Chapter 4
Chapter 4
4.4 SUMMARY............................................................................................................................................................ 18
NOMENCLATURE ....................................................................................................................................................... 20
REFERENCES .............................................................................................................................................................. 21
4-i
Chapter 4: The Grand Composite Curve
4-1
4.1 Introduction
After identifying the pinch temperature and the minimum heating- and cooling-utility
duties, the next question is how to select appropriate utilities. For this, we construct the grand
composite curve (Section 4.2) and place (or target) utilities according to it (Section 4.3).
Essentially, the grand composite curve displays the net heat-flow characteristics of a process
versus its temperature. This allows us to quickly identify regions where heating and cooling
utilities are required. These utilities include heating utilities like high- and low-pressure steam.
4-2
4.2 Grand Composite Curve
The grand composite curve is a graphical representation of the excess heat available to a
process within each temperature interval. In intervals where a net heat surplus exists, we cascade
that heat to lower temperature intervals. Once we have satisfied the demand for heat at lower
temperature intervals, we apply cooling utilities to remove the remaining heat. In intervals where
a net deficit of heat exists, we first use the excess heat from higher temperature intervals. Only
after exhausting heat surpluses from higher temperature intervals, do we apply heating utilities.
In this section, we return to Example 2.1 and investigate the flow of heat cascading down
the temperature intervals. Tables 4.1 and 4.2 repeat the shifted stream data (∆Tmin = 20 °C) and
the temperature-interval diagram (TID) for Example 2.1 first seen in Tables 2.2 and 2.9,
respectively.
4-3
Table 4.1. Shifted stream data for Example 2.1. Temperatures shifted for a
H1 175 45 20 2600
H2 125 65 40 2400
C1 60 195 30 4050
C2 80 152 15 1080
Figure 2.1 illustrates the temperature intervals of Example 2.1. This figure shows the net
heat deficits (i.e., a negative heat surplus) in temperature intervals 2, 5, 6 and 7. In contrast,
intervals 1, 3, and 4 exhibit net heat surpluses, which are found in the “Net Heat Surplus”
column of Table 4.2. Beginning with the highest temperature interval (T* 8 = 195 °C to T* 7 = 175
°C), we see a heat deficit. Because no net heat surplus exists in higher temperature intervals, we
apply heating utilities (600 kW) to satisfy the net heat deficit within the interval. We see similar
net heat deficits in the next two lower temperature interval (T* 7 = 175 °C to T* 6 = 152 °C, and
T* 6 = 152 °C to T* 5 = 125 °C). Intervals 6 and 5 require heating utilities of 230 and 675 kW,
respectively.
4-4
Table 4.2. TID for Example 2.1.
4-5
T*8 = 195 ° C
Interval 7
- 600 kW Heat 600 kW
T*7 = 175 ° C
Interval 6
- 230 kW Heat 230 kW
T*6 = 152 ° C
Interval 5
- 675 kW Heat 675 kW
Interval 4
675 kW
T*4 = 80 ° C
Interval 3
450 kW
T*3 = 65 ° C
Interval 2
- 50 kW
T*2 = 60 ° C
Interval 1
300 kW Heat 1375 kW
T*1 = 45 ° C
Figure 4.1. Cascaded heat for the temperature intervals of Example 2.1. Temperatures
shifted for a minimum approach temperature of 20 ° C.
4-6
Interval 4 (T* 5 = 125 °C to T* 4 = 80 °C) shows the first net surplus of heat (675 kW). In
the long run, we cannot determine if this heat will satisfy heat deficits at lower temperature
intervals or if cooling utilities will be needed to remove it. For now, we reserve this heat for
lower temperature intervals. Continuing down through the temperature intervals, we accumulate
net heat surpluses and apply them in intervals that exhibit net heat deficits.
Figure 4.1 shows that the net heat deficit within temperature interval 2 (T* 3 = 65 °C to T* 2
= 60 °C) consumes 50 kW of the net surplus of interval 3. The remaining 1375 kW of heat from
diagram (TID) to quickly generate the grand composite curve. Here, we repeat the procedure for
generating the data contained in the last two columns of the TID to justify the steps presented in
Section 2.5.3.2. Refer to Table 4.2 for the net heat surplus available within each temperature
interval.
Cascade the net heat surplus starting with zero at the highest temperature-interval
boundary (bottom) in the “Cascaded Surplus” column. This reflects the flow of excess heat from
4-7
Place the negative of the minimum (most negative) value from the cascaded heat surplus
column at the bottom temperature-interval boundary in the final column of the TID. Once again,
cascade the net heat surplus starting with that value at the highest temperature-interval boundary
(bottom right). We locate the pinch temperature(s) at the temperatures where zeros are found in
this column, and find the minimum cooling and heating duties at the top (1375 kW) and bottom
Figure 4.2 is constructed by plotting the first versus last columns of the TID in Table 4.2.
In the figure, pinch-point temperature(s) are identified where the curve touches the y-axis (i.e., a
value of zero in the last column of Table 4.2). The regions labeled with heating and cooling
utilities require external utilities. Recall that the first and last row of the “Adjusted Surplus”
column in a TID give the minimum cooling- and heating-utility requirements of the process.
The slope of the curve in each region reflects how the process acts. Where the curve has a
positive slope, the process is acting as a net heat sink. Conversely, a negative slope suggests that
sufficient (i.e., where a net heat deficit is satisfied by cascaded heat from higher temperature
intervals). Note that process-to-process heat transfer is not limited to these pockets. They simply
reflect where process-to-process heat transfer occurs between streams in different temperature
intervals.
4-8
225
Minimum Heating-Utility Duty,
1505 kW
200
Positive Slope:
175 Process Acts as a Net Heat Sink
150
Pinch Temperature,
Shifted Temperature (°C)
*
T 5 = 125 °C
125
"Pocket": Self-Sufficient Process-to-Process
Heat Transfer
100
75
Negative Slope:
Process Acts as a Net Heat Source
50
0
0 250 500 750 1000 1250 1500 1750
Enthalpy (kW)
Figure 4.2. Grand composite curve for Example 2.1.
4-9
4.3 Utility Placement: Grand Composite Curve
A key question in chemical process design and retrofit is how to optimally place
(integrate) utility systems (e.g., a steam boiler) into a process flowsheet. To answer this question,
we model the heating and cooling requirements of the process through the hot and cold
composite curves and the grand composite curve. The remaining task is to develop models for
those heating and cooling utilities and to place them with respect to the grand composite curve.
In general, we can categorize most heating and cooling utilities as either constant-
temperature (e.g., condensing steam) or variable-temperature (e.g., cooling water) utilities. The
representation of these two types of utilities on the grand composite curve is simple.
Figure 4.3 is the grand composite curve for Example 2.1. Horizontal lines represent
(condensing at a shifted temperature of 210 °C) on the hot side of the grand composite curve. In
this case, the entire heating needs of the process are satisfied by high-pressure steam. Latter, we
shall see that it is often more thermodynamically efficient to satisfy the heating-utility
requirements by multiple levels of heating utilities (i.e., high- and low-pressure steams).
4-10
225
High-Pressure Steam Duty,
1505 kW
200
175
150
Pinch Temperature
Shifted Temperature (°C)
*
T 5 = 125 °C
125
75
50
25
Cooling-Water Duty,
1375 kW
0
0 250 500 750 1000 1250 1500 1750
Enthalpy (kW)
Figure 4.3. Grand composite curve for Example 2.1 with heating and cooling utilities.
4-11
Sloped lines represent variable-temperature utilities on the grand composite curve. On the
cold side of Figure 4.3, a sloped line represents cooling water. We draw this line from the shifted
40 °C. The slope of the line is inversely proportional to the capacity flowrate of cooling water:
Q (kW )
[M& C ] kW
= target CW supply
[ ] (4.1)
°C TCW − TCW (°C )
p CW
where QCW is the cooling-water duty, and Ttarget CW and Tsupply CW are the cooling-water supply and
target temperatures, respectively. Equation 4.2 gives the mass flowrate of cooling water:
⋅
kg QCW (kW )
M CW = (4.2)
s
[
kJ target
C p,CW TCW − TCW
supply
](°C)
kg
Note that the cooling utility does not lie within the pocket region of the grand composite
curve. Heat transfer in these regions is accomplished through process-to-process heat exchange.
In this section, we apply the grand composite curve to answer questions like:
• When multiple steam levels are available, how do we optimize their use in a process?
4-12
• Can the process generate very-low pressure steam? How can the process be applied as
Figure 4.4 illustrates a grand composite curve as an example of utility selection according
to the following “profile matching” heuristic. We choose the utility levels such that their
placement matches the grand composite curve as closely as possible. We prefer to use heating
utilities at the lowest temperature levels, and cooling utilities at the highest temperature levels. In
the figure, steam is available at three levels: 180, 200 and 230 °C (shifted temperatures). First,
Figure 4.4a ignores our heuristic and accomplishes the total heating requirements of the process
with very-high-pressure steam. This arrangement is certainly the least complex method for
heating the process, however, we may wish to reduce operating costs (i.e., use less expensive
high-pressure and low-pressure steam where applicable) at the expense of greater capital costs
(i.e., an increase in complexity). Figure 4.4b illustrates the case where both very-high-pressure
(VHP) and high-pressure (HP) steam are employed. Finally, in Figure 4.4c, we follow our
heuristic by utilizing the greatest amount of steam at the lowest temperature available, 180 °C.
Note that the hashed region represents self-sufficient process-to-process heat exchange, and does
not require steam. Continuing up the grand composite curve, we apply steam at 200 °C and
4-13
VHP Steam VHP Steam
HP Steam
Temperature (°C)
Temperature ( °C)
Pinch Pinch
VHP Steam
HP Steam
LP Steam
Temperature ( °C)
Pinch
Enthalpy (kW)
(c)
Figure 4.4. Grand composite curves with three degrees of profile matching. Operating costs
decrease and capital costs increase from (a) to (c).
4-14
4.3.2.2 Raising Steam from Boiler Feedwater
In contrast to the previous section, we raise steam from boiler feedwater at the highest
possible temperature. Figure 4.5 illustrates the same grand composite curve.
We may utilize the surplus heat of the process to raise low-pressure steam from boiler
feedwater. Figure 4.5 displays two line segments. The first segment (sloped) represents the
sensible heat used for preheating the boiler feedwater. The capacity flowrate of the boiler
feedwater is related to the inverse of the slope of this segment through Equation 4.3.
Q (kW )
[M& C ] kW
= target BF supply
[ ] (4.3)
°C TBF − TBF (°C )
p BF
where QBF is the heat absorbed as sensible heating of the boiler feedwater, and Ttarget BF
and Tsupply BF are the target and supply temperatures of the boiler feedwater, respectively. The
⋅
mass flowrate of the boiler feedwater consumed or the steam produced is, M BF :
⋅
kg ⋅ kg Q BF (kW )
M BF = M LP = (4.4)
s s
[
kJ target
C p,BF TBF − TBF ]
supply
(°C)
kg
4-15
HP Steam
Temperature (°C)
Pinch
TtargetBF
Ts upplyBF
LP Steam Duty,
QL P Boiler-Feedwater Duty,
Q BF
Cooling Water
Enthalpy (kW)
Figure 4.5. Grand composite curves where two qualities of very-low-pressure steam
are generated.
4-16
where Cp,BF is the heat capacity of the boiler feedwater. The second segment (horizontal)
corresponds to the latent heat of vaporization of the boiler feedwater. We relate the length of this
segment to the flowrate of the boiler feedwater consumed or the steam produced) through
Equation 4.5:
where ∆HvapBF is the latent heat of vaporization of boiler feedwater at the temperature and
pressure we are generating steam. In this case, the remaining surplus heat of the process is
4-17
4.4 Summary
• To select appropriate utilities, we construct the grand composite curve (Section 4.2) and
place (or target) utilities according to it (Section 4.3). Utilities include heating utilities like
high- and low-pressure steams and cooling utilities such as cooling water and refrigeration.
• The grand composite curve displays the net heat-flow characteristics of a process versus its
temperature. This allows us to quickly identify regions where heating and cooling utilities are
required.
• We construct the grand composite curve by plotting the first versus last columns of the
where the curve touches the y-axis (i.e., a value of zero in the last column of the TID).
• Utilities do not lie within the pocket regions of the grand composite curve. Heat transfer in
utilities.
4-18
• Generally, we use heating and cooling utilities at the lowest and highest temperature levels
possible, respectively.
4-19
Nomenclature
4-20
References
Linnhoff, B., Townsend, D. W., Boland, D., et al., "A User Guide to Process Integration for the
Shenoy, U. V., Heat Exchanger Network Synthesis: Process Optimization by Energy and
4-21