EEDEN09-100

technical data

air conditioning systems


RZQ100-140BW1

Split
Sky Air
Split - Sky Air

Daikin’s unique position as a man- Het ISO14001 assures an effective “ The present publication is drawn up by way of information only
ufacturer of air conditioning equip- environmental management system in order to and does not constitute an offer binding upon Daikin Europe N.V..
ment, compressors and refrige- help protect human health and the Daikin Europe N.V. has compiled the content of this publication to
rants has led to its close involve- environment from potential impact of our the best of its knowledge. No express or implied warranty is given
ment in environmental issues. For activities, products and services and to assist in for the completeness, accuracy, reliability or fitness for particular pur-
several years Daikin has had the in- maintaining and improving the quality of the pose of its content and the products and services presented therein.
tention to become a leader in the environment. Specifications are subject to change without prior notice. Daikin Eu-
provision of products that have rope N.V. explicitly rejects any liability for any direct or indirect dam-
limited impact on the environ- age, In the broadest sense, arising from or related to the use and/or
ment. This challenge demands the interpretation of this publication. All content is copyrighted by Daikin
eco design and development of a Daikin Europe N.V. is approved by LRQA for its Europe N.V..”
wide range of products and an en- Quality Management System in accordance
ergy management system, result- with the ISO9001 standard. ISO9001 pertains
ing in energy conservation and a to quality assurance regarding design,
reduction of waste. development, manufacturing as well as to
services related to the product.

Daikin units comply with the European


regulations that guarantee the safety of the
product.
Printed in Belgium by Goekint Graphics

Daikin Europe N.V. participates in the Eurovent


Certification Programme for Air Conditioners
(AC), Liquid Chilling Packages (LCP) and Fan Coil
Naamloze Vennootschap Units (FC); the certified data of certified models
are listed in the Eurovent Directory.
Zandvoordestraat 300
EEDEN09-100 - 02/2009

B-8400 Ostend, Belgium


Copyright © Daikin

www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende EEDEN0 9 - 1 0 0
EEDEN09-100

technical data

air conditioning systems


RZQ100-140BW1

Split
Sky Air
• Outdoor Units • R-410A • RZQ100-140B8W1B

TABLE OF CONTENTS
RZQ100-140B8W1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 22


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

• Split Sky Air • Outdoor Units 4


• Outdoor Units • R-410A • RZQ100-140B8W1B

1 Features

W i8 Bn y 0U k 4 S 1 r - o A0t o 0 i d 1 l t4Q puZ- RS•O Outdoor units for pair, twin, triple, double twin application • During start up, the room can be cooled down or heated very quickly.
• The Sky Air Inverter is developed for use in shops, restaurants and Once the temperature in the room has reached its set point, the low
power operation starts to save energy.
small offices. This innovative Daikin unit provides a more
comfortable environment and offers great savings in energy • Daikin outdoor units are neat and sturdy and can be mounted easily

1 •
consumption to shop and office owners.
The use of inverter type outdoor units results in an air conditioning •
on a roof or terrace or simply placed against an outside wall.
Outdoor units are fitted with either a swing or scroll compressor,
1 system with a high energy efficiency and very low sound level renowned for low noise and high energy efficiency
• An inverter driven compressor allows the capacity to be adjusted • A special acryl precoated fin for anti-corrosion treatment on the heat
precisely to match variations in room and outside temperatures. exchanger ensures greater resistance against severe weather
conditions

5 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

2 Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT


For combination indoor Indoor Units
RZQ100B8W1B
FCQ100C7VEB
RZQ125B8W1B
FCQ125C7VEB
RZQ140B8W1B
FCQ140C7VEB
3
units + outdoor units
Cooling capacity Standard kW 10.0 12.50 14.00
Heating capacity Standard kW 11.20 14.00 16.00 1
Power Input Cooling Standard kW 2.640 3.880 5.36
2
Heating Standard kW 3.140 4.360 5.69
For combination EER Nominal 3.79 3.22 2.61
indoor units + outdoor COP Nominal 3.57 3.21 2.81
units
Energy Label Cooling A A D
Heating B C D
Annual energy consumption kWh 1320 1940 2680
Indoor Units FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
Cooling capacity Standard kW 10.00 12.50 14.00
Heating capacity Standard kW 11.20 14.00 16.00
Power Input Cooling Standard kW 2.78 3.91 4.70
Heating Standard kW 2.79 3.69 4.40
For combination EER Nominal 3.60 3.20 2.98
indoor units + outdoor COP Nominal 4.01 3.79 3.64
units
Energy Label Cooling A B C
Heating A
Annual energy consumption kWh 1,390 1,955 2,350
Indoor Units FHQ100BVV1B FHQ125BVV1B FCQH140D7VEB
Cooling capacity Standard kW 10.00 12.50 14.00
Heating capacity Standard kW 11.20 14.00 16.00
Power Input Cooling Standard kW 3.150 4.450 4.640
Heating Standard kW 3.600 4.500 4.480
For combination EER Nominal 3.17 2.81 3.02
indoor units + outdoor COP Nominal 3.11 3.11 3.57
units Energy Label Cooling B C B
Heating D D B
Annual energy consumption kWh 1575 2225 2,325
Indoor Units FUQ100BVV1B FUQ125BVV1B
Cooling capacity Standard kW 10.00 12.50
Heating capacity Standard kW 11.20 14.00
Power Input Cooling Standard kW 3.120 4.050
Heating Standard kW 3.280 4.360
For combination EER Nominal 3.21 3.09
indoor units + outdoor COP Nominal 3.41 3.21
units Energy Label Cooling A B
Heating B C
Annual energy consumption kWh 1560 2025
Indoor Units FAQ100BVV1B FDQ125B8V3B9
Cooling capacity Standard kW 10.00 12.50
Heating capacity Standard kW 11.20 14.00
Power Input Cooling Standard kW 2.780 4.150
Heating Standard kW 3.390 3.690
For combination EER Nominal 3.60 3.01
indoor units + outdoor COP Nominal 3.30 3.79
units Energy Label Cooling A B
Heating C A
Annual energy consumption kWh 1390 2075
Indoor Units FCQH100D7VEB FCQH125D7VEB
Cooling capacity Standard kW 10.00 12.50
Heating capacity Standard kW 11.20 14.00
Power Input Cooling Standard kW 2.430 3.530
Heating Standard kW 2.530 3.570

• Split Sky Air • Outdoor Units 6


• Outdoor Units • R-410A • RZQ100-140B8W1B

2 Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B


For combination EER Nominal 4.12 3.54
indoor units + outdoor COP Nominal 4.43 3.92
units
Energy Label Cooling A A
1 Heating A A
Annual energy consumption kWh 1,220 1,770
2
2-2 TECHNICAL SPECIFICATIONS RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B
Casing Colour Ivory White
Material Painted galvanised steel
Dimensions Unit Height mm 1345 1345 1345
Width mm 900 900 900
Depth mm 320 320 320
Packing Height mm 1524 1524 1524
Width mm 980 980 980
Depth mm 420 420 420
Weight Unit kg 106 106 106
Packed Unit kg 112 112 112
Heat Exchanger Dimensions Length mm 857 857 857
Nr of Rows 2 2 2
Fin Pitch mm 1.40 1.40 1.40
Nr of Passes 5 5 5
Face Area m² 1.131 1.131 1.131
Nr of Stages 60 60 60
Tube type Hi-XSS(8)
Fin Type WF fin
Treatment Anti-corrosion treatment (PE)
Fan Type Propeller
Discharge direction Horizontal
Quantity 2 2 2
Air Flow Rate (nominal Cooling m³/min 103.0 99.0 99.0
at 230V) Heating m³/min 101.0 100.0 100.0
Motor Quantity 2 2 2
Model KFD-325-70-8A
Motor Speed (nominal) Steps 8 8 8
Cooling rpm 789 782 782
(Standard)
Heating rpm 775 767 767
(Standard)
Fan Motor Output W 70 70 70
Compressor Quantity 1 1 1
Motor Model JT1G-VDYR@T
Type Hermetically sealed scroll compressor
Motor Output W 2200 2200 2200
Crankcase W 33 33 33
Heater
Operation Range Cooling Min °CDB -15.0 -15.0 -15.0
Max °CDB 50.0 50.0 50.0
Heating Min °CWB -20.0 -20.0 -20.0
Max °CWB 15.5 15.5 15.5
Sound Level (nominal) Cooling Sound Power dBA 65.0 66.0 66.0
Sound dBA 49.0 50.0 50.0
Pressure
(Standard)
Heating Sound dBA 51.0 52.0 52.0
Pressure
(Standard)
Sound Level (Night Sound Pressure dBA 45.0 45.0 45.0
quiet)

7 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

2 Specifications

2-2 TECHNICAL SPECIFICATIONS


Refrigerant Type
RZQ100B8W1B RZQ125B8W1B
R-410A
RZQ140B8W1B
3
Charge kg 4.30 4.30 4.30
Control Expansion valve (electronic type)
Nr of Circuits 1 1 1 1
Refrigerant Oil Type Daphne FVC68D
2
Charged Volume l 1.0 1.0 1.0
Piping connections Liquid (OD) Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 9.52 9.52 9.52
Gas Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 15.9 15.9 15.9
Drain Quantity 3 3 3
Type Hole
Diameter (OD) mm 26 26 26
Piping Length Minimum m 5 5 5
Maximum m 75 75 75
Equivalent m 95 95 95
Chargeless m 30 30 30
Additional Refrigerant Charge kg/m see installation manual 4PW21412-1
Installation height Maximum m 30.0 30.0 30.0
difference
Max. internunit level difference m 0.5 0.5 0.5
Heat Insulation Both liquid and gas pipes
Defrost Method Pressure equalising
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Safety Devices High pressure switch
Fan motor thermal protector
Fuse
Standard Accessories Item Tie-wraps
Quantity 2 2 2
Item Installation manual
Quantity 1 1 1
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor
temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor
temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m

2-3 ELECTRICAL SPECIFICATIONS RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B


Power Supply Name W1B
Phase 3N~
Frequency Hz 50 50 50
Voltage V 400 400 400
Voltage range Minimum V -10%
Maximum V +10%
Current Recomended fuses A 20 20 20
Wiring connections For Power Supply Remark see installation manual 4PW21412-1
For connection with Remark see installation manual 4PW21412-1
indoor
Power Supply Intake Outdoor unit only
Notes See separate drawings for electrical data
Power supply intake for FDQ is outdoor and indoor unit

• Split Sky Air • Outdoor Units 8


• Outdoor Units • R-410A • RZQ100-140B8W1B

3 Electrical data

RZQ-BW1
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA

1
3

3D048638C

SYMBOLS NOTES
MCA : Min. Circuit Amps (A) 1 RLA is based on the following conditions:
Power supply: 50Hz 230V
TOCA : Total Over Current Amps (A) Cooling Heating
Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB
MFA : Max. Fuse Amps (See note 7) (A) Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB
MSC : MSC means the max. current during the 2 TOCA means the total value of each OC set
starting of compressor. (A) 3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
RLA : Rated Load Amps (A) above listed operation range limits
OFM : Outdoor Fan Motor (A) 4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
IFM : Indoor Fan Motor (next lower standard fuse rating, min.15A)
FLA : Full Load Amps 6 Select wire size based on the larger value of MCA or TOCA
kW : Fan Motor Rated Output (kW) 7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice.

9 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

3 Electrical data

RZQ-BW1
Unit combination Power supply Comp. OFM IFM
3
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA

1
3

3D048638C

SYMBOLS NOTES
MCA : Min. Circuit Amps (A) 1 RLA is based on the following conditions:
Power supply: 50Hz 230V
TOCA : Total Over Current Amps (A) Cooling Heating
Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB
MFA : Max. Fuse Amps (See note 7) (A) Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB
MSC : MSC means the max. current during the 2 TOCA means the total value of each OC set
starting of compressor. (A) 3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
RLA : Rated Load Amps (A) above listed operation range limits
OFM : Outdoor Fan Motor (A) 4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
IFM : Indoor Fan Motor (next lower standard fuse rating, min.15A)
FLA : Full Load Amps 6 Select wire size based on the larger value of MCA or TOCA
kW : Fan Motor Rated Output (kW) 7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice.

• Split Sky Air • Outdoor Units 10


• Outdoor Units • R-410A • RZQ100-140B8W1B

4 Options

RZQ-B8

Kit name
RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B

1 Name of option
RZQS71D7V1B
-
RZQS100D7V1B
RZQ100B8W1B
RZQS125D7V1B
RZQ125B8W1B
RZQS140D7V1B
RZQ140B8W1B
4 Central drain plug EKDK04
Twin KHRQ22M20TA (KHRQ58T): see note

Refrigerant branch piping Triple - KHRQ127H (KHRQ58H): see note


KHRQ22M20TA (KHRQ58T): see note
Double-twin - -
(3x)
Demand adapter kit KRP58M51

NOTE
1 For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.

3TW26739-1F

11 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-1 Combination table
RZQ-B
Multi Combination Possibilities:
3
P = Pair 71 100 125 140
2 = Twin 35+35 50+50 60+60 71+71
3 = Triple
4 = Double Twin
35+35+35 50+50+50 (*)
35+35+35+35 (*)
50+50+50 (*)
35+35+35+35
1
(*) Max capacity depend on outdoor unit 5
Sky-air HH Cassette Thin cassette 2x2 cassette New Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP Duct Floor standing
FCQH100D7VEB

FCQH125D7VEB

FCQH140D7VEB
FCQH71D7VEB

FCQ100C7VEB

FCQ125C7VEB

FCQ140C7VEB

FBQ100C7VEB

FBQ125C7VEB

FBQ140C7VEB

FHQ100BVV1B

FHQ125BVV1B

FUQ100BVV1B

FUQ125BVV1B

FAQ100BVV1B

FDQ125B8V3B
FCQ35C7VEB

FCQ50C7VEB

FCQ60C7VEB

FCQ71C7VEB

FBQ35C7VEB

FBQ50C7VEB

FBQ60C7VEB

FBQ71C7VEB

FHQ35BVV1B

FHQ50BVV1B

FHQ60BVV1B

FHQ71BVV1B

FUQ71BVV1B

FAQ71BVV1B

FVQ100BV1B

FVQ125BV1B
FFQ35B8V1B

FFQ50B8V1B

FFQ60B8V1B

FVQ71BV1B
Model name

RZQ71D7V1B - P 2 P 2 2 P 2 P P P
RZQ100D7V1B RZQ100B8W1B P 3 2 P 3 2 3 2 P 3 2 P P P
RZQ125D7V1B RZQ125B8W1B P 4 3 2 P 4 3 2 4 3 2 P 4 3 2 P P P
RZQ140D7V1B RZQ140B8W1B 2 P 4 3 2 P 4 3 4 3 2 P 4 3 2 2 2

Sky-air HH Cassette Thin cassette 2x2 cassette New Duct (medium ESP) Ceiling suspended 4way ceiling Wall mounted High ESP Duct Floor standing
FCQH100D7VEB

FCQH125D7VEB

FCQH140D7VEB
FCQH71D7VEB

FCQ100C7VEB

FCQ125C7VEB

FCQ140C7VEB

FBQ100C7VEB

FBQ125C7VEB

FBQ140C7VEB

FHQ100BVV1B

FHQ125BVV1B

FUQ100BVV1B

FUQ125BVV1B

FAQ100BVV1B

FDQ125B8V3B
FCQ35C7VEB

FCQ50C7VEB

FCQ60C7VEB

FCQ71C7VEB

FBQ35C7VEB

FBQ50C7VEB

FBQ60C7VEB

FBQ71C7VEB

FHQ35BVV1B

FHQ50BVV1B

FHQ60BVV1B

FHQ71BVV1B

FUQ71BVV1B

FAQ71BVV1B

FVQ100BV1B

FVQ125BV1B
FFQ35B8V1B

FFQ50B8V1B

FFQ60B8V1B

FVQ71BV1B
Model name

RZQ71D7V1B P 2 P 2 2 P 2 P P P
RZQ100D7V1B P 3 2 P 3 2 3 2 P 3 2 P P P
RZQ125D7V1B P 4 3 2 P 4 3 2 4 3 2 P 4 3 2 P P P
RZQ140D7V1B 2 P 4 3 2 P 4 3 4 3 2 P 4 3 2 2

NOTES
1 Individual indoor capacities are not given because the combinations are for simultaneous operation (= indoor units installed in the same room)
2 When different indoor models are used in combination, designate the remote control that is equipped with the most function as the main unit.

3TW26739-2C

• Split Sky Air • Outdoor Units 12


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-2 Cooling capacity tables
RZQ100B (Pair + Twin / triple)
Cooling

1
5
Coefficient of power input ( - )

Capacity range
Rated point

Cooling Capacity (kW)

Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 10.2 6.93 0.86 10.2 7.00 1.01 10.5 7.29 1.12 10.1 7.08 1.23
18.0 25 11.8 7.59 0.94 11.3 7.45 1.03 11.0 7.27 1.13 10.5 7.06 1.24
19.0 27 12.0 7.57 0.95 11.6 7.43 1.03 11.2 7.26 1.13 10.8 7.04 1.24
19.5 27 12.1 7.56 0.95 11.8 7.41 1.03 11.3 7.25 1.13 10.9 7.03 1.24
22.0 30 12.7 7.46 0.96 12.3 7.32 1.04 11.9 7.16 1.14 11.4 6.96 1.25
24.0 32 13.2 7.36 0.96 12.8 7.22 1.05 12.4 7.06 1.15 11.9 6.87 1.27

3TW28121-1A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH100D FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Bx2 FBQ50Cx2 FHQ50x2
AFR 34 23.5 30 28 27 32 24 23 29 AFR 12.5x2 15x2 12x2 14x2 16x2 13x2
(BF) (0.17) (0.16) (0.11) (0.16) (0.20) (0.14) (0.14) (0.10) (0.07) (BF) (0.21x2) (0.16x2) (0.16x2) (0.15x2) (0.16x2) (0.1x2)
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35Bx3 FBQ35Cx3 FHQ35x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)

8 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH100C FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Cx2 FBQ50x2 FHQ50x2
Cooling 2.43 2.64 2.44 2.64 2.86 2.78 3.15 2.78 3.12 Cooling 2.78 2.78 2.79 3.01 2.91 3.32
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35x3 FBQ35Cx3 FHQ35x3
Cooling 2.78 2.78 2.79 3.01 2.91 3.32

13 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-2 Cooling capacity tables
RZQ125B (Pair + Twin / triple / double twin)
Cooling
3

1
5
Coefficient of power input ( - )

Capacity range Rated point

Cooling Capacity (kW)

Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 12.8 8.66 0.87 12.8 8.75 1.01 13.1 9.12 1.13 12.7 8.85 1.24
18.0 25 14.7 9.50 0.95 14.2 9.32 1.04 13.7 9.09 1.14 13.2 8.83 1.25
19.0 27 14.9 9.46 0.96 14.4 9.28 1.04 14.0 9.06 1.14 13.4 8.80 1.25
19.5 27 15.1 9.45 0.96 14.7 9.27 1.04 14.1 9.05 1.14 13.6 8.79 1.25
22.0 30 15.9 9.33 0.97 15.5 9.16 1.05 14.9 8.95 1.15 14.3 8.69 1.27
24.0 32 16.5 9.20 0.97 16.0 9.03 1.06 15.5 8.83 1.16 14.9 8.59 1.28

3TW28131-1A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH125D FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Bx2 FBQ60Cx2 FHQ60x2
AFR 34 27.5 30 31 35 39 30 32 45 AFR 13.5x2 18x2 15x2 19x2 18x2 17x2
(BF) (0.19) (0.19) (0.13) (0.07) (0.14) (0.16) (0.13) (0.07) (0.25) (BF) (0.21x2) (0.1x2) (0.11x2) (0.11x2) (0.15x2) (0.2x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.11x4) (0.15x4) (0.2x4)

8 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH125D FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Cx2 FBQ60Cx2 FHQ60x2
Cooling 3.53 3.88 3.54 3.88 3.98 3.91 4.45 4.05 4.15 Cooling 4.08 4.08 4.13 4.19 4.12 4.45
(Triple) (Double twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
Cooling 4.08 4.08 4.13 4.19 4.12 4.45 Cooling 4.08 4.08 4.13 4.19 4.12 4.45

• Split Sky Air • Outdoor Units 14


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-2 Cooling capacity tables
RZQ140B (Pair + Twin / triple / double twin)
Cooling

1
5
Coefficient of power input ( - )

Capacity range
Rated point

Cooling Capacity (kW)

Cooling
Indoor Outdoor temperature (°C DB)
25 30 35 40
EWB EDB
°C °C TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 14.1 9.53 0.87 14.0 9.61 1.01 14.4 10.0 1.13 13.9 9.72 1.24
18.0 25 16.1 10.5 0.95 15.6 10.2 1.04 15.1 10.0 1.14 14.5 9.70 1.25
19.0 27 16.5 10.4 0.96 16.0 10.2 1.04 15.4 9.98 1.14 14.7 9.68 1.25
19.5 27 16.6 10.4 0.96 16.2 10.2 1.04 45.5 9.96 1.14 15.0 9.67 1.25
22.0 30 17.5 10.3 0.97 16.9 10.1 1.05 16.4 9.85 1.15 15.7 9.56 1.27
24.0 32 18.2 10.1 0.97 17.6 9.93 1.06 17.1 9.71 1.16 16.4 9.45 1.28

3TW28141-3A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total cooling capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions. Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FBQ-C FCQ71Cx2 FCQ71Bx2 FFQ71x2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FAQ71x2 FCQH140Dx2
AFR 34 27.5 30 39 AFR 15.5x2 18x2 19x2 18x2 17x2 19x2 19x2 21x2
(BF) (0.20) (0.19) (0.13) (0.16) (BF) (0.19x2) (0.1x2) (0.11x2) (0.08x2) (0.1x2) (0.07x2) (0.08x2) (0.17x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.15x4) (0.15x4) (0.2x4)

8 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FCQ140B FCQ71Cx2 FCQ71Bx2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FUQ71x2 FAQ71x2 FCQH250Dx2
Cooling 4.64 5.36 4.65 4.70 Cooling 4.81 4.81 4.95 4.96 4.99 4.99 4.92 4.90
(Triple) (Double twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
Cooling 4.81 4.81 4.86 4.95 4.96 4.99 Cooling 4.81 4.81 4.86 4.95 4.96 4.99

15 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-2 Cooling capacity tables
RZQ140BW1 (Pair) 3
Cooling

1
Coefficient of power input. (-)

Cooling capacity (Rated point)


Capacity range
Cooling capacity 400V [50Hz]
Indoor Outdoor temp. (°CDB)
EWB EDB 25 30 35 40
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
(°C) (°C)
(kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-) (kW) (kW) (-)
16.0 22 12.3 8.29 0.76 12.2 8.37 0.89 12.5 8.73 0.99 12.1 8.46 1.09
18.0 25 14.0 9.09 0.83 13.§ 8.91 0.91 13.1 8.70 1.00 12.6 8.44 1.10
19.0 27 14.4 9.06 0.84 13.9 8.89 0.91 13.4 8.68 1.00 12.8 8.42 1.10
19.5 27 14.5 9.05 0.84 14.1 8.87 0.91 13.5 8.66 1.00 13.0 8.41 1.10
22.0 30 15.2 8.93 0.85 14.7 8.77 0.92 14.3 8.57 1.01 13.7 8.32 1.11
24.0 32 15.8 8.81 0.85 15.3 8.64 0.93 14.8 8.45 1.02 14.3 8.22 1.12
3TW28149
NOTES SYMBOLS
1. This capacity table is only valid for pair combination with FBQ140
2. Ratings shown are net capacities which include a deduction for indoor fan motor heat
AFR: Air flow rate (m3/min
3. On the figure the mark j show the max. at standard conditions. BF: Bypass factor
On the figure the mark Q show rated capacity and rated coefficient of power input. EWB: Entering wet bulb temp. (°CWB)
However the max. capacity is not guaranteed, except at standard condition. EDB: Entering dry bulb temp. (°CDB)
4. On the tables Q show rated capacity and rated coefficient of power input. TC: Total cooling/heating capacity (kW)
5. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC: Sensible heating capacity (kW)
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) PI: Power input (kW)
Add SHC* to SHC. (comp.+indoor+outdoor fan motor)
6. Capacities are based on following conditions: CPI: Coefficient of power input. (-)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length : 7.5 m
Level difference :0m Caution:
7. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
8. The value contains less than 5% error acording to indoor unit type. TC and SHC are shown by kW
9. Heating capacity include the drop of frost formation.
10. Air flow rate and BF are tabulated below.
Pair
Model FBQ140
AFR 35
(BF) (0.14)
11. Rated power input of each model is tabulated below.
Pair
Outdoor RZQ140C7
Indoor RZQ140C7
Cooling 4.76kW
Heating 4.82kW

• Split Sky Air • Outdoor Units 16


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-2 Cooling capacity tables
RZQ-B/C

Capacity in function of field piping length for non-inverter

1
5

Capacity (%)

Field piping length (m)


3TW26062-1
Cooling
Heating

17 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-3 Heating capacity tables
RZQ100B (Pair + Twin / triple)
Heating
3

1
5
Coefficient of power input ( - )

Capacity range Rated point

Heating Capacity (kW)

Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 7.16 0.87 7.91 0.92 8.66 0.96 9.41 1.01 12.8 1.06 13.8 1.12
18.0 7.15 0.90 7.90 0.95 8.65 1.00 9.39 1.05 12.8 1.10 13.8 1.16
20.0 7.15 0.94 7.89 0.99 8.64 1.04 9.38 1.09 12.8 1.15 13.8 1.21
21.0 7.14 0.96 7.89 1.01 8.63 1.06 9.38 1.11 12.8 1.17 13.8 1.23
22.0 7.14 0.98 7.88 1.03 8.63 1.08 9.37 1.14 12.8 1.20 13.7 1.25
24.0 7.13 1.02 7.87 1.07 8.62 1.12 9.36 1.17 12.8 1.24 13.7 1.30

3TW28121-1A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH100D FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Bx2 FBQ50Cx2 FHQ50x2
AFR 34 23.5 30 28 27 32 24 23 29 AFR 12.5x2 15x2 12x2 14x2 16x2 13x2
(BF) (0.17) (0.16) (0.11) (0.16) (0.20) (0.14) (0.14) (0.10) (0.07) (BF) (0.21x2) (0.16x2) (0.16x2) (0.15x2) (0.16x2) (0.1x2)
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35Bx3 FBQ35Cx3 FHQ35x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)

9 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH100C FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Cx2 FBQ50x2 FHQ50x2
Heating 2.53 3.14 2.56 3.14 3.00 2.79 3.60 3.39 3.28 Heating 3.31 3.31 3.21 3.16 2.95 3.79
(Triple)
FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35x3 FBQ35Cx3 FHQ35x3
Heating 3.31 3.31 3.21 3.16 2.95 3.79

• Split Sky Air • Outdoor Units 18


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-3 Heating capacity tables
RZQ125B (Pair + Twin / triple / double twin)
Heating

1
5
Coefficient of power input ( - )

Capacity range Rated point

Heating Capacity (kW)

Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 8.83 0.89 9.76 0.94 10.7 0.99 11.6 1.04 16.2 1.09 17.5 1.14
18.0 8.82 0.93 9.74 0.98 10.7 1.03 11.6 1.08 16.2 1.13 17.5 1.19
20.0 8.81 0.97 9.73 1.02 10.7 1.07 11.6 1.12 16.2 1.18 17.5 1.24
21.0 8.81 0.99 9.73 1.04 10.6 1.09 11.6 1.14 16.2 1.20 17.5 1.26
22.0 8.80 1.00 9.72 1.05 10.6 1.11 11.6 1.16 16.2 1.23 17.5 1.29
24.0 8.79 1.04 9.71 1.10 10.6 1.15 11.5 1.21 16.2 1.27 17.4 1.33

3TW28131-1A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH125D FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Bx2 FBQ60Cx2 FHQ60x2
AFR 34 27.5 30 31 35 39 30 32 45 AFR 13.5x2 18x2 15x2 19x2 18x2 17x2
(BF) (0.19) (0.19) (0.13) (0.07) (0.14) (0.16) (0.13) (0.07) (0.25) (BF) (0.21x2) (0.1x2) (0.11x2) (0.11x2) (0.15x2) (0.2x2)
(Triple)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3
AFR 10.5x3 14x3 10x3 11.5x3 16x3 13x3
(BF) (0.28x3) (0.16x3) (0.25x3) (0.15x3) (0.15x3) (0.2x3)

9 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH125C FCQ125C FCQ125D FCQ125B FBQ125B FBQ125C FHQ125 FUQ125 FDQ125 FCQ60Cx2 FCQ60Bx2 FFQ60x2 FBQ60Cx2 FBQ60x2 FHQ60x2
Heating 3.57 4.36 3.59 4.36 3.99 3.69 4.50 4.36 3.69 Heating 4.59 4.59 4.26 4.20 3.90 4.74
(Triple) (Double twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50x3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
Heating 4.59 4.59 4.26 4.20 3.90 4.74 Heating 4.59 4.59 4.26 4.20 3.90 4.74

19 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-3 Heating capacity tables
RZQ140B (Pair + Twin / triple / double twin)
Heating
3

1
5
Coefficient of power input ( - )

Capacity range Rated point

Heating Capacity (kW)

Heating
Indoor Outdoor temperature (°C WB)
-15 -10 -5 0 6 10
EDB
°C TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.0 9.82 0.86 10.8 0.91 11.9 0.95 12.9 1.00 18.0 1.05 19.5 1.11
18.0 9.80 0.90 10.8 0.94 11.8 0.99 12.9 1.04 18.0 1.09 19.4 1.15
20.0 9.79 0.94 10.8 0.98 11.8 1.03 12.9 1.08 18..0 1.14 19.4 1.20
21.0 9.79 0.95 10.8 1.00 11.8 1.05 12.8 1.10 18.0 1.16 19.4 1.22
22.0 9.78 0.97 10.8 1.02 11.8 1.07 12.8 1.12 18.0 1.19 19.4 1.24
24.0 9.77 1.00 10.8 1.06 11.8 1.11 12.8 1.17 18.0 1.23 19.4 1.29

3TW28141-3A

NOTES SYMBOLS
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat. AFR : Air flow rate (m3/min.)
2 On the figure the mark with show the max, onces at standard conditions. BF : Bypass factor
On the figure the mark with show rated capacity and rated coefficient of power input. EWB : Entering wet bulb temp. (°C WB)
However the max. Capacity is not guaranteed ecxept at standard condition. EDB : Entering dry bulb temp. (°C DB)
3 SHC is based on each EWB and EDB. TC : Total heating capacity (kW)
SHC for other dry bulb temperature = SHC + SHC*. SHC : Sensible heat capacity (kW)
SHC* = SHC correction for other dry bulb. PI : Power input (Comp.+indoor+outdoor fan motor).
= 0.02 x AFR (m3/min.) x (1-BF) x (DB*-EDB) CPI : Coefficient of power input (-)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Caution TC and SHC are shown by kW.
Outdoor air: 85% RH.
However, the condition rated capacity is 7°C DB / 6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are given in table below:
(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FBQ140C FCQ71Cx2 FCQ71Bx2 FFQ71x2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FAQ71x2 FCQH140Dx2
AFR 34 27.5 30 39 AFR 15.5x2 18x2 19x2 18x2 17x2 19x2 19x2 21x2
(BF) (0.20) (0.19) (0.13) (0.16) (BF) (0.19x2) (0.1x2) (0.11x2) (0.08x2) (0.1x2) (0.07x2) (0.08x2) (0.17x2)
(Triple) (Double Twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
AFR 12.5x3 15x3 12x3 14x3 16x3 13x3 AFR 10.5x4 14x4 10x4 11.5x4 16x4 13x4
(BF) (0.21x3) (0.16x3) (0.16x3) (0.15x3) (0.16x3) (0.1x3) (BF) (0.28x4) (0.16x4) (0.25x4) (0.15x4) (0.15x4) (0.2x4)

9 Rated power input of each model is tabulated below.


(Pair) (Twin)
FCQH140D FCQ140C FCQ140D FBQ-C FCQ71Cx2 FCQ71Bx2 FBQ71Bx2 FBQ71Cx2 FHQ71x2 FUQ71x2 FAQ71x2 FCQH140Dx2
Heating 4.48 5.69 4.52 4.40 Heating 5.52 5.52 5.06 4.64 5.69 5.05 5.22 4.80
(Triple) (Double twin)
FCQ50Cx3 FCQ50Bx3 FFQ50x3 FBQ50Bx3 FBQ50Cx3 FHQ50x3 FCQ35Cx4 FCQ35Bx4 FFQ35x4 FBQ35Bx4 FBQ35Cx4 FHQ35x4
Heating 5.52 5.52 5.11 5.06 4.64 5.69 Heating 5.52 5.52 5.11 5.06 4.64 5.69

• Split Sky Air • Outdoor Units 20


• Outdoor Units • R-410A • RZQ100-140B8W1B

5 Capacity tables
5-3 Heating capacity tables
RZQ140BW1 (Pair)

Heating

1
Coefficient of power input. (-)

Heating capacity (Rated point)


Capacity range

Heating capacity 400V [50Hz]


Indoor Outdoor temp. (°CWB)
EDB −15 −10 −5 0 6 10
TC CPI TC CPI TC CPI TC CPI TC CPI TC CPI
(°C)
(kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-) (kW) (-)
16.O 9.51 1.05 10.5 1.11 11.5 1.16 12.5 1.22 15.5 0.92 16.8 0.97
18.O 9.49 1.10 10.5 1.15 11.4 1.21 12.5 1.27 15.5 0.96 16.7 1.01
20.0 9.48 1.14 10.5 1.20 11.4 1.26 12.5 1.32 15.5 1.00 16.7 1.05
21.O 9.48 1.16 10.5 1.22 11.4 1.28 12.4 1.34 15.5 1.02 16.7 1.07
22.O 9.47 1.18 10.5 1.24 11.4 1.31 12.4 1.37 15.5 1.04 16.7 1.09
24.0 9.46 1.22 10.5 1.29 11.4 1.35 12.4 1.42 15.5 1.08 16.7 1.13
3TW28149
NOTES SYMBOLS
1. This capacity table is only valid for pair combination with FBQ140
2. Ratings shown are net capacities which include a deduction for indoor fan motor heat
AFR: Air flow rate (m3/min
3. On the figure the mark j show the max. at standard conditions. BF: Bypass factor
On the figure the mark Q show rated capacity and rated coefficient of power input. EWB: Entering wet bulb temp. (°CWB)
However the max. capacity is not guaranteed, except at standard condition. EDB: Entering dry bulb temp. (°CDB)
4. On the tables Q show rated capacity and rated coefficient of power input. TC: Total cooling/heating capacity (kW)
5. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC: Sensible heating capacity (kW)
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) PI: Power input (kW)
Add SHC* to SHC. (comp.+indoor+outdoor fan motor)
6. Capacities are based on following conditions: CPI: Coefficient of power input. (-)
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length : 7.5 m
Level difference :0m Caution:
7. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
8. The value contains less than 5% error acording to indoor unit type. TC and SHC are shown by kW
9. Heating capacity include the drop of frost formation.
10. Air flow rate and BF are tabulated below.
Pair
Model FBQ140
AFR 35
(BF) (0.14)
11. Rated power input of each model is tabulated below.
Pair
Outdoor RZQ140C7
Indoor RZQ140C7
Cooling 4.76kW
Heating 4.82kW

21 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

6 Dimensional drawing & centre of gravity


6-1 Dimensional drawing
RZQ100-125-140BW1 unit (mm) 3
Hole for anchor bolt
4-M12 1 Gas pipe connection J15.9 flare
2 Liquid pipe connection - J9.5 flare
3
4
Service port (in the unit) (2x)
Grounding terminal M5 (in switch box)
1
5 Refrigerant piping intake
6 Power supply wiring intake (knock hole J34) 6
7 Control wiring intake (knock hole J27)
8 Drain outlet

3TW26071-1

• Split Sky Air • Outdoor Units 22


• Outdoor Units • R-410A • RZQ100-140B8W1B

6 Dimensional drawing & centre of gravity


6-2 Centre of gravity
RZQ-BW1

1
6

4TW26079-3

23 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

7 Piping diagram

RZQ100-125-140BW1(Pair) 3
One way valve

One way
valve
One way
valve
1
7
Heat exchanger
Filter
One way One way
Capillary valve valve
Solenoid tube
valve

Capillary Electronic
tube expansion
valve
Receiver Strainer
Capillary tube

Service port
5/16″
Heat exchanger
4-way valve

Filter Low pressure High pressure


switch switch Muffler

Field piping J9.5 C1220T-0 Service port


5/16″
Filter
Field piping J15.9 C1220T-0
Compressor

Indoor unit Outdoor unit Heating


Stop valve Cooling
(with service port 5/16’ flare)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW26745-1

RZQ100-125-140BW1(Twin)
One way valve

One way One way


valve valve
Heat exchanger

Filter Heat exchanger


One way One way
valve valve
Capillary
Solenoid tube
valve
Electronic
Capillary expansion
tube valve
Field piping Receiver Strainer
Capillary tube
Filter Field piping

Service port
Indoor unit 5/16″

4-way valve

Filter Low pressure High pressure


switch switch Muffler

Heat exchanger

Branch duct Field piping J9.5 Service port


connection 5/16″
C1220T-0
Option
Field piping J15.9

C1220T-0 Compressor

Outdoor unit
Field piping Heating
Cooling
Filter Field piping
Note: 1. The pipes between the branch and the indoor units should have the
same size as the indoor connections.
Stop valve
Indoor unit (with service port 5/16’ flare)

3TW26745-2
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split Sky Air • Outdoor Units 24


• Outdoor Units • R-410A • RZQ100-140B8W1B

7 Piping diagram

RZQ100-125-140BW1(Triple)
Indoor unit
Heat exchanger
One way valve

1 One way
valve
One way
valve

7 Stop valve
(with service port 5/16’ flare) Filter Heat exchanger
One way One way
Field piping valve valve
Capillary
Solenoid tube
Filter Field piping valve
Electronic
Capillary expansion
tube valve
Indoor unit Receiver Strainer
Heat exchanger
Capillary tube

Service port
5/16″
4-way valve
Field piping J9.5

C1220T-0
Field piping
Filter Low pressure High pressure
switch switch Muffler
Filter Field piping
Field piping J15.9

C1220T-0
Indoor unit Service port
5/16″
Heat exchanger Branch duct
connection
Option
Compressor

Outdoor unit
Heating
Field piping Note: 1. The pipes between the branch and Cooling
Filter the indoor units should have the same size
Field piping
as the indoor connections.
3TW26745-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQ100-125-140BW1(Double twin)
Heat Indoor unit
exchanger

One way
valve

One One way


way valve
Field piping valve
Filter Field piping Heat exchanger
Filter One One way
way valve
Indoor unit Solenoid Capillary
Heat valve
Field piping valve tube
exchanger
J9.5 Capillary Electronic
tube expansion
valve
Receiver Strainer
Field piping Capillary tube
J15.9
Service port
5/16″
Field piping
4-way valve
Filter Field piping
Low
Field piping J9.5 pressure High pressure
Heat Indoor unit Branch duct Filter switch
sensor
exchanger connection C1220T-0
Option
Field piping J15.9 Service
Muffler port
C1220T-0 5/16″
Compressor

Field piping

Filter Field piping Outdoor unit


Heating
Heat Cooling
exchanger Field piping
J9.5
Stop valve
(with service port 5/16’ flare)
Field piping
J15.9

Field piping Note: 1. The pipes between the branch and the
Field piping
indoor units should have the same size as the
Filter indoor connections.
3TW26755-4
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

25 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

8 Wiring diagram
8-1 Wiring diagram
RZQ100-125-140BW1 3
Indoor
Outdoor

L : Live
1
N : Neutral
8

NOTE 1.
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
: Relay connector

Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow / ON
BRN: Brown / GRN: Green OFF

NOTES:
1. Refer to the optional manual, for connection
wiring to X6A.
2. Confirm the method of setting the selector
switches (DS1) by service manual. When the
unit is shipped by factory all switches are set
Reactor box
to be off.
El. comp. assy front View A

A1P Printed circuit board K1M(A2P) Magnetic contactor R1T Thermistor (air) V2R-V3R Diode module
A2P Printed circuit board (INV) K1R(A1P) Magnetic relay (Y1S) R2T Thermistor (coil) V1T IGBT
BS1 Push button switch (forced defrost / pump down) K2R(A1P) Magnetic relay (Y2S) R3T Thermistor (discharge pipe) X6A Connector (Option)
C1-C2-C3 Capacitor K3R(A1P) Magnetic relay (E1HC) R4T Thermistor (suction pipe) X1M Terminal strip
DS1 Dip switch K4R, K5R Magnetic relay R5T Thermistor (power module) Y1E Expansion valve
F1U (A2P) Fuse (T 6,3A/250V) L1R Reactor S1PH Pressure switch (high) Y1S 4-way valve
F2U Fuse (T 6,3A/250V) M1C Motor compressor S1NPL Pressure sensor (low) Y2S Solenoid valve
F3U Fuse (B 10A/250V) M1F Motor fan RC Signal receiver circuit Z1C, Z2C Noise filter
F4U Fuse (B 10A/250V) PS Power circuit TC Signal transmission circuit Z3C, Z4C
HAP (A1P) Light emitting diode (service monitor green) Q1DI Earth leakage breaker (30mA) V1R Power module Z1F Noise filter 2TW26766-1
HAP (A2P) Light emitting diode (service monitor green) R1-R2 Resistor Z1F Noise filter (with surge absorber)
H1P (A1P) Light emitting diode (service monitor red)

• Split Sky Air • Outdoor Units 26


• Outdoor Units • R-410A • RZQ100-140B8W1B

9 Sound data
9-1 Sound pressure spectrum
RZQ100BW1 - Cooling RZQ100BW1 - Heating
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]


1
9

3TW26747-1 Octave band center frequency (Hz) 3TW26747-2 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)

RZQ125BW1 - Cooling RZQ125BW1 - Heating


Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

3TW26757-1 Octave band center frequency (Hz) 3TW26757-2 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)

27 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

9 Sound data
9-1 Sound pressure spectrum
RZQ140BW1 - Cooling RZQ140BW1 - Heating 3
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]


1
9

3TW26787-1 Octave band center frequency (Hz) 3TW26787-2 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level 3 dB(A) = A-weighted sound pressure level
(A-scale according to IEC) (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa
Measuring location Measuring location
(discharge side) (discharge side)

• Split Sky Air • Outdoor Units 28


• Outdoor Units • R-410A • RZQ100-140B8W1B

9 Sound data
9-2 Sound power spectrum
RZQ100BW1 - Cooling RZQ125BW1 - Cooling
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]


1
9

3TW26747-3 Octave band center frequency (Hz) 3TW26757-3 Octave band center frequency (Hz)

NOTES NOTES

1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal conditions. 2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level (A-scale according to IEC) 3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa

RZQ140BW1 - Cooling
Sound pressure level [dB(A)]

3TW26787-3 Octave band center frequency (Hz)

NOTES

1 Data is valid at free field condition


2 Data is valid at nominal conditions.
3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)
4 Reference acoustic pressure 0dB = 20μPa

29 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • RZQ100-140B8W1B

10 Installation
10 - 1 Installation method
RZQ100-125-140BW1 3
A. Non stacked installation
Legend

Suction side obstacle 1


Discharge side obstacle 10
Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

In these cases, close the


bottom of the installation
frame to prevent discharged
air from being bypassed.

In these cases, only 2 units can


be installed.
This situation is not allowed.

Figures between ( ) indicate the


dimensions only for the 100-125-140
B. Stacked installation class models.

1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet

Do not stack more than one unit.


About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation

1. Installation of one unit per row 2. Installing multiple units (2 units or more) in
lateral connection per row

Relation of dimensions of H, A, and L are shown in the


table below.
L A
0 < L ≤ 1/2 H 150 (250)
L≤H
1/2 H < L 200 (300)
H<L Installation impossible

3TW26739-4

• Split Sky Air • Outdoor Units 30


• Outdoor Units • R-410A • RZQ100-140B8W1B

11 Operation range

RZQ-B (Cooling)

1
11

Allowable range of operation (pull-down)


(Heating)
Outdoor temp. (°CDB)

Operation range

Outdoor temp. (°CWB)

Operation range
operation (warming-up)
Allowable range of
Indoor temp. (°CWB) Indoor temp. (°CDB)

NOTE
1 Depending on operation and istallation conditions. The indoor unit can change over to freeze-up operation (indoor de-icing)
2 To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind.

3TW26733-1B

31 • Split Sky Air • Outdoor Units