3-18 Current Error / PFC Overload Error (Error Code: E462, E484)

The document provides troubleshooting steps for errors E462 and E484 involving a PFC overload error on an outdoor unit. It includes the following steps: 1. Check the power and restart the unit after a power reset. Check that wires are connected and the installation environment is proper. 2. Check that the indoor and outdoor units are installed correctly without obstructions, then check that the service valve is fully open and the compressor is operating normally. 3. If the issue persists, change the outdoor unit inverter PBA and check for normal operation.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views1 page

3-18 Current Error / PFC Overload Error (Error Code: E462, E484)

The document provides troubleshooting steps for errors E462 and E484 involving a PFC overload error on an outdoor unit. It includes the following steps: 1. Check the power and restart the unit after a power reset. Check that wires are connected and the installation environment is proper. 2. Check that the indoor and outdoor units are installed correctly without obstructions, then check that the service valve is fully open and the compressor is operating normally. 3. If the issue persists, change the outdoor unit inverter PBA and check for normal operation.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • 3-18 Current Error / PFC Overload Error

Troubleshooting

3-18 Current error / PFC overload error (Error Code : E462, E484)
1. Check items
1) Check the power and restarting after power reset Error CODE Error description Related model
E462 Outdoor unit total current error AM666FXMDCH series
2) Check the outdoor unit installation and environments E484 Outdoor unit PFC overload error AM666FXMDCH series
o Check if the outdoor unit inverter PBA related wires
are disconnected. Check the installation environment
3) Check for indoor unit installation environment
4) Check for open service valve

2. Check procedure

Turn off the power and turn it


on again after 30 seconds

Check the outdoor unit installation and


environment o Check for normal operation o
End service
No 1. Check for wire disconnection related to outdoor
Is the outdoor unit installed correctly? unit inverter PBA
2. Remove the obstacles on outdoor unit air inlet
and secure enough space
3. Remove the obstacles on outdoor unit air outlet
and secure enough space

Yes

[AM666FXMDCH series]

Check the indoor unit installation and


environment o Check for normal operation o
End service
No
Is the indoor unit installed correctly?? 1. Remove obstacles on air inlet and secure
enough space
2. Remove obstacles on air outlet and secure
enough space
Yes

No
Is the service valve completely open? Open the valve

Yes

No
Is the compressor operating normally? Change the compressor

Yes

Change the outdoor unit inverter PBA and check for normal
operation o End service

38 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine

Troubleshooting
38
Samsung Electronics
3-18 Current error / PFC overload error (Error Code : E462, E484)