Power System Analysis and Design
Power System Analysis and Design
circuit breakers need not be shown in a load flow study but Sub – transient State: X S = X d′′ = X l + 1 1
1
1
are must for protection study. In a single line diagram, the + +
Xa Xf Xad
system components are usually drawn in the form of their where:
symbols. Generators and transformer connections – star, X a - armature reaction reactance
delta and neutral earthing are indicated by symbols drawn
X l - leakage reactance
by the side of the representation of these elements. Circuit
breakers are represented by rectangular blocks. X f - field winding reactance
X ad - damper winding reactance
Synchronous Motors
Same as the generator model except that current flows
toward the motor. The synchronous reactance is also
dependent on its state but considers only the steady state
Figure 6 Single Line Diagram of Power System and sub – transient state period.
Power system engineers have devised the per – unit Steady State: X S = X d = X l + X a
system such that different physical quantities such as Sub – transient State: X S = X d′′ = X l +
1
1 1 1
current, voltage, power and impedance are expressed as a + +
Xa Xf Xad
decimal fraction or multiple of base quantities. In this where:
system, the various voltage levels disappear and a power X a - armature reaction reactance
network consisting synchronous generators, transformers
X l - leakage reactance
and lines reduce to a system of simple impedances.
Representation of Power System Components X f - field winding reactance
Representation of Synchronous Machines X ad - damper winding reactance
Generators Induction Motors
The generator may be modeled in three different ways: Same as the generator model except that current flows
1. Power Injection Model - the real, P, and reactive, Q, toward the motor. The synchronous reactance is also
power of the generator is specified at the node that the dependent on its state but considers only the sub –
generator is connected either the voltage or injected transient period.
current is specified at the connected node, allowing the 1
Sub – transient State: X S = X d′′ = X l + 1 1 1
other quantity to be determined. + +
Xa Xf Xad
2. Thevenin Model - induced AC voltage, E, behind the where:
synchronous reactance, XS
X a - armature reaction reactance
X l - leakage reactance
X f - field winding reactance
X ad - damper winding reactance
Figure 7 Thevenin Model
Representation of Transformers
3. Norton Model - injected AC current, IG, in parallel with Two – Winding Transformers
the synchronous reactance, XS Figure 9 and 10 shows the transformer equivalent circuit of
a two winding transformer.
Zp =
Zps +Zpt −Zst
; Zs =
Zps +Zst −Zpt
; Zt =
Zst +Zpt −Zps Shunt Reactor
2 2 2 I −jQ −jQ
Representation of Transmission Lines Y= = = 2 = −jβ
V VV ∗ V
The modeling of the transmission line depends on the
length of the line:
1. Short line is represented by series impedance only\
2. Medium line is represented by 𝜋 – equivalent
3. Long line is represented by ABCD parameters in the
form of 𝜋 – equivalent
including the line resistances are quite small in comparison Base kVA
with leakage reactances and shunt path which include line If some equipment such as generators, transformers,
charging and transformer magnetizing circuit provide a very transmission lines, etc. are connected in parallel and their
high parallel impedance with fault. In general, it is to be percentage resistances and reactances also refer to their
noted that if the resistance is less than 1/3 of the reactance, respective kVA ratings, it is hard to compare these
and resistance is ignored, the error introduced will not be percentage resistances and reactances and their combined
more than 5%. If, however, the resistance is on the order of effect until and unless they are all referred to a common
½ that of reactance and resistance is ignored errors up to kVA. This common kVA, which is taken as an arbitrary one,
12% may be introduced. By ‘errors’ it is meant that is known as the base kVA of the system.
calculations will result in values higher than in actual case A base kVA may be chosen in the following manner:
being obtained and in some cases, lead to the purchase of 1. Equal to the kVA rating of the largest unit connected to
protective gear with a higher rating than required. the network.
Percentage Resistance and Reactance and Base KVA and 2. Equal to the sum of the kVA ratings of all the units
KV connected to the network.
Resistance and reactance may be expressed in percentage 3. Any arbitrary value.
or ohmic terms. In the case of rotating machines and It must, however, be clearly understood that the value of the
transformers, manufacturer values are always in base kVA, has no bearing whatsoever on the results; since
percentage terms while tables for cables and overhead in the final formula for the calculation of short – circuit
lines are always in ohmic terms. Calculations can be made current base MVA is to be taken into consideration.
using either but not a mixture. For short circuit calculations, The conversion of percentage reactance at rated kVA to the
the percentage values are employed and, therefore, their percentage reactance at base kVA can be made by using
understanding is essential. the following expression:
Percentage Resistance Base kVA
It is the voltage drop across the given resistance expressed × percentage reactance at rated kVA
Rated kVA
as a percentage of normal voltage when carrying full – load Base kV
current about the normal rating. In some cases, it is convenient to work in ohmic values of
IR various reactances rather than in percentage values. The
%R = × 100 method would become simple if all the reactances relate to
V
Percentage Reactance the same voltage but if step – up or step – down
It is the voltage drop across the given reactance expressed transformers or other equipment operating at different
as a percentage of normal voltage when carrying full – load voltages are also included, all the ohmic values will have to
current about the average rating. be reduced to a common base voltage.
IX Reactance can be converted from one operating voltage to
%X = × 100
V the other by the following relation
or E2 2
(%X) × V X 2 = ( ) × X1
X= E1
I × 100 It must, however, be remembered clearly that all the values
(%X) × V × V
X= refer to the phase values and not the line values.
I × 100 × V Per Unit (PU) Method of Representing Quantities
(%X)V 2 The quantities involved in the power system are kVA,
X=
(Output in VA) × 100 voltage, current and impedance of the equivalent circuits of
when the voltage and output are expressed in kV and KVA the various system components. The equivalent circuits are
respectively, then at different voltages and are connected in the system using
(%X)KV 2 × 10 transformers and interconnections. Each apparatus is rated
X=
kVA in kVA, and its impedance in actual ohms or percentage
or value referred to its rated kVA and rated voltage. In power
X(kVA) system analysis, it is usual to express voltage, current, kVA,
%X = and impedance in per unit of base or reference values of
10(kV)2
Thus if actual reactance in ohms is given, percentage these quantities. Such a method simplifies the calculations.
reactance can be determined and vice versa. The per unit value of any quantity is defined as
and since we choose one common base kVA and base kV. Xm IB1 × kVB1
Thus, per unit impedance ot new base, X mpu = ×
1000 × kVB2 kVB1
kVAnew (kVold )2 or
Zpu new = Zpu old × × X m kVAB X m MVAB
KVAold (kVnew )2
X mpu = =
Per Unit Impedance of a Two Winding Transformer 1000 × kVB2 × kVB1 kVB2 × kVB1
The approximate equivalent circuit of a two winding Per Unit Impedance Diagram of a Power System
transformer with all impedances referred to primary (low – Per unit impedance diagram can be drawn directly from the
voltage) side is illustrated in Figure 10. single line diagram of a power system by following the
The total impedance of the transformer referred to primary procedure given:
side in per unit is: a. Choose an appropriaye common kVA (or MVA) base
Z01 × kVAB for the whole system.
Z01 pu =
(kVB1 )2 × 1000 b. Consider the system to be divided into number of
Now, consider the transformer with all its impedances sections/regions/area by the transformers; choose an
referred to secondary side. The total impedance is appropriate kV base in one of the sections and
N2 2 (kVB2 )2 determine kV base of other sections in the ratio of
Z02 = Z01 × ( ) = Z01
(kVB1 )2 transformation
N1
c. Calculate per unit valyes if voltage and impedance for
Thus, the impedance of the transformer in per unit viewed
each section and connect them as per the topology of
from the secondary side,
Z02 × kVAB the single line diagram. The result is the single – phase
Z02 pu = per unit impedance diagram.
(kVB2 )2 × 1000 Examples:
Substituting, 1. Base Voltage = 1.1 kV. Base KVA = 106. What is base
(kVB2 )2 kVAB impedance?
Z02 pu = Z01 × 2
×
(kVB1 ) (kVB2 )2 × 1000 2. If the resistance in ohms is 5 Ω, find the per unit value.
kVAB Given base kVA = 10 and base kV = 11.
Z02 pu = Z01 ×
(kVB1 )2 × 1000 3. A single phase two – winding transformer is rated 25
This shows that the per unit impedance is the same kVA, 1100/440 volts, 50 Hz. The equivalent leakage
regardless of the side from which it is viewed. Thus, the impedance of the transformer referred to the low
equivalent circuit for the two – winding transfomer in which voltage side is 0.06 < 78° Ω. Using transformer
Z01 pu = Z02 pu = Zpu . rating as base values, determine the per – unit leakage
Mutual Impedance in Per Unit Between Lines of impedance referred to low voltage winding and
Different Voltage Levels referred to high voltage winding.
Consider two three – phase lines of different voltage levels 4. A single phase transformer is rated at 2.5 kVA, 11/0.4
running together, with mutual inducatcen Xm present as kV. If the leakage reactance is 0.96 Ω when referred
depicted in Figure 16. to low – voltage side, then determine its leakage
There is one value Xmpu (mutual reactance in per unit), reactance in per unit.
which will serve both lines. 5. For a 110/440 V, 25 kVA, single – phase transformer,
primary and secondary leakage reactances are 0.04 Ω
and 0.10 Ω respectively. Show that net pu leakage
reactance of the transfomer referred to LV side is same
as referred to HV side.
6. An 11/0.4 kV, 200 kVA transformer has an equivalent
impedance of 2.4+j12.4 Ω referred to HV side.
Figure 16 Two Parallel Lines of Same MVA but of Different Voltage Levels Determine the base values for the pu system, the per
Thus in terms of line 2, we have unit equivalent impedance and the equivalent
Xm Xm impedance rop at one – half rated current.
X mpu = = 7. Determine the per unit impedance of a transmission
X mB 1000 × kVB2
IB1 line having an impedance of 30 + j110 Ω on 100 MVA
Xm and 132 kV base voltage.
X mpu = × IB1
1000 × kVB2
8. A 30 MVA, 11 kV generator has a reactance of 0.2 pu Find the per unit impedances of the star – connected
referred to its ratings as bases. Determine the per unit equivalent circuit for a base of 15 MVA, 66 kV base in
reactance when referred to base KVA of 50000 kVA the primary circuit.
and base kV of 33 kV. 14. Draw the per – unit impedance diagram of the system
9. The transformation ratio of the step – up transformer is shown in Figure 19. Assumed base values are 100
11/220 kV. The base MVA = 100 and base kV = 11 on MVA and 100 kV.
the generator side. What is the base kV on the
transmission side?
10. Three generators are rated as follows:
Generator 1: 100 MVA, 33 kV, reactance = 10%
Generator 2: 150 MVA, 32 kV, reactance = 8% Figure 19
Generator 3: 110 MVA, 30 kV, reactance = 12% G1: 50 MVA, 12.2 kV, xg1 = 0.10 pu
Choosing 200 MVA and 35 kV as base quantities, G2: 20 MVA, 13.8 kV, xg2 = 0.10 pu
compute per unit reactances of the three generators T1: 80 MVA, 12.2/132 kV, xT1 = 0.10 pu
referred to these base quantities. Draw reactance T2: 40 MVA, 13.8/132 kV, xT2 = 0.10 pu
diagram and mark per unit reactances. The three Load: 50 MVA, 0.8 pf lagging operating at 124 kV.
generators are connected to common bus – bars. 15. Figure 20 shows a sample power system network. Find
11. Figure 17 shows single line diagram of a single – phase the current supplied by the generator, the transmission
circuit. Using the base values of 3 kVA and 230 V, draw line current, the load current, the load voltage and the
the per – unit circuit diagram and determine the per – power consumed by the load.
unit impedances and per – unit source voltage. Also,
calculate the load current both in per unit and in
Amperes.
Figure 20
16. The single line diagram of a three – phase system is
shown in Figure 21. Select a common base of 100
MVA and 13.8 kV on the generator side. Draw per –
Figure 17
unit impedance diagram.
12. A 100 MVA, 33 kV, three phase generator has a
reactance of 15%. The generator is connected to the
motors through a transmission line and transformers
as shown. Motors have rated inputs of 40 MVA, 30
MVA and 20 MVA at 30 kV with 20% reactance each.
Draw the per – unit circuit diagram.
Figure 21
G: 90 MVA, 13.8 kV, xg = 18%
T1: 50 MVA, 13.8/220 kV, xT1 = 10%
Figure 18 T2: 50 MVA, 220/11 kV, xT2 = 10%
13. The three – phase ratings of a three – winding
T3: 50 MVA, 13.8/132 kV, xT3 = 10%
transformer are:
Primary – Y – connected, 66 kV, 15 MVA T4: 50 MVA, 132/11 kV, xT4 = 10%
Secondary – Y – connected, 13.2 kV, 10 MVA M: 80 MVA, 10.45 kV, xm = 20%
Tertiary – Δ – connected, 2.3 kV, 5 MVA Load: 57 MVA, 0.8 pf (lagging) at 10.45 kV.
Neglecting resistances, the leakage impedances are: xline1 = 50 Ω
ZPS = 0.08 pu on 15 MVA, 66 kV base xline2 = 70 Ω
ZPT = 0.10 pu on 15 MVA, 66 kV base 17. Figure 22 shows single – line diagram of a power
ZST = 0.09 pu on 10 MVA, 13.2 kV base system.
the same cyclic order as those in a normal supply, the Also, Ib2 = AIa2 and Ic2 = A2Ia2
conventional counter – clockwise rotation, which can be In matrix notation:
seen in Figure 25. A balanced system corresponding to Ia 1 1 1 Ia0
normal conditions contains positive phase sequence only. [Ib ] = [1 a2 a ] [Ia1 ]
It is also condition for a 3 – phase fault. Ic 1 a a2 Ia2
Negative Sequence Component and
Ia0 1 1 1 1 Ia
Ib2 = AIa2 [Ia1 ] = [1 a a2 ] [Ib ]
3
IY2 = AIR2 Ia2 1 a2 a I c
Some Facts about Sequence Currents
Ic2 = A2 Ia2 1. A balanced 3 phase system consists of positive
IB2 = A2 IR2 sequence components only; the negative and zero
sequence components being zero.
2. The presence of negative or zero sequence currents in
Figure 26
a 3 – phase system introduces unsymmetry and is
The negative – sequence component is that system in indicative of an abnormal condition of the circuit in
which the phasor still rotate counter – clockwise but attains which these components are found.
a maximum in reverse order. This sequence only arises 3. The vector sum of the positive and negative sequence
under conditions of unbalance as when an unsymmetrical currents of an unbalanced 3 phase system is zero. The
fault occurs. resultant solely consists of three zero sequence
Evaluation of the Components currents.
Expressing Symmetrical Components of IB and IC in terms Ia0 + Ib0 + Ic0
of IA symmetrical components: 4. In a 3 phase, 4 wire unbalanced system, the magnitude
Ia = Ia0 + Ia1 + Ia2 of zero sequence components is one third of the
Ib = Ia0 + A2 Ia1 + AIa2 current in the neutral wire
Ic = Ia0 + AIa1 + A2 Ia2 1
I0 = In
Adding them up: 3
Ia + Ib + Ic = 3Ia0 + Ia1 (1 + A + A2 ) + Ia2 (1 + A In the absence of path through the neutral of a 3 – phase
+ A2 ) system, the neutral current is zero and the line currents
But 1 + A + A = 0 also 1 + A2 + A4 = 0
2 contain no zero sequence components. A delta connected
Therefore, load provides no path to the neutral and the line currents
Ia0 = 1/3(Ia + Ib + Ic ) flowing to delta connected load can contain no zero
Also, Ia0 = Ib0 = Ic0 sequence components.
Multiply Ia by 1, Multiply Ib by A and Multiply Ic by A2 5. In a 3 phase, unbalanced system, the magnitude of
negative sequence components cannot exceed that of
Ia = Ia0 + Ia1 + Ia2
the positive sequence components. If the negative
AIb = AIa0 + A3 Ia1 + A2 Ia2
sequence components were the greater, the phase
A2 Ic = A2 Ia0 + A3 Ia1 + A4 Ia2
sequence of the resultant system would be reversed.
Adding them up,
6. The current of a single – phase load drawn from a 3 –
Ia + AIb + A2 Ic = Ia0 (1 + A + A2 ) + 3Ia1 + Ia2 (1 phase system comprises equal positive, negative and
+ A2 + A4 ) zero sequence components.
Ia1 = 1/3(Ia + AIb + A2 Ic ) Power associated with Sequence Components
Also, Ib1 = A Ia1 and Ic1 = AIa1
2
The total three phase power of a circuit can be expressed
Multiply Ia by 1, Multiply Ib by A2 and Multiply Ic by A in terms of the symmetrical components of the line currents
Ia = Ia0 + Ia1 + Ia2 and the symmetrical components of the line – to – neutral
A2 Ib = A2 Ia0 + A4 Ia1 + A3 Ia2 voltages.
AIc = AIa0 + A2 Ia1 + A3 Ia2 P = 3(E0 I0 cos θ0 + E1 I1 cos θ1 + E2 I2 cos θ2 )
Adding them up, where θ0 is the angle between E0 and I0 , θ1 is the angle
Ia + AIb + A2 Ic = Ia0 (1 + A + A2 ) + 3Ia1 + Ia2 (1 between E1 and I1 and θ2 is the angle between E2 and I2 .
+ A2 + A4 ) The equation shows that the total power is the sum of the
Ia2 = 1/3(Ia + A2 Ib + AIc ) three components of power; but the power in one phase of
Electrical Engineering Department | Engr. Gerard Francesco DG. Apolinario 9
Power System Analysis and Design
an unbalanced circuit is not one third of the above 6. A balanced star connected load takes 90 A from a
expression, since each phase will contain components of balanced 3 phase, 4 wire supply. If the fuses in the Y
power resulting from zero sequence voltage and positive and B phases are removed, find the symmetrical
sequence current, etc. This power “between sequences” is components of the line currents:
generated in one phase and absorbed by the others, and a. before the fuses are removed
does not appear in the expression for total three phase b. after the fuses are removed
power. 7. A 3 φ, 4 wire system supplies loads which are
Only positive sequence power is developed by the unequally distributed in the three phases. An analysis
generators. This power is converted to negative sequence of the current flowing in R, Y and B lines shows that in
and zero sequence power by a circuit dissymmetry such as R line, positive phase sequence component is 200 ∠0°
occurs from a single line – to – ground or a line – to – line A and the negative phase sequence component is 100
fault. The unbalanced fault, unbalanced load, or other ∠60° A. The total observed current flowing back to the
dissymmetry in the circuit thus acts as the “generator” for supply in the neutral conductor is 300 ∠300° A.
negative sequence and zero sequence power. Calculate the currents in the three lines.
For reactive power: 8. One conductor of a 3 – phase line is open. The current
Q = 3(E0 I0 sin θ0 + E1 I1 sin θ1 + E2 I2 sin θ2 ) flowing to the Δ – connected load through the line R is
and for Apparent power: 10 A. With the current in line R as reference and if line
S = 3(E0 I0 + E1 I1 + E2 I2 ) B is open, find the symmetrical components of the line
Examples: currents.
1. In a 3 phase, 4 wire system, the currents in R, Y and B
lines under abnormal conditions of loading are as
under:
IR = 100∠30° A
IY = 50∠300° A
IB = 30∠180° A
Calculate the positive, negative and zero sequence
currents in the R – line and return current in the neutral
wire. Figure 27
2. The currents in a 3 – phase unbalanced system are: 9. Three resistors of 5Ω, 10Ω and 20Ω are connected in
IR = (12 + j6) A delta across the three phases of a balanced 100 V
IY = (12 − j12) A supply. What are the sequence components in the
IB = (−15 + j10) A resistors and in supply lines?
The phase sequence in RYB. Calculate the zero, 10. A delta connected load is supplied from a 3 – phase
positive and negative sequence components of the supply. The fuse in the B line is removed and current
currents. in the other two lines is 20 A. Find the symmetrical
3. The sequence voltages in the red phase are: components of line currents.
ER0 = 100 V 11. Three impedances of 5 – j10, 6 + j 5 and 3 + j15 ohms
ER1 = (200 − j100) V are connected in star to red, yellow and blue lines of a
ER2 = −100 V 3300 V, 3-phase, 3-wire supply. The phase sequence
is RYB. Calculate the line current IR.
Find the phase voltages.
12. A star connected load consists of three equal resistors
4. The zero and positive sequence components of red
of 1 Ω resistance. The load is assumed to be
phase are:
connected to an unsymmetrical 3 phase supply, the
ER0 = 0.5 − j0.866 V
line voltages are 200 V, 346 V and 400 V. Find the
ER1 = 2∠0° V
magnitude of current in any phase by the method of
If the phase voltage ER = 3∠0° V, find the negative
symmetrical components.
sequence component of red phase and the phase
13. The line currents in a 3 phase, 4 wire system are:
voltages EY and EB.
Ia = 300 + j400 A
5. The current from neutral to ground connection is 12 A.
Ib = 200 + j200 A
Calculate the zero phase sequence components in
Ic = 400 − j200 A
phases.
Calculate the positive, negative and zero components Let us consider, 3 – phase star – delta transformer with
of all the line currents. primary side Y – connected and secondary side delta –
14. The sequence components of phase A currents are: connected as shown in Figure 28. Windings shown parallel
Ia0 = 0.47 + j1.49 A to each other, being wound on the same core, are
Ia1 = 18.4 cis − 31.6° A magnetically coupled. The polarity markings are indicated
Ia2 = 3.23 cis 168.2° A on each phase. The dots at the windings indicate the
Calculate the following: terminals which are positive at the same time with respect
a. The line current Ia to the undotted terminals. With phase marked as ABC on
b. The line current Ib the star side, there are number of ways of labelling the
c. The line current Ic phases a b c on the delta side. The labelling indicated on
15. If the currents of a wye – connected transformer are: the diagram corresponds to + 90° connection in which the
Ia = 10 cis − 30° A positive sequence phase a to neutral voltage (delta side)
Ib = 12 cis 215° A leads phase A to neutral voltage (star side) by 90° and so
Ic = 15 cis 82° A the line currents in a and A. This labelling is computationally
What is the phase b positive sequence component? convenient: The alternative way is to bale delta as b → a,
16. Three equal impedances (8+j6) ohms are connected in c → b and a → c, and thus we get standards Yd1, - 30°
wye across a 3 phase, 3 wire supply. The symmetrical connection. If the polarities on the delta side are also
components of the phase A voltage are reversed, we have standard Yd11, 30° connection.
Va0 = 40 + j0 V Double suffixes are used for line – to – line voltages and
Va1 = 220 + j28.9 V delta currents and single suffix are used for line currents
Va2 = −40 − j28.9 V and phase (line – to – neutral) voltages. Line – to – line
If there is no connection between the load neutral and transformation ratio is being taken to unity.
the supply neutral. Calculate the line currents Ia, Ib and The positive and negative sequence voltages on primary
Ic . (star) and secondary (delta) sides of the transformer are
Phase Shift in Star – Delta Transformers shown in Figure 29 while the positive and negative
The angular difference between phasors representing the sequence currents on the two sides of the transformer are
voltage induced between high voltage and low voltage shown in Figure 30.
terminals having same marking letters and the
corresponding neutral points (real or imaginary), expressed
about the high voltage side is known as phase
displacement (or shift) of the transformer. In a star – star or
delta – delta 3 – phase transformer, there is no phase shift
between the corresponding voltages of any phase to
neutral on either side. However, delta connected winding is
desirable in many power transformers for reasons of
harmonic elimination. As such most of the power
transformers are either star – delta or delta – star
connected. In such transformers, even under normal
operating condition, the phase – to – phase voltages and Figure 29 Positive Sequence Voltages in Y - Δ Transformer
phase – to – neutral voltages of HV side are displaced from
the corresponding voltages of LV side. The phase shift of
30° or – 30° occurs. similarly, the currents on two sides are
displaced. Generally, in short – circuit calculations the
phase shift needs not to be considered.
From these figures, it is observed that seen that for this condition the relative phase positions of
Va1 = jVA1 ; Ia1 = jIA1 ; Va2 = −jVA2 and Ia2 = −jIA2 the voltages applied to the stator of the motor are the same
In case of reversal of power flow, when delta acts as as for the negative sequence set. Thus, the field developed
primary and star as secondary, the voltage phasors do not by the set of negative sequence voltages will rotate in a
change but all current phasors reverse. The phasor direction opposite to that of the field developed by the set
relationship between star and delta voltages and currents of positive sequence voltages. Phase sequence should not
therefore remain the same. be confused with the rotation of phasors. For both sets of
Thus, we see that magnitude of phase shift is same for positive and negative sequence voltages, the standard
positive sequence components and negative sequence convention of counter – clockwise rotation if followed. The
components. However, the direction of phase shift in case zero sequence voltages are single phase voltages and,
of negative phase sequence components is reverse of that therefore, they give rise to an alternating field in space.
applicable to the positive sequence components (due to The positive and negative sequence sets are balanced
reverse phase sequence). The magnitude and direction of ones, if only positive and/or negative sequence currents are
phase shift depends on the transformer group and flowing, the phasor sum of each will be zero and there will
allocation of phase references. Phase shit of zero be no residual current. However, the zero sequence
sequence quantities need not be considered in star – delta components of currents in the three phases are equal in
transformers because the zero sequence currents do not magnitude and are in phase and, therefore, the residual
flow in lines on delta – connected side. current will be three times the zero – sequence current of
one phase. In case of an earth fault, the positive and
negative sequence currents flow through the ground and
ground wires.
Sequence Impedances and Sequence Networks
Unbalanced Impedances and Admittances
The three star impedances of Figure 33(a), which form an
unbalanced load. Their sequence components are:
1
𝐙𝟎 = (Za + Zb + Zc )
3
1
Figure 31 Positive Sequence Currents in Y – Δ Transformer 𝐙𝟏 = (Za + aZb + a2 Zc )
3
1
𝐙𝟐 = (Za + a2 Zb + aZc )
3
The sequence components of current through the The components of the three – phase line currents and the
impedances, and the sequence components of the line components of the three – phase voltage drops created by
voltages impressed across them are interrelated by the the mutual impedances will be interrelated by the following
following equations: equations:
1 1
E0 = (Ean + Ebn + Ecn ) = I0 𝐙𝟎 + I1 𝐙𝟐 + I2 𝐙𝟏 E0 = (Eaa′ + Ebb′ + Ecc′ )
3 3
1 = 2I0 𝐙𝐦𝟎 − I1 𝐙𝐦𝟐 − I2 𝐙𝐦𝟏
E1 = (Ean + aEbn + a2 Ecn ) = I0 𝐙𝟏 + I1 𝐙𝟎 + I2 𝐙𝟐
3 1
1 E1 = (Eaa′ + aEbb′ + a2 Ecc′ )
E2 = (Ean + a2 Ebn + aEcn ) = I0 𝐙𝟐 + I1 𝐙𝟏 + I2 𝐙𝟎 3
3
The above equations illustrate the fundamental principle = −I0 𝐙𝐦𝟏 − I1 𝐙𝐦𝟎 + 2I2 𝐙𝐦𝟐
1
that there is mutual coupling between sequences when the E0 = (Eaa′ + a2 Ebb′ + aEcc′ )
circuit constants are not symmetrical. As the equations 3
reveal, both positive and negative sequence current (as = −I0 𝐙𝐦𝟐 + 2I1 𝐙𝐦𝟏 − I2 𝐙𝐦𝟎
well as zero sequence current) create a zero – sequence If, as in Figure 34 (b), both self and mutual impedances are
voltage drop. If Za = Zb = Zc, the impedances are present in a section of a three – phase circuit, the
symmetrical, Z1 = Z2 = 0, and Z0 = Za. For this condition, symmetrical components of the three voltage drop across
E0 = I0 𝐙𝟎 the section are:
1
E1 = I1 𝐙𝟎 E0 = (Eaa′ + Ebb′ + Ecc′ )
E2 = I2 𝐙𝟎 3
= I0 (𝐙𝟎 + 2𝐙𝐦𝟎 ) + I1 (𝐙𝟐 − 𝐙𝐦𝟐 ) + I2 (𝐙𝟏 − 𝐙𝐦𝟏 )
and, as expected, the sequences are independent. If the 1
neutral point is not grounded in Figure 33 (a) I0 = 0 but E0 = E1 = (Eaa′ + aEbb′ + a2 Ecc′ )
I1Z2 + I2Z1 so that there is a zero – sequence voltage, 3
= I0 (𝐙𝟏 − 𝐙𝐦𝟏 ) + I1 (𝐙𝟎 − 𝐙𝐦𝟎 ) + I2 (𝐙𝟐 + 2𝐙𝐦𝟐 )
representing a neutral voltage shift, created by positive and 1
negative sequence current flowing through the unbalanced E0 = (Eaa′ + a2 Ebb′ + aEcc′ )
3
load. = I0 (𝐙𝟐 − 𝐙𝐦𝟐 ) + I1 (𝐙𝟏 + 2𝐙𝐦𝟏 ) + I2 (𝐙𝟎 − 𝐙𝐦𝟎 )
The previous Self – Impedances – Unbalanced Again, if both self and mutual impedances are symmetrical,
impedances can be resolved into symmetrical components, in all three phases,
although the impedances are vector operators, and not E0 = I0 (𝐙𝟎 + 2𝐙𝐦𝟎 ) = I0 Z0
rotating vectors as E1 = I1 (𝐙𝟎 − 𝐙𝐦𝟎 ) = I1 Z1
are three – phase E2 = I0 (𝐙𝟎 − 𝐙𝐦𝟎 ) = I2 Z2
voltages and Where Z0, Z1 and Z2 are, respectively, the impedance to
currents. Consider zero, positive, and negative sequence. For this condition,
equations also hold positive sequence currents produce only a positive
for unsymmetrical sequence voltage drop, etc. Z0, Z1 and Z2 are commonly
series line referred to as the zero sequence, positive sequence and
impedances, as negative sequence impedances. Note, however, that this is
shown in Figure 33 not strictly correct and that Z1, the impedance to positive
(b), where E0, E1 sequence currents, should not be confused with Z1, the
and E2 are Figure 34 Mutual Impedances
positive sequence component of self – impedances. Since
components of Ea, Eb and Ec, the voltage drops across the Z0, Z1 and Z2 are used more frequently than Z0, Z1, and Z2
impedances in the three phases. the shorter expression “zero – sequence impedance” is
Mutual Impedances between phases can also be resolved usually used to refer to Z0 rather than Z. For a circuit that
into components. Consider Zmbc of Figure 34(a), as has only symmetrical impedances, both self and mutual,
reference, then the sequences are independent of each other, and positive
1 sequence current produces only positive sequence voltage
𝐙𝐦𝟎 = (Zmbc + Zmca + Zmab )
3 drops, etc. Fortunately, except for unsymmetrical loads,
1 unsymmetrical transformer connections, etc., the three –
𝐙𝐦𝟏 = (Zmbc + aZmca + a2 Zmab )
3 phase system usually encountered are symmetrical (or
1
𝐙𝐦𝟐 = (Zmbc + a2 Zmca + aZmab ) balanced) and the sequences are independent.
3
Figure 43 Y - D Connection
6. Delta – Delta connection: In this case zero sequence
current circulate the delta connected windings, but no
current can leave the delta terminals.
Figure 44 D - D Connection
Three Winding Transformers
Three phase, three winding
have an additional tertiary Figure 48 Equivalent Zero Sequence Network for Three Winding Transformer
winding, and may be A particular point to keep in mind is that what is generally
represented by a single line available from measurements for a 3 – winding transformer
diagram corresponding to the would be the impedances across a pairs of windings. (ie.
ampere – turn balance, or ZPS, ZPT, and ZST), with the third winding on open circuit.
power balance. Thus, we could relate the values to the effective primary,
NP IP + NS IS + NT IT = 0 Figure 45 Three Winding
Transformer secondary and tertiary impedances (ZP, ZS and ZT) as
or VP IP + VS IS + VT IT = 0 follows, about the equivalent circuit.
which in per unit quantities would yield the common Zps = Zp + Zs
equation
Zpt = Zp + Zt
IP,pu + IS,pu + IT,pu = 0
Zst = Zs + Zt
This may be represented
The values of ZP, ZS and ZT can then be determined as
by three reactances
Zp = 0.5(Zps + Zpt − Zst )
connected in T, giving the
general single line diagram Zs = 0.5(Zps + Zst − Zpt )
for fault studies for the 3 – Zt = 0.5(Zpt + Zst − Zps )
winding transformer as Circuit Figure 46 Equivalent Transformer As in the case of the 2 – winding transformer, 3Zn is
for Three Winding Transformer
seen in Figure 46. included wherever earthing of a neutral point is done
The positive sequence and negative sequence diagrams through an impedance Zn.
would have a direct connection to the T connection of Sequence Impedance and Networks of Load
reactances from P, S and T. For a star – connected load with isolated neutral, there is
The zero – sequence network would again be built up from no path for the flow of zero sequence currents and the star
the single winding arrangements described and would yield point of the load will not be connected to the reference bus,
the single line diagrams given in Figure 47 and 48. as shown in Figure 49. Thus, the zero – sequence
impedance is infinite beyond the neutral point. This fact is
indicated by an open circuit in the zero – sequence network
between the neutral of the star – connected load and the
reference bus in Figure 49 (b).
When the star point of the load is grounded, there will be then negative and zero sequence networks are required
continuity of the load circuit to ground and the star point of also.
the load, n will be connected to the reference bus. The A power system network consists of synchronous
current flowing through the neutral under unbalanced machines, transformers and lines. Each component is
condition of system is zero sequence current. If the neutral converted to its equivalent sequence network. The positive
point of load is grounder through a reactor of impedance Zn, sequence network is drawn by examining one line diagram
the zero – sequence voltage drop caused by flow of current of the power system. In fact, the single line reactance
3Ia0 through Zn will be the same as if current Ia0 flows diagram, as employed for calculation of symmetrical fault
through 3Zn. Thus, impedance 3Zn is introduced between current, is the positive sequence diagram of the power
neutral point n and the reference bus, when representing system.
on the zero – sequence network. The negative sequence network is quite same as the
positive sequence network – only generators or rotating
machines may have different sequence impedances and
the negative sequence network does not contain any
voltage source. The negative sequence impedances for
transmission lines and transformers are the same as the
positive sequence impedances. In many cases, only one
sequence network is drawn for positive and negative
sequence representation. The reference bus for positive
Figure 50 Zero Sequence Network for Star - Connected Load with Neutral and negative sequence networks is the system neutral any
Grounded through Impedance Zn
The zero – sequence impedance of the load is equal to its impedance connected between a neutral and ground is not
positive or negative sequence impedance if the load is included in the positive and negative sequence networks as
balanced. neither of these sequence currents can flow through such
The positive sequence network is composed of positive an impedance.
sequence impedances only and since positive sequence Zero sequence subnetworks for different elements of a
currents do no flow to ground therefore neutral point n and power system can be easily combined to form complete
the ground are at same potential. Thus, impedance inserted zero sequence network. The zero – sequence network
between neutral and ground has no effect on positive does not contain any voltage source. Any impedance
sequence currents. included in generator or transformer neutral becomes three
times its value in a zero – sequence network.
All the sequence impedances are expressed in per unit
values and referred to the same base MVA and base kV.
Examples:
1. Draw the three sequence networks for the
transmission network shown in Figure 52.
Figure 54
4. Draw the zero – sequence network of the power
system in Figure 55.
Figure 60
10. Draw the Zero sequence network. Data is given as:
G1 : 100 MVA, 11 kV, Xg10 = 0.05 pu
Figure 55 G2 : 100 MVA, 11 kV, Xg20 = 0.05 pu
5. Draw the positive, negative and zero sequence T1 : 100 MVA, 11/220 kV, XT1 = 0.06 pu
component of the power system in Figure 56. T2 : 100 MVA, 220/11 kV, XT2 = 0.07 pu
Line 1 : XL10 = 0.3 pu
Line 2 : XL20 = 0.3 pu
Figure 56
6. Draw the zero – sequence network of the sample
Figure 61
power system in Figure 57. 11. Draw the zero – sequence network as shown in Figure 62.
Figure 57
7. Draw the zero – sequence network of the sample
power network in Figure 58.
Figure 62
Bus Admittance Matrix
The matrix equation for relating the nodal voltages to the currents
Figure 58
that flow into and out of a network using the admittance values of
8. Draw the zero – sequence network of the sample circuit branches is called Admittance Matrix.
power system shown in Figure 59. Data are given as: It is used to form the network model of an interconnected power
G : xg0 = 0.05 pu system where:
M : xm0 = 0.03 pu - Nodes represent substation bus bars
T1 : xt1 = 0.12 pu - Branches represent transmission lines and transformers
Yii = ∑ yik , j ≠ i
k=0
Off – diagonal element of Y matrix is known as short circuit
Figure 64 Power System Model transfer admittance or mutual admittance
Using source transformation, all generator or voltage sources are Yik = Yki = −yik
converted to current source and injects currents to their Examples:
respective buses. Node 0 (which is normally ground) is taken as 1. Determine the admittance matrix for the single line diagram
reference. in Figure 66.
Figure 66
2. Formulate the admittance matrix for Figure 67.
Under normal operating conditions, δk − δi is quite small. time per each characteristic.
Therefore, θik − δi + δk = θik and the equation reduces to iteration. iteration. So speed of
∂Pi More number of Less number convergence
= −|Vi ||Vk |Bik iterations to of iterations. is fast.
∂δk obtain solution Quadratic
Assuming |Vk | ≈ 1.0 Linear convergence
∂Pi convergence characteristic.
= −|Vi |Bik
∂δk characteristic. So speed of
Similarly, the diagonal elements of J4 may be written as So slow rate of convergence
n convergence. is fast.
∂Qi
= −|Vi ||Yii | sin θii − ∑|Vi ||Vk ||Yik | sin(θik − δi + δk ) Convergence Convergence
∂|Vi | affected by ill – not affected
k=1
∂Q i conditioned by ill –
= −|Vi ||Yii | sin θii + Q i system – series conditioned
∂|Vi |
capacitors system,
∂Q i
= −|Vi |Bii + Q i Number of
∂|Vi | Dependency iterations
Number of iterations does not
Again Bii ≫ Q i , Q i may be neglected. on system increases with
depend on system size
∂Q i size increase in size
= −|Vi |Bii of system
∂|Vi |
Simplicity of
Assuming θik − δi + δk = δik the equation can be written as Simple Complex Simple
programming
∂Q i
= −|Vi |Bik Memory Less than NR
∂|Vk | Less More
requirement method
The simplified form of the equations are Convergence is
∆P ∆P Selection of affected by Convergence is not affected by
= −B ′ ∆δ ⇒ ∆δ = −[B ′ ]−1 slack bus selection of slack selection of slack bus
|Vi | |Vi |
∆Q ∆Q bus
= −B ′′ ∆|V| ⇒ ∆|V| = −[B ′′ ]−1 Suitable for
|Vi | |Vi | contingency
B’ and B’’ are the imaginary part of the bus admittance matrix evaluation for
YBUS. B’ and B’’ are constant matrices and they need to be security
inverted once. The decoupled and fast decoupled power flow Suitable for Suitable for
Application assessment
small system large system
solutions requires more iterations than the coupled NR method and for
but requires less computing time per iteration. solving
Example: optimization
Using the fast decoupled Power Flow, Find the power flow problems
solution for Figure 95. Both
Rectangular rectangular Polar
Coordinate
coordiante and polar coordinate
coordinates
Table 7 Comparison of Power Flow Methods
Holomorphic Embedding Load Flow Method
The Holomorphic Embedding Load – Flow Method (HELM) is
a solution method for the power flow equations of electrical power
systems. Its main features are that it is direct (that is, non –
iterative) and that it mathematically guarantees a consistent
selection of the correct operative branch of the multivalued
problem, also signalling the condition of voltage collapse when
Figure 95 there is no solution. These properties are relevant not only for the
Comparison of Power Flow Methods reliability of existing off – line and real – time applications, but also
Attribute GS NR FDLF because they enable new types of analytical tools that would be
More impossible to build with existing iterative load flows (due to their
Less accurate
Reliabilty accurate and More reliable convergence problems). An example of this would be decision –
and less reliable
more reliable support tools providing validated action plans in real time.
Less number of Less time per The HELM load flow algorithm was invented by Antonio Trias
More times
arithmetic iteration.
per iteration and has been granted two US Patents. A detailed description was
Speed of operation to More number
as Jacobian presented at the 2012 IEEE PES General Meeting, and published
Convergence complete one of iterations
is to be in. The method is founded on advanced concepts and results
iteration and Geometric
computed in from complex analysis, such as holomorphicity, the theory of
therefore less convergence
Figure 101
6. An asymmetrical current wave is not symmetrical about
the zero – axis. The axis of symmetry is displaced or offset
from the zero axis, and the magnitude above and below the Figure 104
zero axis are not equal. The axis of symmetry of an offset In figure 104, the DC component decays to zero in about
wave resembles a DC current. (see Figure 102) four cycles. The rate of decay is called “Decrement” and
depends upon the circuit constants. The DC components
would never decay in a circuit having reactance but zero
resistance, and would remain constant forever. In a circuit
having resistance but zero reactance the DC component
would decay instantly. These are theoretical conditions and
all practical circuits have some resistance and reactance,
and the DC component disappears in a few cycles. Since
fault currents are neither symmetrical nor fully asymmetrical
so what is the available short circuit current? We can say
Figure 102 that short circuit current normally takes on an asymmetrical
The asymmetrical currents can be readily handled, if characteristic during the first few cycles of duration and it is
considered to have an AC component and a DC component. symmetrical after about 4 cycles, and we can properly talk
Both components are theoretical. The DC component is about the available short circuit current in RMS symmetrical
generated within the AC system and has no external source. amperes after the DC component becomes zero. We can
also determine current at 1, 2, 3 cycles of any other time
after the short circuit started. The accepted practice is to use
the current which is available ½ cycle after the short circuit
starts.
9. Closing Angle: A short circuit fault can occur at any point
on the voltage wave of the circuit. The voltage wave
resembles the current wave and the two waves may be in
phase or out of phase. The magnitude and symmetry of the
current wave on a short circuit depends on the point of the
voltage wave at which the short occurs. In laboratory tests,
Figure 103
it is possible to pick the point on the voltage wave where the
Figure 103 shows a fully offset asymmetrical current with a
fault occurs by closing the circuit at any desired angle on the
steady DC component as its axis of symmetry. The
voltage wave. We can say that we pick the closing angle to
symmetrical component has the zero – axis as its axis of
produce the current conditions which we wish. This is called
symmetry. If the RMS or effective value of the symmetrical
‘controlled closing’.
current is 1, then the peak of the symmetrical current is 1.41.
10. Random Closing: In real life, faults occur at any and every
This is also the effective value of the DC component.
point on the voltage wave and in a laboratory, this can be
We can add these two effective currents together by the
duplicated by closing the circuit at random. This is known as
square root of the sum of the squares and get the effective
random closing. The following is true of a short circuit having
or RMS value of the asymmetrical current.
negligible resistance:
Iasm =√Idc 2 +Isym 2 a. If the fault occurs at zero voltage the current wave is
fully asymmetrical, thus the maximum value of short
7. An over current is a current that exceeds the ampere rating circuit current is obtained.
of the conductors (cable), equipment (motors, instruments) b. If the fault occurs at maximum voltage the current wave
or other devices. Overcurrent include short circuits and is completely symmetrical, and a minimum value of
overloads. They can occur because of normal conditions short circuit current is obtained.
such as motor starting, or abnormal conditions such as a
fault.
Electrical Engineering Department | Engr. Gerard Francesco DG. Apolinario 39
Power System Analysis and Design
c. Most natural faults occur somewhere between these Z = impedance (Ω)
two extremes. The phase angle θ gives the phase relationship between
11. Every practical circuit contains resistance (R) and inductive current and the voltage.
reactance (X). These are electrically in series. Their 12. Power factor is defined as a ratio of real power (KW) to
combined effect is called “Impedance (Z)”. Impedance is apparent power (KVA).
defined as the total opposition to current flow in a circuit. The KW Power
mathematical representation for the magnitude of pf= =Real
KVA Apparent Power
impedance in an AC circuit is
Z=√R2 +X2
where
Z = impedance (Ω) Figure 106 Power Triangle
R = resistance (Ω) The active current is in phase with the voltage. The actual
X = net reactance (Ω) current, as read on an ammeter, lags the voltage by an
amount equal to the phase angle.
Power factor= cos θ
The power factor is said to be 1 or unity or 100% when the
current and the voltage are in phase i.e. when 𝜃 =
0° (cos 0° = 1). The power factor is 0 when 𝜃 =
90° (cos 90° = 0).
13. X/R Ratio: In the impedance diagram above, the resultant
angle 𝜃 is between the voltage and current waves and is
called the “Phase Angle”. The voltage leads the current or
the current lags the voltage by an amount equal to the phase
angle.
Figure 105 Impedance Triangle The X/R value is determinant as to how long a short circuit
The current through a certain resistance is always in phase current will remain on a circuit, if uninterrupted by an
with the applied voltage. Resistance is shown on the zero – overcurrent protective device. Mathematically it is given by
axis. The current through an inductor lags applied voltage by X
= tan θ
90°; inductive reactance is shown along the 90° axis. R
Current through a capacitor leads applied voltage by 90°; If a circuit has an X/R ratio less than the value specified for
capacitive reactance is shown along the - 90° axis. Net the proof testing of a given breaker type, the circuit breaker
reactance in an AC circuit is the difference between can be evaluated by direct comparison of its short circuit
inductive and capacitive reactance. The mathematical rating with the calculated symmetrical fault current. When
representation for the calculation of net reactance when XL the circuit X/R ratio is above the specified value, multiplying
is greater than XC is factors must be applied to the calculated symmetrical short
X=XL -XC circuit current to properly evaluate the device rating.
where The X/R ratio determines the power factor of a circuit and
X = net reactance (Ω) table 9 shows the short circuit power factor relationships
XL = inductive reactance (Ω) Multiplying Factor
XC = capacitive reactance (Ω) Maximum Average
Equation below is the mathematical representation for the Short Single Three Maximum
Short
calculation of net reactance when XC is greater than XL. Circuit Phase Phase Peak
Circuit
Power RMS RMS Amperes
X=XC -XL X/R Ratio
Factor % amperes amperes at ½
Impedance is the vector sum of the resistance and net
at ½ at ½ Cycle
reactance (X) in a circuit. The angle θ is the phase angle and Cycle Cycle
gives the phase relationship between the applied voltage 0 Infinite 1.732 1.394 2.828
and the current. Impedance in an AC circuit corresponds to 5 19.975 1.568 1.301 2.625
the resistance of a DC circuit. The voltage drop across an 10 9.9501 1.436 1.229 2.455
AC circuit element equals the current times the impedance. 20 4.8990 1.247 1.127 2.183
Equation below is the mathematical representation of the 30 3.1798 1.130 1.066 1.978
voltage drop across an AC circuit. 50 1.7321 1.026 1.013 1.694
V=IZ 100 0.0 1.000 1.000 1.414
where Table 8
V = voltage drop (V) 14. Withstand Rating: The energy of a fault can be measured
I = current (A) by the formula; Thermal Energy = I2t. For example, if a short
circuit is 10,000 amps (I) for .01 second, I2t = 1,000,000. A
Electrical Engineering Department | Engr. Gerard Francesco DG. Apolinario 40
Power System Analysis and Design
short circuit of 7,500 amps can melt a #8 copper wire in 0.1 4πτ
second. The maximum specified value of Voltage and -
√ X
Current that equipment can safely “handle” is known as its k(τ)= 1+2e R
phase fault, which means all three phases connected together Resistance and reactance are calculated at the voltages for
with no added impedance. X/R is the ratio of reactance to the points in the circuit where the short circuit currents are
resistance in the supply. In a MV network the rated voltage is the calculated. For example, even though the utility voltage may
unique parameter usually known. The short circuit power can be 69 kV, if the short circuit currents are being calculated
indicatively vary from 250MVA to 500MVA for systems up to further down the circuit where the voltage is 2400 V, the
30kV. When the voltage level rises, the short circuit power can resistance and reactance will be calculated at 2400 V.
indicatively vary between 700MVA and 1500MVA. The voltage Calculate resistance and reactance for the utility at the utility
values of the MV distribution network and the relevant short circuit voltage and work down through a circuit, encountering
power values accepted by the Standard IEC 60076 – 5 are transformers. Applying the conservation of energy, energy
reported in table 10: into the transformer (V12/R1) equals energy out of the
Distribution
Short Circuit Short Circuit transformer (V22/R2).
Apparent Power Apparent Power V2 2
Network Voltage
(MVA) – European (MVA) – North R2 =R1 ( )
(kV) V1
Practice American Practice
7.2 – 12 – 17.5 – 24 500 500 where R2 = resistance at the secondary voltage
RA =(0.16+0.72)∥6=0.7674 Ω 410 V
IB = =35182.7305 A=ISC3
ZA =√X2A +R2A =1.7236 Ω
√3(6.7281 m)
R
-3( B )
20 kV k=1.02+0.98e XB =1.4605
IA = =6699.3533 A=ISC3 IPB =√2ISC3 k= 72667.1878 A
√3(1.7236) If Fault Arc occurs,
R
-3( A )
k=1.02+0.98e XA =1.2405 ISC3 (max)=0.8 ISC3 =28146.1844 A
IPA =√2ISC3 k=11753.0041 A IPB (max)=58133.75 A
ISC3 (min)=0.5 ISC3 =17591.3653 A
IPB (min)=36333.59 A
At Fault C (LV sub distribution board):
Circuit Breaker
Xcb =0.15 mΩ
Cable 1 (one 400 mm2 cable per phase)
0.15m
XC1 = ×80=12 mΩ
1m
ρl 80
RC1 = =0.036× =7.2 mΩ
A 400
XC =XB +0.15m+12m=18.6511 mΩ
RC =RB +7.2m=8.933 mΩ
Advantages:
1. If a fault occurs on any feeder, the voltage drop in its reactors Advantages:
will not affect the busbar voltage, thus there is little tendency 1. There are effectively two reactors in series between
for the generator to lose synchronism. sections so that the reactors must have
2. The fault on the other feeder will not affect the other feeders approximately half the reactance of those used in
and consequently the effects of faults are localized. comparable ring system.
Disadvantages: 2. Additional generators may be connected to the
1. There is a constant power loss and voltage drop in the system without requiring changes in the existing
reactors even during normal operation. reactors.
2. If a short circuit occurs at the bus bars, no protection is Examples:
provided to the generators. However, this is of little 1. A 3 phase, 20 MVA, 10 kV alternator has internal reactance
importance because such faults are rare and modern of 5% and negligible resistance. Find the external reactance
generators have considerable leakage reactance to enable
per phase to be connected in series with the alternator so
them to withstand short circuit across their terminals.
3. If the number of generators is increased, the size of feeder that steady current on short circuit does not exceed 8 times
reactors will have to be increased to keep the short circuit the full load current.
currents within the ratings of the feeder circuit breakers. 2. Three 20 MVA generators, each with 0.15 pu reactance, are
Bus bar Reactors – the reactors are located in the busbars connected through three reactors to a common bus – bar of
a. Ring System voltage 11 kV. Each feeder connected to the generator side
In this system, busbar is divided into sections and these of a reactor has 200 MVA circuit breaker. Determine the
sections are connected through reactors as shown. minimum value of reactor reactance.
3. The section bus bars A and B are linked by a bus bar reactor
rated at 5000 kVA with 10% reactance. On bus bar A, there
are two generators each of 10,000 kVA with 10% reactance
and on B two generators each of 8000 kVA with 12%
reactance. Find the steady MVA fed into a dead short circuit
between all phases on B with bus bar reactor in the circuit.
Advantages:
1. Under normal operating conditions, each generator
will supply its own section of the load and very little 4. A three phase short – circuit fault occurs at point F in the
power will be fed by other generators. system show. Calculate the fault current.
2. Low power loss and voltage drop in the reactors
3. If a fault occurs on any feeder, only one generator
mainly feeds the fault while the current fed from other
generators is small due to the presence of the
reactors.
fault applied. The 𝜆𝑚𝑎𝑥 and 𝜆𝑚𝑖𝑛 values for turbo generators and for machines
Peak short circuit current iP with salient poles are indicated as: (series 1 in IEC 60909)
Peak value iP of the short circuit current in no meshed systems,
the peak value iP of the short circuit current may be calculated for
all types of faults using the equation:
ip =K√2IK "
K = is a factor depending on R/X and can be calculated
approximately using the following equation:
R
-3( )
K=1.02+0.98e X
Short circuit breaking current I b
Calculation of the short circuit breaking current IB is required only
when the fault is near the generator and protection is ensured by
time delayed circuit breakers. Note that this current is used to
determine the breaking capacity of these circuit breakers.