Design Calculation of Thrustblock: Central Doha & Corniche Beautification Package 2A
Design Calculation of Thrustblock: Central Doha & Corniche Beautification Package 2A
DUCTILE
PIPE SIZE PLASTIC
DETERMINE IRON
CROSS 4" 13.203 14.120
SECTIONAL 6" 29.802 29.033
8" 53.716 50.014
AREA OF PIPE
10" 83.000 75.276
INTERIOR:
12" 119.597 105.683 195 SQ / IN
.12567 SQM
HIGHEST
ANTICIPATED
WATER
PRESSURE: 130.60
P.S.I
9 bar
ANGLE OF 45.00
T = Thrust DEG.
CHANGE & 45 degree
RESULTING P = Water Pressure
THRUST ON A = Cross sectional area
19491.60
FITTING: of pipes interior
LBS THRUST
Note:
HEIGHT OF 1. Block height should be equal to or less than one
BLOCK: half the total depth to the bottom of the block, but
not less than the pipe diameter.
2. Block height should be chosen such that the
calculated block width is between one & two times 3.93 FEET 1.2m
the height.
0.679 m2
Note:
7.31 ft REQUIRED AREA
1. Thrust blocks shall be of a concrete mix not
0.567m
1.86 ft
leaner than: 1 part cement CALCULATED
REQUIRED
2-1/2 parts sand WIDTH
BLOCK AREA,
5 parts stone
WIDTH, DEPTH &
0.93 ft
CALCULATED
VOLUME 2. Where possible the bearing surface of the block should be placed 0.284m
DEPTH
against undisturbed soil. Where it is not possible, fill between the
0.192 m3
6.80 cu.ft.
bearing surface and undisturbed soil must be compacted to at least 90% CALCULATED
standard proctor density VOLUME