Design KN/M.: 388 Relnforced

The document provides the design of a rectangular reinforced concrete footing to support a column load of 1150 kN. The key steps are: 1) Calculate the factored soil pressure of 266.21 kN/m^2 and determine the footing size as 1.80 m x 3.60 m based on allowable soil pressure. 2) Calculate the minimum depth of the footing using one-way shear, two-way shear, and bending moment criteria, obtaining values of 0.681 m, 0.607 m, and 0.330 m, respectively. 3) The governing depth is 0.681 m obtained from the one-way shear criterion. The final design depth of the

Uploaded by

Subhajyoti Das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
435 views6 pages

Design KN/M.: 388 Relnforced

The document provides the design of a rectangular reinforced concrete footing to support a column load of 1150 kN. The key steps are: 1) Calculate the factored soil pressure of 266.21 kN/m^2 and determine the footing size as 1.80 m x 3.60 m based on allowable soil pressure. 2) Calculate the minimum depth of the footing using one-way shear, two-way shear, and bending moment criteria, obtaining values of 0.681 m, 0.607 m, and 0.330 m, respectively. 3) The governing depth is 0.681 m obtained from the one-way shear criterion. The final design depth of the

Uploaded by

Subhajyoti Das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

388 Relnforced Cement Concrete

Design
of uniform thickness for an axially loaded o
I Example 14.2. Design a rectangular footing
is 1150 kN. Safe bearing capacity
of the soil is 200 1
oI size 300 mm x 600 mm load on column
Use M20 concrete and Fe 415 steel.
KN/m.
Solution. W= 1150 kN
115 kN
W= 10h of w,
=

+ 1265 kN =

9 200 kN/m*

For M20 concrete and Fe 415 steel umax = 0.48 and R, = 2.76 ITables 4.2 and 4.3

Area of footing A = We+W 1265 6.325 m


200
Considering length to width ratio of footing same as that of column, i.e., 2,
2x
Area of footing = x xy =xx 2x

2
= 6.325

6.32 1.78 m say 1.80 m


2
y 2x = 3.60 m
Soil pressure due to column load only

1150=177.47
3.60x 1.80
kN/m2
Factored soil pressure = 1.5 x177.47 266.21 kN/m*

Calculation of depth offooting


(a) By one way shear criterion: Critical section is at d from face to column [Fig. 14.15 and Fig. 14.16)

S.F in longer direction = 266.21

= 958.356 x 0.75 - 958.356 d


(18-0.3-d
x 3.6 x L8-0.3
2
= 718.767 - 958.356d

(3.6 0.6
S.F. in shorter direction = 266.211 x 1.8 x* -d

d
2
718.767 -479.178d
S.F. in shorter direction is more.
S.F. resisted by the concrete = T, Xd IT= 0.32for 0.2% steel reinforcement from Table 5.

O.32 x 106 x1.80 x d


103
576 d ..i)
1.80 389
1.80

600
0.80|

300
0.30

Fig. 14.15.
Fig. 14.16.
Equating (i) and (i)
718.767 479.178d = 576 d
d 0.681 m
A]
6) Depth of footing by two way shear eriterion: Critical section is at d/2 from the face of column.
Fig. 14.17)

1.80

/2

0.30

Fig. 14.17.

ocar force at critical section due to shaded area

266.21 x (3.6 x 1.80 (0.3+ d)x (0.6+ d)


= 1725-266.21 (0.18 +0.9d +d)
1677.08 - 239.59d - 266.21d*
iii)
Reinforced Cement Concrete Dei.
390 esiqn
Punching shear resisted by
section =
T, XA

where = 0.25 sa =0.25/20 1.118 N/mm


xKd
A = Area of critical section perimeter
=

= [(0.30+ d) + (0.60 + d)] xd

= (0.90+ 2d) d =0.9d+2d


10
1.118 x x (0.9d + 2d)
Shear force resisted =

103
= 1006.2d+ 2236d
Equating (ii) and (iv), we get
1677.08 239.59d - 266.21d = 1006.2d +2236d*

or +0.498d - 0.67 = 0
-0.498 t 0.498 +4 x 0.67
d =
2
d = 0.607m
(c) Depth of footing by bending moment criterion: Critical section is at the face of the columa
(Fig. 14.18)

0.75 m

0.30 m

0.60 m 0.60 m
0.30 m

1.80 m 1.80 m
-
Fig. 14.18.
B.M. in longer direction =
266.21x1.80x 1.5 x

539.08 kNm
B.M, in shorter direction
266.21 3.60x0.75 x 0.75
=
x
. 2
269.54 kNm. Hence B.M.
in longer direetion is more.
ounooons 391
Moment of resistance in longer direction

M, = 0.138 Sok x d2
For Fe 415 from Table 4.3
= 0.138 x 20x 1800xd2
=
4968 d Nmm.
.vi)
and (vi), we get
Equating (v)
539.08 x 10 x 10 = 496842

2539.08 x 106 = 108510.5


4968
d 330 mm = 0.330 m
.C
Out ofEqs. [A), [B] and .C, the value of Eq. [A], i.e., 681 mm is highest.
dia, and 50 mm clear cover,
Using 16 mm
Overall depth, D = 690 +8 + 50

748 mm say 750 mm


d 750-8- 50
692 mm

Area of reinforcement

M, = 0.87 , A, bd fek
539.08 x 10 = 0.87 x 415 x A,, x 692 x|1 Ag x 415 |
For longer direction
1800 x 692 x 20

A
=
249846.6 A 60028.92)
= 249846.6 A, -4.162 AG,

or
A,-60030.41 A, +(129.52 x10°) =0
60030.41t60030.41 -4x 129.52 x 10
As
2225 mm

Using 16 bars,spacing X1800 =162.60 mm

225
Provide 16@ 160
For shorter direction
mm clc

269.54x 10°= 249846.6 A, A


60028.92
= 249846.6 A, -4.162 A

or
A -60030.41 A +(64.76 x 10°) =0
392 Reinforced Cement Concres
Concrete Del
60030.41 t 60030.41 -4x 64.76 x 106
2
A 1098.91 mm

Minimum reinforcement 0.12% =


x 3600 x 750
100
3240 mm'> 1098 mm
As per IS code provisions
Reinforcement in central band
Total reinforcement in shorter direction +1

where B 0=2
18

Hence Reinforcement in central band


3240

or Reinforcement in central band = x 3240

= 2160 mm
This reinforcement shall be distributed in central 1.8 m bandwidth.

Spacing of16 bars = 201 1800


x1800
2160
= 167.5 mm say 160 mm

Provide 16 @ 160 mm cle in central band


Balance area of steel to be distributed in outer bands
=
3240 -2160 1080 mm =

Spacing of 16 ¢ bars 201 1800= 335


1080
Maximumspacing allowed = 300 mm
or d (692) whichever is less.
Provide 16 o bars@ 300 mm ele for the outer bands.

Check for development length

LL, = 0.87f, 0.87 x415 x 16


bd
T1.92 from Table5.
4x1.92
= 752.2 mm
Available length in shorter direction, beyor column face
1800 300
2
=
750 mm< 752.2 mm
Provide 90 degree bend at the free end of the
bend = 80 = 128 mm. reinforcement, as per IS provisions, anchorage
v
Hence, total anchorage length =
750 + 128
878 mm> 752.2 mm. Hence OK
KMnoDons
393

#16 300 mm clc

#16 160 mm clc

#16 160 mm clc


(Ceniral band)

#16 300 mm c/c


(Outer band)

1800mm
Plan

#16 300 mm c/c


(outer band)
300 mm #16 160 mm clc
(central band)
#16 160 mm clc

750

1800 mm
Section at XX

Fig. 14.19