RZQ 100-140 B8W1 Technical Data
RZQ 100-140 B8W1 Technical Data
technical data
Split
Sky Air
Split - Sky Air
Daikin’s unique position as a man- Het ISO14001 assures an effective “ The present publication is drawn up by way of information only
ufacturer of air conditioning equip- environmental management system in order to and does not constitute an offer binding upon Daikin Europe N.V..
ment, compressors and refrige- help protect human health and the Daikin Europe N.V. has compiled the content of this publication to
rants has led to its close involve- environment from potential impact of our the best of its knowledge. No express or implied warranty is given
ment in environmental issues. For activities, products and services and to assist in for the completeness, accuracy, reliability or fitness for particular pur-
several years Daikin has had the in- maintaining and improving the quality of the pose of its content and the products and services presented therein.
tention to become a leader in the environment. Specifications are subject to change without prior notice. Daikin Eu-
provision of products that have rope N.V. explicitly rejects any liability for any direct or indirect dam-
limited impact on the environ- age, In the broadest sense, arising from or related to the use and/or
ment. This challenge demands the interpretation of this publication. All content is copyrighted by Daikin
eco design and development of a Daikin Europe N.V. is approved by LRQA for its Europe N.V..”
wide range of products and an en- Quality Management System in accordance
ergy management system, result- with the ISO9001 standard. ISO9001 pertains
ing in energy conservation and a to quality assurance regarding design,
reduction of waste. development, manufacturing as well as to
services related to the product.
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende EEDEN0 9 - 1 0 0
EEDEN09-100
technical data
Split
Sky Air
• Outdoor Units • R-410A • RZQ100-140B8W1B
TABLE OF CONTENTS
RZQ100-140B8W1B
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1 Features
W i8 Bn y 0U k 4 S 1 r - o A0t o 0 i d 1 l t4Q puZ- RS•O Outdoor units for pair, twin, triple, double twin application • During start up, the room can be cooled down or heated very quickly.
• The Sky Air Inverter is developed for use in shops, restaurants and Once the temperature in the room has reached its set point, the low
power operation starts to save energy.
small offices. This innovative Daikin unit provides a more
comfortable environment and offers great savings in energy • Daikin outdoor units are neat and sturdy and can be mounted easily
1 •
consumption to shop and office owners.
The use of inverter type outdoor units results in an air conditioning •
on a roof or terrace or simply placed against an outside wall.
Outdoor units are fitted with either a swing or scroll compressor,
1 system with a high energy efficiency and very low sound level renowned for low noise and high energy efficiency
• An inverter driven compressor allows the capacity to be adjusted • A special acryl precoated fin for anti-corrosion treatment on the heat
precisely to match variations in room and outside temperatures. exchanger ensures greater resistance against severe weather
conditions
2 Specifications
2 Specifications
2 Specifications
3 Electrical data
RZQ-BW1
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA
1
3
3D048638C
SYMBOLS NOTES
MCA : Min. Circuit Amps (A) 1 RLA is based on the following conditions:
Power supply: 50Hz 230V
TOCA : Total Over Current Amps (A) Cooling Heating
Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB
MFA : Max. Fuse Amps (See note 7) (A) Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB
MSC : MSC means the max. current during the 2 TOCA means the total value of each OC set
starting of compressor. (A) 3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
RLA : Rated Load Amps (A) above listed operation range limits
OFM : Outdoor Fan Motor (A) 4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
IFM : Indoor Fan Motor (next lower standard fuse rating, min.15A)
FLA : Full Load Amps 6 Select wire size based on the larger value of MCA or TOCA
kW : Fan Motor Rated Output (kW) 7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice.
3 Electrical data
RZQ-BW1
Unit combination Power supply Comp. OFM IFM
3
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA
1
3
3D048638C
SYMBOLS NOTES
MCA : Min. Circuit Amps (A) 1 RLA is based on the following conditions:
Power supply: 50Hz 230V
TOCA : Total Over Current Amps (A) Cooling Heating
Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB
MFA : Max. Fuse Amps (See note 7) (A) Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB
MSC : MSC means the max. current during the 2 TOCA means the total value of each OC set
starting of compressor. (A) 3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
RLA : Rated Load Amps (A) above listed operation range limits
OFM : Outdoor Fan Motor (A) 4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
IFM : Indoor Fan Motor (next lower standard fuse rating, min.15A)
FLA : Full Load Amps 6 Select wire size based on the larger value of MCA or TOCA
kW : Fan Motor Rated Output (kW) 7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice.
4 Options
RZQ-B8
Kit name
RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
1 Name of option
RZQS71D7V1B
-
RZQS100D7V1B
RZQ100B8W1B
RZQS125D7V1B
RZQ125B8W1B
RZQS140D7V1B
RZQ140B8W1B
4 Central drain plug EKDK04
Twin KHRQ22M20TA (KHRQ58T): see note
NOTE
1 For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.
3TW26739-1F
5 Capacity tables
5-1 Combination table
RZQ-B
Multi Combination Possibilities:
3
P = Pair 71 100 125 140
2 = Twin 35+35 50+50 60+60 71+71
3 = Triple
4 = Double Twin
35+35+35 50+50+50 (*)
35+35+35+35 (*)
50+50+50 (*)
35+35+35+35
1
(*) Max capacity depend on outdoor unit 5
Sky-air HH Cassette Thin cassette 2x2 cassette New Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP Duct Floor standing
FCQH100D7VEB
FCQH125D7VEB
FCQH140D7VEB
FCQH71D7VEB
FCQ100C7VEB
FCQ125C7VEB
FCQ140C7VEB
FBQ100C7VEB
FBQ125C7VEB
FBQ140C7VEB
FHQ100BVV1B
FHQ125BVV1B
FUQ100BVV1B
FUQ125BVV1B
FAQ100BVV1B
FDQ125B8V3B
FCQ35C7VEB
FCQ50C7VEB
FCQ60C7VEB
FCQ71C7VEB
FBQ35C7VEB
FBQ50C7VEB
FBQ60C7VEB
FBQ71C7VEB
FHQ35BVV1B
FHQ50BVV1B
FHQ60BVV1B
FHQ71BVV1B
FUQ71BVV1B
FAQ71BVV1B
FVQ100BV1B
FVQ125BV1B
FFQ35B8V1B
FFQ50B8V1B
FFQ60B8V1B
FVQ71BV1B
Model name
RZQ71D7V1B - P 2 P 2 2 P 2 P P P
RZQ100D7V1B RZQ100B8W1B P 3 2 P 3 2 3 2 P 3 2 P P P
RZQ125D7V1B RZQ125B8W1B P 4 3 2 P 4 3 2 4 3 2 P 4 3 2 P P P
RZQ140D7V1B RZQ140B8W1B 2 P 4 3 2 P 4 3 4 3 2 P 4 3 2 2 2
Sky-air HH Cassette Thin cassette 2x2 cassette New Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP Duct Floor standing
FCQH100D7VEB
FCQH125D7VEB
FCQH140D7VEB
FCQH71D7VEB
FCQ100C7VEB
FCQ125C7VEB
FCQ140C7VEB
FBQ100C7VEB
FBQ125C7VEB
FBQ140C7VEB
FHQ100BVV1B
FHQ125BVV1B
FUQ100BVV1B
FUQ125BVV1B
FAQ100BVV1B
FDQ125B8V3B
FCQ35C7VEB
FCQ50C7VEB
FCQ60C7VEB
FCQ71C7VEB
FBQ35C7VEB
FBQ50C7VEB
FBQ60C7VEB
FBQ71C7VEB
FHQ35BVV1B
FHQ50BVV1B
FHQ60BVV1B
FHQ71BVV1B
FUQ71BVV1B
FAQ71BVV1B
FVQ100BV1B
FVQ125BV1B
FFQ35B8V1B
FFQ50B8V1B
FFQ60B8V1B
FVQ71BV1B
Model name
RZQ71D7V1B P 2 P 2 2 P 2 P P P
RZQ100D7V1B P 3 2 P 3 2 3 2 P 3 2 P P P
RZQ125D7V1B P 4 3 2 P 4 3 2 4 3 2 P 4 3 2 P P P
RZQ140D7V1B 2 P 4 3 2 P 4 3 4 3 2 P 4 3 2 2
NOTES
1 Individual indoor capacities are not given because the combinations are for simultaneous operation (= indoor units installed in the same room)
2 When different indoor models are used in combination, designate the remote control that is equipped with the most function as the main unit.
3TW26739-2C
5 Capacity tables
5-2 Cooling capacity tables
RZQ100B (Pair + Twin / triple)
Cooling
1
5
Coefficient of power input ( - )
Capacity range
Rated point
Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 10.2 6.93 0.86 10.2 7.00 1.01 10.5 7.29 1.12 10.1 7.08 1.23
18.0 25 11.8 7.59 0.94 11.3 7.45 1.03 11.0 7.27 1.13 10.5 7.06 1.24
19.0 27 12.0 7.57 0.95 11.6 7.43 1.03 11.2 7.26 1.13 10.8 7.04 1.24
19.5 27 12.1 7.56 0.95 11.8 7.41 1.03 11.3 7.25 1.13 10.9 7.03 1.24
22.0 30 12.7 7.46 0.96 12.3 7.32 1.04 11.9 7.16 1.14 11.4 6.96 1.25
24.0 32 13.2 7.36 0.96 12.8 7.22 1.05 12.4 7.06 1.15 11.9 6.87 1.27
3TW28121-1A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH100D FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Bx2 FBQ50Cx2 FHQ50x2
AFR 34 23.5 30 28 27 32 24 23 29 AFR 12.5x2 15x2 12x2 14x2 16x2 13x2
(BF) (0.17) (0.16) (0.11) (0.16) (0.20) (0.14) (0.14) (0.10) (0.07) (BF) (0.21x2) (0.16x2) (0.16x2) (0.15x2) (0.16x2) (0.1x2)
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35Bx3 FBQ35Cx3 FHQ35x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)
5 Capacity tables
5-2 Cooling capacity tables
RZQ125B (Pair + Twin / triple / double twin)
Cooling
3
1
5
Coefficient of power input ( - )
Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 12.8 8.66 0.87 12.8 8.75 1.01 13.1 9.12 1.13 12.7 8.85 1.24
18.0 25 14.7 9.50 0.95 14.2 9.32 1.04 13.7 9.09 1.14 13.2 8.83 1.25
19.0 27 14.9 9.46 0.96 14.4 9.28 1.04 14.0 9.06 1.14 13.4 8.80 1.25
19.5 27 15.1 9.45 0.96 14.7 9.27 1.04 14.1 9.05 1.14 13.6 8.79 1.25
22.0 30 15.9 9.33 0.97 15.5 9.16 1.05 14.9 8.95 1.15 14.3 8.69 1.27
24.0 32 16.5 9.20 0.97 16.0 9.03 1.06 15.5 8.83 1.16 14.9 8.59 1.28
3TW28131-1A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH125D FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Bx2 FBQ60Cx2 FHQ60x2
AFR 34 27.5 30 31 35 39 30 32 45 AFR 13.5x2 18x2 15x2 19x2 18x2 17x2
(BF) (0.19) (0.19) (0.13) (0.07) (0.14) (0.16) (0.13) (0.07) (0.25) (BF) (0.21x2) (0.1x2) (0.11x2) (0.11x2) (0.15x2) (0.2x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.11x4) (0.15x4) (0.2x4)
5 Capacity tables
5-2 Cooling capacity tables
RZQ140B (Pair + Twin / triple / double twin)
Cooling
1
5
Coefficient of power input ( - )
Capacity range
Rated point
Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 14.1 9.53 0.87 14.0 9.61 1.01 14.4 10.0 1.13 13.9 9.72 1.24
18.0 25 16.1 10.5 0.95 15.6 10.2 1.04 15.1 10.0 1.14 14.5 9.70 1.25
19.0 27 16.5 10.4 0.96 16.0 10.2 1.04 15.4 9.98 1.14 14.7 9.68 1.25
19.5 27 16.6 10.4 0.96 16.2 10.2 1.04 45.5 9.96 1.14 15.0 9.67 1.25
22.0 30 17.5 10.3 0.97 16.9 10.1 1.05 16.4 9.85 1.15 15.7 9.56 1.27
24.0 32 18.2 10.1 0.97 17.6 9.93 1.06 17.1 9.71 1.16 16.4 9.45 1.28
3TW28141-3A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FBQ-C FCQ71Cx2 FCQ71Bx2 FFQ71x2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FAQ71x2 FCQH140Dx2
AFR 34 27.5 30 39 AFR 15.5x2 18x2 19x2 18x2 17x2 19x2 19x2 21x2
(BF) (0.20) (0.19) (0.13) (0.16) (BF) (0.19x2) (0.1x2) (0.11x2) (0.08x2) (0.1x2) (0.07x2) (0.08x2) (0.17x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.15x4) (0.15x4) (0.2x4)
5 Capacity tables
5-2 Cooling capacity tables
RZQ140BW1 (Pair) 3
Cooling
1
Coefficient of power input. (-)
5 Capacity tables
5-2 Cooling capacity tables
RZQ-B/C
1
5
Capacity (%)
5 Capacity tables
5-3 Heating capacity tables
RZQ100B (Pair + Twin / triple)
Heating
3
1
5
Coefficient of power input ( - )
Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 7.16 0.87 7.91 0.92 8.66 0.96 9.41 1.01 12.8 1.06 13.8 1.12
18.0 7.15 0.90 7.90 0.95 8.65 1.00 9.39 1.05 12.8 1.10 13.8 1.16
20.0 7.15 0.94 7.89 0.99 8.64 1.04 9.38 1.09 12.8 1.15 13.8 1.21
21.0 7.14 0.96 7.89 1.01 8.63 1.06 9.38 1.11 12.8 1.17 13.8 1.23
22.0 7.14 0.98 7.88 1.03 8.63 1.08 9.37 1.14 12.8 1.20 13.7 1.25
24.0 7.13 1.02 7.87 1.07 8.62 1.12 9.36 1.17 12.8 1.24 13.7 1.30
3TW28121-1A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH100D FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Bx2 FBQ50Cx2 FHQ50x2
AFR 34 23.5 30 28 27 32 24 23 29 AFR 12.5x2 15x2 12x2 14x2 16x2 13x2
(BF) (0.17) (0.16) (0.11) (0.16) (0.20) (0.14) (0.14) (0.10) (0.07) (BF) (0.21x2) (0.16x2) (0.16x2) (0.15x2) (0.16x2) (0.1x2)
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35Bx3 FBQ35Cx3 FHQ35x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)
5 Capacity tables
5-3 Heating capacity tables
RZQ125B (Pair + Twin / triple / double twin)
Heating
1
5
Coefficient of power input ( - )
Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 8.83 0.89 9.76 0.94 10.7 0.99 11.6 1.04 16.2 1.09 17.5 1.14
18.0 8.82 0.93 9.74 0.98 10.7 1.03 11.6 1.08 16.2 1.13 17.5 1.19
20.0 8.81 0.97 9.73 1.02 10.7 1.07 11.6 1.12 16.2 1.18 17.5 1.24
21.0 8.81 0.99 9.73 1.04 10.6 1.09 11.6 1.14 16.2 1.20 17.5 1.26
22.0 8.80 1.00 9.72 1.05 10.6 1.11 11.6 1.16 16.2 1.23 17.5 1.29
24.0 8.79 1.04 9.71 1.10 10.6 1.15 11.5 1.21 16.2 1.27 17.4 1.33
3TW28131-1A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH125D FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Bx2 FBQ60Cx2 FHQ60x2
AFR 34 27.5 30 31 35 39 30 32 45 AFR 13.5x2 18x2 15x2 19x2 18x2 17x2
(BF) (0.19) (0.19) (0.13) (0.07) (0.14) (0.16) (0.13) (0.07) (0.25) (BF) (0.21x2) (0.1x2) (0.11x2) (0.11x2) (0.15x2) (0.2x2)
(Triple)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)
5 Capacity tables
5-3 Heating capacity tables
RZQ140B (Pair + Twin / triple / double twin)
Heating
3
1
5
Coefficient of power input ( - )
Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 9.82 0.86 10.8 0.91 11.9 0.95 12.9 1.00 18.0 1.05 19.5 1.11
18.0 9.80 0.90 10.8 0.94 11.8 0.99 12.9 1.04 18.0 1.09 19.4 1.15
20.0 9.79 0.94 10.8 0.98 11.8 1.03 12.9 1.08 18..0 1.14 19.4 1.20
21.0 9.79 0.95 10.8 1.00 11.8 1.05 12.8 1.10 18.0 1.16 19.4 1.22
22.0 9.78 0.97 10.8 1.02 11.8 1.07 12.8 1.12 18.0 1.19 19.4 1.24
24.0 9.77 1.00 10.8 1.06 11.8 1.11 12.8 1.17 18.0 1.23 19.4 1.29
3TW28141-3A
NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FBQ140C FCQ71Cx2 FCQ71Bx2 FFQ71x2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FAQ71x2 FCQH140Dx2
AFR 34 27.5 30 39 AFR 15.5x2 18x2 19x2 18x2 17x2 19x2 19x2 21x2
(BF) (0.20) (0.19) (0.13) (0.16) (BF) (0.19x2) (0.1x2) (0.11x2) (0.08x2) (0.1x2) (0.07x2) (0.08x2) (0.17x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.15x4) (0.15x4) (0.2x4)
5 Capacity tables
5-3 Heating capacity tables
RZQ140BW1 (Pair)
Heating
1
Coefficient of power input. (-)
3TW26071-1
1
6
4TW26079-3
7 Piping diagram
RZQ100-125-140BW1(Pair) 3
One way valve
One way
valve
One way
valve
1
7
Heat exchanger
Filter
One way One way
Capillary valve valve
Solenoid tube
valve
Capillary Electronic
tube expansion
valve
Receiver Strainer
Capillary tube
Service port
5/16″
Heat exchanger
4-way valve
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW26745-1
RZQ100-125-140BW1(Twin)
One way valve
Service port
Indoor unit 5/16″
4-way valve
Heat exchanger
C1220T-0 Compressor
Outdoor unit
Field piping Heating
Cooling
Filter Field piping
Note: 1. The pipes between the branch and the indoor units should have the
same size as the indoor connections.
Stop valve
Indoor unit (with service port 5/16’ flare)
3TW26745-2
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
7 Piping diagram
RZQ100-125-140BW1(Triple)
Indoor unit
Heat exchanger
One way valve
1 One way
valve
One way
valve
7 Stop valve
(with service port 5/16’ flare) Filter Heat exchanger
One way One way
Field piping valve valve
Capillary
Solenoid tube
Filter Field piping valve
Electronic
Capillary expansion
tube valve
Indoor unit Receiver Strainer
Heat exchanger
Capillary tube
Service port
5/16″
4-way valve
Field piping J9.5
C1220T-0
Field piping
Filter Low pressure High pressure
switch switch Muffler
Filter Field piping
Field piping J15.9
C1220T-0
Indoor unit Service port
5/16″
Heat exchanger Branch duct
connection
Option
Compressor
Outdoor unit
Heating
Field piping Note: 1. The pipes between the branch and Cooling
Filter the indoor units should have the same size
Field piping
as the indoor connections.
3TW26745-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ100-125-140BW1(Double twin)
Heat Indoor unit
exchanger
One way
valve
Field piping
Field piping Note: 1. The pipes between the branch and the
Field piping
indoor units should have the same size as the
Filter indoor connections.
3TW26755-4
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
8 Wiring diagram
8-1 Wiring diagram
RZQ100-125-140BW1 3
Indoor
Outdoor
L : Live
1
N : Neutral
8
NOTE 1.
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
: Relay connector
Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow / ON
BRN: Brown / GRN: Green OFF
NOTES:
1. Refer to the optional manual, for connection
wiring to X6A.
2. Confirm the method of setting the selector
switches (DS1) by service manual. When the
unit is shipped by factory all switches are set
Reactor box
to be off.
El. comp. assy front View A
A1P Printed circuit board K1M(A2P) Magnetic contactor R1T Thermistor (air) V2R-V3R Diode module
A2P Printed circuit board (INV) K1R(A1P) Magnetic relay (Y1S) R2T Thermistor (coil) V1T IGBT
BS1 Push button switch (forced defrost / pump down) K2R(A1P) Magnetic relay (Y2S) R3T Thermistor (discharge pipe) X6A Connector (Option)
C1-C2-C3 Capacitor K3R(A1P) Magnetic relay (E1HC) R4T Thermistor (suction pipe) X1M Terminal strip
DS1 Dip switch K4R, K5R Magnetic relay R5T Thermistor (power module) Y1E Expansion valve
F1U (A2P) Fuse (T 6,3A/250V) L1R Reactor S1PH Pressure switch (high) Y1S 4-way valve
F2U Fuse (T 6,3A/250V) M1C Motor compressor S1NPL Pressure sensor (low) Y2S Solenoid valve
F3U Fuse (B 10A/250V) M1F Motor fan RC Signal receiver circuit Z1C, Z2C Noise filter
F4U Fuse (B 10A/250V) PS Power circuit TC Signal transmission circuit Z3C, Z4C
HAP (A1P) Light emitting diode (service monitor green) Q1DI Earth leakage breaker (30mA) V1R Power module Z1F Noise filter 2TW26766-1
HAP (A2P) Light emitting diode (service monitor green) R1-R2 Resistor Z1F Noise filter (with surge absorber)
H1P (A1P) Light emitting diode (service monitor red)
9 Sound data
9-1 Sound pressure spectrum
RZQ100BW1 - Cooling RZQ100BW1 - Heating
Sound pressure level [dB(A)]
3TW26747-1 Octave band center frequency (Hz) 3TW26747-2 Octave band center frequency (Hz)
NOTES NOTES
1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)
3TW26757-1 Octave band center frequency (Hz) 3TW26757-2 Octave band center frequency (Hz)
NOTES NOTES
1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)
9 Sound data
9-1 Sound pressure spectrum
RZQ140BW1 - Cooling RZQ140BW1 - Heating 3
Sound pressure level [dB(A)]
3TW26787-1 Octave band center frequency (Hz) 3TW26787-2 Octave band center frequency (Hz)
NOTES NOTES
1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)
9 Sound data
9-2 Sound power spectrum
RZQ100BW1 - Cooling RZQ125BW1 - Cooling
Sound pressure level [dB(A)]
3TW26747-3 Octave band center frequency (Hz) 3TW26757-3 Octave band center frequency (Hz)
NOTES NOTES
1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level (A-scale according to IEC) 3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
RZQ140BW1 - Cooling
Sound pressure level [dB(A)]
NOTES
10 Installation
10 - 1 Installation method
RZQ100-125-140BW1 3
A. Non stacked installation
Legend
Obstacle is present
1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet
C. Multiple-row installation
1. Installation of one unit per row 2. Installing multiple units (2 units or more) in
lateral connection per row
3TW26739-4
11 Operation range
RZQ-B (Cooling)
1
11
Operation range
Operation range
operation (warming-up)
Allowable range of
Indoor temp. (°CWB) Indoor temp. (°CDB)
NOTE
1 Depending on operation and istallation conditions. The indoor unit can change over to freeze-up operation (indoor de-icing)
2 To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind.
3TW26733-1B