Data sheet 6ES7132-6BH01-0BA0

SIMATIC ET 200SP, Digital output module, DQ 16x 24V DC/0,5A


Standard, Source output (PNP,P-switching) Packing unit: 1 piece, fits to
BU-type A0, Colour Code CC00, substitute value output, module
diagnostics for: short-circuit to L+ and ground, wire break, supply voltage

General information
Product type designation DQ 16x24VDC/0.5A ST
HW functional status From FS03
Firmware version V0.0
● FW update possible No
usable BaseUnits BU type A0
Color code for module-specific color identification plate CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from V14
version
● STEP 7 configurable/integrated from version V5.5 SP3
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 60 mA; without load
Output voltage
Rated value (DC) 24 V
Power loss
Power loss, typ. 1W
Address area
Address space per module
● Address space per module, max. 2 byte; + 2 bytes for QI information

6ES71326BH010BA0 Subject to change without notice


8.9.2021
Page 1/3 © Copyright Siemens
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 + Potential distributor module
● 3-wire connection BU type A0 + Potential distributor module
● 4-wire connection BU type A0 + Potential distributor module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection Yes
● Response threshold, typ. 1 A; 0.7 to 1.3 A
Open-circuit detection Yes
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output current
● for signal "1" rated value 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", typ. 50 µs
● "1" to "0", typ. 100 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 2 Hz
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A
● Current per module, max. 8A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8A
— up to 50 °C, max. 6A
— up to 60 °C, max. 4A
vertical installation
— up to 30 °C, max. 8A
— up to 40 °C, max. 6A
— up to 50 °C, max. 4A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms

6ES71326BH010BA0 Subject to change without notice


8.9.2021
Page 2/3 © Copyright Siemens
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; Module-wise
● Short-circuit to M Yes; Module-wise
● Short-circuit to L+ Yes; Module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Suitable for safety-related tripping of standard modules Yes
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1 PL d
● SIL acc. to IEC 61508 SIL 2
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; < 0 °C as of FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; < 0 °C as of FS03
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 30 g

last modified: 2/6/2021

6ES71326BH010BA0 Subject to change without notice


8.9.2021
Page 3/3 © Copyright Siemens