0% found this document useful (0 votes)
288 views8 pages

Single Phase Recloser Catalog

The document provides information on Rockwill Electric's RCW series of automatic circuit reclosers for overhead distribution lines and substations ranging from 11kV to 38kV. It details the technical specifications, components, protection functions, communication capabilities, and dimensions of the recloser models. The reclosers integrate control, protection, measurement, communication and fault detection for distribution automation applications.

Uploaded by

Cesar Venturo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
288 views8 pages

Single Phase Recloser Catalog

The document provides information on Rockwill Electric's RCW series of automatic circuit reclosers for overhead distribution lines and substations ranging from 11kV to 38kV. It details the technical specifications, components, protection functions, communication capabilities, and dimensions of the recloser models. The reclosers integrate control, protection, measurement, communication and fault detection for distribution automation applications.

Uploaded by

Cesar Venturo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

RCW□-1

Pole mounted single phase vacuum Recloser


6kV,….38kV, 630A,..800,….1250A

Provided Customized manufacture


Whole solutions for design, assembly, test…

Catalog

Best solution for your power!


1. Summary
Rockwill Electric strives to bring our customers the latest technology and competitive pricing and
best service for distribution automatic.
The RCW series automatic circuit reclosers can use on overhead distribution lines as well as
distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power
system. and its rated current can reach 1250A.
The RCW series automatic circuit reclosers integrates the functions of control, protection,
measurement, communication, fault detection, on-line monitoring of closing or opening.

2. Service environment
a) Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 2500m or more higher.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake

3. Offering
With optional classes for rated current range:
For 15kV, with 630A, 20kA Breaking capacity. 800A, 20kA capacity, and 1250A, 20kA.
For 27kV, with 630A, 20kA Breaking capacity. 800A, 16kA capacity, and 1250A, 25kA.
For 38kV, with 800A, 20kA,. and expanding 1250A, .25kA RCW38M type..
With optional classes for installation styles:
Single phase, vacuum recloser and Three phase, vacuum recloser.
With optional relay protection curves for user choice:
Instantaneous over-current protection.
Timing over-current protection.
Negative sequence over-current protection.
Directional over-current protection(*).
Over-voltage protection./Under voltage protection.
Earth fault protection/Sensitive earth fault protection.
More relay functions can be customized.
With optional choice by locally or remotely.
With optional communication protocols & I/O port for user choice:
RS-232 and RS-485 ports supporting.
DNP3.0 communication protocol support(*).
Modbus communication protocol is optional(*).
IEC 60870-5-101 communication protocol support.
IEC 60870-5-104 communication protocol support. (*).
The recloser can communicate through GPRS(Or GSM) modem with English or Chinese languege
(*).With optional functions for user.
Rated currents, System phase current. Rated voltages, System phase voltage& secondary low
voltage power supply voltage. Frenquency, power(kWh), reactive power(kVarh),power factor .
With optional reclosing interval for user pre-program:
Reclosing times setting support.
Dead time setting support.
With events recording function:
SOE 1000 operations record.
Fault record and normal operation record.
Note: (*) mean should customized by manufacturer if needed.

4. Recloser feature

4.1 Outline of recloser:


The RCW series vacuum recloser is mainly combined
with integration terminal, current transformer, permanent
magnetic actuator and its recloser controller.

4.2 The recloser tank feature:


The Vacuum recloser tanks are manufactured from
304#grade stainless steel and are powder coated
a light grey colour.
Whole recloser IP65 protection class, equipped with
a auxiliary plug to connect with recloser controller by
control cable, Diameter Max22mm, 6 M length(8M for special). .
Its can performance serve more than 20 years long term under heavy duty circumstance.

4.3 The recloser vacuum embedded pole feature:


The recloser’s vacuum interrupter insert in
an epoxy resin solid pole, and external
coated with a high reliable, stable material:
Fluorocarbon silicone rubber
(γ-trifluoro propyl methyl polysiloxane)
With excellent electric insulation,
weather resistance, ozone, biological inertia,
can be stand under the long-term use in -55 ~ +200 ℃.

Creepage Distances of RCW


15kV BIL 15kV BIL 27kV BIL 27kV BIL 38kV BIL
Description
95/110kV 125kV 125kV 150kV 170/185kV
T to T* 480/646mm 646mm 796mm 796mm 1145mm
T to G/E* 480/763mm 763mm 763mm 1126mm 1126mm

T to T* -----Terminal to terminal creepage


T to G/E* -----Terminal to ground/earth creepage
5. Main new advantages of RCW
High reliable manual opening device

Visible ON/OFF indicator IP64 class waterproof plug connector


Note:
ROCKWIILL Supply special design manual closing device technology with own patent,It applied for
nomal and abnormal situation closing. Its closing speed(time) comply with IEC62271-100.
This function can offset from magnetic actuator fault which when ctuator can’t work will cause the
major accident..
----------------------------------------------------------------------------------------------------------------------

Primacy incomer Vacuum interrupter(Adopt the


terminal(directly connect to APG technology with external
interrupter reduce power lost) silicone rubber mold pressure
Current transformer(external covering, increasing the whole
modular design easy for quality insulation and weathering
control and maintenance) performance)

----------------------------------------------------------------------------------------------------------------------
Internal Voltage sensors
Shielded 4-conductor cable
incorporated within the
connection
vacuum interrupter module
Magnitude Accuracy: ±2.0%
Source-side or Load side
Phase Accuracy:±1.5 %
connections
Voltage Sensor Ratio:500/1 or
Eliminate external
1000/1
voltage-sensing PTs
----------------------------------------------------------------------------------------------------------------------
Apply ANSOFT design the high performance magnetic actuator,
high reliable and free maintenance. Through 35,000 times opening
reverse excitation test, the demagnetization rate less than 1%.
Note:
ROCKWIILL supply special patent modular design mono-stable
type magnetic actuator with two coils controlling.Its the best design
for vacuum circuit breaker.
6. Main technical data

No. Item Unit data


1 Rated voltage kV 11/15 27 38
2 Rated current A 630 630/1250 630/1250
3 Rated frequency HZ 50/60
4 Power frequency 1min Dry kV 49/55 65 85/95*
Wet 38/45 55 80
5 Lightning impulse withstand voltage(peak kV 95/110 150 185
value)alternate, opposite/fracture
6 Rated short circuit breaking current kA 20 16/25 20/25
7 Rated short current switching current(peak value) kA 50 40/63 50/63
8 Rated peak value withstand current kA 50 40/63 50/63
9 4S short time withstand current kA 20 16/25 20
10 Rated operating circulate O-T1-CO-T2-CO-T3-CO-T4-CO
11 Breaking current frequency under rated short times 30
circuit
12 Mechanism life times 10000
13 Secondary loop 1 min power frequency withstand kV 2
voltage

7. Accessories of RCW

Upper voltage shield 3 pcs/set Lower expaning bushing 3 pcs/set


Note:
all above insulating components for BIL 170kV expanding using. Any question pls contact with
our engineer.

Upper terminal 3 pcs/set Lower termianl 3 pcs/set


Note:
Standard made of T2 copper material, for 630A rated current using.
With expanding range.
8. Outline &Sizes for RCW
38kV BIL170/185kV Recloser switch dimensional drawing

Installation reference for single pole schema


15/27kV BIL125/150kV Recloser switch dimensional drawing

Installation reference for single pole schema


12/15kV BIL110kV Recloser switch dimensional drawing

9. Technical service
Rockwill,China. Provide with best support, If you have any question pls consult below.
Rockwill, CHINA. Tel: 0086-577-27869968 . Email: [email protected]