DTSU666-H and DTSU666-H 250 A/50mA Smart
Power Sensor
Quick Guide
Issue: 03
Date: 2019-09-29
HUAWEI TECHNOLOGIES CO., LTD.
1 Overview
Models
• DTSU666-H: with three 100 A/40 mA CT
• DTSU666-H 250 A/50 mA: with three 250 A/50 mA CT
Smart Power Sensor dimensions
100 A CT dimensions
250 A CT dimensions
Appearance
Differences between DTSU666-H and DTSU666-H 250 A/50 mA:
• Parameters on the panel
DTSU666-H DTSU666-H 250 A/50 mA
1 Copyright © Huawei Technologies Co., Ltd. 2019. All
rights reserved.
Appearance
• Nameplate
DTSU666-H DTSU666-H 250 A/50 mA
Performance and Specification
Category DTSU666-H DTSU666-H 250 A/50 mA
Nominal voltage 230 V AC / 400 V AC 230 V AC / 400 V AC
Current Measurement range 0–100 A 0–250 A
Power grid system 3P4W 3P4W or 3P3W
Port Definition
Voltage Input: 3×230/400 V or 3×400 V
Current Transformer(CT): 100 A/40 mA or 250 A/50 mA;
2
2 Installing the DTSU666-H and DTSU666-H 250 A/50 mA
1. Install the smart power
sensor on the standard
din rail of DIN35mm
2. Install the Smart Power
Sensor to the standard
din rail from the top to
the bottom, and then
push the instrument to
the din rail from the
bottom to the front
part.
3 Installing the Cable
Prepare cables
Conductor
Cross- Outer
Cable Port Type Source
sectional Area Diameter
Range
Ua-3
Four-core
AC power Ub-6 outdoor 10-21 Prepared by
4-6 mm2
cable copper mm the customer
Uc-9
cable
Un-10
IA*-13 / / /
IA-14 / / /
IB*-16 / / /
CT cable Manufacturer
IB-17 / / /
IC*-19 / / /
IC-21 / / /
RS485A-24 Two-core
Comm.
outdoor
cable 0.25-1 mm2 4-11 mm Manufacturer
shielded
RS485B-25 twisted pair
3
NOTE
A fuse and a thermistor are
connected to each phase of Ua,
Ub, and Uc inside the power
meter to prevent damage caused
by external short circuits. Ua, Ub,
and Uc do not need to be
protected by external fuses.
Wiring Diagram--Three Phase Four Wire
Support model:
• DTSU666-H
• DTSU666-H 250 A/50 mA
Operating voltage: 0.7–1.3 Un
1. Three phase four wire:
Connect the Ua, Ub, Uc,
Un voltage lines to the 3, 6,
9 and 10 terminals of the
collector. Connect current
transformer outlets IA*, IA,
IB*, IB, IC*, IC to terminals
13, 14, 16, 17, 19, 21 of
the collector.
2. Connect RS485A and
RS485B to the
communication host. NOTE
The CT direction must be consistent with the arrow direction as
shown in the preceding figure.
Wiring Diagram--Three Phase Three Wire
Support model:
• DTSU666-H 250 A/50 mA
Operating voltage: 0.7–1.3 Un
1. Three phase three wire:
Connect the Ua, Uc, Ub
voltage lines to the 3, 9 and
10 terminals of the
collector. Connect current
transformer outlets IA*, IA,
IB*, IB, IC*, IC to terminals
13, 14, 16, 17, 19, 21 of the
collector.
2. Connect RS485A and
RS485B to the
communication host. NOTE
The CT direction must be consistent with the arrow direction as
shown in the preceding figure.
4
4 User Interface
Display (Auto loop)
If no button is pressed for 60 seconds, the backlight turns off. Auto loop Switch time = 5s.
No. Display interface Description No. Display interface Description
Imp. active Exp. active
1 energy = 2 energy
10000.0 kWh = 2345.67 kWh
Phase A
Active power
3 4 voltage
= 3.291 kW
= 220.0 V
Phase C
Phase B voltage
5 6 voltage
= 220.1 V
= 220.20 V
Phase B
Phase A current
7 8 current
= 5.000 A
= 5.001 A
Phase C current Frequency
9 10
= 5.002 A freq = 50.00 Hz
5
Display (Change by key " ")
No. Display interface Description No. Display interface Description
Comb. active Imp. active
1 energy 2 energy
= 7654.33 kWh = 10000.0 kWh
None parity,
Exp. active
1 stop bit,
3 energy 4
Baud = 9600
= 2345.67 kWh
bps
Phase A
001 represents
5 6 voltage
address
= 220.0 V
Phase B Phase C
7 voltage 8 voltage
= 220.1 V = 220.20 V
Phase A Phase B
9 current 10 current
= 5.000 A = 5.001 A
Phase C Phase active
11 current 12 power = 3.291
= 5.002 A kW
Phase A active Phase B active
13 power = 1.090 14 power = 1.101
kW kW
Phase C active
Power factor
15 power 16
PFt = 0.500 L
= 1.100 kW
Phase A power Phase B power
17 factor 18 factor PFb =
Pfa = 1.000 L 0.500 L
Phase C power
Frequency freq
19 factor PFc = 20
= 50.00 Hz
0.500 C
Comb. active energy = Imp. active energy - Exp. active energy
6
Parameter
Parameter Value range Description
Settings for communication stop bit and
1: 645; Parity bits:
2: n.2; 1: Factory mode;
3: n.1; 2: None parity, 2 stop bits, n.2;
4: E.1; 3: None parity, 1 stop bit, n.1;
5: O.1; 4: Even parity, 1 stop bit, E.1;
5: Odd parity, 1 stop bit, O.1;
Communication baud rate:
0: 4.800;
0: 4800 bps;
1: 9.600;
1: 9600 bps;
11–19 Communication address
(Optional) Parameter Setup
NOTE
Communications parameters have been configured for the power meter before delivery. If the
communication is abnormal, check and set the parameters.
Button description: "SET" represents "confirm" or "cursor shift" (when entering digits), "ESC"
represents "exit", and "→" represents "add". The password is 701 by default.
7
5 Troubleshooting
Fault phenomenon Factor analysis Elimination method
1. If the wiring mode is incorrect,
please connect based on the
1. Incorrect wiring mode. correct wiring mode (see the
No display after the
2. Abnormal voltage supplied for wiring diagram).
instrument being
the instrument. 2. If the supplied voltage is
powered on
abnormal, please supply the
voltage on the instrument
specification.
1. If any problems for the
1. The RS485 communication
communication cable, please
cable is disconnected, short
change the cable.
circuit or reversely connected.
Abnormal RS485 2. Set the address, baud rate,
2. The address, baud rate, data
communication data bit and parity bit of the
bit and parity bit of the
instrument to be the same as the
instrument is not in accordance
inverter through buttons and so
with the inverter.
as the "parameter setting".
1. Wrong wiring, please check 1. For wrong wiring, please
whether the corresponding connect based on the correct
phase sequence of voltage and wiring mode (see the wiring
current is correct. diagram).
Power metering 2. Check whether the high and 2. If a negative value is
inaccuracy low ends of the current displayed, change the cable
transformer inlet are reversely connection mode of the current
connected. Pa, Pb, and Pc are transformer to ensure that the
abnormal if the values are high and low ends are
negative. connected properly.
6 Verifying the Installation
1. Check that all mounting brackets are securely installed and all screws are tightened.
2. Check that all cables are reliably connected with correct polarity and no short circuit.
7 Powering On the System
For details, see DTSU666-H and DTSU666-H 250 A (50 mA) Smart Power Sensor User Manual.
8
8 Customer Service Contact
Customer Service Contact
Region Country Service Support Email Phone
France
Germany
Spain
[email protected] 0080033888888
Europe Italy
UK
Netherlands
Other countries For details, see solar.huawei.com.
Australia [email protected] 1800046639
Turkey [email protected] -
0080021686868
Malaysia
/1800220036
Asia (+66) 26542662 (charged by
[email protected]
Pacific local call)
Thailand
1800290055 (free in Thailand)
China [email protected] 4008229999
Other countries [email protected] 0060-3-21686868
Japan Japan [email protected] 0120258367
South
[email protected] South Korea -
Korea
North USA
[email protected] 1-877-948-2934
America Canada
[email protected] 1-855-482-9343
018007703456
Mexico
/0052-442-4288288
Argentina 0-8009993456
Latin
Brazil
[email protected] 0-8005953456
America
Chile 800201866 (only for fixed)
Other countries 0052-442-4288288
08002229000
Egypt
/0020235353900
UAE 08002229000
Middle South Africa 0800222900
East and [email protected]
Africa Saudi Arabia 8001161177
Pakistan 0092512800019
Morocco 0800009900
Other countries 0020235353900
9
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang,
Shenzhen 518129, People's Republic of China
solar.huawei.com