Belimo Actuator Catalogue
Belimo Actuator Catalogue
Technical Databook
Version
Ver. 2 4
Torque
Power Supply
AC/DC 24V 24
AC 100...240V (AC 230 for Mechanical Fail-Safe Damper Actuator) 230
General Damper Actuator
Open/Close, 3-point Blank
Open/Close (only for CMU230..) -RES
Modulating DC 2(0)...10V Control -SR
Auxiliary Switch -S
Form fit -F
Terminal Connection -T
Mechanical Fail-Safe Damper Actuator
Open/Close Blank
Modulating DC 2(0)...10V Control -SR
3-point -3
Auxiliary Switch -S, -S2
For customising types of Damper Actuators please contact your nearest Belimo sales representative.
V4. 12. 2010 . Subject to modification
2
Contents
Product overview 4
General Damper Actuator, 2Nm
CMU24(-F8/-F10)(-T) 6
CMU24-SR-R 7
CMU230(-F8/-F10) 8
CMU230(-F8/-F10)-RES 9
General Damper Actuator, 5Nm
LMU24(-S/-F/-T) 10
LMU24-SR 11
LMU230(-S/-F) 12
LMU230SR 13
General Damper Actuator, 10Nm
NMU24(-S/-F/-T) 14
NMU24-SR 15
NMU230(-S/-F) 16
NMU230SR 17
General Damper Actuator, 20Nm
SMU24(-S/-F/-T) 18
SMU24-SR 19
SMU230(-S/-F) 20
SMU230SR 21
General Damper Actuator, 40Nm
GMU24 22
GMU24-SR 23
GMU230 24
Fast Running Damper Actuator, 4Nm
LMQU24 25
LMQU24-SR 26
Fast Running Damper Actuator, 8Nm
NMQU24 27
NMQU24-SR 28
Fast Running Damper Actuator, 16Nm
SMQU24 29
SMQU24-SR 30
Mechanical Fail-Safe Damper Actuator, 2Nm
TF24(-S) 31
TF24-3 32
TF24-SR 33
TF230(-S) 34
TF230-SR 35
Note: Mechanical Fail-Safe Damper Actuator, 4Nm
LF24(-S) 36
Using Belimo Damper Actuators: LF24-3 37
• The actuators listed in this catalogue are intended for the LF24-SR 38
operation of air dampers in HVAC systems. LF230(-S) 39
• The Damper Actuator is not allowed to be used outside the
Mechanical Fail-Safe Damper Actuator, 10Nm
specified field of application, especially in aircraft.
NFU 40
• The enclosure of the actuator equipment may only be
NFU-S2 41
opened by the manufacturer. It contains no components NFU24-SR 42
which the user can replace or repair.
Mechanical Fail-Safe Damper Actuator, 20Nm
• The device contains electrical and electronic
SFU 43
components and is not allowed to be disposed of as
SFU-S2 44
household refuse. All locally valid regulations and SFU24-SR 45
requirements must be observed.
Mounting instructions 46
Wiring diagrams 56
Torque requirements:
Auxiliary switch adjustment 61
• When calculating the torque required to operate
Electrical accessories 62
dampers, it is essential to take into account all the data
Mechanical accessories 63
V4. 12. 2010 . Subject to modification
3
Damper Actuator product overview
4
Damper Actuator product overview
5
LMU230(-S/-F)
Technical data
Dimensions [mm]
LMU230(-S) LMU230-F
61
61
47
47
1620 116
116
28.5 100.5
66
5.2
66
30
22 94 41 22 94 41
12
LMU230SR
Technical data
Dimensions [mm]
61
47
116
66
V4. 12. 2010 . Subject to modification
22 116 41
13
NMU24(-S/-F/-T)
Technical data
Dimensions [mm]
60
38
124 18 124 16
124
32 102
V4. 12. 2010 . Subject to modification
80
30
5.2
80
80
25 99 41 25 99 25 99 41
14
NMU24-SR
Technical data
Dimensions [mm]
62
60
124
80
V4. 12. 2010 . Subject to modification
25 99 41
15
NMU230(-S/-F)
Technical data
Dimensions [mm]
NMU230(-S) NMU230-F
62
62
60
38
124 18 124 16
32 102
30
5.2
80
25 99 41 25 99 41
16
NMU230SR
Technical data
Dimensions [mm]
62
60
124
V4. 12. 2010 . Subject to modification
80
25 121 41
17
SMU24(-S/-F/-T)
Technical data
Dimensions [mm]
56
30 109
23 97 139 139
88
88
18
SMU24-SR
Technical data
Dimensions [mm]
64
56
139
V4. 12. 2010 . Subject to modification
88
30 109 41
19
SMU230(-S/-F)
Technical data
Dimensions [mm]
SMU230-F SMU230(-S)
64
56
30 109
139
23 97
75
88
4.2
30 109 41
8.8
20
SMU230-SR
Technical data
Dimensions [mm]
64
56
139
V4. 12. 2010 . Subject to modification
88
30 131 41
21
GMU24
Technical data
Dimensions [mm]
Standard :
179
12...22mm 12...18mm
116
22...26.7mm 12...18mm
36 143 41
22
GMU24-SR
Technical data
Dimensions [mm]
Standard :
179
12...22mm 12...18mm
116
V4. 12. 2010 . Subject to modification
23
GMU230
Technical data
Dimensions [mm]
Standard :
179
12...22mm 12...18mm
116
22...26.7mm 12...18mm
36 143 41
24
LMQU24
Technical data
Dimensions [mm]
75
52
124
V4. 12. 2010 . Subject to modification
25 121 41
25
LMQU24-SR
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 13W @ running / 1.5W @ holding
Wire sizing 23VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 4Nm @ nominal voltage
Control signal DC 2(0)...10V, input impedance 100kΩ
Feedback signal DC 2...10V, max. 0.5mA
Position accuracy +5%
Direction of rotation Reversible with switch 0/1
Direction of motion at Y = 0 V At switch position 0 resp. 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical stops
Running time 2.5s for 90°
Automatic adjustment of operating Manual triggering of the adaption by pressing the
range and measuring signal U to match «Adaption» button
the mechanical angle of rotation
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, only AC) = 50%
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Mode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 187x80x75mm
Weight Approximately 850g
Dimensions [mm]
75
52
124
V4. 12. 2010 . Subject to modification
25 121 41
26
NMQU24
Technical data
Dimensions [mm]
77
52
139
V4. 12. 2010 . Subject to modification
30 131 41
27
NMQU24-SR
Technical data
Dimensions [mm]
77
52
139
V4. 12. 2010 . Subject to modification
30 131 41
28
SMQU24
Technical data
Dimensions [mm]
83
62
179
V4. 12. 2010 . Subject to modification
12...22mm 12...18mm
116
29
SMQU24-SR
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V
Power consumption 15W @ running / 1.5W @ holding
Wire sizing 26VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 16Nm @ nominal voltage
Control signal Y DC 2(0)...10V, input impedance 100kΩ
Position feedback (Measuring voltage) DC 2...10V, max. 0.5mA
Position accuracy +5%
Direction of rotation Reversible with switch 0/1
Direction of motion at Y = 0 V At switch position 0 or 1
Manual override Gearing latch disengaged by pushbutton, self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 7s for 90°
Automatic adjustment of operating range Manual triggering of the adaption by pressing the
and measuring signal U to match the «Adaption» button
mechanical angle of rotation
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, only AC) = 50%
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage / UL Class 2 supply)
Degree of protection IP54 in any mounting position
NEMA 2, UL Enclosure Type 2
EMC CE according to 2004/108/EC
Certification cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1 (EN 60730-1)
Ambient temperature –30...+40°C (without restrictions)
! +50°C (with restrictions)
Non-operating temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x83mm
Weight Approximately 1.7kg
Dimensions [mm]
83
179
V4. 12. 2010 . Subject to modification
12...22mm 12...18mm
116
Technical data
Dimensions [mm]
17
6...12
84
61
6
104
V4. 12. 2010 . Subject to modification
77
20 84 36
31
Mechanical Fail-Safe Damper Actuator TF24-3
Technical data
Dimensions [mm]
17
6...12
84
61
6
104
V4. 12. 2010 . Subject to modification
77
20 84 36
32
Mechanical Fail-Safe Damper Actuator TF24-SR
Technical data
Dimensions [mm]
17
6...12
84
616
104
77
V4. 12. 2010 . Subject to modification
20 84 36
33
Mechanical Fail-Safe Damper Actuator TF230(-S)
Technical data
Electrical data Nominal voltage AC 100...240V 50/60Hz
Nominal supply range AC 85...265V
Power consumption 2.5W @ running / 1.5W @ holding
Wire/transformer sizing 5VA
Auxiliary switch TF230-S 1 SPDT, 1mA...3 (0.5)A, AC 250V , adjustable
Connection cable - Motor Cable 1m, 2x0.75mm2
- Auxiliary switch TF230-S Cable 1m, 3x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage
- Spring return 2Nm
Direction of rotation - Motor Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor 75s
- Spring return 25s @ -20...50°C/max. 60s @ -30°C
Sound power level Motor max. 50dB(A), Spring approximately 62dB(A)
Position indication Mechanical
Service life > 60,000 full cycles
Working conditions Protection class II (totally insulated)
Degree of protection IP42 in any direction
EMC CE according to 89/336/EEC
Low voltage directive CE according to 73/23/EEC
Mode of operation Type 1. AA to EN 60730-1
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mm
Shaft length Clamp up Min. 84mm
Clamp down Min. 20mm
Shaft diameter 6...12mm
Weight Approximately 600g
Dimensions [mm]
17
6...12
84
61
6
104
V4. 12. 2010 . Subject to modification
77
20 84 36
34
Mechanical Fail-Safe Damper Actuator TF230-SR
Technical data
Dimensions [mm]
17
84
6...12
61 6
104
V4. 12. 2010 . Subject to modification
77
20 84 36
35
Mechanical Fail-Safe Damper Actuator LF24(-S)
Technical data
Dimensions [mm]
18.5
82
8...16
57
6.5
181
155
25 12.6
6.5
.8
.6
.4
1
.2
0
49
18 93
125
36
Mechanical Fail-Safe Damper Actuator LF230(-S)
Technical data
Dimensions [mm]
18.5
82
57
8...16
6.5
181
155
25 12.6
6.5
V4. 12. 2010 . Subject to modification
.8
.6
.4
1
.2
0
80
98
18 93
125
39
Mechanical Fail-Safe Damper Actuator NFU
•ΓTorque: 10Nm
•ΓNominal voltage: AC 24...240V/DC 24...125V
•ΓControl: Open/Close
Technical data
Dimensions [mm]
20
Standard :
¾”- clamp (with insert)
85
59
Optional 1:
1”- clamp (without insert)
2-FRONT
Optional 2:
½” - clamp (optional via configuration)
Damper shaft Length
≥85 10...19 14...20
≥15 10...19 14...20 32
162
172
182
236
40
Mechanical Fail-Safe Damper Actuator NFU-S2
•ΓTorque: 10Nm
•ΓNominal voltage: AC 24...240V/DC 24...125V
•ΓControl: Open/Close
•Γ2x SPDT auxiliary switches built-in
Technical data
Dimensions [mm]
20
Standard :
85
59
Optional 1:
2-F
Optional 2:
½”- clamp (optional via configuration) 32 27
162
Damper shaft Length 172
≥85 10...19 14...20 182
•ΓTorque: 10Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: modulating DC 2(0)...10V
position feedback DC 2...10V
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption in operation 3.5W @ running/2.5W @ holding
For wire sizing 6.0VA
Connection Cable 1m, 4x0.75mm2
Functional data Torque - Motor Min. 10Nm @ nominal voltage
- Spring return Min. 10Nm
Control Control signal Y DC 0...10V, typical input impedance 100KΩ
Working range DC 2...10V
Position feedback (Measuring voltage) DC 2...10V, max. 1mA
Position accuracy ±5%
Direction of rotation - Motor Reversible with switch or
- Spring return Selectable by mounting L/R
Direction of rotation at Y=0V At switch position resp. 1
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor 150s/90°
- Spring return < 20s @ -20...50°C/max. 60s @ -30°C
Sound power level - Motor Max. 40dB(A)
- Spring return ~62dB(A)
Working conditions Position indication Mechanical
Protection class III (safety extra-low voltage)
Degree of protection IP54
EMC CE according to 2004/108/EC
Control pollution degree 3
Rated Impulse Voltage 800V
Mode of operation Type 1.AA
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 236x98x58mm
Weight Approximately 2000g
Dimensions [mm]
20
Standard :
¾”- clamp (with insert)
85
59
Optional 1:
1”- clamp (without insert)
2-FRONT
Optional 2:
½” - clamp (optional via configuration)
Damper shaft Length
≥85 10...19 14...20 32
≥15 10...19 14...20 162
172
182
42 236
Mechanical Fail-Safe Damper Actuator SFU
•ΓTorque: 20Nm
•ΓNominal voltage: AC 24...240V
DC 24...125V
•ΓControl: Open/Close
Technical data
Dimensions [mm]
20
85
59
Standard :
¾”- clamp (with insert)
Damper shaft Length
≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4
2-FRONT
Optional 1:
V4. 12. 2010 . Subject to modification
Optional 2:
½”- clamp (optional via configuration)
32
Damper shaft Length
162
≥85 10...19 14...20 172
≥15 10...19 14...20 182
236
43
Mechanical Fail-Safe Damper Actuator SFU-S2
•ΓTorque: 20Nm
•ΓNominal voltage: AC 24...240V
DC 24...125V
•ΓControl: Open/Close
•Γ2x SPDT auxiliary switches built-in
Technical data
Dimensions [mm]
20
Standard :
¾”- clamp (with insert)
85
Optional 1:
R
F
2
Optional 2:
½”- clamp (optional via configuration)
Damper shaft Length 32 27
14...20 162
≥85 10...19
172
≥15 10...19 14...20 182
236
44
Mechanical Fail-Safe Damper Actuator SFU24-SR
•ΓTorque: 20Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl Modulating: DC 2(0)...10V
•ΓPosition feedback: DC 2...10V
Technical data
Dimensions [mm]
20
85
59
Standard :
¾”- clamp (with insert)
Damper shaft Length
≥85 10...22 10 14...25.4
≥15 10...22 10 14...25.4
2-FRONT
Optional 1:
1”- clamp (without insert)
V4. 12. 2010 . Subject to modification
Optional 2:
½” - clamp (optional via configuration)
32
Damper shaft Length
162
≥85 10...19 14...20 172
≥15 10...19 14...20 182
236
45
CMU.. mounting instructions
1 2 3
>32 2.5°
m m 90°
75 60 45
90 30
5
10
6...12.7mm
15
12
2.5°
15
12
5 30
10 45
0
75 9 60
70 ± 20mm 1
2 90
75
60 45 3
0
5
10
0
12
60 45 30
75
90
5
10
0
12
5
10
0
90
12
60 45 3
75 0
90
3.1...3.2mm
5
10
0
12
0
5
10
12
90
1 2 12
0
5
90
10
8
60 45 3
75 0
90
60 45 3
5
10
75 0
0
12
90
5
10
0
12
6Nm 12
0
90 1
05
!
0
12
05
90 1
75 60 45
120° 60°
90 30
5
10
0
15
12
75
90
5
10
0
15
12
5 30
12
10
60
45
75
0
75 9 60
90 45
5 30
10
0
15
12
5 30
10 45
75 90 60
15
75 60 45
90 30
5
10
0
15
12
60 45 3
75 0
90
0
15
12
60 45 3
5
75 0
10
5 30
10
90 45
0
0
75 9
12
60
5
10
0
12
0
12
05
90 1
0
ma
CMU24-SR.. x
.9
5°
75 60 45
90
5 30
10
0
15
12 0
15
12
5 30
10 45
0
75 9 60
A
V4. 12. 2010 . Subject to modification
24V
0
46
LMU../LMS.. mounting instructions
1 2
> 37
3 4
6 Nm
10
1
1m m
2 1
Z-PI
65°
V4. 12. 2010 . Subject to modification
47
NMU../NMS.. mounting instructions
1 2
40
8...26
10...26
3 4
9Nm
10
10
1
1mm
Z-PI
65°
V4. 12. 2010 . Subject to modification
48
SMU../SMS.. mounting instructions
1 2
48
10...20
10...20
3 4 9Nm
10
10
1 1 mm
Z-PI
65°
V4. 12. 2010 . Subject to modification
49
GMU../GMS.. mounting instructions
1 2
>52
2
12...22 mm 12...18 mm
4
2
13
22...26.7 mm 12...18 mm
1
3 15Nm
1m m
1 1
2
2 1
2
>20 1
Z-PI 4
5
2
V4. 12. 2010 . Subject to modification
65° 3
50
LMQU24../NMQU24.. mounting instructions
1 2
>52
2
12...22mm 12...18mm
4
2
13
22...26.7mm 12...18mm
1
3 15Nm
1m m
1 1
2
2 1
2
>20 1
Z-PI 4
V4. 12. 2010 . Subject to modification
5
2
65° 3
51
SMQU24.. mounting instructions
1 2
>52
2
12...22mm 12...18mm
4
2
13
22...26.7mm 12...18mm
1
3 15Nm
1m m
1 1
2
2 1
2
>20 1
Z-PI 4
5
2
V4. 12. 2010 . Subject to modification
65° 3
52
TF.. mounting instructions
1 2
L
L
min
. 84
6...12.7
3 4
R
37...100%
R
ZG-TF1
Subject to technical changes.
max 1 Nm
53
TF../LF.. mounting instructions
1 2
ZDB-TF
min
. 20
6...12.7
3 4
37...100%
R
ZDB-TF
54
NFU../SFU.. mounting instructions
A B
21...26 21...26
13
10 Nm
33...100%
.2
.4
.9
.6
.8
.8
.7
.6
.5
.4
.3
.2 .1
V4. 12. 2010 . Subject to modification
55
Wiring diagrams — General Damper Actuator
Notes:
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.
1 2 3 1 2 3
CMU24(-T) CMU24(-T)
CMU24-F8(-F10) CMU24-F8(-F10)
Modulating
~ Connection via safety
T AC/DC 24V ! isolated transformer
- +
Y DC 2(0)…10V
U DC 2…1V
1 2 3 5
BK RD WH OG
T ~
Y U
- + CMU24-SR-R
N L AC 100...240V N L AC 100...240V
1 2 3 1 2 3
CMU230 CMU230
CMU230-F8(-F10) CMU230-F8(-F10)
Open/Close control
Connection via safety
N
! isolated transformer
L AC 230V
V4. 12. 2010 . Subject to modification
1 2 3
CMU230-RES
CMU230-F8 (-F10)-RES
56
Wiring diagrams—General Damper Actuator
Wiring diagrams: Open/Close actuators—Parallel connection possible, please note the performance data
1 1 1 1
S1 S2 S3 S1 S2 S3 S1 S2 S3 S1 S2 S3
1 2 3 S1 S2 S3 1 2 3 S1 S2 S3
0 0 0 0
N L1 AC 100...240V N L1 AC 100...240V
Wiring diagram: Modulating actuators—Parallel connection possible, please note the performance data
T ~ anti-clockwise clockwise-
Y U LMU24-SR, NMU24-SR SMU24-SR, GMU24-SR -closing closing
- +
LMQU24-SR, NMQU24-SR, SMQU24-SR 0 Y
damper damper
0 2 5 10 [ V ]
N L1 AC 100...240V 0
Direction of rotation
AC 24V power output 1
Y DC 2(0)…10V
V4. 12. 2010 . Subject to modification
U DC 2…10V
Measuring voltage U
for position indicating
1 2 1 2 3 5 or as master-slave
control signal.
T ~
Y U LMU230SR, NMU230SR
SMU230SR
57
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
Notes:
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.
1 2 S1 S2 S3
1 2 S1 S2 S3
<x
M x = 0...100% TF230-S, TF24-S M
<x
x = 0...100% LF230-S, LF24-S
>x
>x
N L1 AC 24...240V
DC 24...125V
1 2 S1 S2 S3 S4 S5 S6
M NFU, SFU
V4. 12. 2010 . Subject to modification
58
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
Notes:
•ΓConnection via safety isolating transformer.
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.
Mounting side
~ Connect via safety
T
AC 24V ! isolating transformer .8
1 1
.8
.6 .6
.4 .4
.2 .2
0 0
L R
Reversing switch
a b
a b (Y 1 ) (Y 2 )
Y1 Y 2 TF24-3
Mounting side
Reversing switch
a b
(Y 1 ) (Y 2 ) R L R L
T ~
LF24-3, NFS24-3, SF24-3
V4. 12. 2010 . Subject to modification
59
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
Notes:
•ΓConnection via safety isolating transformer.
•ΓParallel connection of several actuators is possible.
•ΓPower consumption must be observed.
Mounting side
T ~ AC/DC 24V Connect via safety
! isolating transformer 1 1
– + .8 .8
.6 .6
Y DC 2(0)...10V .4 .4
.2 .2
0 0
L R
U DC 2...10V
Reversing switch
R L R L
with with with with
Y=0 Y=0 Y=0 Y=0
Mounting side
T ~ Connect via safety
AC/DC 24V !
– + isolating transformer 1 1
.8 .8
.6 .6
Y DC 2(0)…1V .4
.2 .2
.4
0 0
U DC 2…10V L R
Reversing switch
1 2 3 5
Y DC 2(0)…10V
U DC 2…10V
/ 5
Reversing switch
1 2 1 3 5
60
Auxiliary switch adjustment
Procedure 1
Turn the knob of the auxiliary switch until the
tip of the arrow is pointing to the required .8 1
.8
switching position (see right). Example: .6
Switching point setting = 4 corresponds to .4
.6
40% angle of rotation. .2
0
.4
When the actuator runs to the operating S2 S2
.2 S1 S1
position (ccw ), the switch knob will also
rotate counter-clockwise (ccw ) and the 0 S3 S3
auxiliary switch will operate as the tip of the R
arrow passes the scale zero (S1–S3 linked).
61
Electrical accessories
SGE24
SGF24
ZAD24
1) For ..-SR
62
Mechanical accessories
NMU
SMU
NMQU
SMQU
LMQU
AN-20
Actuator arm
AH-GMA
Actuator arm
Zinc-plated steel
63
Mechanical accessories
NMU
SMU
NMQU
SMQU
LMQU
64
Replacement table for Mechanical Fail-Safe Damper Actuators
65
Innovation, Quality and Consultancy:
A partnership for motorising HVAC Actuators
BELIMO Automation AG BELIMO Actuators (Shanghai) Trading Ltd. BELIMO Aircontrol (USA), Inc.
Brunnenbachstrasse 1 479 Chun Dong Road, Building C-2 43 Old Ridgebury Road
8340 Hinwil, Switzerland Xin Zhuang Industry Park Danbury, CT 06813-2928, USA
Tel: +41 43 843 61 11 Shanghai 201108, P.R. China Tel: +800 543-9038 / 203 791-9915
Fax: +41 43 843 62 68 Tel: +86 21 5483 2929 Fax: +800 228-8283 / 203 791-9919
E-mail: [email protected] Fax: +86 21 5483 2930
E-mail: [email protected]
93010-00139