Modbus Master
Modbus Master
The MODBUS RTU Master protocol driver has the following features:
Communications Cable
The Maple OIT should be connected to the device’s Modbus port.
A list of communications cables offered by Maple Systems as well as cable
assembly instructions to assist you in assembling your own communications
cable are available on our website at www.maple-systems.com/cables.htm.
WARNING: If your communications cable is not wired exactly as shown in
our cable assembly instructions, damage to the OIT or loss of communications
can result.
Controller Settings
The Modbus port on the Controller must be set to RTU Slave master
mode in order to properly communicate with the OIT (working as a
slave).
1035-0045, Rev. 01
Accessible Memory
Register Memory
The following table lists the controller’s register memory ranges that the Maple OITs are able to access.
Please note that your controller’s memory range may be smaller or larger than that supported by these
OITs. The following register memory can be displayed in 16, 32, or 64 bit format on the Maple OIT.
1The Sw3x and Sw4x registers read and write to the same memory areas as the 3x and 4x respectively.
However, these registers swap the word order when 32-bit values are used.
Discrete Memory
The following table lists the controller’s discrete memory ranges that Maple’s OITs are able to access.
Please note that your controller’s memory range may be smaller or larger than that supported by Maple’s
OITs. The following discrete memory is displayable in single-bit format on the Maple OIT.
2 The Bit3x and Bit4x coils read and write to the same memory as the 3x and 4x registers respectively.
However, these coils allow access to individual bits within the memory registers. The bit number is
specified by using the ‘/’character followed by the bit number, 0-15.
If you are connecting multiple PLCs/Controllers on a network to a BLU300 OIT, you specify the
network node address for each object when you place the object onto the screen. In the Edit
PLC/Controller Address Dialog, there is a field titled “Net Addr”. Specify the slave station’s node
address in this field.
Maple Systems, Inc. · 808 134th Street SW, Suite 120 · Everett, WA 98204-7333 · USA
Page 2 1035-0045, Rev. 01
BlueLeaf Communication Settings
The following table lists the communications settings that must be configured in BlueLeaf software.
These settings can be found in the Tools...HMI-PLC Communications Settings menu.
• The Recommended Settings column provides recommended settings based upon the default
settings most commonly used in the Modbus controller
• The Options column lists BlueLeaf’s options; your controller may not support every option.