0% found this document useful (0 votes)
117 views1 page

Design Calculation of Thrustblock: Central Doha & Corniche Beautification Package 2A

This document summarizes the calculation of the thrust block for a water pipeline project. It determines the soil type and bearing strength is 4000 pounds per square foot. It then calculates the cross-sectional area of the pipe as 195 square inches. The highest anticipated water pressure is 130.6 PSI. This results in a thrust of 19491.6 pounds on a 45 degree fitting. The required size of the concrete thrust block is then calculated as 7.31 square feet in area, 7.31 feet in width, 1.86 feet in depth, and 6.8 cubic feet in volume. The summary concludes that this thrust block design is safe.

Uploaded by

Md Arif
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
117 views1 page

Design Calculation of Thrustblock: Central Doha & Corniche Beautification Package 2A

This document summarizes the calculation of the thrust block for a water pipeline project. It determines the soil type and bearing strength is 4000 pounds per square foot. It then calculates the cross-sectional area of the pipe as 195 square inches. The highest anticipated water pressure is 130.6 PSI. This results in a thrust of 19491.6 pounds on a 45 degree fitting. The required size of the concrete thrust block is then calculated as 7.31 square feet in area, 7.31 feet in width, 1.86 feet in depth, and 6.8 cubic feet in volume. The summary concludes that this thrust block design is safe.

Uploaded by

Md Arif
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DESIGN CALCULATION OF THRUSTBLOCK

PROJECT NAME: Central Doha & Corniche Beautification Package 2A

PROJECT NUMBER: 0-00-00396


DATE: 16.08.2014 BY: ARIF SK

BEARING STRENGTH LB / FT SQ.


MUCK: 0
SOFT CLAY: 1000
DETERMINE SOIL SILT: 1500
TYPE & BEARING SANDY SILT: 3000
STRENGTH: SAND: 4000
SANDY CLAY: 6000
HARD CLAY: 9000 4000 LB / FT SQ. 200 KN/M2

DUCTILE
PIPE SIZE PLASTIC
DETERMINE IRON
CROSS 4" 13.203 14.120
SECTIONAL 6" 29.802 29.033
8" 53.716 50.014
AREA OF PIPE
10" 83.000 75.276
INTERIOR:
12" 119.597 105.683 195 SQ / IN
.12567 SQM

HIGHEST
ANTICIPATED
WATER
PRESSURE: 130.60
P.S.I
9 bar

ANGLE OF 45.00
T = Thrust DEG.
CHANGE & 45 degree
RESULTING P = Water Pressure
THRUST ON A = Cross sectional area
19491.60
FITTING: of pipes interior
LBS THRUST

Note:
HEIGHT OF 1. Block height should be equal to or less than one
BLOCK: half the total depth to the bottom of the block, but
not less than the pipe diameter.
2. Block height should be chosen such that the
calculated block width is between one & two times 3.93 FEET 1.2m
the height.

0.679 m2
Note:
7.31 ft REQUIRED AREA
1. Thrust blocks shall be of a concrete mix not
0.567m
1.86 ft
leaner than: 1 part cement CALCULATED
REQUIRED
2-1/2 parts sand WIDTH
BLOCK AREA,
5 parts stone
WIDTH, DEPTH &
0.93 ft
CALCULATED
VOLUME 2. Where possible the bearing surface of the block should be placed 0.284m
DEPTH
against undisturbed soil. Where it is not possible, fill between the
0.192 m3
6.80 cu.ft.
bearing surface and undisturbed soil must be compacted to at least 90% CALCULATED
standard proctor density VOLUME

HENCE THE THRUST BLOCK IS SAFE