SmartLine

Technical Information

SLG 700 SmartLine Guided-Wave Radar


Level Specification
34-SL-03-03, August 2016

Introduction

Part of the SmartLine® family of products, the SLG 700


series level transmitters feature high performance guided
wave radar level technology. They provide high accuracy,
stability, and applicability suitable for a variety of level and
interface applications. SmartLine SLG 700 level transmitters
are ideally suited for your demanding process tank level
needs.

The SmartLine Level transmitter features the same powerful


features with the other transmitters in the SmartLine family
including modular design, polarity insensitivity, transmitter
messaging, tamper notification, and integration with
Experion® PKS thus providing the highest level of
compatibility assurance and integration capabilities.
A new SmartLine Application and Validation Tool provides a
new level of user experience and increases engineering
productivity.

Best in Class Features:

o Two-wire, loop-powered 4-20 mA transmitter


o Accuracy ±3 mm or 0.03% of measured distance
Figure 1 - SLG 700 SmartLine Level Transmitter
whichever is greater
o Repeatability ±1mm
Best in Class Features (continued):
o Integral dual seal design for safety based on
ANSI/NFPA 70-202 and ANSI/ISA 12.27.01 o 4-20 mA, HART and Foundation Fieldbus output
o Temperature range: -60 to 450C o External zero, span, & configuration capability
o Pressure range: -1 to 400 bar o 0.4 to 50 m range
o SS316L or Hastelloy-C (C-276) wetted parts
o Automatic temperature compensation Communications / Output Options:
o Advanced local display and local push buttons o 4-20 mA DC
(optional)
o HART® (version 7.0)
o Polarity insensitive electrical connections
o Comprehensive on-board diagnostic capabilities o FOUNDATION™ Fieldbus
o Full compliance to SIL 2/3 requirements as a standard
SmartLine Level transmitters are available with the
o Modular design
above listed communications protocols.
o Dual compartment design
2 SLG 700 SmartLine Level Transmitter

Figure 2 - Inserting tank specific details into Application and Validation Tool.

Description
The SmartLine Guided Wave Radar Level transmitter In addition to serving as engineering documentation, the
utilizes Time Domain Reflectometry (TDR) technology AVT output also serves as input to the Honeywell order
which is proven to be effective for a majority of level management system thus ensuring correct input of the
measuring applications. transmitter model and the advantage of a transmitter with
configuration parameters already specified to match the
targeted tank application. Errors are eliminated and the
Unique Out-of-the-Box, Fool Proof User engineering effort is preserved from start to finish.
Experience
The user experience of the SmartLine Level transmitter The SmartLine Application and Validation Tool also allows
addresses one of the most common failure modes users to collaboratively use and share the active session
associated with specifying, ordering and implementing level with any web connected colleague or expert. This
transmitters, which is the specification of the correct level interactive, collaborative capability eliminates roadblocks
transmitter for the tank level application. Unique to the and delays, thus users can access resources to help start
SmartLine Level offering is a new, online SmartLine and finish the engineering task in a single effort. This online
Application and Validation Tool (AVT), which allows users tool also dynamically reformats the user interface to
to specify their tank level application and the options correctly display on an Apple iPad, iPhone or Android
desired for their level transmitter. The AVT intelligently device.
guides the user through the engineering process and
electronically captures and documents the choices and
inputs.
SLG 700 SmartLine Level Transmitter 3

Unique Indication/Display Options Modular Design


The SmartLine SLG series level transmitter’s modular To help contain maintenance and inventory costs, all SLG
design accommodates a unique advanced graphics LCD series transmitters are modular in design supporting the
display with many unparalleled features (as an option). user’s ability to change electronic modules without affecting
overall performance or approval body certifications.
Electronic modules may be swapped with another electronics
module without losing in-tolerance performance
characteristics.

Modular Features
o Exchange / replace electronics / comms modules
o Add or remove lightning protection (terminal connection)
With no performance effects, Honeywell’s unique modularity
results in lower inventory needs and lower overall
operating costs.

Configuration Tools
Integral Three Button Configuration Option
Suitable for all electrical and environmental requirements,
SmartLine offers the ability to configure the transmitter and
Advanced Graphics LCD Display Features display via three externally accessible buttons. Zero or
o Modular (may be added or removed in the field) span capabilities are also optionally available via these
o 0, 90, 180, & 270 degree position adjustments buttons, without selection of a display option.
o Standard and custom measurement units available.
(custom measurement units applicable only for FF) Hand Held Configuration
o Eight display screens with 3 formats are possible SmartLine transmitters feature two-way communication and
o 128 by 64 dot matrix graphics display configuration capability between the operator and the
o Large PV, Bar graph and Trend graph format transmitter. This is accomplished via Honeywell’s field-rated
supported (for any of the 8 screens). Echo stem plots Multiple Communication Configurator (MCT202 and
with Distance to Product and Distance to Interface MCT404).
Configurable screen rotation timing The MCT202 and 404 are capable of field configuring DE and
HART Devices and can also be ordered for use in intrinsically
o The Display supports English, German, safe environments. All Honeywell transmitters are designed
French, Spanish, Italian, Turkish & Russian and tested for compliance with the offered communication
protocols and are designed to operate with any properly
Diagnostics
validated hand held configuration device.
SmartLine transmitters all offer digitally accessible
diagnostics which aid in providing advanced warning of Field Service Tool – DTM based technology
possible failure events minimizing unplanned shutdowns, SmartLine Level utilizes the standard unified DTM
providing lower overall operational costs technology to access device parameters but utilizes its
fullest potential in the creation of our new Field Service
System Integration Tool. Using a commonly available DTM container, the
o SmartLine communications protocols all meet the most SmartLine Level Field Service Tool provides both a novice
current published standards for HART or FOUNDATION mode and an expert user mode. Novice users are offered a
Fieldbus. guided experience to setup the device parameters while
o Integration with Honeywell’s Experion PKS offers the expert users can easily access the parameters desired
through the organized parameter pages. The Field Service
following unique advantages.
Tool runs on any PC and avoids the need for a handheld
 Transmitter messaging configurator.
 Maintenance mode indication
 Tamper reporting Personal Computer Configuration
 FDM Plant Area Views with Health summaries Honeywell’s Field Device Manager (FDM) Software and FDM
 The SLG series is Experion tested to provide the Express are available for managing HART & FOUNDATION
highest level of compatibility assurance. Fieldbus device configurations.
4 SLG 700 SmartLine Level Transmitter

General Specifications
Parameter Description
Measurable media Liquids and solids (future)
Measurements performed Level, volume, interface
Process Storage Tank types Vertical and horizontal cylinders, rectangular tanks, spheres, stilling / bypass wells
SIL certification SIL 2/3

Measuring range Liquids 0.4 to 50 m (1.3 to 164 ft)

Available probe types Rod, wire, coax

Wetted materials SS 316L, C-276, PTFE (future)

O-Ring Seal Materials Material Min Temp Max Temp


Please see Figure 4 ®
Viton or Fluorocarbon -26 degC 200 deg C

Ethyelene Propylene (EPDM) -40 degC 150 deg C


Kalrez 6375 perfluorelastomer -20 degC 200 degC (sat steam max 150 degC)

Buna-N -40 degC 120 degC


Metallic - 17-4 PH -60 degC 450 degC
Metallic - Alloy 718 NACE -60 degC 450 degC
Pure polyester powder-coated low copper (<0.6%) aluminum
Electronic Housing Meets NEMA 4X, IP66, IP67
All stainless steel housing and remote electronics (with 3 m cable) is optional
User Interface 3 button keypad
Display 128 x 64 pixels LCD
Output Units Level: ft, in, m, cm, or mm
Volume: ft3, in3, US gal, Imp gal, barrels, yd3, m3, liters
Rate: ft/s, m/s, in/min, m/h, ft/min, in/sec
Output Process Variables • Level
• Percentage Level
• Distance to Level
• Level Rate
• Volume
• Vapor (Ullage) Thickness
• Vapor (Ullage) Thickness %
• Vapor (Ullage) Volume
• Distance to Interface
• Interface Level
• Interface Level Rate
• Upper Layer Thickness
• % Interface Level
• Lower Volume
• Upper Volume
Language English, German, Italian, French, Spanish, Russian and Turkish
Electrical Connections SLG 700 series: ½ -inch NPT(female), M20 (female)
Wiring Accepts up to 16 AWG (1.5 mm diameter).
Mounting Available with compact housing or remote mount housing option (future).
Dimensions See page 14 for dimensional drawings.
Net Weight SLG 700 series: 3.2 kilograms (7 lbs) for aluminum housing
SLG 700 SmartLine Level Transmitter 5

Operating Conditions – All Models


Parameter Rated Condition Operative Limits Transportation and
Storage
C F C F C F
Ambient Temperature1 -40 to 85 -40 to 185 -40 to 85 -40 to 185 -55 to 120 -67 to 248

Process Connector2
SLG 720 -40 to 200 -40 to 392 -40 to 200 -40 to 392 -55 to 125 -67 to 257
SLG 726 -60 to 450 -76 to 842 -60 to 450 -76 to 842 -55 to 125 -67 to 257
Humidity %RH 0 to 100 0 to 100 0 to 100
Maximum Allowable Working SLG720: 40 bar (580 psi)
Pressure
SLG726: 400 bar (5800 psi)
(MAWP) 3, 4
Supply Voltage, Current, and Voltage at HART terminal is 14.0 to 42.0 Vdc (IS versions limited to 30 Vdc)
Load Resistance
0 to 1300 ohms (as shown in Figure 3 -)
(HART)

1 LCD Display operating temperature -20C to +70C . Storage temperature -30C to 80C.

2 rated Condition and Operative Limit temperatures subject to O-Ring selection and ambient temperature conditions. See Error! Reference source not found.

or details.
3 Units can withstand overpressure of 1.5 x MAWP without damage

4 Consult factory for MAWP of SLG 700 transmitter with CRN approval

Figure 3 - Supply voltage and Loop resistance chart & calculations


(not applicable for Fieldbus)
6 SLG 700 SmartLine Level Transmitter

Performance Under Rated Conditions – All Models


Parameter Description
Measuring principle Time Domain Reflectometry (TDR)
Analog Output Two-wire, 4 to 20 mA (HART transmitters only)
Digital Communications: HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant
All transmitters, irrespective of protocol have polarity insensitive connection.
Output Failure Modes Honeywell Standard: NAMUR NE 43 Compliance:
Normal Limits: 3.8 – 20.8 mA 3.8 – 20.5 mA
Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA ≤ 3.6 mA and ≥ 21.0 mA
Span 0.4 m (15.75 inches) to 50 m (164 feet)
Resolution ±1 mm (0.04 inch)
Accuracy Rod 0.03% of level or ± 3mm (whichever is greater)
Reference conditions are
Wire 0.03% of level or ± 3mm (whichever is greater)
given in the table below
Coax 0.03% of level or ± 3mm (whichever is greater)
Ambient temperature Effect ±0.2mm/degree K or ±30 ppm/Deg K of measured value whichever is greater
Repeatability ±1 mm (0.04 inch)
Dielectric constant (minimum) 1.4
Damping Time Constant HART: Adjustable from 0 to 60 seconds in 0.1 increments.
Default Value: 2 seconds
Electromagnetic Compatibility IEC61326 (All transmitters), NAMUR NE21 (HART & 4-20mA)
Lightning Protection Option Leakage Current: 10 uA max @ 42.0 VDC 93C
Impulse rating:
8/20 uS 5000 A (>10 strikes) 10000 A (1 strike min.)
10/1000 uS 200 A (> 300 strikes)

Reference Conditions
Parameter Unit Reference Condition
Ambient Temperature C 25 ± 1
Process Temperature C 25 ± 1
Humidity % RH 0 - 85
Flange diameter for rod, wire configurations mm >300
Reference product in the Single NA Air / Water
tank Two (non-flooded) NA Air / Oil (DC=2) / Water
Minimum distance to walls and obstacles mm 400
Process pressure kPa 100 ± 10

Sensor Details – All Models


Parameter Description
Type Min/ Max length Materials
Rod 0.4m (1.3 ft) / 6.3m (20.7 ft) SS 316L, C-276
Probe
Wire 1.0m (3.3 ft) / 50m (164 ft) SS 316
Coax 0.4m (1.3 ft) / 6.3m (20.7 ft) SS 316L, C-276
SLG 700 SmartLine Level Transmitter 7

Maximum measurement range versus Dielectric Constant


Probe Wire Rod Coax
Min DC Range (m) Min DC Range (m) Min DC Range (m)
1.4 15 1.4 6.3 1.4 6.3
1.8 25
3 42
4 46
6 50

Centering Disk
Parameter Description
Type Min/ Max diameter Materials
Centering Disk
Rod and Wire 5.08 cm (2 in) / 20.32 cm (8 in) SS 316L, C-276

Figure 4 - Transmitter O-Ring Seal Material Temperature Applicability SLG720


8 SLG 700 SmartLine Level Transmitter

Figure 5 - SLG 726 Temperature Limits

Figure 6 - SLG 726 Maximum Pressure based on Maximum Temperature


SLG 700 SmartLine Level Transmitter 9

MAX PRESSURE AMBIENT TEMPERATURE [oC]


[bar]
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 85
-60 400 400 400 400 400 400 400 400 375 375 350 350 325 325
-50 400 400 400 400 400 400 400 400 375 375 350 350 325 325
0 400 400 400 400 400 400 400 375 375 350 350 325 325 300
PROCESS TEMPERATURE [oC]

50 400 400 400 400 400 400 400 375 375 350 350 325 300 300
100 400 400 400 400 400 400 375 375 350 350 325 325 300 -

150 400 400 400 400 400 400 375 375 350 350 325 325 300 -
200 400 400 400 400 400 375 375 350 350 325 325 300 - -
250 400 400 400 400 400 375 375 350 350 325 325 300 - -

300 400 400 400 400 375 375 350 350 325 325 300 300 - -
350 400 400 400 400 375 375 350 350 325 325 300 - - -
400 400 400 400 375 375 350 350 325 325 300 300 - - -

450 400 400 400 375 375 350 350 325 325 300 300 - - -

INTRINSICALLY SAFE (IS) NON-(IS)

Figure 7 - SLG 726 Maximum pressure based on maximum operating temperature in tabular form
10 SLG 700 SmartLine Level Transmitter

Communications Protocols & Diagnostics


HART Protocol
Schedule Entries
Version: HART 7 45 maximum schedule entries
Power Supply 50 maximum Links
Voltage: 14.0 to 42.0 Vdc at terminals Number of VCRs: 50 max
Load: Maximum 1300 ohms. See Operating Conditions –
Compliance Testing: Tested according to ITK 6.1.2
All Models table.
Minimum Load: 0 ohms. (For handheld communications a
Software Download
minimum load of 250 ohms is required)
Utilizes Class-3 of the Common Software Download
procedure as per FF-883 which allows the field devices of
FOUNDATION Fieldbus (FF) any manufacturer to receive software upgrades from any
Power Supply Requirements host.
Voltage: 9.0 to 32.0 Vdc at terminals
Standard Diagnostics
Steady State Current: 19.6 mAdc
SLG 700 series top level diagnostics are reported as
Software Download Current: 29.4 mAdc
either critical or non-critical and readable via DD or DTM
Block Type Qty Execution Time tools or integral display.
Resource 1P NA/a Other Certification Options
Level Transducer 1P NA See Approval Certifications Table for details on page 11.
Materials
Level Auxillary Transducer 1P NA
o NACE MRO175, MRO103, ISO15156
Diagnostic 1P NA

LCD Display 1P NA o For Hazardous Location certifications to:


CSA (Canada and USA), ATEX, IECEx, SAEx, FM,
Analog Input 1P 5I 30 ms NEPSI and CCoE.
PID w/Autotune 1P 1I 45 ms
 FM for Explosion Proof and Intrinsic Safety
Arithmetic 1P 1I 30 ms
 Canadian Standards (CSA) Explosion Proof and
Input Selector 1P 1I 30 ms
Intrinsic Safety
P = Permanent Block
I = Instantiable Block  Cenelec ATEX Explosion Proof and Intrinsic
Safety
All available function blocks adhere to FOUNDATION  IECEx Explosion Proof and Intrinsic Safety
Fieldbus standards. PID blocks support ideal & robust
PID algorithms with full implementation of Auto-tuning. o Steam Boiler Certification (future)
Link Active Scheduler o Pressure Equipment Directive (PED)
Transmitters can perform as a backup Link Active
Scheduler and take over when the host is disconnected. o CE Mark

Acting as a LAS, the device ensures scheduled data o Overfill protection (WHG)
transfers typically used for the regular, cyclic transfer of
o CRN Registration (see table below for specifics)
control loop data between devices on the Fieldbus.
Number of Devices/Segment o SIL 2/3 Level Compliance
Entity IS model: 6 devices / segment
o Positive Material Identification (PMI)
SLG 700 SmartLine Level Transmitter 11

Approval Certifications:
COMM. FIELD AMBIENT TEMP
AGENCY TYPE OF PROTECTION
OPTION PARAMETERS (Ta)

Explosion Proof with intrinsically safe


output:
Class I, Division 1, Groups A, B, C, D;
Class I, Zone 0/1 AEx d[ia] IIC T4 Ga/Gb
Ex d[ia] IIC T4 Ga/Gb
All Note 1 -50 °C to 85 °C

Dust Ignition Proof:


Class II, Division 1, Groups E, F, G; T4
Class II Zone 21 AEx tb IIIC T95 oC
CSA DIP A21/II, III /1/EFG/Ex tb IIIC T95 oC
cCSAus Intrinsically Safe:
(Canada and 4-20 mA / HART Note 2a -50 °C to 70 °C
Class I, II, III, Division 1, Groups A, B, C,
USA)
D, E, F, G; T4
Class 1 Zone 0 AEx ia IIC T4 Ga FOUNDATION
Note 2b/2c
-50 °C to 70 °C
Ex ia IIC T4 Ga Fieldbus / FISCO

Nonincendive with intrinsically safe


4-20 mA / HART Note 1 -50 °C to 85 °C
output:
Class I, Division 2, Groups A, B, C, D; T4
Class I, Zone 0/2 AEx nA[ia] IIC T4 Ga/Gc FOUNDATION
Note 1 -50 °C to 85 °C
Ex nA[ia] IIC T4 Ga/Gc Fieldbus / FISCO

Enclosure: Type 4X/ IP66/ IP67 All All -


All SLG 700 models are registered in all provinces and territories
Canadian Registration Number (CRN):
in Canada.
Explosion proof with intrinsically safe
probe:
XP-IS Class I, Division 1, Groups A, B, C, D,
T4 with Intrinsically safe probe
Class 1, Zone 0/1 AEx ia/d IIC Ga/Gb T4

Dust Ignition Proof with intrinsically safe All Note 1 -50 °C to 85 °C


probe:
DIP-IS Class II, Division 1, Groups E, F, G,
T4 with Intrinsically Safe Probe

Zone 21 AEx tb IIIC Db T95 oC


FM Probe : Zone 20 AEx ia IIIC Da T95 oC
ApprovalsTM
Intrinsically Safe: 4-20 mA / HART Note 2 -50 °C to 70 °C
IS Class I, II, III, Division 1, Groups A, B, C,
D, E, F, G, T4 FOUNDATION -50 °C to 70 °C
Class l, Zone 0, AEx ia IIC T4 Ga Note 2
Fieldbus / FISCO

Nonincendive with intrinsically safe


probe: 4-20 mA / HART Note 1 -50 °C to 85 °C
NI-IS Class I, II, III, Division 2, Groups A, B,
C, D, F, G, T4 with Intrinsically Safe Probe
FOUNDATION
Class l, Zone 2, AEx nA IIC T4 Note 1 -50 °C to 85 °C
Fieldbus / FISCO
Enclosure: Type 4X/ IP66/ IP67 All All -
12 SLG 700 SmartLine Level Transmitter

Approval Certifications: (Continued)

Flameproof with IS output:


2[1] G Ex d[ia] IIC T4 Gb[Ga]
All Note 1 -50 º°C to 85 °C
Dust Ignition Proof :
II 2 D Ex tb IIIC T 95oC IP 66
4-20 mA / HART Note 2a -50 °C to 70 °C
Intrinsically Safe:
ATEX II 1 G Ex ia IIC T4 Ga FOUNDATION -50 °C to 70 °C
Note 2b/2c
Fieldbus / FISCO
4-20 mA / HART Note 1 -50 º°C to 85 °C
Nonincendive with IS output:
3[1] G Ex nA[ia] IIC t4 Gb[Ga] FOUNDATION
Note 1 -50 º°C to 85 °C
Fieldbus / FISCO
Enclosure: IP66/ IP67 All All -

Flameproof with IS output:


Ex d[ia] IIC T4 Gb[Ga]
All Note 1 -50 º°C to 85 °C
Dust Ignition Proof :
Ex tb IIIC T 95oC IP 66

IECEx 4-20 mA / HART Note 2a -50 °C to 70 °C


(World) Intrinsically Safe:
Ex ia IIC T4 Ga FOUNDATION
Note 2b/2c -50 °C to 70 °C
Fieldbus / FISCO
Nonincendive with IS output: 4-20 mA / HART Note 1 -50 º°C to 85 °C
Ex nA[ia] IIC T4 Gc[Ga] FOUNDATION
Note 1 -50 º°C to 85 °C
Fieldbus / FISCO
Enclosure: IP66/ IP67 All All -
Flameproof with IS output:
Ex d[ia] IIC T4 Gb[Ga]
All Note 1 -50 º°C to 85 °C
CCoE Dust Ignition Proof :
(India) Ex tb IIIC T 95oC
4-20 mA / HART Note 2a -50 °C to 70 °C
SAEx Intrinsically Safe:
Ex ia IIC T4 Ga FOUNDATION
(South Africa) Note 2b -50 °C to 70 °C
Fieldbus
Nonincendive with IS output: 4-20 mA / HART Note 1 -50 º°C to 85 °C
KOSHA
(Korea) Ex nA[ia] IIC T4 Gc[Ga] FOUNDATION
Note 1 -50 º°C to 85 °C
Fieldbus
Enclosure: IP66/ IP67 All All -
(Future Flameproof with IS output:
Certifications) Ex d[ia] IIC T4 Gb[Ga]
INMETRO All Note 1 -50 º°C to 85 °C
Dust Ignition Proof :
(Brazil) Ex tb IIIC T 95oC IP 66
4-20 mA / HART Note 2a -50 °C to 70 °C
GOST Intrinsically Safe:
Ex ia IIC T4 Ga FOUNDATION
(Russia) Note 2b -50 °C to 70 °C
Fieldbus
Nonincendive with IS output: 4-20 mA / HART Note 1 -50 º°C to 85 °C
Ex nA[ia] IIC T4 Gc[Ga] FOUNDATION Note 1
-50 º°C to 85 °C
Fieldbus
Enclosure : IP 66/67 All All -
SLG 700 SmartLine Level Transmitter 13

Flameproof with IS output:


Ex d[ia] IIC T4 Ga/Gb
All Note 1 -50 º°C to 85 °C
Dust Ignition Proof :
Ex tb IIIC T 95oC IP 66

NEPSI 4-20 mA / HART Note 2a -50 °C to 70 °C


Intrinsically Safe:
(China) Ex ia IIC T4 Ga FOUNDATION
Note 2b -50 °C to 70 °C
Fieldbus
Nonincendive with IS output: 4-20 mA / HART Note 1 -50 º°C to 85 °C
Ex nA[ia] IIC T4 Ga/Gc FOUNDATION
Note 1 -50 º°C to 85 °C
Fieldbus
Enclosure : IP 66/67 All All -
Notes:
1. Operating Parameters:
Voltage= 14.0 to 42.0 V DC (HART) Current= 4-20 mA Normal (3.5 – 23 mA Faults) (HART)
= 9 to 32 V (FF) = 29.4 mA Max (FF)
2. Intrinsically Safe Entity Parameters
a. Analog/ HART Entity Values:
Vmax= Ui = 30 V Imax= Ii= 225 mA Ci = 4 nF Li = 0 Pi =0.9 W
b. Foundation Fieldbus- Entity Values
Vmax= Ui = 30 V Imax= Ii= 225 mA Ci = 0 nF Li = 0 Pi =1.0 W
c. Foundation Fieldbus (FISCO)- Entity Values
Vmax= Ui = 17.5 V Imax= Ii= 380 mA Ci = 0 nF Li = 0 Pi =5.32 W
When Installed as FISCO Ta= -50C to 45C

WHG
Overfill Protection Certificate #: Z-65.16-556. TÜV-tested and approved for overfill protection according to the German WHG
regulations

SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV Nord Sys
Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.
Note: Only transmitters with SIL markings are certified for SIL applications. – Transmitters ordered with SIL
certification will signify the SIL Level on the SLG700 Nameplate.
14 SLG 700 SmartLine Level Transmitter

Mounting & Dimensional Drawings

millimeters
Reference Dimensions: inches

Figure 8 - SLG720 SmartLine Level with NPT fitting


SLG 700 SmartLine Level Transmitter 15

Figure 9 -SLG720 SmartLine Level with BSP (British Standard Pipe) fitting
16 SLG 700 SmartLine Level Transmitter

Figure 10 - SLG720 SmartLine Level with Flange


SLG 700 SmartLine Level Transmitter 17

Figure 11 - SmartLine Level with remote housing option (Shown with SLG720)

Figure 12 -SLG720 SmartLine Level rod probes


18 SLG 700 SmartLine Level Transmitter

Figure 13 - SLG720 SmartLine Level coaxial probes


SLG 700 SmartLine Level Transmitter 19

Figure 14 - SLG726 Threaded NPT Mount Transmitter


20 SLG 700 SmartLine Level Transmitter

Figure 15 - SLG726 Flange Mount Transmitter


SLG 700 SmartLine Level Transmitter 21

Figure 16 - SLG726 Threaded BSP/G Mount Transmitter


22 SLG 700 SmartLine Level Transmitter

Figure 17 - SLG726 Probes


SLG 700 SmartLine Level Transmitter 23

Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model please check for the latest revision of the Model Selection Guides which are
published at: www.honeywellprocess.com/en-US/pages/default.aspx
Model Selection Guide
Model SLG72X Series Liquid Measurement
Guided Wave Radar Level Transmitter
Model Selection Guide
34-SL-16-01 Issue 4A

Instructions
● Select the desired Key Number. The arrow to the right marks the selection available.
● Make one selection from each Table (I, II and IX) using the column below the proper arrow.
● A (●) denotes unrestricted availability. A letter denotes restricted availability.
● Restrictions follow Table IX.

Key Num ber I II III IV V VI VII VIII (Optional) IX

SLG72 _ - _____________ - ____ - _ - ___ - _____ - _ - ___ - __,__ - _____

KEY NUMBER Application Selection Availability


Standard T/P Liquid Level Measurement (-40 to 200C/-1 to 40 bar) SLG720

High Temperature/High Pressure Liquid Level Measurement (-60 to 450C/-1 to 400 bar) SLG726

TABLE I Probe and Material Selections

Min/Max Length Selection


Probe Material Measurement Probe Type & Dia.
Meters (Feet)

None - Customer Supplied (Single


000_________ _ ● ●
Rod and Wire Only)
Rod, Single 8 mm dia., segmented,
0.4m (1.3 ft) / 6.3m (20.7 ft) SRA _ _ _ _ _ _ _ _ _ _ a
2000 mm segments
Rod, Single 12 mm dia., segmented,
0.4m (1.3 ft) / 6.3m (20.7 ft) SRB _ _ _ _ _ _ _ _ _ _ a
2000 mm segments
Rod, Single 16 mm dia., segmented,
0.4m (1.3 ft) / 6.3m (20.7 ft) SRC _ _ _ _ _ _ _ _ _ _ d
2000 mm segments
Rod, segmented, 8 mm dia, 500 mm
0.4m (1.3 ft) / 6.3m (20.7 ft) SRH _ _ _ _ _ _ _ _ _ _ a
segments
Rod, segmented, 8 mm dia, 1000
0.4m (1.3 ft) / 6.3m (20.7 ft) SRJ _ _ _ _ _ _ _ _ _ _ a
mm segments
Rod, segmented, 12 mm dia, 500
0.4m (1.3 ft) / 6.3m (20.7 ft) SRM _ _ _ _ _ _ _ _ _ _ a
mm segments
316/316L General Liquids Rod, segmented, 12 mm dia, 1000
0.4m (1.3 ft) / 6.3m (20.7 ft) SRN _ _ _ _ _ _ _ _ _ _ a
mm segments
Rod, segmented, 16 mm dia, 500
0.4m (1.3 ft) / 6.3m (20.7 ft) SRK _ _ _ _ _ _ _ _ _ _ d
mm segments
Rod segmented, 16 mm dia, 1000
0.4m (1.3 ft) / 6.3m (20.7 ft) SRL _ _ _ _ _ _ _ _ _ _ d
mm segments

Wire, Single 4 mm dia 1.0m (3.3 ft) / 50m (164 ft) SWA _ _ _ _ _ _ _ _ _ _ e e

a. Wetted materials
and probe type Wire, Single 4 mm dia, max 300 mm
1.3m (4.3 ft) / 50m (164 ft) SWB _ _ _ _ _ _ _ _ _ _ v v
nozzle height center rod

Coaxial (22 mm OD), segmented,


0.4m (1.3 ft) / 6.3m (20.7 ft) SCA _ _ _ _ _ _ _ _ _ _ h
2000 mm segments

Coaxial (42 mm OD), segmented,


2000 mm segments (see Note 3 0.4m (1.3 ft) / 6.3m (20.7 ft) SCB _ _ _ _ _ _ _ _ _ _ k
below)
Rod, Single 8 mm dia., segmented,
0.4m (1.3 ft) / 6.3m (20.7 ft) ARA _ _ _ _ _ _ _ _ _ _ l
2000 mm segments
Rod, segmented, 8 mm dia., 500 mm
0.4m (1.3 ft) / 6.3m (20.7 ft) ARD _ _ _ _ _ _ _ _ _ _ l
segments
Rod, segmented, 8 mm dia., 1000
0.4m (1.3 ft) / 6.3m (20.7 ft) ARE _ _ _ _ _ _ _ _ _ _ l
mm segments

Alloy C-276 Liquids

Coaxial (22 mm OD), 2000 mm


0.4m (1.3 ft) / 6.3m (20.7 ft) ACA _ _ _ _ _ _ _ _ _ _ i
segments

TABLE I (con't) Probe and Material Selections Selection 20 26


b. Probe End None ___N_________ u u
End Type
Treatment Weight ___W_________ p p
None ____00_______ ● ●
2" Centering Disk (see Note 2 below) ____S2_______ q q
3" Centering Disk (see Note 2 below) ____S3_______ q q
316/316L 4" Centering Disk (see Note 2 below) ____S4_______ q q
6" Centering Disk (see Note 2 below) ____S6_______ q q
c. Centering Disk 8" Centering Disk (see Note 2 below) ____S8_______ q q
2" Centering Disk (see Note 2 below) _ _ _ _ A2 _ _ _ _ _ _ _ y
3" Centering Disk (see Note 2 below) _ _ _ _ A3 _ _ _ _ _ _ _ y
Alloy C-276 4" Centering Disk (see Note 2 below) _ _ _ _ A4 _ _ _ _ _ _ _ y
6" Centering Disk (see Note 2 below) _ _ _ _ A6 _ _ _ _ _ _ _ y
8" Centering Disk (see Note 2 below) _ _ _ _ A8 _ _ _ _ _ _ _ y
Viton® or Fluorocarbon Elastomer (-26 to 200C) _ _ _ _ _ _ V_ _ _ _ _ _ ●
Kalrez perfluorelastomer (-20 to 200C; saturated steam max 150C) ______K______ ●
EPDM (-40 to 150C) ______E______ ●
d. Seal material
Buna-N (-40 to 120C) ______B______ ●
Metallic - Alloy 718 NACE _ _ _ _ _ _ M_ _ _ _ _ _ ●
Metallic - 17-4 PH ______N______ ●

e. Probe length units Metric (millimeters) _ _ _ _ _ _ _ M_ _ _ _ _ ● ●

f. Probe length 400 mm to 50000 mm (in 100 mm increments) (Probe length 00000 available only with table 1A selection 000.) _ _ _ _ _ _ _ _ XXXXX ● ●

Note: All flanges are 316L; when coated or C-276 wetted materials are selected a wetted material barrier is provided.
Note 2: A drilling jig needs to be ordered when ordering centering disk for rod probes. See accessory part numbers for drilling jig part.
Note 3: For transmitters with threaded process connections and probe lengths over 2000mm, probe will need to be assembled from within the tank.
24 SLG 700 SmartLine Level Transmitter

TABLE II Connection Types Material Size Rating Selection 20 26


Class 150lb RF AS1A ●
1-1/2"
Class 300lb RF AS1B ●
Class 150lb RF AS2A ● ●
Class 300lb RF AS2B ● ●
2" Class 600lb RF AS2C ●
Class 900lb RF AS2D ●
Class 1500lb RF AS2H ●
Class 600lb RTJ AS2J ●
Class 900lb RTJ AS2K ●
Class 1500lb RTJ AS2L ●
Class 150lb RF AS3A ● ●
Class 300lb RF AS3B ● ●
3" Class 600lb RF AS3C ●
Class 900lb RF AS3D ●
316/316L
Class 1500lb RF AS3H ●
Class 600lb RTJ AS3J ●
Flanges Class 900lb RTJ AS3K ●
ANSI B16.5 (CRN) Class 1500lb RTJ AS3L ●
Class 150lb RF AS4A ● ●
Class 300lb RF AS4B ● ●
4" Class 600lb RF AS4C ●
Class 900lb RF AS4D ●
Class 1500lb RF AS4H ●
Class 600lb RTJ AS4J ●
Class 900lb RTJ AS4K ●
Class 1500lb RTJ AS4L ●
6" Class 150lb RF AS6A ● ●
8" Class 150lb RF AS8A ● ●
Class 150lb RF AC1A ●
1-1/2"
Class 300lb RF AC1B ●
Class 150lb RF AC2A ●
C-276 2"
Class 300lb RF AC2B ●
Class 150lb RF AC3A ●
3"
Class 300lb RF AC3B ●
DN40 DN40 PN10-40 DS4A ●
DN50 PN10/16 DS5A ● ●
DN50 PN25/40 DS5B ● ●
DN50 PN63 DS5H ●
DN50
DN50 PN100 DS5J ●
DN50 PN160 DS5K ●
DN50 PN250 DS5L ●
DN80 PN10/16 DS8A ● ●
DN80 PN25/40 DS8B ● ●
316/316L DN80 PN63 DS8H ●
DN80
DN80 PN100 DS8J ●
DN80 PN160 DS8K ●
DN80 PN250 DS8L ●
Flanges DN100 PN10/16 DS1A ● ●
DIN EN 1092 DN100 PN25/40 DS1B ● ●
DN100 PN63 DS1H ●
DN100
DN100 PN100 DS1J ●
DN100 PN160 DS1K ●
DN100 PN250 DS1L ●
DN150 DN150 PN10/16 DS1Y ● ●
DN200 DN200 PN16 DS2A ● ●
DN40 DN40 PN10/40 DC4C ●
DN50 PN10/16 DC5A ●
DN50
DN50 PN25/40 DC5B ●
C-276 DN80 PN10/16 DC8A ●
DN80
DN80 PN25/40 DC8B ●
DN100 PN10/16 DC1A ●
DN100
DN100 PN25/40 DC1B ●
Fisher 249B/259B 600lb FS1C ● ●
Flanges
316/316L Fisher 249C 600lb FS1D ● ●
Special
Masoneilan 7-1/2" 600 psi MS1C ● ●
3/4" NPT (CRN) NS7A ●
1" NPT (CRN) NS1A ●
1 - 1/2" NPT (CRN) NS5A ● ●
316/316L 2" NPT (CRN) NS2A ●
3/4" BSP (G 3/4") GS7A ●
1" BSP (G 1") GS1A ●
Threaded
1-1/2" BSP/G 1-1/2 GS5A ● ●
Fittings
3/4" NPT (CRN) NC7A ●
ISO228 and ANS
1" NPT (CRN) NC1A ●
1 - 1/2" NPT (CRN) NC5A ●
C-276 2" NPT (CRN) NC2A ●
3/4" BSP (G 3/4") GC7A ●
1" BSP (G 1") GC1A ●
1-1/2" BSP/G 1-1/2 GC5A ●
SLG 700 SmartLine Level Transmitter 25

TABLE III Agency Approvals (see data sheet for Approval Code Details) Selection 20 26
No Explosion Protection Approvals Required 0 ● ●
FM Explosion/Flame proof, Intrinsically Safe, Non-Incendive/Sparking, & Dust Ignition Proof A ● ●
CSA (Canada & USA) Explosion/Flame proof, Intrinsically Safe, Non-Incendive/Sparking, & Dust Ignition Proof B ● ●
ATEX Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof C ● ●
IECEx Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof D ● ●
Approvals SAEx Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof E ● ●
INMETRO Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof F ● ●
NEPSI Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof G ● ●
CCoE Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof H ● ●
KOSHA Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof K ●
EAC TR-CU Flameproof, Intrinsically Safe, Non-Sparking, & Dust Ignition Proof L ● ●

TABLE IV TRANSMITTER ELECTRONICS SELECTIONS


Selection
Material Connection Lightning Protection
Polyester Pow der Coated Aluminum 1/2 NPT None A_ _ ● ●
Polyester Pow der Coated Aluminum M20 None B__ ● ●
Polyester Pow der Coated Aluminum 1/2 NPT Yes C__ ● ●
Polyester Pow der Coated Aluminum M20 Yes D__ ● ●
a. Electronic Housing 316 Stainless Steel (Grade CF8M) 1/2 NPT None E__ ● ●
Material & 316 Stainless Steel (Grade CF8M) M20 None F__ ● ●
Connection Type 316 Stainless Steel (Grade CF8M) 1/2 NPT Yes G__ ● ●
316 Stainless Steel (Grade CF8M) M20 Yes H__ ● ●
Remote 3m - Polyester Pow der Coated Aluminum 1/2 NPT None J__ ● ●
Remote 3m - Polyester Pow der Coated Aluminum M20 None K__ ● ●
Remote 3m - Polyester Pow der Coated Aluminum 1/2 NPT Yes L__ ● ●
Remote 3m - Polyester Pow der Coated Aluminum M20 Yes M_ _ ● ●
Analog Output Digital Protocol
b. Output/ Protocol 4-20mA dc HART Protocol _H_ ● ●
n/a Foundation Fieldbus _F_ ● ●
Indicator Ext Zero, Span & Config Buttons Languages
None None None __0 ● ●
c. Customer
None Yes (Zero/Span Only) None __A f f
Interface Selections
Advanced None EN, DE, IT, FR, SP, RU, TU __D ● ●
Advanced Yes EN, DE, IT, FR, SP, RU, TU __E ● ●

TABLE V CONFIGURATION SELECTIONS


Selection 20 26
Diagnostics
a. Diagnostics
Standard Diagnostics 1____ ● ●
Interface Options
b. Interface None - Standard Level _0___ ● ●
Measurement Interface Measurement _1___ ● ●
Flooded Interface Measurement _2___ ● ●

c. Compensations __0__ ● ●
None
3
Write Protect Fail Mode High & Low Output Lim its
Disabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _ _ _1 _ f f
d. Output Limit, Disabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _ __ 2_ f f
Failsafe & Write Enabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _ __ 3_ f f
Protect Settings Enabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _ __ 4_ f f
Enabled N/A N/A Fieldbus or Profibus _ _ _5_ g g
Disabled N/A N/A Fieldbus or Profibus _ _ _6_ g g
e. General Factory Standard ____ S ● ●
Configuration Custom Configuration (Unit Data Required from customer) ____ C ● ●
3
NAMUR Output Limits 3.8 - 20.5mAdc can be configured by the customer.

TABLE VI CALIBRATION & ACCURACY SELECTIONS


Selection
Accuracy and Accuracy Calibrated Range Calibration Qty
Calibration Std Accuracy (+/-3mm or +/-0.03%) Factory Std (uses RF cable calibrator) Single Range A ● ●
Std Accuracy (+/-3mm or +/-0.03%) Custom calibration w/ certificate (Unit Data Single Range B t t

TABLE VII ACCESSORY SELECTIONS Selection


No customer tag 0__ ● ●
a. Customer
One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) 1__ ● ●
Tag
Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line) 2__ ● ●
No Conduit Plugs or Adapters Required _ A0 ● ●
b. Unassembled 1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter _ A2 n n
Conduit 1/2 NPT 316 SS Certified Conduit Plug _ A6 n n
Plugs & M20 316 SS Certified Conduit Plug _ A7 m m
Adapters ®
Minifast 4 pin (1/2 NPT) _ A8 n n
Minifast® 4 pin (M20) _ A9 m m

TABLE VIII OTHER Certifications & Options: (String in sequence com m a delim ited (XX, XX, XX,….) Selection
None 00 ● ●
NACE MR0175; MR0103; ISO15156 Process wetted, pressure retaining parts only FG ● ●
EN10204 Type 3.1 Material Traceability; pressure retaining parts FX ● ●
Certificate of Conformance F3 ● ●
Calibration Test Report & Certificate of Conformance F1 ● ●
Certificate of Origin F5 ● ●
Certifications &
FMEDA (SIL 2/3) Certification FE j j
Warranty
WHG Overfill Protection WG ● ●
PMI Certification PM ● ●
Extended Warranty Additional 1 year 01 ● ●
Extended Warranty Additional 2 years 02 ● ●
Extended Warranty Additional 3 years 03 ● ●
Extended Warranty Additional 4 years 04 ● ●

TABLE IX Manufacturing Specials Selection


Application and Validation Tool (AVT) Configuration File Reference # _____ ● ●
Factory Factory Default Configuration, No AVT File 00000 ● ●
26 SLG 700 SmartLine Level Transmitter

MODEL RESTRICTIONS
Available Only with Not Available with
Restriction Letter
Table Selection(s) Table Selection(s)

probe length 400 mm to 6300 mm (_


_ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
a If _ 6300)

II _S__
b Select only one option from this group

probe length 400 mm to 6300 mm (_


_ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
If _ 6300) II NS7A, NS1A, GS7A, GS1A
c

II _S__

probe length 400 mm to 6300 mm (_


d _ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
If _ 6300)

probe length 1000 mm to 50000 mm


(_ _ _ _ _ _ _ _ _ 1000 to _ _ _ _ _ _ _
If _ 50000)
e

II _ S_ _
f IVb _F_
g IVb _F_

probe length 400 mm to 6300 mm (_


II NS7A, GS7A
If _ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
h _ 6300)

If probe length > 2000 mm

II _S__

probe length 400 mm to 6300 mm (_


II NC7A, GC7A
If _ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
_ 6300)
i
If probe length > 2000 mm

II _C__

j IVb _H_ Vd _ _ _1 _, _ _ _2 _, _ _ _6 _

probe length 400 mm to 6300 mm (_


k If _ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
_ 6300)
II NS7A, NS1A, NS2A, GS1A, GS7A

probe length 400 mm to 6300 mm (_


_ _ _ _ _ _ _ _ _ 400 to _ _ _ _ _ _ _ _
If _ 6300)
l

II _C__
m IVa B_ _, D_ _, F_ _, H_ _, K _ _, M _ _
n IVa A_ _, C_ _, E_ _, G_ _, J _ , L _ _

SWA_ _ _ _ _ _ _ _ _ _,
SWB_ _ _ _ _ _ _ _ _ _,
p Ia
SWAW _ _ _ _ _ _ _ _ _,
SWBW _ _ _ _ _ _ _ _ _,
SRA_ _ _ _ _ _ _ _ _ _,
SRB_ _ _ _ _ _ _ _ _ _,
SRH_ _ _ _ _ _ _ _ _ _,
SRJ_ _ _ _ _ _ _ _ _ _,
SRM_ _ _ _ _ _ _ _ _ _,
SRN_ _ _ _ _ _ _ _ _ _,
SRK_ _ _ _ _ _ _ _ _ _,
SRL_ _ _ _ _ _ _ _ _ _,
q 1a,1b SRC_ _ _ _ _ _ _ _ _ _

probe length 1000 mm to 50000 mm


(_ _ _ _ _ _ _ _ _ 1000 to _ _ _ _ _ _ _
If _ 50000) II NS7A, NS1A, GS7A, GS1A
r

II _ S_ _

SWA_ _ _ _ _ _ _ _ _ _,
Ia SWB_ _ _ _ _ _ _ _ _ _
t

probe lengths more than 20


meters
If (>_ _ _ _ _ _ _ _ 20000)
SWA_ _ _ _ _ _ _ _ _ _,
u SWB_ _ _ _ _ _ _ _ _ _,
Ia

probe length 1300 mm to 50000 mm


(_ _ _ _ _ _ _ _ _ 1300 to _ _ _ _ _ _ _
If _ 50000)
v

II _ S_ _
ARA_ _ _ _ _ _ _ _ _ _,
y ARD_ _ _ _ _ _ _ _ _ _,
1a ARE_ _ _ _ _ _ _ _ _ _
SLG 700 SmartLine Level Transmitter 27

ACCESSORIES
Description Part Number
SmartLine Anytime Tool (for firmware upgrade) 50127238-501
SmartLine Level Drilling Jig for Rod Probes, reusable 51000000-502

FIELD INSTALLABLE REPLACEMENT PARTS


Description Kit Number
GWR Level Basic Indicator Kit 50096657-501
GWR Level Advanced Indicator Kit 50096657-502
GWR Level Terminator Module w/Lightning Protection Kit for HART Modules 50095191-502
GWR Level Terminator Module w/Lightning Protection Kit for FF Modules 50095191-510
GWR Level Terminator Module w/o Lightning Protection Kit for HART Modules 50095191-501
GWR Level Terminator Module w/o Lightning Protection Kit for FF Modules 50095191-509
GWR Level HART Electronics module w/o connection for external configuration button 50096656-501
GWR Level HART Electronics module w/connection for external configuration button 50096656-502
GWR Level FF Electronics module w/o connection for external configuration button 50096656-503
GWR Level FF Electronics module w/connection for external configuration button 50096656-504

HART® is a registered trademark of HART Communication Foundation.


FOUNDATIONTM Fieldbus is a trademark of Fieldbus Foundation.
Viton® is a registered trademark of DuPont Performance Elastomers.
Teflon® is a registered trademark of DuPont.
FM ApprovalsSM is a service mark of FM Global
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.

ASIA PACIFIC EMEA AMERICAS


Honeywell Process Solutions, Honeywell Process Solutions, Honeywell Process Solutions,
(TAC) hfs-tac- Phone: + 80012026455 or Phone: (TAC) 1-800-423-9883 or
[email protected] +44 (0)1344 656000 215/641-3610
(Sales) 1-800-343-0228
Australia Email: (Sales)
Honeywell Limited [email protected] Email: (Sales)
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481 or [email protected]
Toll Free 1300-36-39-36 (TAC) or
Toll Free Fax: [email protected] (TAC)
1300-36-04-70 [email protected]
China – PRC - Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826

Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033

South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015

Specifications are subject to change without notice.

For more information


To learn more about SmartLine Transmitters,
visit www.honeywellprocess.com
Or contact your Honeywell Account Manager

Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042

Honeywell Control Systems Ltd


Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB

Shanghai City Centre, 100 Jungi Road


Shanghai, China 20061
34-SL-03-03
August 2016
www.honeywellprocess.com 2016 Honeywell International Inc.

You might also like