
65° 3

51
SMQU24.. mounting instructions

1 2

>52
2

12...22mm 12...18mm

4
2

13
22...26.7mm 12...18mm

1
3 15Nm

1m m

1 1

2
2 1

2
>20 1
Z-PI 4
5
2
V4. 12. 2010 . Subject to modification

65° 3

52
TF.. mounting instructions

1 2

L
L
min
. 84

6...12.7

3 4
R

37...100%
R

ZG-TF1
Subject to technical changes.

max 1 Nm

53
TF../LF.. mounting instructions

1 2

ZDB-TF

min
. 20

6...12.7

3 4

37...100%
R
ZDB-TF

V4. 12. 2010 . Subject to modification

54
NFU../SFU.. mounting instructions

A B

min 10...21 min


10...21 . 85 . 15

21...26 21...26

13
10 Nm

33...100%

.2
.4

.9
.6
.8
.8
.7
.6
.5
.4
.3
.2 .1
V4. 12. 2010 . Subject to modification

55
Wiring diagrams — General Damper Actuator

Wiring diagrams : CMU.. series actuators

Notes:
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.

Open/Close control 3-point control Connection via safety


T ~ T ~ ! isolated transformer
AC/DC 24V AC/DC 24V
- + - +

1 2 3 1 2 3

CMU24(-T) CMU24(-T)
CMU24-F8(-F10) CMU24-F8(-F10)

Modulating
~ Connection via safety
T AC/DC 24V ! isolated transformer
- +
Y DC 2(0)…10V
U DC 2…1V

1 2 3 5

BK RD WH OG

T ~
Y U
- + CMU24-SR-R

Connection via safety


Open/Close control 3-point control ! isolated transformer

N L AC 100...240V N L AC 100...240V

1 2 3 1 2 3

CMU230 CMU230
CMU230-F8(-F10) CMU230-F8(-F10)

Open/Close control
Connection via safety
N
! isolated transformer
L AC 230V
V4. 12. 2010 . Subject to modification

1 2 3

CMU230-RES
CMU230-F8 (-F10)-RES

56
Wiring diagrams—General Damper Actuator

Wiring diagrams: Open/Close actuators—Parallel connection possible, please note the performance data

1-wire control Connection via safety


2-wire control Connection via safety
! isolated transformer
! isolated transformer
T ~ AC/DC 24V 0
T ~ AC/DC 24V 0

- + Direction of rotation - + Direction of rotation


1 1
0
0 (while direction of rotation reverses)
(while direction of rotation reverses) 1
1
0

1 1 1 1
S1 S2 S3 S1 S2 S3 S1 S2 S3 S1 S2 S3
1 2 3 S1 S2 S3 1 2 3 S1 S2 S3
0 0 0 0

LMU24-S, NMU24-S LMU24-S, NMU24-S


0...100% SMU24-S 0...100% SMU24-S

LMU24(-T/-F), NMU24(-T/-F) LMU24(-T/-F), NMU24(-T/-F)


SMU24(-T/-F), GMU24
LMQU24, NMQU24, SMQU24 SMU24(-T/-F), GMU24*

N L1 AC 100...240V N L1 AC 100...240V

*GMU.. only for Open/Close


0 application
1 1 1 1
S1 S2 S3 S1 S2 S3 S1 S2 S3 S1 S2 S3
1 2 3 S1 S2 S3 1 2 3
0 0 0 0

LMU230-S, NMU230-S LMU230-S, NMU230-S


0...100% SMU230-S 0...100% SMU230-S

LMU230(-F), NMU230(-F) LMU230(-F), NMU230(-F)


SMU230(-F), GMU230 SMU230(-F), GMU230*

Wiring diagram: Modulating actuators—Parallel connection possible, please note the performance data

~ Connection via safety


Position - signal voltage
T AC/DC 24V
! isolated transformer
- +
% of 95° Reversing Reversing
Y DC 2(0)…10V switch 0 switch 1
100 Y=0 Y=0
U DC 2…10V
Open Open
Measuring voltage U
for position indicating
or as master-slave 50
1 2 3 5 Closed Closed
control signal.

T ~ anti-clockwise clockwise-
Y U LMU24-SR, NMU24-SR SMU24-SR, GMU24-SR -closing closing
- +
LMQU24-SR, NMQU24-SR, SMQU24-SR 0 Y
damper damper
0 2 5 10 [ V ]
N L1 AC 100...240V 0
Direction of rotation
AC 24V power output 1

Y DC 2(0)…10V
V4. 12. 2010 . Subject to modification

U DC 2…10V
Measuring voltage U
for position indicating
1 2 1 2 3 5 or as master-slave
control signal.

T ~
Y U LMU230SR, NMU230SR
SMU230SR
57
Wiring diagrams—Mechanical Fail-Safe Damper Actuator

Wiring diagrams: Open/Close actuators

Notes:
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.

N L1 AC 100...240V (for TF230..) N L1 AC 230V (for LF230..)


AC/DC 24V Connect via safety
! isolating transformer AC/DC 24V
! Connect via safety
isolating transformer

1 2 S1 S2 S3
1 2 S1 S2 S3

<x
M x = 0...100% TF230-S, TF24-S M
<x
x = 0...100% LF230-S, LF24-S
>x
>x

M TF230, TF24 M LF230, LF24

N L1 AC 24...240V
DC 24...125V

1 2 S1 S2 S3 S4 S5 S6

M 10% 10%...90% adjustable NFU-S2, SFU-S2

M NFU, SFU
V4. 12. 2010 . Subject to modification

58
Wiring diagrams—Mechanical Fail-Safe Damper Actuator

Wiring diagrams: 3-point actuators

Notes:
•ΓConnection via safety isolating transformer.
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.

Mounting side
~ Connect via safety
T
AC 24V ! isolating transformer .8
1 1

.8

.6 .6

.4 .4

.2 .2
0 0

L R

Reversing switch
a b
a b (Y 1 ) (Y 2 )

1 2 3 4 stop stop stop stop

Y1 Y 2 TF24-3

Mounting side

AC/DC 24V Connect via safety


! isolating transformer

Reversing switch
a b
(Y 1 ) (Y 2 ) R L R L

stop stop stop stop

T ~
LF24-3, NFS24-3, SF24-3
V4. 12. 2010 . Subject to modification

59
Wiring diagrams—Mechanical Fail-Safe Damper Actuator

Wiring diagram: Modulating actuators

Notes:
•ΓConnection via safety isolating transformer.
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.

Mounting side
T ~ AC/DC 24V Connect via safety
! isolating transformer 1 1

– + .8 .8

.6 .6
Y DC 2(0)...10V .4 .4
.2 .2
0 0

L R
U DC 2...10V
Reversing switch

R L R L
with with with with
Y=0 Y=0 Y=0 Y=0

LF24-SR, NFU24-SR, SFU24-SR

Mounting side
T ~ Connect via safety
AC/DC 24V !
– + isolating transformer 1 1

.8 .8

.6 .6

Y DC 2(0)…1V .4

.2 .2
.4

0 0

U DC 2…10V L R

Reversing switch
1 2 3 5

with with with with


Y=0 Y=0 Y=0 Y=0
TF24-SR

Connect via safety Mounting side


N L
T ! isolating transformer
 

 

 Y DC 2(0)…10V  

 

 U DC 2…10V 
 


/ 5

Reversing switch

1 2 1 3 5

with with with with


Y=0 Y=0 Y=0 Y=0
M TF230-SR
V4. 12. 2010 . Subject to modification

60
Auxiliary switch adjustment

Auxiliary switch adjustment for General Damper Actuators

1. Press the pushbutton, manually operate the universal clamp to


S2 S3 S2 S3
desired switch position.
1
2. Turn switch pointer to the middle line. S1 S1

3. When actuator moves clockwise (counter clockwise) to switch


position, switch indicator passes the middle line counter clockwise 2
(clockwise), the contact between S1 and S3 is disconnected
1
(connected) and the contact between S1 and S2 is connected
(disconnected).

Note: The switching point should be about 5° from the mechanical


end stops (1 short step on the scale).

Auxiliary switch adjustment for Mechanical Fail-Safe Damper Actuators

LF..-S (Mounting side R); NFU-S2, SFU-S2 (Mounting side L)

Starting point: Actuator in safe position

Procedure 1
Turn the knob of the auxiliary switch until the
tip of the arrow is pointing to the required .8 1
.8
switching position (see right). Example: .6
Switching point setting = 4 corresponds to .4
.6
40% angle of rotation. .2
0
.4
When the actuator runs to the operating S2 S2
.2 S1 S1
position (ccw ), the switch knob will also
rotate counter-clockwise (ccw ) and the 0 S3 S3
auxiliary switch will operate as the tip of the R
arrow passes the scale zero (S1–S3 linked).

Fast Running Q.. Actuators operating controls and indicators


V4. 12. 2010 . Subject to modification

61
Electrical accessories

S..A.. Auxiliary switch, add-on


S1A 1x SPDT 3A(0.5A), AC 250V
S2A 2x SPDT 3A(0.5A), AC 250V
S2A-F 2x SPDT 3A(0.5A), AC 250V

P..A.. Feedback potentiometer, add-on


P140A.. 140Ω
P500A.. 500Ω
P1000A.. 1000Ω
P2800A.. 2800Ω
P5000A.. 5000Ω
P10000A.. 10000Ω
P200A-F 200Ω
SGA24

SGE24

SGF24

ZAD24

1) For ..-SR

V4. 12. 2010 . Subject to modification

62
Mechanical accessories

NMU
SMU
NMQU
SMQU
LMQU
AN-20
Actuator arm

AH-25 Actuator arm

AH-GMA
Actuator arm

AV6-20 Shaft extension


Length approximately 170mm
For damper spindles 6...20mm
Extension 10mm

AV8-25 Shaft extension


Length approximately 250mm
For damper spindles 8...25mm
Extension 20mm

IND-AFB NFU/SFU.. position indicator

K6-1 Spindle clamp for LF...


For damper spindles 16...20mm

K7-2 NFU/SFU.. standard clamp


1/2", 3/4", 1.05"

K-ENSA Spindle clamp


For damper spindles 8...20mm

K-NA Reversible spindle clamp


For damper spindles 8...20mm

K-SA Reversible spindle clamp


For damper spindles 10...20mm

KG8 Ball joint


Suitable for damper crank arm KH8
For round steel rod with 8mm
Zinc-plated steel

KG10A Ball joint


Suitable for damper crank arm KH8
For round steel rod with 10mm
V4. 12. 2010 . Subject to modification

Zinc-plated steel

63
Mechanical accessories

NMU
SMU
NMQU
SMQU
LMQU

ZG-118 NFU/SFU.. mounting bracket

ZG-AFB NFU/SFU.. crank arm adapter kit.

ZG-AFB118 NFU/SFU.. crank arm adapter kit

ZG-GMA Mounting kit


For flat and side mounting

ZG-LF1 Damper linkage kit


For side mounting (with 2 ball joints KG8)

ZG-LF3 Damper linkage kit


For side mounting (with 2 ball joints KG8)

ZG-NMA Mounting kit


For flat and side mounting

ZG-SMA Mounting kit


For flat and side mounting

ZG-TF1 Damper linkage kit


For flat mounting

Z-AF Retrofit adapter for NG NFU/SFU.. while


replacing old NF/AF/AFR..

ZF10-NSA-F 10x10 formfit adaptor


mutipack 20pieces

ZF12-NSA-F 12x12 formfit adaptor


mutipack 20pieces

ZF16-NSA-F 16x16 formfit adaptor


mutipack 20pieces
V4. 12. 2010 . Subject to modification

64
Replacement table for Mechanical Fail-Safe Damper Actuators

Series Old models New Generation Description


NFU.. NF24 NFU Open/Close 10Nm

NF230 Open/Close 10Nm

NF24-S NFU-S2 Open/Close 10Nm, 2x SPDT auxiliary switch

NF230-S Open/Close 10Nm, 2x SPDT auxiliary switch

NF24-SR NFU24-SR Modulating 10Nm

SFU.. AF24 SFU Open/Close 20Nm

AFR24 Open/Close 20Nm

AF230 Open/Close 20Nm

AFR230 Open/Close 20Nm

AF24-S SFU-S2 Open/Close 20Nm, 2x SPDT auxiliary switch

AFR24-S Open/Close 20Nm, 2x SPDT auxiliary switch

AF230-S Open/Close 20Nm, 2x SPDT auxiliary switch

AFR230-S Open/Close 20Nm, 2x SPDT auxiliary switch

AF24-SR SFU24-SR Modulating 20Nm

AFR24-SR Modulating 20Nm


V4. 12. 2010 . Subject to modification

65
Innovation, Quality and Consultancy:
A partnership for motorising HVAC Actuators

BELIMO Automation AG BELIMO Actuators (Shanghai) Trading Ltd. BELIMO Aircontrol (USA), Inc.
Brunnenbachstrasse 1 479 Chun Dong Road, Building C-2 43 Old Ridgebury Road
8340 Hinwil, Switzerland Xin Zhuang Industry Park Danbury, CT 06813-2928, USA
Tel: +41 43 843 61 11 Shanghai 201108, P.R. China Tel: +800 543-9038 / 203 791-9915
Fax: +41 43 843 62 68 Tel: +86 21 5483 2929 Fax: +800 228-8283 / 203 791-9919
E-mail: [email protected] Fax: +86 21 5483 2930
E-mail: [email protected]

93010-00139