Electromagnetic Flowmeter: Watermaster
Electromagnetic Flowmeter: Watermaster
WaterMaster
Electromagnetic flowmeter
2 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Octagonal bore
DS/WM–EN Rev. H 3
WaterMaster
Electromagnetic flowmeter
Transmitter display
4 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
DS/WM–EN Rev. H 5
WaterMaster
Electromagnetic flowmeter
6 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
DS/WM–EN Rev. H 7
WaterMaster
Electromagnetic flowmeter
8 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
4 DN100
3 WaterMaster Class 1
Specification
Flowrate (m3/h)
6 DN100
WaterMaster Class 2
Specification
4
Typical Meter
Performance
Error (%)
2
4
OIML R49 Class 2
Accuracy Limits
Q1 Q2 Q 0.4 % Q3 Q4
6 Q3
0.1 1.0 10.0 100.0 1,000.0
Flowrate (m3/h)
Although OIML R49 does not define the flow accuracy below Q1, WaterMaster continues to measure flow at lower flow rates down to
a cutoff velocity of ±5 mm/s (±0.2 in/s). The accuracy between cutoff and Q1 is typically ±0.9 mm/s (±0.04. in/s).
DS/WM–EN Rev. H 9
WaterMaster
Electromagnetic flowmeter
Note. OIML R49–1 allow Class 1 only for meters with Q3 ≥ 100 m3/h. Meters outside this range have been tested and conform
to Class 1.
10 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
DS/WM–EN Rev. H 11
WaterMaster
Electromagnetic flowmeter
Housing material
Carbon steel (sizes DN40 to 200 [11/2 to 8 NB]
and DN700 to 2200 [28 to 84 NB])
Plastic (sizes DN250 to 600 [10 to 24 NB])
Aluminium (FEW, sizes DN10 to DN32 [3/8 to 11/4 NB])
(FEW, sizes DN350 to DN400 [14 to 16 NB])
Carbon steel (FEW, sizes DN450 to DN600 [18 to 24 NB])
12 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
DS/WM–EN Rev. H 13
WaterMaster
Electromagnetic flowmeter
Sensor dimensions
A B
Max. Max.
14 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
A Max. B Max.
A Max. B Max.
DS/WM–EN Rev. H 15
WaterMaster
Electromagnetic flowmeter
A B
Max. Max.
A B
Max. Max.
DN450 to DN600
16 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Transmitter dimensions
Integral transmitter
Dimensions in mm (in)
200 (7.9 )
118 (4.6)
Remote transmitter
Dimensions in mm (in)
98 (3.8) R3.2 (0.12)
205 (8.0)
179 (7.0)
71 (2.8)
DS/WM–EN Rev. H 17
WaterMaster
Electromagnetic flowmeter
Electrical connections
Fuse F1 (AC)
N/L2
L/L1
Internal Earth Screws –
can be used as a
Protective Earth (PE) if
L/L1 N/L2 PE required by national
standards
OR
AC or DC power via a
suitable isolator and fuse
18 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Ordering information
Electromagnetic flowmeter WaterMaster FEF12 and FEF18
Variant digit number 1…5 6 7 … 9 10 11 12 13 14, 15 16 17 18 19 20 21 22 23 24 25 26 27
Options
Flowmeter system, full bore,
FEF12
remote mount
XXX X X X X XX X X X X X X X X X X X X
Full bore sensor only, for use with
FEF18
WaterMaster transmitter / remote
Design
Non-hazardous areas 1
Hazardous areas (DN≥700) 5
Bore diameter
DN250 (10 in) 250
DN300 (12 in) 300
DN350 (14 in) 350
DN375 (15 in) 375
DN400 (16 in) 400
DN450 (18 in) 450
DN500 (20 in) 500
DN600 (24 in) 600
DN700 (28 in) 700
30 in 760
DN800 (32 in) 800
DN900 (36 in) 900
DN1000 (40 in) 001
42 in 051
DN1200 (48 in) 201
DN1400 (54 in) 401
60 in 501
DN1600 (66 in) 601
DN1800 (72 in) 801
DN2000 (78 in) 002
DN2200 (84 in) 202
Others 999
Liner material
Elastomer K
FEP B
Neoprene C
Linatex J
Polyurethane U
Electrode design
Standard 1
Others 9
Measuring electrodes material
Stainless steel 316 S
Hastelloy® C-22 C
Others Z
Grounding accessories
Standard 1
One potential equalizing ring (stainless steel) 3
Two potential equalizing rings (stainless steel) 4
Others 9
Continued on page 20
DS/WM–EN Rev. H 19
WaterMaster
Electromagnetic flowmeter
Options
Flowmeter system, full bore,
FEF12
remote mount
XXX X X X X XX X X X X X X X X X X X X
Full bore sensor only, for use with
FEF18
WaterMaster transmitter / remote
Process connection type
Flanges ASME B16.5 class 150 A1
Flanges ASME B16.5 class 300 A3
Flanges AWWA C207 class B C1
Flanges AWWA C207 class D C2
Flanges AS 4087 PN21 E0
Flanges AS 4087 PN16 E1
Flanges AS 4087 PN14 E2
Flanges AS 2129 Table F E3
Flanges AS 2129 Table E E4
Flanges AS 2129 Table D E5
Flanges AS 2129 Table C E6
Flanges JIS 10K J1
Flanges JIS 5K J2
Flanges ISO / EN PN6 S0
Flanges ISO / EN PN10 S1
Flanges ISO / EN PN16 S2
Flanges ISO / EN PN25 S3
Flanges ISO / EN PN40 S4
Others Z9
Process connection material
Carbon steel flanges B
Others Z
Usage certifications
Standard 1
Calibration type
Class 2 Calibration – standard accuracy 0.4 % A
Class 1 Calibration – enhanced accuracy 0.2 % B
Class 2 Calibration – standard accuracy 0.4 % with VeriMaster D
Class 1 Calibration – enhanced accuracy 0.2 % with VeriMaster H
Temperature range installation / ambient temperature range
Standard design / –20 … 60 °C (–4 … 140 °F) 1
Nameplate
Adhesive A
Continued on page 21
20 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Options
Flowmeter system, full bore,
FEF12
remote mount
XXX X X X X XX X X X X X X X X X X X X
Full bore sensor only, for use with
FEF18
WaterMaster transmitter / remote
Signal cable length and type*
Without signal cable 0
5 m (15 ft.) cable 1
10 m (30 ft.) cable 2
20 m (60 ft.) cable 3
30 m (100 ft.) cable 4
50 m (165 ft.) cable 5
80 m (260 ft.) cable 6
100 m (325 ft.) cable 7
150 m (490 ft.) cable 8
Special Length > 150 m (> 490 ft.) (and / or armored cable) 9
Explosion protection certification
General purpose (non-Ex design) A
FM Class 1 Div. 2 (DN≥600, DN≤1600) G
FMc Class 1 Div. 2 (DN≥600, DN≤1600) P
Others Z
Protection class transmitter / protection class sensor
IP67 (NEMA 4X) / IP68 (NEMA 6P) – cable not fitted and not potted 2
IP67 (NEMA 4X) / IP68 (NEMA 6P) – cable fitted and potted 3
Cable conduits *
M20 x 1.5 A
NPT 1/2 in B
M20 SWA armored D
M20 SWA sensor, output and power connector F
Power supply
Without (FEF18 only) 0
100... 230 V AC (50 Hz) 1
24 V AC or 24 V DC (50 Hz) 2
100... 230 V AC (60 Hz) 3
24 V AC or 24 V DC (60 Hz) 4
Input and output signal type
HART + 20 mA + pulse + contact output (FEF12 only) A
PROFIBUS DP RS485 physical layer + pulse + contact output (FEF121 only) G
Without (FEF181 only) Y
Configuration type / diagnostics type
Without (FEF18 only) 0
Factory defaults / standard diagnostics (FEF12 only) 1
Options**
Documentation language
German M1 English M5 (default)
Italian M2 Portuguese MA
Spanish M3 Russian MB
French M4 Danish MF
Power supply frequency (sensor FEF 18 only)
50 Hz F5 60 Hz F6
* The type of signal cable supplied (standard or armored) depends on the type of cable conduit (variant digit number 24) ordered.
For FM or FMC Approved versions, NPT only permitted.
**Add codes for options.
DS/WM–EN Rev. H 21
WaterMaster
Electromagnetic flowmeter
Options
Variant digit number 1…5 6 7 … 9 10 11 12 13 14, 15 16 17 18 19 20 21 22 23 24 25 26 27
Continued on page 23
22 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Options
Variant digit number 1…5 6 7 … 9 10 11 12 13 14, 15 16 17 18 19 20 21 22 23 24 25 26 27
* The type of signal cable supplied (standard or armored) depends on the type of cable conduit (variant digit number 24) ordered.
For FM or FMC Approved versions, NPT only permitted.
**Add codes for options.
DS/WM–EN Rev. H 23
WaterMaster
Electromagnetic flowmeter
Options
Transmitter cartridge FET10
X X X X X X X X X
Remote transmitter FET12
Design
Non-hazardous area 1
Hazardous area 5
Temperature range installation / ambient temperature range
Standard design / –20 … 60 °C (–4 … 140 °F) 1
Nameplate
Adhesive A
Signal cable length and type
Without signal cable 0
Explosion protection certification
Without (transmitter only) Y
FM Class 1 Div. 2 G
FMc Class 1 Div. 2 P
Others Z
Protection class transmitter / protection class sensor
IP67 (NEMA 4X) / IP67 (NEMA 4X) 1
Cable conduits
M20 x 1.5 (FET121 only) A
NPT 1/2 in (FET121 only) B
M20 SWA armored (FET121 only) D
M20 Plastic power/output + M20 SWA armored sensor cable entry (FET121 only) F
Power supply
100... 230 V AC 1
24 V AC or 24 V DC 2
Input and output signal type*
HART + 20 mA + pulse + contact output A
PROFIBUS DP RS485 physical layer + pulse + contact output (FET101 and FET121 only) G
Configuration type / diagnostics type
Factory defaults/standard diagnostics 1
Options**
Documentation language
German M1 English M5 (default)
Italian M2 Portuguese MA
Spanish M3 Russian MB
French M4 Danish MF
*The transmitter cartridge Input and Output Signal Type must match the transmitter backplane output configuration
(HART or PROFIBUS) – see IM/WM.
**Add codes for options.
24 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Options
Flowmeter system – full bore,
FEW11
integral mount (DN10 to DN32 Only)
Flowmeter system – full bore, remote
FEW12 XXX X X X X XX X X X X X X X X X X X X
mount
Full bore sensor only – for use with
FEW18
WaterMaster transmitter/remote
Design
Non-hazardous areas 1
Hazardous areas 5
Bore diameter
DN10 (3/8 in) 010
DN15 (1/2 in) 015
DN20 (3/4 in) 020
DN25 (1 in) 025
DN32 (11/4 in) 032
DN350 (14 in) (FEW12 and FEW 18 only) 350
DN400 (16 in) (FEW12 and FEW 18 only) 400
DN450 (18 in) (FEW12 and FEW 18 only) 450
DN500 (20 in) (FEW12 and FEW 18 only) 500
DN600 (24 in) (FEW12 and FEW 18 only) 600
Liner material
PTFE (DN10 to 32 only) A
Elastomer NSF (DN350 to 600 only) M
Electrode design
Standard 1
Other 9
Measuring electrodes material
Hastelloy® C-4 (2.4610) – DN10 to DN32 D
Stainless steel 316 (1.4571) – DN350 to DN600 S
Grounding accessories
Not required 0
One potential equalizing ring (stainless steel) 3
Two potential equalizing rings (stainless steel) 4
Other 9
Continued on page 26
DS/WM–EN Rev. H 25
WaterMaster
Electromagnetic flowmeter
Options
Flowmeter system – full bore,
FEW11
integral mount (DN10 to DN32 Only)
Flowmeter system – full bore, remote
FEW12 XXX X X X X XX X X X X X X X X X X X X
mount
Full bore sensor only – for use with
FEW18
WaterMaster transmitter/remote
Process connection type
ASME B16.5 B class 150 A1
ASME B16.5 B class 300 A3
ISO / EN PN40 – DN10 to DN32 only S4
Other Z9
Process connection material
Carbon steel flanges – DN20 to DN32 and DN350 to DN600 B
Stainless steel flange 1.4571 (316 Ti) – DN10 to DN15 D
Other Z
Usage certifications
Standard (without PED) 1
Other 9
Calibration type
Class 2 calibration – without fingerprint A
Class 1 calibration – without fingerprint B
Class 2 calibration – with VeriMaster D
Class 1calibration – with VeriMaster H
Temperature range installation / ambient temperature range
Standard design/ –20 … 60 °C (–4 … 140 °F) 1
Nameplate
Adhesive A
Signal cable length and type
Without signal cable 0
5 m (15 ft.) cable 1
10 m (30 ft.) cable 2
20 m (60 ft.) cable 3
30 m (100 ft.) cable 4
50 m (165 ft.) cable 5
80 m (260 ft.) cable 6
100 m (325 ft.) cable 7
150 m (490 ft.) cable 8
Special length or cable type 9
Explosion protection certification
General purpose A
FM Class 1 Div. 2 G
FMc Class 1 Div. 2 P
Others Z
Continued on page 27
26 DS/WM–EN Rev. H
WaterMaster
Electromagnetic flowmeter
Options
Flowmeter system – full bore,
FEW11
integral mount (DN10 to DN32 Only)
Flowmeter system – full bore, remote
FEW12 XXX X X X X XX X X X X X X X X X X X X
mount
Full bore sensor only – for use with
FEW18
WaterMaster transmitter/remote
Protection class transmitter / protection class sensor
IP67 (NEMA 4X) / IP67 (NEMA 4X) – cable not fitted and potted to sensor (DN10 to DN32 only) 1
IP67 (NEMA 4X) / IP68 (NEMA 6P) – cable not fitted and potted to sensor (DN350 to DN600 only) 2
IP67 (NEMA 4X) / IP68 (NEMA 6P) – cable fitted and potted to sensor (DN350 to DN600 only) 3
IP67 (NEMA 4X) / IP67 (NEMA 4X) – cable fitted and potted to sensor (DN10 to DN32 only) 7
Cable conduits *
M20 (Plastic) – glands: all 20 mm plastic A
NPT 1/2 in (blanked) – no glands or conduit adaptors supplied B
M20 SWA (armored) – glands: all 20 mm armored D
M20 SWA sensor, M20 others – glands: 20 mm armored for sensor connections, plastic for other connections F
Not required Y
Other Z
Power supply
Without 0
100... 230 V AC, 50 Hz 1
24 V AC or 24 V DC, 50 Hz 2
100... 230 V AC, 60 Hz 3
24 V AC or 24 V DC, 60 Hz 4
Input and output signal type
HART + 20 mA + pulse + contact output A
PROFIBUS DP RS485 physical layer and contact output (FEW111 and FEW121 only) G
Without Y
Configuration type / diagnostics type
Not required (FEW18 only) 0
Standard / Standard (FEW11 and FEW12 only) 1
Options**
Documentation language
German M1 English M5 (default)
Italian M2 Portuguese MA
Spanish M3 Russian MB
French M4 Danish MF
Power supply frequency (sensor FEW 18 only)
50 Hz F5 60 Hz F6
* For FM or FMC Approved versions, NPT only permitted.
** Add codes for options.
DS/WM–EN Rev. H 27
Contact us
Rev. H 02.2011
Process Automation We reserve the right to make technical changes or
modify the contents of this document without prior
Oldends Lane
notice. With regard to purchase orders, the agreed
Stonehouse particulars shall prevail. ABB does not accept any
Gloucestershire GL10 3TA responsibility whatsoever for potential errors or
DS/WM-EN
UK possible lack of information in this document.
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183 Microsoft is a registered trademark of Microsoft
Corporation in the United States and/or other
countries
www.abb.com Modbus is a registered trademark of the Modbus-
IDA organization
HART is a registered trademark of the HART
Communication Foundation